Communications Point Data Base COOPER POWER SERIES

Voltage Regulators
Technical Data
TD225004EN
Effective XXX 2015
Supersedes 240-40 August 2012
COOPER POWER
SERIES
Communications Point Data Base
for Serial and Ethernet Communications Protocol DNP3
For use with Eaton’s Cooper Power series
CL-7 Voltage Regulator Control
CL-7 DNP3 Device Profile Data Dictionary
CL-7 DNP3 Map Points
June 3, 2015
v2.00
THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE PROPERTY OF EATON.
UNAUTHORIZED REPRODUCTION OR MODIFICATION IS PROHIBITED.
Document
1.00
2.00
Date
4/29/2013
6/3/2015
Description
Initial Release
Updates for Summer 2015 release
This document references the "CL7 Default With Events" and "CL7 Multiphase Default With Events" point maps available
on the CL-7 control and in the ProView NXG software.
Page 1
Cover Page
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
VR1 Bandwidth Low
VR1 Bandwidth High
VR1 Voltage Limiter Low
VR1 Voltage Limiter High
Voltage Reduction Active
VR1 Auto Operation Blocking Status Blocked (Follows FC069)
VR1 HMI LED Auto Tap Blocked ON
VR1 System Power Direction Indeterminate
VR1 System Power Direction Reverse
VR1 Control Power Direction Reverse
VR1 Blocking Relay Active
VR1 HMI LED Neutral Position On
VR1 HMI Switch Auto/Manual Auto
HMI Switch Supervisory Off
HMI LED Alarm On
HMI LED Warning On
HMI LED Diagnostic Error On
VR1 Motor Trouble
Tap To Neutral Active
Soft Add-Amp Active
AltConfigActive
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic User Defined LED 1 On
Configurable Logic User Defined LED 2 On
Configurable Logic User Defined LED 3 On
Configurable Logic Point 01 to SCADA
Configurable Logic Point 02 to SCADA
Configurable Logic Point 03 to SCADA
Configurable Logic Point 04 to SCADA
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
Hex Index
Default
Event
Class
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 2
Default Event Variation
Obj 02 Var 2 Binary input with time
Binary Inputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
VR1 Operations Counter
VR1 Operations 24HR Counter
VR1 Operations 30DY Counter
VR1 Operations Month Counter
VR1 Operations Last Month Counter
VR1 Operations Year Counter
VR1 Operations Last Year Counter
VR1 TPI Neutral Resynch Counter
VR1 Lower to Neutral Sync Retry Counter
VR1 Raise to Neutral Sync Retry Counter
VR1 Taps Past 16R Counter
VR1 Taps Past 16L Counter
Measured/Incremental TPI Mismatch Count
COM1 Rx Message Counter
COM2 Rx Message Counter
COM1 Tx Message Counter
COM2 Tx Message Counter
COM1 Message Error Counter
COM2 Message Error Counter
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
Page 3
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Event Deadband
Class
3
3
3
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
Counter Inputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
VR1 Load Voltage Secondary
VR1 Load Voltage Primary
VR1 Compensated Voltage Secondary
VR1 Load Current Primary
VR1 Source Voltage Secondary
VR1 Source Voltage Primary
VR1 Tap Position
VR1 Percent Reg
VR1 Power Factor
VR1 KVA Load
VR1 kW Load
VR1 KVAR Load
Frequency
VR1 Harm Total Voltage Harmonics
VR1 Harm Total Current Harmonics
VR1 kWh Forward
VR1 KWH Reverse
VR1 KQH Forward
VR1 KQH Reverse
VR1 Operation Counter
VR1 Load Current Real
VR1 Load Current Reactive
VR1 Phase Angle
Voltage Reduction In Effect
Active Configuration
Active Adaptive Add Amp Level
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10
100
10
10
10
100
1
10
1000
10
10
10
100
10
10
100
100
100
100
1
10
10
1
10
1
1
Page 4
Units
Deadband
Volts
kVolts
Volts
Amps
Volts
kVolts
-%
-kVA
kW
kvar
Hz
%
%
kWHr
kWHr
kvarHr
kvarHr
-Amps
Amps
Degrees
%
%
--
10
10
10
10
10
10
1
10
1
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Analog Inputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Description
Forward Set Voltage
Forward Bandwidth
Forward Time Delay
Forward LDC Resistance
Forward LDC Reactance
Reverse Set Voltage
Reverse Bandwidth
Reverse Time Delay
Reverse LDC Resistance
Reverse LDC Reactance
Reverse Sense Mode
Reverse Threshold
Voltage Limiting Mode
Voltage Limiting High
Voltage Limiting Low
Voltage Reduction Mode
Local/Digital-Remote Voltage Reduction Setting %
Analog Voltage Reduction Setting 1 %
Analog Voltage Reduction Setting 2 %
Analog Voltage Reduction Setting 3 %
Voltage Reduction Analog Step Count
Voltage Reduction Per Step
Soft Add-Amp Mode
Soft Add-Amp High
Soft Add-Amp Low
Control ID Number
Control Operating Mode
Demand Time Interval
HMI Remote Security Override Elevation
VR1 Regulator Type
VR1 Tap Changer Type
TPI Sense Method
VR1 Regulator Configuration
System Line Voltage
VR1 Overall PT Ratio
VR1 Internal PT Ratio
VR1 CT Rating
Data Profiler Duration
Data Profiler Sample Period
PMT Mode A Time Delay
PMT Mode B Current Limit
PMT Mode B Max Dev
PMT Mode B Time Delay
Com Top Side DNP Remote Address
Com Top Side DNP Active Map
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
10
10
1
10
10
10
10
1
10
10
1
1
1
10
10
1
10
10
10
10
1
10
1
1
1
1
1
10
1
1
1
1
1
1
10
10
1
1
1
1
1
1
1
1
1
Page 5
Units
Volts
Volts
Seconds
Volts
Volts
Volts
Volts
Seconds
Volts
Volts
-%
-Volts
Volts
-%
%
%
%
-%
-----Seconds
-----Volts
--Amps
Minutes
Minutes
Days
%
# of Taps
Days
--Analog Outputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Description
Com Bottom Side DNP Remote Address
Com Bottom Side DNP Active Map
LoopShare Comms Timeout
LoopShare Table Assignment
LoopShare Transmit Delay
Leader/Follower Devices Configured
Leader/Follower Tap Wait Timer
Leader/Follower Timeout
Leader/Follower Retry Delay
Leader/Follower Retries
Leader/Follower Designation
Leader/Follower Mode
VR1 Operations Counter
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
45
46
47
48
49
50
51
52
53
54
55
56
57
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Units
Scale Factor
Class
none
1
-none
1
-none
1
Seconds
none
1
-none
1
mSec
none
1
-none
1
mSec
none
1
Seconds
none
1
Seconds
none
1
-none
1
-none
1
-none
1
--
Page 6
Analog Outputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
Desc
Operation Type
Operation
(Support)
Mask
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Latched
Latched
Self-Resetting
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Latched
Latched
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Default
Condition
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Conditioned by
Supervisory State Description
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 7
VR1 Raise Tap
VR1 Lower Tap
Auto Block Enable
VR1 Source Side Voltage Calculation
Interval Operations Counters Enable
VR1 Operations Counter Month Reset
VR1 Operations Counter Year Reset
VR1 Operations Counter 24HR Reset
VR1 Operations Counter 30DY Reset
VR1 Operations Counter Last Month Reset
VR1 Operations Counter Last Year Reset
VR1 TPI Neutral Mismatch Reset
VR1 Lower To Neutral Sync Retry Count Reset
VR1 Raise To Neutral Sync Retry Count Reset
VR1 Taps Past 16L Counter Reset
VR1 Taps Past 16R Counter Reset
Rx COM1 Counter Reset
Rx COM2 Counter Reset
Tx COM1 Counter Reset
Tx COM2 Counter Reset
Message Error COM1 Counter Reset
Message Error COM2 Counter Reset
Reset Energy All
Reset All Demand Values
Event Recorder Enable
Data Profiler Enable
Data Profiler Snapshot
Tap To Neutral Feature Enable
PMT Mode A Enable
PMT Mode B Enable
PMT Mode A Test
PMT Mode B Test
Data Alarms Enable
Status Alarms Enable
VR1 Time On Tap Reset
Top Side Port LoopShare Enabled
Bottom Side Port LoopShare Enabled
Leader/Follower Enable
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic Output from SCADA 1
Configurable Logic Output from SCADA 2
Configurable Logic Output from SCADA 3
Configurable Logic Output from SCADA 4
HMI Remote Security Override Mode
Binary Outputs, Single Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
VR1 Bandwidth Low
VR2 Bandwidth Low
VR3 Bandwidth Low
VR1 Bandwidth High
VR2 Bandwidth High
VR3 Bandwidth High
VR1 Voltage Limiter Low
VR2 Voltage Limiter Low
VR3 Voltage Limiter Low
VR1 Voltage Limiter High
VR2 Voltage Limiter High
VR3 Voltage Limiter High
Voltage Reduction Active
VR1 Auto Operation Blocking Status Blocked (Follows FC069)
VR2 Auto Operation Blocking Status Blocked
VR3 Auto Operation Blocking Status Blocked
VR1 HMI LED Auto Tap Blocked ON
VR2 HMI LED Auto Tap Blocked ON
VR3 HMI LED Auto Tap Blocked ON
VR1 System Power Direction Indeterminate
VR2 System Power Direction Indeterminate
VR3 System Power Direction Indeterminate
VR1 System Power Direction Reverse
VR2 System Power Direction Reverse
VR3 System Power Direction Reverse
VR1 Control Power Direction Reverse
VR2 Control Power Direction Reverse
VR3 Control Power Direction Reverse
VR1 Blocking Relay Active
VR1 HMI LED Neutral Position On
VR2 HMI LED Neutral Position On
VR3 HMI LED Neutral Position On
VR1 HMI Switch Auto/Manual Auto
VR2 HMI Switch Auto/Manual Auto
VR3 HMI Switch Auto/Manual Auto
HMI Switch Supervisory Off
HMI LED Alarm On
HMI LED Warning On
HMI LED Diagnostic Error On
VR1 Motor Trouble
VR2 Motor Trouble
VR3 Motor Trouble
Tap To Neutral Active
Soft Add-Amp Active
AltConfigActive
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
Hex Index
Default
Event
Class
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Page 8
Default Event Variation
Obj 02 Var 2 Binary input with time
Binary Inputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Binary Inputs
Description
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic User Defined LED 1 On
Configurable Logic User Defined LED 2 On
Configurable Logic User Defined LED 3 On
Configurable Logic Point 01 to SCADA
Configurable Logic Point 02 to SCADA
Configurable Logic Point 03 to SCADA
Configurable Logic Point 04 to SCADA
Default Static Variation
Obj 01 Var 01 Binary input w/o status
Index
Hex Index
45
46
47
48
49
50
51
52
53
54
2D
2E
2F
30
31
32
33
34
35
36
Page 9
Default Event Variation
Obj 02 Var 2 Binary input with time
Default
Event
Class
1
1
1
1
1
1
1
1
1
1
Binary Inputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Counters
Description
VR1 Operations Counter
VR2 Operations Counter
VR3 Operations Counter
VR1 Operations 24HR Counter
VR2 Operations 24HR Counter
VR3 Operations 24HR Counter
VR1 Operations 30DY Counter
VR2 Operations 30DY Counter
VR3 Operations 30DY Counter
VR1 Operations Month Counter
VR2 Operations Month Counter
VR3 Operations Month Counter
VR1 Operations Last Month Counter
VR2 Operations Last Month Counter
VR3 Operations Last Month Counter
VR1 Operations Year Counter
VR2 Operations Year Counter
VR3 Operations Year Counter
VR1 Operations Last Year Counter
VR2 Operations Last Year Counter
VR3 Operations Last Year Counter
VR1 TPI Neutral Resynch Counter
VR2 TPI Neutral Resynch Counter
VR3 TPI Neutral Resynch Counter
VR1 Lower to Neutral Sync Retry Counter
VR2 Lower to Neutral Sync Retry Counter
VR3 Lower to Neutral Sync Retry Counter
VR1 Raise to Neutral Sync Retry Counter
VR2 Raise to Neutral Sync Retry Counter
VR3 Raise to Neutral Sync Retry Counter
VR1 Taps Past 16R Counter
VR2 Taps Past 16R Counter
VR3 Taps Past 16R Counter
VR1 Taps Past 16L Counter
VR2 Taps Past 16L Counter
VR3 Taps Past 16L Counter
Regulator Tap Position Sync Count
COM1 Rx Message Counter
COM2 Rx Message Counter
COM1 Tx Message Counter
COM2 Tx Message Counter
COM1 Message Error Counter
COM2 Message Error Counter
Default Static Variation
Obj 20 Var 2 16 bit Counter
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
Default Event Variation
Obj 22 Var 2 16 bit Counter w/o time
Default
Event Deadband
Class
0
0
0
0
0
0
0
0
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
Page 10
Counter Inputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
VR1 Load Voltage Secondary
VR2 Load Voltage Secondary
VR3 Load Voltage Secondary
Average Load Voltage Secondary
VR1 Load Voltage Primary
VR2 Load Voltage Primary
VR3 Load Voltage Primary
Average Load Voltage Primary
VR1 Compensated Voltage Secondary
VR2 Compensated Voltage Secondary
VR3 Compensated Voltage Secondary
Average Compensated Voltage Secondary
VR1 Load Current Primary
VR2 Load Current Primary
VR3 Load Current Primary
Average Load Current Primary
VR1 Source Voltage Secondary
VR2 Source Voltage Secondary
VR3 Source Voltage Secondary
Average Source Voltage Secondary
VR1 Source Voltage Primary
VR2 Source Voltage Primary
VR3 Source Voltage Primary
Average Source Voltage Primary
VR1 Tap Position
VR2 Tap Position
VR3 Tap Position
Average Tap Position
VR1 Percent Reg
VR2 Percent Reg
VR3 Percent Reg
Average Percent Reg
VR1 Power Factor
VR2 Power Factor
VR3 Power Factor
Average Power Factor
Regulator Tap Position Sync Count
VR2 KVA Load
VR3 KVA Load
Total KVA Load
VR1 kW Load
VR2 kW Load
VR3 kW Load
Total kW Load
VR1 KVAR Load
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10
10
10
10
100
100
100
100
10
10
10
10
10
10
10
10
10
10
10
10
100
100
100
100
1
1
1
1
10
10
10
10
1000
1000
1000
1000
1
10
10
10
10
10
10
10
10
Page 11
Units
Deadband
Volts
Volts
Volts
Volts
kVolts
kVolts
kVolts
kVolts
Volts
Volts
Volts
Volts
Amps
Amps
Amps
Amps
Volts
Volts
Volts
Volts
kVolts
kVolts
kVolts
kVolts
----%
%
%
%
-----kVA
kVA
kVA
kW
kW
kW
kW
kvar
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
1
10
10
10
10
10
10
10
1
10
10
10
10000
10
10
10
10
10
10
10
10
Analog Inputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
INPUT SUBSYSTEM
Analog Inputs
Description
VR2 KVAR Load
VR3 KVAR Load
Total KVAR Load
Frequency
VR1 Harm Total Voltage Harmonics
VR2 Harm Total Voltage Harmonics
VR3 Harm Total Voltage Harmonics
VR1 Harm Total Current Harmonics
VR2 Harm Total Current Harmonics
VR3 Harm Total Current Harmonics
VR1 kWh Forward
VR2 kWh Forward
VR3 kWh Forward
Total kWh Forward
VR1 KWH Reverse
VR2 KWH Reverse
VR3 KWH Reverse
Total KWH Reverse
VR1 KQH Forward
VR2 KQH Forward
VR3 KQH Forward
Total KQH Forward
VR1 KQH Reverse
VR2 KQH Reverse
VR3 KQH Reverse
Total KQH Reverse
VR1 Operation Counter
VR2 Operation Counter
VR3 Operation Counter
Diagnostic Error Code
VR1 Load Current Real
VR2 Load Current Real
VR3 Load Current Real
Average Load Current Real
VR1 Load Current Reactive
VR2 Load Current Reactive
VR3 Load Current Reactive
Average Load Current Reactive
VR1 Phase Angle
VR2 Phase Angle
VR3 Phase Angle
Voltage Reduction In Effect
Active Configuration
Active Adaptive Add Amp Level
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
0
10
0
10
0
10
0
100
0
10
0
10
0
10
0
10
0
10
0
1
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
100
0
1
0
1
0
1
0
1
0
10
0
10
0
10
0
10
0
10
0
10
0
10
0
10
0
1
0
1
0
1
0
10
0
1
0
1
Page 12
Units
Deadband
kvar
kvar
kvar
Hz
%
%
%
%
%
%
kWHr
kWHr
kWHr
kW
kWHr
kWHr
kWHr
kW
kvarHr
kvarHr
kvarHr
kvar
kvarHr
kvarHr
kvarHr
kvar
----Amps
Amps
Amps
Amps
Amps
Amps
Amps
Amps
Degrees
Degrees
Degrees
%
%
--
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
10
Analog Inputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Description
Forward Set Voltage
Forward Bandwidth
Forward Time Delay
Forward LDC Resistance
Forward LDC Reactance
Reverse Set Voltage
Reverse Bandwidth
Reverse Time Delay
Reverse LDC Resistance
Reverse LDC Reactance
Reverse Sense Mode
Reverse Threshold
Voltage Limiting Mode
Voltage Limiting High
Voltage Limiting Low
Voltage Reduction Mode
Local/Digital-Remote Voltage Reduction Setting %
Analog Voltage Reduction Setting 1 %
Analog Voltage Reduction Setting 2 %
Analog Voltage Reduction Setting 3 %
Voltage Reduction Analog Step Count
Voltage Reduction Per Step
Soft Add-Amp Mode
Soft Add-Amp High
Soft Add-Amp Low
Control ID Number
Control Operating Mode
Demand Time Interval
HMI Remote Security Override Elevation
VR1 Regulator Type
VR2 Regulator Type
VR3 Regulator Type
VR1 Tap Changer Type
VR2 Tap Changer Type
VR3 Tap Changer Type
TPI Sense Method
VR1 Regulator Configuration
VR2 Regulator Configuration
VR3 Regulator Configuration
System Line Voltage
VR1 Overall PT Ratio
VR2 Overall PT Ratio
VR3 Overall PT Ratio
VR1 Internal PT Ratio
VR2 Internal PT Ratio
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
none
10
10
1
10
10
10
10
1
10
10
1
1
1
10
10
1
10
10
10
10
1
10
1
1
1
1
1
10
1
1
1
1
1
1
1
1
1
1
1
1
10
10
10
10
10
Page 13
Units
Volts
Volts
Seconds
Volts
Volts
Volts
Volts
Seconds
Volts
Volts
-%
-Volts
Volts
-%
%
%
%
-%
-----Seconds
-----------Volts
-----Analog Outputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM
Analog Outputs
Description
VR3 Internal PT Ratio
VR1 CT Rating
VR2 CT Rating
VR3 CT Rating
Data Profiler Duration
Data Profiler Sample Period
PMT Mode A Time Delay
PMT Mode B Current Limit
PMT Mode B Max Dev
PMT Mode B Time Delay
Com Top Side DNP Remote Address
Com Top Side DNP Active Map
Com Bottom Side DNP Remote Address
Com Bottom Side DNP Active Map
LoopShare Comms Timeout
LoopShare Table Assignment
LoopShare Transmit Delay
Leader/Follower Devices Configured
Leader/Follower Tap Wait Timer
Leader/Follower Timout, Sec
Leader/Follower Retry Delay
Leader/Follower Retries
Leader/Follower Designation
Leader/Follower Mode
VR1 Operations Counter
Not Used
VR2 Operations Counter
VR3 Operations Counter
Default Static Variation
Obj 30 Var 2 16 bit
Index
Hex Index
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
2D
2E
2F
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
Default Event Variation
Obj 32 Var 2 16 bit w/o time
Default
Division
Event
Scale Factor
Class
none
10
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
none
1
--none
1
none
1
Page 14
Units
-Amps
Amps
Amps
Minutes
Minutes
Days
%
# of Taps
Days
----Seconds
-mSec
-mSec
Seconds
Seconds
--------
Analog Outputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
30
31
32
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
Desc
Operation Type
Operation
(Support)
Mask
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
Self-Resetting
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Default
Condition
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Conditioned by
Supervisory State Description
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Page 15
VR1 Raise Tap
VR2 Raise Tap
VR3 Raise Tap
VR1 Lower Tap
VR2 Lower Tap
VR3 Lower Tap
Auto Block Enable
VR1 Source Side Voltage Calculation
VR2 Source Side Voltage Calculation
VR3 Source Side Voltage Calculation
Interval Operations Counters Enable
VR1 Operations Counter Month Reset
VR2 Operations Counter Month Reset
VR3 Operations Counter Month Reset
VR1 Operations Counter Year Reset
VR2 Operations Counter Year Reset
VR3 Operations Counter Year Reset
VR1 Operations Counter 24HR Reset
VR2 Operations Counter 24HR Reset
VR3 Operations Counter 24HR Reset
VR1 Operations Counter 30DY Reset
VR2 Operations Counter 30DY Reset
VR3 Operations Counter 30DY Reset
VR1 Operations Counter Last Month Reset
VR2 Operations Counter Last Month Reset
VR3 Operations Counter Last Month Reset
VR1 Operations Counter Last Year Reset
VR2 Operations Counter Last Year Reset
VR3 Operations Counter Last Year Reset
VR1 TPI Neutral Mismatch Reset
VR2 TPI Neutral Mismatch Reset
VR3 TPI Neutral Mismatch Reset
VR1 Lower To Neutral Sync Retry Count Reset
VR2 Lower To Neutral Sync Retry Count Reset
VR3 Lower To Neutral Sync Retry Count Reset
VR1 Raise To Neutral Sync Retry Count Reset
VR2 Raise To Neutral Sync Retry Count Reset
VR3 Raise To Neutral Sync Retry Count Reset
VR1 Taps Past 16L Counter Reset
VR2 Taps Past 16L Counter Reset
VR3 Taps Past 16L Counter Reset
VR1 Taps Past 16R Counter Reset
VR2 Taps Past 16R Counter Reset
VR3 Taps Past 16R Counter Reset
Rx COM1 Counter Reset
Rx COM2 Counter Reset
Tx COM1 Counter Reset
Tx COM2 Counter Reset
Message Error COM1 Counter Reset
Message Error COM2 Counter Reset
Reset Energy All
Binary Outputs, Multi Phase
CL-7 DNP3 Device Profile Data Dictionary
OUTPUT SUBSYSTEM - Control Output Relay Block Operations and Status
Default Static Variation
Description
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Binary Output
Index Hex Index Obj Var
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
54
55
56
57
58
59
5A
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
Desc
Operation Type
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
CROB
Self-Resetting
Latched
Latched
Self-Resetting
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Latched
Latched
Self-Resetting
Self-Resetting
Self-Resetting
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Latched
Self-Resetting
Self-Resetting
Latched
Operation
(Support)
Mask
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
0xff
Default
Condition
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Conditioned by
Supervisory State
(Factory Default)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Description
Reset All Demand Values
Event Recorder Enable
Data Profiler Enable
Data Profiler Snapshot
Tap To Neutral Feature Enable
PMT Mode A Enable
PMT Mode B Enable
PMT Mode A Test
PMT Mode B Test
Data Alarms Enable
Status Alarms Enable
VR1 Time On Tap Reset
VR2 Time On Tap Reset
VR3 Time On Tap Reset
Top Side Port LoopShare Enabled
Bottom Side Port LoopShare Enabled
Leader/Follower Enable
Configurable Logic Output from SCADA Tap to Neutral Activate
Configurable Logic Output from SCADA Voltage Reduction Level 1 Activate
Configurable Logic Output from SCADA Voltage Reduction Level 2 Activate
Configurable Logic Output from SCADA 1
Configurable Logic Output from SCADA 2
Configurable Logic Output from SCADA 3
Configurable Logic Output from SCADA 4
Configurable Logic Output from SCADA 5
Configurable Logic Output from SCADA 6
Configurable Logic Output from SCADA 7
Configurable Logic Output from SCADA 8
AltConfig1 Auto Block Enable
AltConfig1 Tap To Neutral Feature Enable
AltConfig2 Auto Block Enable
AltConfig2 Tap To Neutral Feature Enable
AltConfig3 Auto Block Enable
AltConfig3 Tap To Neutral Feature Enable
ARL AltConfigTerminate
ARLC Ready
ARLC Activate
Max Deviation Cancel Alt Mode
Test Battery
HMI Remote Security Override Mode
* Momentary/Self Resetting, always read FALSE
*** Hot Line Tag activates a latching relay in the control "close" circuit.
Page 16
Binary Outputs, Multi Phase
Technical Data TD225004EN
Communications
Point Data Base

Effective June 2015
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD225004EN
June 2015
Supersedes R225-70-31 (5/2013)
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
For Eaton's Cooper Power series CL-7 voltage
regulator control information
call 1-877-277-4636 or visit:
www.eaton.com/cooperpowerseries.