Instruction Leaflet IL032019EN Effective December 2015 Version 2.0 245U-E wireless Ethernet modem installation guide Installation steps This guide provides installation drawings and instructions appropriate for most applications. For more information, refer to the user manual. 1. Connect the GND terminal on the back of the 245U-E to earth/ground. 2. Install the antenna. 3. Connect the 245U-E to a DC power supply and power on. 4. Connect the 245U-E to your computer via Ethernet and configure the 245U-E. Refer to the user manual for configuration details. Antenna installation When selecting an antenna, consider radio proximity. Use Figure 1 as a guide for installing an antenna and attaching it to the 245U-E. NOTE Figure 1. Antenna Installation This equipment is suitable for use in Class I Division 2 groups A, B, C and D hazardous locations, or nonhazardous locations only. Antenna* 1 Wavelength (minimum) Wavelengths: 2.4 GHz = 5.1" (13 cm) 5 GHz = 2.4" (6 cm) WARNING EXPLOSION HAZARD Stress Relief Loop Do not disconnect equipment while the circuit is live or unless the area is known to be free of ignitable concentrations. Substitution of any component may impair suitability for Class I Division 2. Weatherproof Connections (recommended: 3M™ 23 selfbonding tape) Surge Arrestor (recommended) Coaxial Cable Statutory requirements FCC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses. GND Mast 245U-E Earth Conductor at least 5 AWG (16 mm2) M4 x 5 mm * For maximum range, install above local obstructions. GND at least 11 AWG (4 mm2) Earth Stake Module Connection Provide good ground connection to mast, module, and surge arrestor. If ground conditions are poor, use more than one stake. Instruction Leaflet IL032019EN 245U-E wireless Ethernet modem installation guide EATON_245U-E Install Guide Effective December 2015 Version 2.0 RS-232 connections NOTE All connections must be SELV <50 Vac and <120 Vdc. If the wireless Ethernet modem is installed as Category 3 equipment, it must be installed in an enclosure that maintains an ingress protection rating of IP54 and meets the enclosure requirements of EN 50014 or EN60079-0. 100M LINK RUN SETUP ETHERNET If the wireless Ethernet modem is installed in a hazardous environment, coaxial cable must be installed in a metallic conduit, per NEC requirements. RD TD SG RTS WARNING CTS DSR DTR DCD The wireless Ethernet modem enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. This must be taken into account during installation. The following illustration shows the ports and switches on the 245U‑E. The Ethernet port is wired for a hub or switch. Factory Default Switch B A LINK RUN B A SETUP ETHERNET (HUB) 2 3 3 5 5 7 7 8 8 6 6 4 4 1 1 RS-232 B A RS-485 (DCE) + COM DIO SUPPLY RJ-45 Ethernet Port (Connects to hub or switch) RS-485 Resistor Termination Switch SUPPLY 245U to DCE (Modem) RD RD TD TD SG SG RTS RTS CTS CTS DSR DSR DTR DTR 2 2 3 3 5 5 7 7 8 8 6 6 4 4 1 1 DCD DCD DB-9 FEMALE (DTE is Male) DB-9 MALE (245U is Female) RD TD SG RTS CTS DSR DTR DCD DB-9 MALE (DCE is Female) RS-485 connections Use shielded twisted pair cable to interconnect modules to reduce potential RFI. B A B A Maintain the polarity of the two RS‑485 wires. RS-232 Port 100M 2 DB-9 MALE (245U is Female) B A RS-485 (DCE) 245U to DTE (Host) Digital Output will activate for approximately 5 seconds during the device power up sequence. The non-metallic cover of the wireless Ethernet modem constitutes an electrostatic discharge hazard. Clean only with a damp cloth. RS-232 (HUB) A BB A RS-485 RS-485 Terminate each end of the network with a 120‑ohm resistor. An on-board terminating resistor is provided in the modem and can be engaged by setting the DIP switch on the end plate to ON. + COM DIO SUPPLY 115S-xx B 115S-xx A B - Digital input and output wiring Power supply wiring The digital input/output (DIO) channel can be wired as either input or output. The module power supply –Ve terminal is not isolated from earth/ground. B A Digital Output Digital Input B A B A RS-485 B A -++ COM DIO SUPPLY B A B A * Connect the negative ( – ) supply terminal and the M4 GND screw (located on the rear of the module) to earth/ ground as close to the unit as possible. A + B A RS-485 9-30 Vdc Supply 2A Fuse or Circuit Breaker CAUTION! Avoid ground loops. Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s wireless business www.eaton.com/wireless + COM DIO COM DIO RS-232 (DCE) SUPPLY B A B A RS-485 + COM COM DIO DIO SUPPLY DC Load (relay) Max 30 Vdc 0.5A Connect to Ground as close to the module as possible © 2015 Eaton All Rights Reserved Printed in USA Publication No. IL032019EN December 2015 Voltage-Free Contact or Transistor Device Eaton is a registered trademark. All other trademarks are property of their respective owners.