Occupancy Sensor – IHB Cx Kit Industrial High Bay Lighting Fixture

advertisement
Occupancy Sensor – IHB Cx Kit
Industrial High Bay Lighting Fixture
IF 1758
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
Occupancy sensor kit for industrial LED Luminaire. Suitable for ordinary
locations only.
WARNING
To avoid the risk of fire, explosion or electric shock, this product
should be installed, inspected and maintained by a qualified electrician
only, in accordance with all applicable electrical codes.
WARNING
To avoid electric shock:
•
Be certain electrical power is OFF before and during installation
and maintenance.
•
Luminaire must be supplied by a wiring system with an
equipment grounding conductor.
To avoid burning hands:
•
Make sure luminaire lens and housing are cool when installing
and performing maintenance.
3.
connector to wire the occupancy to the luminaire. Connections will be
made at the existing lever lock connectors and the additional supplied
connectors will be used when required. Note: use only solid copper
wires for occupancy sensor connections.
When all wiring connections are complete, install the sensor assembly
with the four (4) 10-24 screws and tighten until fully seated. Ensure
sensor is securely connected in sensor housing and nut is tightened to
25-30 in.-lbs. Ensure occupancy sensor lens is secured to sensor.
Cover
(4) 10-24 Screws
WARNING
WIRING DIAGRAM
WHITE (NEUTRAL)
WHITE (NEUTRAL)
Make sure the wire supply voltage is the same as the occupancy
sensor supply. Do not operate in ambient temperatures above
those indicated on the luminaire nameplate.
Use proper supply wiring as specified on the luminaire
nameplate.
BLACK (LINE)
•
Luminaire
Figure 1
To avoid product degradation:
•
Driver Housing
Cable Gland
LOAD
LINE
NEUT
BLACK (LOAD)
DIMMING
DRIVER
GRND
DIMDIM+
OCCUPANCY
SENSOR
GREEN (GROUND)
GREY (DIM-)
PURPLE (DIM+)
Figure 2
OPERATING INSTRUCTIONS
For detailed operating instructions, refer to WattStopper FSP-211 data sheet.
For instructions for adjusting settings, refer to WattStopper FSIR-100
Wireless IR Commissioning Tool data sheet.
INSTALLATION
IHB
Occupancy
Kit
Occupancy
Sensor Lens
Sensor
Mounting
Height (Feet)
Sensor Maximum
Coverage
Diameter (Feet)
OCCUPANCY SENSOR ASSEMBLY
IHB C1 KIT
FSP-L2
8
48
8L
1.
2.
Remove four (4) 10-24 screws and cover from the end of the driver
housing enclosure closest to the cable glands as shown in Figure 1.
Locate the power wires, ground wire and dimming wires in driver
housing. Wire occupancy sensor to light luminaire wiring according
to wiring diagram in Figure 2. Refer to IF 1726 for wiring diagram of
IHB luminaire. The occupancy sensor kit includes six (6) solid copper
wires, two (2) 5-pole lever lock connectors and one (1) 2-pole lever lock
Light
Fixture
IHB C2 KIT
FSP-L3
20
40
16L, 24L, 32L,
48L, 64L
IHB C3 KIT
FSP-L4
40
60
48L, 64L
IHB C4 KIT
FSP-L7
40
100
48L, 64L
For instructions on occupancy sensor lenses, refer to WattStopper FSP-Lx.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or
completeness thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale,” and since conditions of use are outside our
control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Eaton’s Crouse-Hinds Business
1201 Wolf Street, Syracuse, New York 13208 • U.S.A.
Copyright© 2015
IF 1758
Revision 2
Revised 06/15
Supercedes 05/15
Download