Voltage Regulators Technical Data TD225006EN Effective XXX 2015 Supersedes 240-40 August 2012 COOPER POWER SERIES Communications Point Availability Available Data Points for CL-7 Communications Protocols For use with Eaton’s Cooper Power series CL-7 Voltage Regulator Control CL-7 Available Data Points CL-7 Communications Point Availability June 4, 2015 v2.00 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON. UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED. Document 1.00 2.00 Date 4/29/2013 6/4/2015 Description Initial Release Updates for Summer 2015 release The data points listed in this document are available for mapping to any of the CL-7 SCADA protocol User Maps as described in service document MN225021EN (previously S225-70-3), CL-7 Regulator Control Communications. Page 1 Cover Page CL-7 Available Data Points Binary Input Points Description VR1 Bandwidth Low VR1 Bandwidth High VR1 Voltage Limiter Low VR1 Voltage Limiter High Voltage Reduction Active VR1 Auto Operation Blocking Status Blocked (Follows FC069) VR1 HMI LED Auto Tap Blocked ON VR1 System Power Direction Indeterminate VR1 System Power Direction Reverse VR1 Control Power Direction Reverse VR1 Blocking Relay Active VR1 HMI LED Neutral Position On VR1 HMI Switch Auto/Manual Auto HMI Switch Supervisory Off HMI LED Alarm On HMI LED Warning On HMI LED Diagnostic Error On VR1 Motor Trouble Tap To Neutral Active Soft Add-Amp Active AltConfigActive Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic User Defined LED 1 On Configurable Logic User Defined LED 2 On Configurable Logic User Defined LED 3 On Configurable Logic Point 01 to SCADA Configurable Logic Point 02 to SCADA Configurable Logic Point 03 to SCADA Configurable Logic Point 04 to SCADA Configurable Logic Point 05 to SCADA Configurable Logic Point 06 to SCADA Configurable Logic Point 07 to SCADA Configurable Logic Point 08 to SCADA VR1 Source Voltage Calculation ENABLED Analog Voltage Reduction #1 ACTIVE Analog Voltage Reduction #2 ACTIVE VR1 HMI Switch Power Internal VR1 HMI Switch Power External VR1 HMI Switch Auto/Manual Manual VR1 HMI Switch Auto/Manual Off ARL Ready State Ready ARL AltConfig ACTIVE Tap To Neutral Enabled PMT Mode A Enabled PMT Mode B Enabled Event Recorder Enabled Data Alarms Enabled Status Alarms Enabled Data Profiler Enabled Interval Ops Enabled Daylight Saving Time Enable Daylight Saving Time Active LoopShare Comms Loss Of Communications Leader/Follower Unable To Operate Leader/Follower Inactive/Not Ready LoopShare Comms Active AltConfig1 Reg Blocked AltConfig2 Reg Blocked AltConfig3 Reg Blocked AltConfig1 Tap To Neutral Enabled AltConfig2 Tap To Neutral Enabled AltConfig3 Tap To Neutral Enabled General Purpose Input 1 Page 2 Binary Input Points CL-7 Available Data Points Binary Input Points Description General Purpose Input 2 General Purpose Input 3 VR2 Bandwidth Low VR3 Bandwidth Low VR2 Bandwidth High VR3 Bandwidth High VR2 Voltage Limiter Low VR3 Voltage Limiter Low VR2 Voltage Limiter High VR3 Voltage Limiter High VR2 Auto Operation Blocking Status Blocked VR3 Auto Operation Blocking Status Blocked VR2 HMI LED Auto Tap Blocked ON VR3 HMI LED Auto Tap Blocked ON VR2 System Power Direction Indeterminate VR3 System Power Direction Indeterminate VR2 System Power Direction Reverse VR3 System Power Direction Reverse VR2 Blocking Relay Active VR3 Blocking Relay Active VR2 Control Power Direction VR3 Control Power Direction VR2 HMI LED Neutral Position On VR3 HMI LED Neutral Position On VR2 HMI Switch Auto/Manual Auto VR3 HMI Switch Auto/Manual Auto VR2 Motor Trouble VR3 Motor Trouble VR2 Source Voltage Calculation On VR3 Source Voltage Calculation On VR2 HMI Switch Power Internal VR3 HMI Switch Power Internal VR2 HMI Switch Power External VR3 HMI Switch Power External VR2 HMI Switch Auto/Manual Manual VR3 HMI Switch Auto/Manual Manual VR2 HMI Switch Auto/Manual Off VR3 HMI Switch Auto/Manual Off Configurable Logic Point 09 to SCADA Configurable Logic Point 10 to SCADA Configurable Logic Point 11 to SCADA Configurable Logic Point 12 to SCADA Configurable Logic Point 13 to SCADA Configurable Logic Point 14 to SCADA Configurable Logic Point 15 to SCADA Configurable Logic Point 16 to SCADA Configurable Logic Point 17 to SCADA Configurable Logic Point 18 to SCADA Configurable Logic Point 19 to SCADA Configurable Logic Point 20 to SCADA Configurable Logic Point 21 to SCADA Configurable Logic Point 22 to SCADA Configurable Logic Point 23 to SCADA Configurable Logic Point 24 to SCADA Configurable Logic Point 25 to SCADA Configurable Logic Point 26 to SCADA Configurable Logic Point 27 to SCADA Configurable Logic Point 28 to SCADA Configurable Logic Point 29 to SCADA Configurable Logic Point 30 to SCADA Configurable Logic Point 31 to SCADA Configurable Logic Point 32 to SCADA Configurable Logic Point 33 to SCADA Configurable Logic Point 34 to SCADA Configurable Logic Point 35 to SCADA Configurable Logic Point 36 to SCADA Page 3 Binary Input Points CL-7 Available Data Points Binary Input Points Description Configurable Logic Point 37 to SCADA Configurable Logic Point 38 to SCADA Configurable Logic Point 39 to SCADA Configurable Logic Point 40 to SCADA Aux Module 1 Contact I/O Input 1 Aux Module 1 Contact I/O Input 2 Aux Module 1 Contact I/O Input 3 Aux Module 1 Contact I/O Input 4 Aux Module 1 Contact I/O Input 5 Aux Module 1 Contact I/O Input 6 Aux Module 1 Contact I/O Input 7 Aux Module 1 Contact I/O Input 8 Aux Module 1 Contact I/O Output 1 State Aux Module 1 Contact I/O Output 2 State Aux Module 1 Contact I/O Output 3 State Aux Module 1 Contact I/O Output 4 State Aux Module 2 Contact I/O Input 1 Aux Module 2 Contact I/O Input 2 Aux Module 2 Contact I/O Input 3 Aux Module 2 Contact I/O Input 4 Aux Module 2 Contact I/O Input 5 Aux Module 2 Contact I/O Input 6 Aux Module 2 Contact I/O Input 7 Aux Module 2 Contact I/O Input 8 Aux Module 2 Contact I/O Output 1 State Aux Module 2 Contact I/O Output 2 State Aux Module 2 Contact I/O Output 3 State Aux Module 2 Contact I/O Output 4 State Aux Module 3 Contact I/O Input 1 Aux Module 3 Contact I/O Input 2 Aux Module 3 Contact I/O Input 3 Aux Module 3 Contact I/O Input 4 Aux Module 3 Contact I/O Input 5 Aux Module 3 Contact I/O Input 6 Aux Module 3 Contact I/O Input 7 Aux Module 3 Contact I/O Input 8 Aux Module 3 Contact I/O Output 1 State Aux Module 3 Contact I/O Output 2 State Aux Module 3 Contact I/O Output 3 State Aux Module 3 Contact I/O Output 4 State Aux Module 4 Contact I/O Input 1 Aux Module 4 Contact I/O Input 2 Aux Module 4 Contact I/O Input 3 Aux Module 4 Contact I/O Input 4 Aux Module 4 Contact I/O Input 5 Aux Module 4 Contact I/O Input 6 Aux Module 4 Contact I/O Input 7 Aux Module 4 Contact I/O Input 8 Aux Module 4 Contact I/O Output 1 State Aux Module 4 Contact I/O Output 2 State Aux Module 4 Contact I/O Output 3 State Aux Module 4 Contact I/O Output 4 State OMAP File Ready To Read OMAP Debug Mode Time Set Event OMAP Reset HMI Switch Supervisory On VR1 Voltage Sag Level 1 Status VR1 Voltage Sag Level 2 Status VR1 Voltage Sag Level 3 Status VR2 Voltage Sag Level 1 Status VR2 Voltage Sag Level 2 Status VR2 Voltage Sag Level 3 Status VR3 Voltage Sag Level 1 Status VR3 Voltage Sag Level 2 Status VR3 Voltage Sag Level 3 Status Page 4 Binary Input Points CL-7 Available Data Points Binary Input Points Description Block Before Remote Tap User Input1 User Input2 User Input3 User Input4 Tap -VR1 Dead Phase Status Tap -VR2 Dead Phase Status Tap -VR3 Dead Phase Status Page 5 Binary Input Points CL-7 Available Data Points Analog Input Points Description VR1 Load Voltage Secondary VR1 Load Voltage Primary VR1 Compensated Voltage Secondary VR1 Load Current Primary VR1 Source Voltage Secondary VR1 Source Voltage Primary VR1 Tap Position VR1 Percent Reg VR1 Power Factor VR1 KVA Load VR1 kW Load VR1 KVAR Load Frequency VR1 Harm Total Voltage Harmonics VR1 Harm Total Current Harmonics VR1 kWh Forward VR1 KWH Reverse VR1 KQH Forward VR1 KQH Reverse VR1 Operations Counter VR1 Load Current Real VR1 Load Current Reactive VR1 Phase Angle Voltage Reduction In Effect Active Configuration Active Adaptive Add Amp Level VR1 Calculated Motor Voltage VR1 Contact Duty Cycle Monitor VR1 User Voltage Calibration VR1 User Current Calibration VR1 Ops Count Last Change Leader/Follower State Battery Voltage Battery Current VR2 Load Voltage Secondary VR3 Load Voltage Secondary Average Load Voltage Secondary VR2 Load Voltage Primary VR3 Load Voltage Primary Average Load Voltage Primary VR2 Compensated Voltage Secondary VR3 Compensated Voltage Secondary Average Compensated Voltage Secondary VR2 Load Current Primary VR3 Load Current Primary Average Load Current Primary VR2 Source Voltage Secondary VR3 Source Voltage Secondary Average Source Voltage Secondary VR2 Source Voltage Primary VR3 Source Voltage Primary Average Source Voltage Primary VR2 Tap Position VR3 Tap Position Average Tap Position VR2 Percent Reg VR3 Percent Reg Average Percent Reg VR2 Power Factor VR3 Power Factor Average Power Factor VR2 KVA Load VR3 KVA Load Total KVA Load VR2 kW Load Page 6 Analog Input Points CL-7 Available Data Points Analog Input Points Description VR3 kW Load Total kW Load VR2 KVAR Load VR3 KVAR Load Total KVAR Load VR2 Harm Total Voltage Harmonics VR3 Harm Total Voltage Harmonics VR2 Harm Total Current Harmonics VR3 Harm Total Current Harmonics VR2 kWh Forward VR3 kWh Forward Total kWh Forward VR2 KWH Reverse VR3 KWH Reverse Total KWH Reverse VR2 KQH Forward VR3 KQH Forward Total KQH Forward VR2 KQH Reverse VR3 KQH Reverse Total KQH Reverse VR2 Operations Counter VR3 Operations Counter HMI Last Self-Test Results VR2 Load Current Real VR3 Load Current Real Average Load Current Real VR2 Load Current Reactive VR3 Load Current Reactive Average Load Current Reactive VR2 Phase Angle VR3 Phase Angle VR2 Calculated Motor Voltage VR3 Calculated Motor Voltage VR2 Contact Duty Cycle Monitor VR3 Contact Duty Cycle Monitor VR2 User Voltage Calibration VR3 User Voltage Calibration VR2 User Current Calibration VR3 User Current Calibration VR2 Ops Count Last Change VR3 Ops Count Last Change VR1 Forward Demand Load Voltage Minimum VR1 Forward Demand Load Voltage Maximum VR1 Forward Demand Load Voltage Present VR1 Forward Demand Source Voltage Minimum VR1 Forward Demand Source Voltage Maximum VR1 Forward Demand Source Voltage Present VR1 Forward Demand Compensated Voltage Minimum VR1 Forward Demand Compensated Voltage Maximum VR1 Forward Demand Compensated Voltage Present VR1 Forward Demand Load Current Minimum VR1 Forward Demand Load Current Maximum VR1 Forward Demand Load Current Present VR1 Forward Demand KVA Load Minimum VR1 Forward Demand KVA Load Maximum VR1 Forward Demand KVA Load Present VR1 Forward Demand KW Load Minimum VR1 Forward Demand KW Load Maximum VR1 Forward Demand KW Load Present VR1 Forward Demand KVAR Load Minimum VR1 Forward Demand KVAR Load Maximum VR1 Forward Demand KVAR Load Present VR1 Forward Power Factor Minimum VR1 Forward Power Factor Maximum VR1 Forward Load Current Real Minimum Page 7 Analog Input Points CL-7 Available Data Points Analog Input Points Description VR1 Forward Load Current Real Maximum VR1 Forward Load Current Real Present VR1 Forward Load Current Reactive Minimum VR1 Forward Load Current Reactive Maximum VR1 Forward Load Current Reactive Present VR1 Minimum Tap Position VR1 Maximum Tap Position VR1 Maximum Percent Boost VR1 Maximum Percent Buck VR1 Reverse Demand Load Voltage Minimum VR1 Reverse Demand Load Voltage Maximum VR1 Reverse Demand Load Voltage Present VR1 Reverse Demand Source Voltage Minimum VR1 Reverse Demand Source Voltage Maximum VR1 Reverse Demand Source Voltage Present VR1 Reverse Demand Compensated Voltage Minimum VR1 Reverse Demand Compensated Voltage Maximum VR1 Reverse Demand Compensated Voltage Present VR1 Reverse Demand Load Current Minimum VR1 Reverse Demand Load Current Maximum VR1 Reverse Demand Load Current Present VR1 Reverse Demand KVA Load Minimum VR1 Reverse Demand KVA Load Maximum VR1 Reverse Demand KVA Load Present VR1 Reverse Demand KW Load Minimum VR1 Reverse Demand KW Load Maximum VR1 Reverse Demand KW Load Present VR1 Reverse Demand KVAR Load Minimum VR1 Reverse Demand KVAR Load Maximum VR1 Reverse Demand KVAR Load Present VR1 Reverse Power Factor Minimum VR1 Reverse Power Factor Maximum VR1 Reverse Load Current Real Minimum VR1 Reverse Load Current Real Maximum VR1 Reverse Load Current Real Present VR1 Reverse Load Current Reactive Minimum VR1 Reverse Load Current Reactive Maximum VR1 Reverse Load Current Reactive Present VR2 Forward Demand Load Voltage Minimum VR2 Forward Demand Load Voltage Maximum VR2 Forward Demand Load Voltage Present VR2 Forward Demand Source Voltage Minimum VR2 Forward Demand Source Voltage Maximum VR2 Forward Demand Source Voltage Present VR2 Forward Demand Compensated Voltage Minimum VR2 Forward Demand Compensated Voltage Maximum VR2 Forward Demand Compensated Voltage Present VR2 Forward Demand Load Current Minimum VR2 Forward Demand Load Current Maximum VR2 Forward Demand Load Current Present VR2 Forward Demand KVA Load Minimum VR2 Forward Demand KVA Load Maximum VR2 Forward Demand KVA Load Present VR2 Forward Demand KW Load Minimum VR2 Forward Demand KW Load Maximum VR2 Forward Demand KW Load Present VR2 Forward Demand KVAR Load Minimum VR2 Forward Demand KVAR Load Maximum VR2 Forward Demand KVAR Load Present VR2 Forward Power Factor Minimum VR2 Forward Power Factor Maximum VR2 Forward Load Current Real Minimum VR2 Forward Load Current Real Maximum VR2 Forward Load Current Real Present VR2 Forward Load Current Reactive Minimum VR2 Forward Load Current Reactive Maximum Page 8 Analog Input Points CL-7 Available Data Points Analog Input Points Description VR2 Forward Load Current Present VR2 Minimum Tap Position VR2 Maximum Tap Position VR2 Maximum Percent Boost VR2 Maximum Percent Buck VR2 Reverse Demand Load Voltage Minimum VR2 Reverse Demand Load Voltage Maximum VR2 Reverse Demand Load Voltage Present VR2 Reverse Demand Source Voltage Minimum VR2 Reverse Demand Source Voltage Maximum VR2 Reverse Demand Source Voltage Present VR2 Reverse Demand Compensated Voltage Minimum VR2 Reverse Demand Compensated Voltage Maximum VR2 Reverse Demand Compensated Voltage Present VR2 Reverse Demand Load Current Minimum VR2 Reverse Demand Load Current Maximum VR2 Reverse Demand Load Current Present VR2 Reverse Demand KVA Load Minimum VR2 Reverse Demand KVA Load Maximum VR2 Reverse Demand KVA Load Present VR2 Reverse Demand KW Load Minimum VR2 Reverse Demand KW Load Maximum VR2 Reverse Demand KW Load Present VR2 Reverse Demand KVAR Load Minimum VR2 Reverse Demand KVAR Load Maximum VR2 Reverse Demand KVAR Load Present VR2 Reverse Power Factor Minimum VR2 Reverse Power Factor Maximum VR2 Reverse Load Current Real Minimum VR2 Reverse Load Current Real Maximum VR2 Reverse Load Current Real Present VR2 Reverse Load Current Reactive Minimum VR2 Reverse Load Current Reactive Maximum VR2 Reverse Load Current Reactive Present VR3 Forward Demand Load Voltage Minimum VR3 Forward Demand Load Voltage Maximum VR3 Forward Demand Load Voltage Present VR3 Forward Demand Source Voltage Minimum VR3 Forward Demand Source Voltage Maximum VR3 Forward Demand Source Voltage Present VR3 Forward Demand Compensated Voltage Minimum VR3 Forward Demand Compensated Voltage Maximum VR3 Forward Demand Compensated Voltage Present VR3 Forward Demand Load Current Minimum VR3 Forward Demand Load Current Maximum VR3 Forward Demand Load Current Present VR3 Forward Demand KVA Load Minimum VR3 Forward Demand KVA Load Maximum VR3 Forward Demand KVA Load Present VR3 Forward Demand KW Load Minimum VR3 Forward Demand KW Load Maximum VR3 Forward Demand KW Load Present VR3 Forward Demand KVAR Load Minimum VR3 Forward Demand KVAR Load Maximum VR3 Forward Demand KVAR Load Present VR3 Forward Power Factor Minimum VR3 Forward Power Factor Maximum VR3 Forward Load Current Real Minimum VR3 Forward Load Current Real Maximum VR3 Forward Load Current Real Present VR3 Forward Load Current Reactive Minimum VR3 Forward Load Current Reactive Maximum VR3 Forward Load Current Present VR3 Minimum Tap Position VR3 Maximum Tap Position VR3 Maximum Percent Boost Page 9 Analog Input Points CL-7 Available Data Points Analog Input Points Description VR3 Maximum Percent Buck VR3 Reverse Demand Load Voltage Minimum VR3 Reverse Demand Load Voltage Maximum VR3 Reverse Demand Load Voltage Present VR3 Reverse Demand Source Voltage Minimum VR3 Reverse Demand Source Voltage Maximum VR3 Reverse Demand Source Voltage Present VR3 Reverse Demand Compensated Voltage Minimum VR3 Reverse Demand Compensated Voltage Maximum VR3 Reverse Demand Compensated Voltage Present VR3 Reverse Demand Load Current Minimum VR3 Reverse Demand Load Current Maximum VR3 Reverse Demand Load Current Present VR3 Reverse Demand KVA Load Minimum VR3 Reverse Demand KVA Load Maximum VR3 Reverse Demand KVA Load Present VR3 Reverse Demand KW Load Minimum VR3 Reverse Demand KW Load Maximum VR3 Reverse Demand KW Load Present VR3 Reverse Demand KVAR Load Minimum VR3 Reverse Demand KVAR Load Maximum VR3 Reverse Demand KVAR Load Present VR3 Reverse Power Factor Minimum VR3 Reverse Power Factor Maximum VR3 Reverse Load Current Real Minimum VR3 Reverse Load Current Real Maximum VR3 Reverse Load Current Real Present VR3 Reverse Load Current Reactive Minimum VR3 Reverse Load Current Reactive Maximum VR3 Reverse Load Current Reactive Present Average Forward Load Voltage Minimum Average Forward Load Voltage Maximum Average Forward Load Voltage Present Average Forward Compensated Voltage Minimum Average Forward Compensated Voltage Maximum Average Forward Compensated Voltage Present Average Forward Load Current Minimum Average Forward Load Current Maximum Average Forward Load Current Present Average Forward Source Voltage Minimum Average Forward Source Voltage Maximum Average Forward Source Voltage Present Total Forward KVA Load Minimum Total Forward KVA Load Maximum Total Forward KVA Load Present Total Forward kW Load Minimum Total Forward kW Load Maximum Total Forward kW Load Present Total Forward KVAR Load Minimum Total Forward KVAR Load Maximum Total Forward KVAR Load Present Average Forward Load Current Real Minimum Average Forward Load Current Real Maximum Average Forward Load Current Real Present Average Forward Load Current Reactive Minimum Average Forward Load Current Reactive Maximum Average Forward Load Current Reactive Present Average Minimum Tap Position Average Maximum Tap Position Average Maximum Percent Boost Average Maximum Percent Buck Average Reverse Load Voltage Minimum Average Reverse Load Voltage Maximum Average Reverse Load Voltage Present Average Reverse Compensated Voltage Minimum Average Reverse Compensated Voltage Maximum Page 10 Analog Input Points CL-7 Available Data Points Analog Input Points Description Average Reverse Compensated Voltage Present Average Reverse Load Current Minimum Average Reverse Load Current Maximum Average Reverse Load Current Present Average Reverse Source Voltage Minimum Average Reverse Source Voltage Maximum Average Reverse Source Voltage Present Total Reverse KVA Load Minimum Total Reverse KVA Load Maximum Total Reverse KVA Load Present Total Reverse kW Load Minimum Total Reverse kW Load Maximum Total Reverse kW Load Present Total Reverse KVAR Load Minimum Total Reverse KVAR Load Maximum Total Reverse KVAR Load Present Average Reverse Load Current Real Minimum Average Reverse Load Current Real Maximum Average Reverse Load Current Real Present Average Reverse Load Current Reactive Minimum Average Reverse Load Current Reactive Maximum Average Reverse Load Current Reactive Present VR1 Operations 24HR Counter VR1 Operations 30DY Counter VR1 Operations Month Counter VR1 Operations Last Month Counter VR1 Operations Year Counter VR1 Operations Last Year Counter VR1 TPI Neutral Resynch Counter VR1 Lower to Neutral Sync Retry Counter VR1 Raise to Neutral Sync Retry Counter VR1 Taps Past 16R Counter VR1 Taps Past 16L Counter Measured/Incremental TPI Mismatch Count COM1 Rx Message Counter COM2 Rx Message Counter COM1 Tx Message Counter COM2 Tx Message Counter COM1 Message Error Counter COM2 Message Error Counter VR2 Operations 24HR Counter VR3 Operations 24HR Counter VR2 Operations 30DY Counter VR3 Operations 30DY Counter VR2 Operations Month Counter VR3 Operations Month Counter VR2 Operations Last Month Counter VR3 Operations Last Month Counter VR2 Operations Year Counter VR3 Operations Year Counter VR2 Operations Last Year Counter VR3 Operations Last Year Counter VR2 TPI Neutral Resynch Counter VR3 TPI Neutral Resynch Counter VR2 Lower to Neutral Sync Retry Counter VR3 Lower to Neutral Sync Retry Counter VR2 Raise to Neutral Sync Retry Counter VR3 Raise to Neutral Sync Retry Counter VR2 Taps Past 16R Counter VR3 Taps Past 16R Counter VR2 Taps Past 16L Counter VR3 Taps Past 16L Counter Regulator Tap Position Sync Count Forward Set Voltage Forward Bandwidth Forward Time Delay Page 11 Analog Input Points CL-7 Available Data Points Analog Input Points Description VR1 Duration of Last Level1 VR1 Duration of Longest Level1 VR1 Duration of Last Level2 VR1 Duration of Longest Level2 VR1 Duration of Last Level3 VR1 Duration of Longest Level3 VR2 Duration of Last Level1 VR2 Duration of Longest Level1 VR2 Duration of Last Level2 VR2 Duration of Longest Level2 VR2 Duration of Last Level3 VR2 Duration of Longest Level3 VR3 Duration of Last Level1 VR3 Duration of Longest Level1 VR3 Duration of Last Level2 VR3 Duration of Longest Level2 VR3 Duration of Last Level3 VR3 Duration of Longest Level3 VR2 Basic Forward Set Voltage VR2 Basic Forward Bandwidth VR2 Basic Forward Time Delay VR2 Basic Forward LDC Resistance VR2 Basic Forward LDC Reactance VR2 Basic Reverse Set Voltage VR2 Basic Reverse Bandwidth VR2 Basic Reverse Time Delay VR2 Basic Reverse LDC Resistance VR2 Basic Reverse LDC Reactance VR3 Basic Forward Set Voltage VR3 Basic Forward Bandwidth VR3 Basic Forward Time Delay VR3 Basic Forward LDC Resistance VR3 Basic Forward LDC Reactance VR3 Basic Reverse Set Voltage VR3 Basic Reverse Bandwidth VR3 Basic Reverse Time Delay VR3 Basic Reverse LDC Resistance VR3 Basic Reverse LDC Reactance Nominal Secondary Load Voltage Software Version Revision Number value Software Version Revision Major Number Software Version Revision Minor Number Software Version Revision Developer Number Software Version Revision Date Software Version Revision Month Date Software Version Revision Year Page 12 Analog Input Points CL-7 Available Data Points Counter Input Points Description VR1 Operations Counter VR1 Operations 24HR Counter VR1 Operations 30DY Counter VR1 Operations Month Counter VR1 Operations Last Month Counter VR1 Operations Year Counter VR1 Operations Last Year Counter VR1 TPI Neutral Resynch Counter VR1 Lower to Neutral Sync Retry Counter VR1 Raise to Neutral Sync Retry Counter VR1 Taps Past 16R Counter VR1 Taps Past 16L Counter Measured/Incremental TPI Mismatch Count COM1 Rx Message Counter COM2 Rx Message Counter COM1 Tx Message Counter COM2 Tx Message Counter COM1 Message Error Counter COM2 Message Error Counter VR2 Operations Counter VR3 Operations Counter VR2 Operations 24HR Counter VR3 Operations 24HR Counter VR2 Operations 30DY Counter VR3 Operations 30DY Counter VR2 Operations Month Counter VR3 Operations Month Counter VR2 Operations Last Month Counter VR3 Operations Last Month Counter VR2 Operations Year Counter VR3 Operations Year Counter VR2 Operations Last Year Counter VR3 Operations Last Year Counter VR2 TPI Neutral Resynch Counter VR3 TPI Neutral Resynch Counter VR2 Lower to Neutral Sync Retry Counter VR3 Lower to Neutral Sync Retry Counter VR2 Raise to Neutral Sync Retry Counter VR3 Raise to Neutral Sync Retry Counter VR2 Taps Past 16R Counter VR3 Taps Past 16R Counter VR2 Taps Past 16L Counter VR3 Taps Past 16L Counter Regulator Tap Position Sync Count Page 13 Counter Input Points CL-7 Available Data Points Binary Output Points Description VR1 Raise Tap VR1 Lower Tap Auto Block Enable VR1 Source Side Voltage Calculation Interval Operations Counters Enable VR1 Operations Counter Month Reset VR1 Operations Counter Year Reset VR1 Operations Counter 24HR Reset VR1 Operations Counter 30DY Reset VR1 Operations Counter Last Month Reset VR1 Operations Counter Last Year Reset VR1 TPI Neutral Mismatch Reset VR1 Lower To Neutral sync Retry Count Reset VR1 Raise To Neutral Sync Retry Count Reset VR1 Taps Past 16L Counter Reset VR1 Taps Past 16R Counter Reset Rx COM1 Counter Reset Rx COM2 Counter Reset Tx COM1 Counter Reset Tx COM2 Counter Reset Message Error COM1 Counter Reset Message Error COM2 Counter Reset Reset Energy All Reset All Demand Values Event Recorder Enable Data Profiler Enable Data Profiler Snapshot Tap To Neutral Feature Enable PMT Mode A Enable PMT Mode B Enable PMT Mode A Test PMT Mode B Test Data Alarms Enable Status Alarms Enable VR1 Time On Tap Reset Top Side Port LoopShare Enabled Bottom Side Port LoopShare Enabled Leader/Follower Enable Configurable Logic Output from SCADA Tap to Neutral Activate Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate Configurable Logic Output from SCADA 1 Configurable Logic Output from SCADA 2 Configurable Logic Output from SCADA 3 Configurable Logic Output from SCADA 4 Configurable Logic Output from SCADA 5 Configurable Logic Output from SCADA 6 Configurable Logic Output from SCADA 7 Configurable Logic Output from SCADA 8 AltConfig1 Auto Block Enable AltConfig1 Tap To Neutral Feature Enable AltConfig2 Auto Block Enable AltConfig2 Tap To Neutral Feature Enable AltConfig3 Auto Block Enable AltConfig3 Tap To Neutral Feature Enable ARL AltConfigTerminate ARLC Ready ARLC Activate Max Deviation Cancel Alt Mode Test Battery VR2 Raise Tap VR3 Raise Tap VR2 Lower Tap VR3 Lower Tap VR2 Source Side Voltage Calculation Page 14 Binary Output Points CL-7 Available Data Points Binary Output Points Description VR3 Source Side Voltage Calculation VR2 Operations Counter Month Reset VR3 Operations Counter Month Reset VR2 Operations Counter Year Reset VR3 Operations Counter Year Reset VR2 Operations Counter 24HR Reset VR3 Operations Counter 24HR Reset VR2 Operations Counter 30DY Reset VR3 Operations Counter 30DY Reset VR2 Operations Counter Last Month Reset VR3 Operations Counter Last Month Reset VR2 Operations Counter Last Year Reset VR3 Operations Counter Last Year Reset VR2 TPI Neutral Mismatch Reset VR3 TPI Neutral Mismatch Reset VR2 Lower to neutral sync retry count Reset VR3 Lower to neutral sync retry count Reset VR2 Raise to neutral sync retry count Reset VR3 Raise to neutral sync retry count Reset VR2 Taps Past 16L Counter Reset VR3 Taps Past 16L Counter Reset VR2 Taps Past 16R Counter Reset VR3 Taps Past 16R Counter Reset VR2 Time On Tap Reset VR3 Time On Tap Reset Reset KWHR Fwd Reset KWHR Rev Reset KVARHR Fwd Reset KVARHR Rev Tap Position Meas-Incr Mismatch Count Reset Daylight Saving Time Enable Reset Forward Load Volts Min Reset Forward Load Volts Max Reset Forward Comp Volts Min Reset Forward Comp Volts Max Reset Forward Source Volts Min Reset Forward Source Volts Max Reset Forward Load Current Min Reset Forward Load Current Max Reset Forward kVA Load Min Reset Forward kVA Load Max Reset Forward kW Load Min Reset Forward kW Load Max Reset Forward kvar Load Min Reset Forward kvar Load Max Reset Forward Reactive Load Current Min Reset Forward Reactive Load Current Max Reset Forward Real Load Current Min Reset Forward Real Load Current Max VR1 Min Tap Position Reset VR1 Max Tap Position Reset VR2 Min Tap Position Reset VR2 Max Tap Position Reset VR3 Min Tap Position Reset VR3 Max Tap Position Reset VR1 Min Boost Reset VR1 Max Boost Reset VR2 Min Boost Reset VR2 Max Boost Reset VR3 Min Boost Reset VR3 Max Boost Reset Reset Reverse Load Volts Min Reset Reverse Load Volts Max Reset Reverse Comp Volts Min Reset Reverse Comp Volts Max Reset Reverse Source Volts Min Page 15 Binary Output Points CL-7 Available Data Points Binary Output Points Description Reset Reverse Source Volts Max Reset Reverse Load Current Min Reset Reverse Load Current Max Reset Reverse kVA Load Min Reset Reverse kVA Load Max Reset Reverse kW Load Min Reset Reverse kW Load Max Reset Reverse kvar Load Min Reset Reverse kvar Load Max Reset Reverse Reactive Load Current Min Reset Reverse Reactive Load Current Max Reset Reverse Real Load Current Min Reset Reverse Real Load Current Max Configurable Logic Output from SCADA 9 Configurable Logic Output from SCADA 10 Configurable Logic Output from SCADA 11 Configurable Logic Output from SCADA 12 Configurable Logic Output from SCADA 13 Configurable Logic Output from SCADA 14 Configurable Logic Output from SCADA 15 Configurable Logic Output from SCADA 16 Configurable Logic Output from SCADA 17 Configurable Logic Output from SCADA 18 Configurable Logic Output from SCADA 19 Configurable Logic Output from SCADA 20 Configurable Logic Output from SCADA 21 Configurable Logic Output from SCADA 22 Configurable Logic Output from SCADA 23 Configurable Logic Output from SCADA 24 Configurable Logic Output from SCADA 25 Configurable Logic Output from SCADA 26 Configurable Logic Output from SCADA 27 Configurable Logic Output from SCADA 28 Configurable Logic Output from SCADA 29 Configurable Logic Output from SCADA 30 Configurable Logic Output from SCADA 31 Configurable Logic Output from SCADA 32 Configurable Logic Output from SCADA 33 Configurable Logic Output from SCADA 34 Configurable Logic Output from SCADA 35 Configurable Logic Output from SCADA 36 Configurable Logic Output from SCADA 37 Configurable Logic Output from SCADA 38 Configurable Logic Output from SCADA 39 Configurable Logic Output from SCADA 40 HMI Remote Security Override Mode Regulator Tap Position Sync Count Reset Voltage Sag Monitoring Enable Reset All Last And Longest Voltage Sag Duration Block Before Remote Tap User Input1 User Input2 User Input3 User Input4 Page 16 Binary Output Points CL-7 Available Data Points Analog Output Points Description Forward Set Voltage Forward Bandwidth Forward Time Delay Forward LDC Resistance Forward LDC Reactance Reverse Set Voltage Reverse Bandwidth Reverse Time Delay Reverse LDC Resistance Reverse LDC Reactance Reverse Sense Mode Reverse Threshold Voltage Limiting Mode Voltage Limiting High Voltage Limiting Low Voltage Reduction Mode Local/Digital-Remote Voltage Reduction Setting % Analog Voltage Reduction Setting 1 % Analog Voltage Reduction Setting 2 % Analog Voltage Reduction Setting 3 % Voltage Reduction Analog Step Count Voltage Reduction Per Step Soft Add-Amp Mode Soft Add-Amp High Soft Add-Amp Low Control ID Number Control Operating Mode Demand Time Interval HMI Remote Security Override Elevation VR1 Regulator Type VR1 Tap Changer Type TPI Sense Method VR1 Regulator Configuration System Line Voltage VR1 Overall PT Ratio VR1 Internal PT Ratio VR1 CT Rating Data Profiler Duration Data Profiler Sample Period PMT Mode A Time Delay PMT Mode B Current Limit PMT Mode B Max Dev PMT Mode B Time Delay Com Top Side DNP Remote Address Com Top Side DNP Active Map Com Bottom Side DNP Remote Address Com Bottom Side DNP Active Map LoopShare Comms Timeout, Sec LoopShare Table Assignment LoopShare Transmit Delay, mSec Leader/Follower Devices Configured Leader/Follower Tap Wait Timer, mSec Leader/Follower Timout, Sec Leader/Follower Retry Delay, Sec Leader/Follower Retries Leader/Follower Designation Leader/Follower Mode VR1 Operations Counter AltConfigMode AltConfigSelect AltConfig1 Forward Set Voltage AltConfig1 Forward Bandwidth AltConfig1 Forward LDC Reactance AltConfig1 Forward LDC Resistance AltConfig1 Forward Time Delay Page 17 Analog Output Points CL-7 Available Data Points Analog Output Points Description AltConfig1 Reverse Bandwidth AltConfig1 Reverse LDC Reactance AltConfig1 Reverse LDC Resistance AltConfig1 Reverse Sense Mode AltConfig1 Reverse Set Voltage AltConfig1 Reverse Time Delay AltConfig1 Operating Mode AltConfig1 Voltage Limiting Mode AltConfig1 Voltage Limiting High AltConfig1 Voltage Limiting Low AltConfig1 Voltage Reduction Mode AltConfig1 LOCAL/DIGITAL-REMOTE Voltage Reduction Setting % AltConfig1 Analog Voltage Reduction Setting 1 % AltConfig1 Analog Voltage Reduction Setting 2 % AltConfig1 Analog Voltage Reduction Setting 3 % AltConfig1 Soft Add-Amp State AltConfig1 Soft Add-Amp High AltConfig1 Soft Add-Amp Low AltConfig2 Forward Set Voltage AltConfig2 Forward Bandwidth AltConfig2 Forward LDC Reactance AltConfig2 Forward LDC Resistance AltConfig2 Forward Time Delay AltConfig2 Reverse Bandwidth AltConfig2 Reverse LDC Reactance AltConfig2 Reverse LDC Resistance AltConfig2 Reverse Sense Mode AltConfig2 Reverse Set Voltage AltConfig2 Reverse Time Delay AltConfig2 Operating Mode AltConfig2 Voltage Limiting Mode AltConfig2 Voltage Limiting High AltConfig2 Voltage Limiting Low AltConfig2 Voltage Reduction Mode AltConfig2 LOCAL/DIGITAL-REMOTE Voltage Reduction Setting % AltConfig2 Analog Voltage Reduction Setting 1 % AltConfig2 Analog Voltage Reduction Setting 2 % AltConfig2 Analog Voltage Reduction Setting 3 % AltConfig2 Soft Add-Amp State AltConfig2 Soft Add-Amp High AltConfig2 Soft Add-Amp Low AltConfig3 Forward Set Voltage AltConfig3 Forward Bandwidth AltConfig3 Forward LDC Reactance AltConfig3 Forward LDC Resistance AltConfig3 Forward Time Delay AltConfig3 Reverse Bandwidth AltConfig3 Reverse LDC Reactance AltConfig3 Reverse LDC Resistance AltConfig3 Reverse Sense Mode AltConfig3 Reverse Set Voltage AltConfig3 Reverse Time Delay AltConfig3 Operating Mode AltConfig3 Voltage Limiting Mode AltConfig3 Voltage Limiting High AltConfig3 Voltage Limiting Low AltConfig3 Voltage Reduction Mode AltConfig3 LOCAL/DIGITAL-REMOTE Voltage Reduction Setting % AltConfig3 Analog Voltage Reduction Setting 1 % AltConfig3 Analog Voltage Reduction Setting 2 % AltConfig3 Analog Voltage Reduction Setting 3 % AltConfig3 Soft Add-Amp State AltConfig3 Soft Add-Amp High AltConfig3 Soft Add-Amp Low ARL AltConfigActivate ARL AltConfigTimer Page 18 Analog Output Points CL-7 Available Data Points Analog Output Points Description VR2 Regulator Type VR3 Regulator Type VR2 Tap Changer Type VR3 Tap Changer Type VR2 Regulator Configuration VR3 Regulator Configuration VR2 Overall PT Ratio VR3 Overall PT Ratio VR2 Internal PT Ratio VR3 Internal PT Ratio VR2 CT Rating VR3 CT Rating VR2 Operations Counter VR3 Operations Counter Auto Tap Dead Phase Mode Delay Timer Dead Phase VR2 Basic Forward Set Voltage VR2 Basic Forward Bandwidth VR2 Basic Forward Time Delay VR2 Basic Forward LDC Resistance VR2 Basic Forward LDC Reactance VR2 Basic Reverse Set Voltage VR2 Basic Reverse Bandwidth VR2 Basic Reverse Time Delay VR2 Basic Reverse LDC Resistance VR2 Basic Reverse LDC Reactance VR3 Basic Forward Set Voltage VR3 Basic Forward Bandwidth VR3 Basic Forward Time Delay VR3 Basic Forward LDC Resistance VR3 Basic Forward LDC Reactance VR3 Basic Reverse Set Voltage VR3 Basic Reverse Bandwidth VR3 Basic Reverse Time Delay VR3 Basic Reverse LDC Resistance VR3 Basic Reverse LDC Reactance Nominal Secondary Load Voltage Bias Co-Generation Alt Mode AltConfig1 Bias Co-Generation Alt Mode AltConfig2 Bias Co-Generation Alt Mode AltConfig3 Bias Co-Generation Alt Mode Page 19 Analog Output Points Technical Data TD225006EN Communications Point Availability Effective June 2015 Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton’s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries © 2015 Eaton All Rights Reserved Printed in USA Publication No. TD225006EN June 2015 Supersedes R225-70-35 (5/2013) Eaton is a registered trademark. All other trademarks are property of their respective owners. For Eaton's Cooper Power series CL-7 voltage regulator control information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.