CHAMP® LED Luminaires VMV and NVMV Series LED Fixtures IF 1594 Installation & Maintenance Information SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE NVMV: NEC/CEC • Class I, Division 2, Groups A, B, C, D • Class II, Groups E, F, G • Class III • Simultaneous presence • Wet location, Type 4X IEC Ex/ATEX • IECEx UL 10.0008 • Ex nA IIC T4 Gc Tamb -30°C to +40°C • Ex nA IIC T3 Gc Tamb -30°C to +55°C • Ex nA IIC T3 Gc Tamb -30ºC to +40ºC • Ex tb IIIC T63°C Db IP66 Tamb -30°C to +40°C • Ex tb IIIC T104ºC Db IP66 Tamb -30ºC to +40ºC • 0359 DEMKO 11 ATEX6248 BLK N WHT ACL(BLK) BLK PURPLE RED BLK BLK PURPLE RED BLK BLK (N)VMV7L (N)VMV9L (N)VMV11L DRIVER V+(PURPLE) ACN(WHT) GRN PE GROUND OUTPUT V-(BLK) TERMINATE AT TERMINAL BLOCK ON NVMV SERIES L1 BLK N WHT ACN(WHT) GRN (GND) ACL(BLK) LINE VOLTAGE V+(RED) DRIVER INPUT DIAGRAM #2: RED or PURPLE RED BLK BLK OUTPUT V-(BLK) (N)VMV5L (N)VMV7L (N)VMV9L WIRING DIAGRAM FOR: 5L, 7L & 9L DRIVER BLK ACL(BLK) V+(RED) INPUT GRN GROUND PE RED or PURPLE RED BLK BLK OUTPUT WHT ACN(WHT) V-(BLK) (GND) GRN TERMINATE AT TERMINAL BLOCK ON NVMV SERIES WARNING L1 BLK ACL(BLK) LINE VOLTAGE WIRING DIAGRAM FOR: DRIVER INPUT N V+(RED) RED RED BLK BLK (N)VMV3L OUTPUT WHT (N)VMV3L SERIES To avoid explosion: ACN(WHT) GRN V-(BLK) GND Make sure the supply voltage is the same as the luminaire voltage. GROUND PE GRN Do not install where the marked operating temperatures exceed the ignition temperature of the hazardous atmosphere. Do not operate in ambient temperatures above those indicated on the luminaire nameplate. To avoid electric shock: Be certain electrical power is OFF before and during installation and maintenance. LINE VOLTAGE L1 BLK 190/270 V 347/480 V ACL(BLK) Use proper supply wiring as specified on the luminaire nameplate. N TRANSFORMER All gasket seals must be clean. WHT ACN(WHT) GRN GND (SEE NOTE 4 SHT 1) ACL(BLK) INPUT COM WHT Wiring GROUND 1. Pull field wiring into cover module. 2. Close all unused conduit entries with conduit plugs provided. To prevent galling and to ensure water-tightness, lubricate conduit plugs with Cooper Crouse-Hinds HTL lubricant before installing, and secure wrench-tight with at least five (5) full threads engaged (42-52 ft.-lb. for 3/4” plugs, and 58-68 ft.-lb. for 1” plugs). • Ceiling and wall mount: mark and drill desired location on mounting surface. Secure with 1/4" (6mm) bolts or lag screws (not provided). • Pendant, stanchion mount: securely thread onto the appropriate NPT size conduit. Tighten set-screw located in the conduit hub. See Figure 1. • Cooper Crouse-Hinds HTL thread lubricant must be added to the conduit threads to prevent water from entering the fixture. Open Hinge BLK BLK (N)VMV3L (N)VMV5L V+(RED) DRIVER # 2 ACN(WHT) GRN Mount the cover module in its support position. V-(BLK) (N)VMV7L (N)VMV9L BLK 347 OR 480 VOLT TRANSFORMER COM Mounting RED OUTPUT WIRING DIAGRAM FOR: Make sure lens and housing are cool when performing maintenance. INSTALLATION DRIVER # 1 DIAGRAM #4: Before opening, electrical power to the luminaire must be turned off. Keep tightly closed when in operation. To avoid burning hands: RED or PURPLE V+(RED) INPUT Luminaire must be supplied by a wiring system with an equipment grounding conductor. RED or PURPLE RED BLK BLK OUTPUT V-(BLK) GND (SEE NOTE 4 SHT 1) GRN PE NJB040903 Enclosure LINE VOLTAGE L1 347/480 V 190/270 V BLK ACL(BLK) DRIVER # 1 N WHT TRANSFORMER V+(GREY) GREY RED BLK BLK OUTPUT INPUT ACN(WHT) V-(BLK) DIAGRAM #5: WIRING DIAGRAM FOR: 3. Hang LED luminaire on the cover module hinge hook. See Figure 2a. 4. Connect supply wires to luminaire wire leads (or terminal blocks) per the attached wiring diagrams using methods that comply with all applicable codes. See Figure 2b. Tighten all electrical connections. 5. 6. Set-screw V-(BLK) ACN(WHT) WHT 347V (VMV only) 480V (VMV only) WARNING FIGURE 1 RED BLK OUTPUT INPUT DIAGRAM #3: 1. V+(PURPLE) DRIVER ACL(BLK) NVMV complies with IEC60598-1 and IEC60598-2 (issued 1996). To avoid the risk of fire, explosion, or electric shock, this product should be installed, inspected, and maintained by a qualified electrician only, in accordance with all applicable electrical codes. V-(BLK) BLK • II 2 D Ex tb IIIC T63°C Db IP66 Tamb -30°C to +40°C • II 2 D Ex tb IIIC T104°C Db IP66 Tamb -30°C to +40°C • DEMKO 10 ATEX0915702 • II 3 G Ex nA IIC T4 Gc Tamb -30°C to +40°C • II 3 G Ex nA IIC T3 Gc Tamb -30°C to +55°C • II 3 G Ex nA IIC T3 Gc Tamb -30ºC to +40ºC WARNING PURPLE OUTPUT WIRING DIAGRAM FOR: Luminaire construction is designed for use indoors and outdoors in marine and wet locations, where moisture, dirt, corrosion, vibration, and rough usage may be present. VMV: L1 V+(PURPLE) DRIVER 7L Model M2, 9L Model M2 and 11L Refer to the luminaire nameplate for specific classification information, maximum ambient temperature suitability, and corresponding operating temperature (TCode). VMV and NVMV supplied with a choice of voltages: 100-277VAC 50/60 Hz (both VMV and NVMV) 108-250VDC (both VMV and NVMV) ACN(WHT) INPUT DIAGRAM #1: Champ® VMV and NVMV Series Luminaires are suitable for use in the following hazardous (classified) areas as defined by the National Electrical Code (NEC®). CSA Standards • CSA C22.2 No. 137 ACL(BLK) LINE VOLTAGE APPLICATION UL Standards • UL 844 Hazardous (classified) • UL1598 Luminaires, UL1598A Marine BLK WHT INPUT TERMINATE AT TERMINAL BLOCK ON NVMV SERIES 347 OR 480 VOLT TRANSFORMER BLK ON VMV11L ACL(BLK) DRIVER # 2 INPUT COM COM WHT ACN(WHT) BLK ACL(BLK) WHT ACN(WHT) V+(GREY) GREY RED BLK BLK GREY RED BLK BLK VMV11L OUTPUT V-(BLK) PE GROUND Close driver housing onto cover module, making sure that all wires are safely inside driver. Tighten captive closing screw to 30 in.-lbs. (3.4 N-m). Ensure two (2) bosses on driver housing are in contact with cover module. GRN DRIVER # 3 INPUT NOTE: Ground wire must be added to mounting plate ground lug and to lugs on entry hubs. Ground wire included. V+(GREY) OUTPUT V-(BLK) Turn power on. Ground Wires DENOTES CONNECTION CLOSED END CRIMP CONNECTOR PER BOM DENOTES WIRE CROSS OVER, NOT CONNECTION POINT FIGURE 2b FIGURE 2a IF 1594 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 1 IF 1594 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 2 FIELD ASSEMBLED FIXTURES WARNING Champ® VMV Series Lighting Fixtures, 50-140 Watt Complete lighting fixture consists of cover, LED luminaire PENDANT CEILING APM2 3/4 IN. APM3 1 IN. HPM2 3/4 IN. CM2 3/4 IN. CM3 1 IN. 5._______ Verify all electrical connections are tightened. 6._______ Verify all wires are safely and neatly inside driver housing and not on top of wire terminal. Close driver housing onto cover module. 7._______ Verify captive closing screw is tightened to 30 in.-lbs. (3.4 N-m) and two (2) bosses on driver housing are in contact with cover module. To avoid electric shock: Be certain electrical power is OFF before and during installation and maintenance. Luminaire must be supplied by a wiring system with an equipment grounding conductor. STANCHION JM5 PM5 1 1/2 IN 1 1/2 IN. WALL TWM2 3/4 IN. TWM3 1 IN. To avoid burning hands: Make sure globe or refractor and lamp are cool when performing maintenance. DM1, DM2, DM3, DM4 INSTALLATION CHECKLIST (N) VMV9L/7L/5L VMV3L/11L NPT Entries 1._______ 5 1 1 5 1 MOUNTING AND WIRING OF VMV11L347/480 K1 3.82 Verify sufficient HTL lubricant is on conduit plugs (recommend approximately 1/8” bead around the first thread of plug) and that all unused conduit entries on the cover module are closed with lubricated plugs. 6 9 1 3 4 8.63 MTG 9.50 2 5 7 8 WIRING 10 9 8 7 6 5 4 3 2 1 1 1 1 2 4 1 1 1 INSTRUCTION SHEET (NOT SHOWN) N/PLT #10 WASHER GROUND WIRE ASSEMBLY (NOT SHOWN) HUB, 3/4" SCREW, RD HD, #10-32 X .375 BRACKET, TRANSFORMER TRANSFORMER MOUNTING PLATE, 480V TRANSFORMER 1 1 NJB040903 2._______ Verify conduit plugs are installed to at least five (5) full threads into the cover module conduit entries. 3._______ Verify installed conduit plugs are torqued to 42-52 ft.-lbs. for 3/4” plugs and 58-68 ft.-lbs. for 1” plug. 4._______ Verify supply wires are connected to luminaire wire leads (or terminal block) per wiring diagrams. ø.281 MTG HOLE 2.69 MTG 1.14 3.23 NO. PART NUMBER QTY. DESCRIPTION BODY INTERIOR Wire per wiring diagram and per required electrical codes. INSTALLATION / MOUNTING OF VMV11L347/480 K1 This needs four (4) mounting bolts (provided by others) to attach the box to a surface or it could be conduit supported. (See IF 388 for specific mounting instructions). MAINTENANCE LED MODULE REPLACEMENT INSTRUCTIONS 1. Perform visual, electrical, and mechanical inspections on a regular basis. The environment and frequency of use should determine this. However, it is recommended that checks be made at least once a year. We recommend an Electrical Preventive Maintenance Program as described in the National Fire Protection Association Bulletin NFPA No. 70B: Recommended Practice For Electrical Equipment Maintenance (www.nfpa.org). 2. The lens should be cleaned periodically to ensure continued lighting performance. To clean, wipe the lens with a clean, damp cloth. If this is not sufficient, use a mild soap or a liquid cleaner such as Collinite NCF or Duco #7. Do not use an abrasive, strong alkaline, or acid cleaner. Damage may result. 3. Visually check for undue heating evidenced by discoloration of wires or other components, damaged parts, or leakage evidenced by water or corrosion in the interior. Replace all worn, damaged, or malfunctioning components, and clean gasket seals before putting the luminaire back into service. 4. Electrically check to make sure that all connections are clean and tight. 5. Mechanically check that all parts are properly assembled. REPLACEMENT PARTS Cooper Crouse-Hinds VMV and NVMV Series Champ Luminaires are designed to provide years of reliable lighting performance. However, should the need for replacement parts arise, they are available through your authorized Cooper Crouse-Hinds distributor. Assistance may also be obtained through your local Cooper Crouse-Hinds representative. 1. Turn off electrical power to the luminaire before opening. 2. Loosen captive closing screw, open luminaire, and leave hanging on cover module hinge hook. 3. Disconnect supply wire from luminaire wire leads and remove luminaire from cover module. 4. At workbench, remove wire nut connections from both LED drivers’ DC outputs to LED module (see Step 1). 5. Unthread the three (3) housing bolts using a 3/16” hex tool; do not remove bolts from assembly. 6. Carefully separate the heat sink/driver housing from the LED module, pulling the LED wires through the bushing in the driver housing. 7. Remove any gasket material from the bottom of the heat sink with a shop rag (see Step 2). 8. Place new LED module on workbench and inspect gasket to ensure proper sealing during assembly (see Step 3). 9. Gently place heat sink/driver housing into LED module while feeding the paired wires from the LED module through the bushing in the driver housing, being sure to align the bolts with the tapped holes in the LED module. 10. Thread the three (3) housing bolts into the LED module using a 3/16” hex tool. Torque bolts to 50 in.-lbs. (5.7 N-m). 11. Use supplied wire nuts to connect LED driver DC output to LED module wires, noting correct polarity. 12. Mount and wire luminaire per Installation Instructions. Cooper Crouse-Hinds Sales Service Department, P.O. Box 4999, Syracuse, New York 13221, Phone (315) 477-7000. STEP 1 STEP 2 STEP 3 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale," and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith. Cooper Crouse-Hinds LLC PO Box 4999, Syracuse, New York 13221 • USA Copyright © 2012, Cooper Industries IF 1594 • 09/12 Copyright © 2012, Cooper Industries, Inc. Page 3 IF 1594 Revision 6 Revised 09/12 Supercedes 06/12