IF 1461 ATTESTATION OF CONFORMITY Manufacturer: Cooper Crouse-Hinds Address: P.O. Box 4999, Syracuse, NY 13221 USA Certificate: INTERTEK ITS12ATEX47591X 0359 Equipment: Conduit Hubs SSTGK1 - SSTGK10 (1/2 inch to 4 inch) and STGK1 - STGK10 (1/2 inch to 4 inch) II 2 G Ex e IIC Gb Ta -15°C to +120°C We herewith confirm that: The equipment is designed and manufactured as to provide protection against other hazards as specified in Directives, 94/9/EC, Annex II, clause 1.2.7; EN60079-0:2009 - Electrical apparatus for potentially explosive atmospheres - General requirements; and EN60079-7:2007 - Electrical apparatus for potentially explosive atmospheres - Increased safety 'e'. EN60529:1992, IP66. Where the risks referred to in this paragraph are wholly or partly covered by other Community Directives, Directive 94/9/EC is not applied or shall cease to apply in the case of this equipment and of such risks upon application of those specific Directives. Intertek Testing & Certification Limited (0359) Intertek House, Cleeve Road, Leatherhead, Surrey, KT22 7SB England. Signed: Name: Laureen Antinelli, Manager, Quality Assurance Date: May 08, 2013 INSTALLATION INSTRUCTIONS - ( II 2 G Ex e IIC Gb Ta -15°C to +120°C) Determine location for the hub mounting hole, making sure there is enough room internally to install the locking nut. Using the dimensions in the table below, machine a mounting hole in the enclosure, following the maximum wall thickness dimensions. Secure the locking nut to the hub body using the torque values below. Tighten the locking ring set screw. Install Ground [Earth] Lead, consisting of a maximum of TWO 6-AWG TO 14-AWG solid or stranded copper wires, between the ground bracket and the lock nut and tighten the ground screw to the specified torque. If the available Ground [Earth] Lead AWG is greater than specified, a copper lug style connector, specified per NEC may be utilized. Reference NEC for Ground [Earth] Lead preparation and insulation stripping requirements. Both screws should be tightened to 35 lb/in (4.0 Nm). Hub is now ready to accept NPT threaded conduit or cable fittings (glands). Max. Panel Thickness Plastic Enclosure Mounting Hole Metal Enclosure Tightening Torque Catalog Number Inches (mm) Inches (mm) Inches (mm) lbf-in. (Nm) STGK-1* STGK-2* STGK-3* STGK-4* STGK-5* STGK-6* STGK-7* STGK-8* STGK-9* STGK-10* 0.86 - 0.88 1.06 - 1.13 1.33 - 1.38 1.67 - 1.75 1.92 - 2.00 2.39 - 2.50 2.92 - 3.00 3.56 – 3.66 4.06 - 4.17 4.56 - 4.69 (21.8 - 22.4) (26.9 - 28.7) (33.8 - 35.0) (42.4 - 44.5) (48.8 - 50.8) (60.7 - 63.5) (74.1 – 76.2) (90.5 – 93.0) (103.2 – 106.0) (115.9 – 119.0) 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) 300 500 700 1000 1200 1600 1600 1600 1600 1600 (33.9) (56.5) (79.1) (113.0) (136.0) (181.0) (181.0) (181.0) (181.0) (181.0) SSTGK-1** SSTGK-2** SSTGK-3** SSTGK-4** SSTGK-5** SSTGK-6** SSTGK-7** SSTGK-8** SSTGK-9** SSTGK-10** 0.86 - 0.88 1.06 - 1.13 1.33 - 1.38 1.67 - 1.75 1.92 - 2.00 2.39 - 2.50 2.92 - 3.00 3.56 – 3.66 4.06 - 4.17 4.56 - 4.69 (21.8 - 22.4) (26.9 - 28.7) (33.8 - 35.0) (42.4 - 44.5) (48.8 - 50.8) (60.7 - 63.5) (74.1 – 76.2) (90.5 – 93.0) (103.2 – 106.0) (115.9 – 119.0) 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 (4.76) (4.76) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 (4.76) (4.76) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) (6.35) 300 500 700 1000 1200 1600 1600 1600 1600 1600 (33.9) (56.5) (79.1) (113.0) (136.0) (181.0) (181.0) (181.0) (181.0) (181.0) * STGK-1 to STGK-6 thickness range of 0.080 in (2 mm) - 0.25 in (6.35 mm) Metal Enclosure. * STGK-1 to STGK-10 thickness range of 0.125 in (3.2 mm) - 0.25 in (6.35 mm) Plastic Enclosure. ** SSTGK-1 to SSTGK-6 thickness range of 0.080 in (2 mm) - 0.25 in (6.35 mm) Metal Enclosure. ** SSTGK-1 thickness range of 0.125 in (2 mm) - 0.25 in (6.35 mm) Plastic Enclosure. ** SSTGK-2 to SSTGK-10 enclosure thickness of 0.25 in (6.35 mm) Plastic Enclosure. Cooper Industries Inc. Crouse-Hinds Division PO Box 4999, Syracuse, New York 13221 • U.S.A. Copyright© 2013, Cooper Industries, Inc. IF 1461 Revision 9 Revised 05/13 Supercedes 06/12