Surge Protection Made Simple™ for Wind Power Applications Description BSPM3230WE(R)

advertisement
Surge Protection Made Simple™ for Wind Power Applications
IEC Class II Surge Arrester for 230, 400 and 690 Volt, TNC Systems
Description
The Cooper Bussmann® IEC Class II 230, 400 and 690 volt three-pole,
modular surge arresters feature local, easy ID™ visual indication and optional
remote contact signaling. The unique module locking system fixes the
protection module to the base part. Modules can be easily replaced without
tools by simply depressing the release buttons. Integrated mechanical coding
between the base and protection module ensures against installing an
incorrect replacement module.
BSPM3230WE(R)
BSPM3400WE(R)
BSPM3690WE(R)
TNC System Arresters
The features of these three-pole devices are for use as a single device.
Remote Signaling Contact
The three-pole terminal remote signaling contact versions have a floating
changeover contact for use as a break or make contact, according to circuit
concept.
Visual Status Indication
Dimensions - mm
Remote Signal
Contact Available
Module Circuit Diagrams - Shown with optional remote contact signaling
MOV
Thermal Disconnector
Shown with optional remote contact signaling
BSPM3230WE(R)
BSPM3400WE(R)
BSPM3690WE(R)
www.cooperbussmann.com/surge
0211
BU-SB11186
Page 1 of 2
Data Sheet 2094
Ordering Information
System Voltage/Poles
Max. Continuous operating AC voltage (MCOV) [UC]
Catalog Numbers:
Without Remote Signaling
(Base + Modules)
With Remote Signaling
Replacement Modules
230V/3
275V
BSPM3230WE
BSPM3230WER
BPM275WE
400V/3
440V
BSPM3400WE
BSPM3400WER
BPM440WE
690V/3
600V
BSPM3690WE
BSPM3690WER
BPM750WE
Specifications
Line System Type
Nominal AC Voltage [UN]
Rated Varistor Voltage [Umov]
Nominal Discharge Current (8/20 µs) [In]
Max. Discharge Current (8/20 µs) [Imax]
Voltage Protection Level [UP]
Voltage Protection Level at 5kA [UP]
Response Time [tA]
Max. Mains-side Overcurrent Protection
Short-circuit Withstand Capability for Max. Mains-side Overcurrent Protection
Temporary Overvoltage (TOV) [UT]
Standards Information
SPD According to EN 61643-11
SPD According to IEC 61643-1
TOV Characteristics
Operating Temperature Range [TU]
Operating State/Fault Indication
Number of Ports
Cross-Sectional Area (min.)
Cross-Sectional Area (max.)
Mounting
Enclosure Material
Location Category
Degree of Protection
Capacity
Standards Information
Product Warranty
TNC
230/400V
275V
20kA
40kA
<
_1.25kV
<
_1kV
<
_25 ns
125A gL/gG
50kArms
335V / 5 sec.
KEMA
TNC
TNC
400/690V
600V
440V
750V
20kA
15kA
40kA
25kA
<
_ 2kV
<
_3kV
<
_ 1.7kV
<
_2.5kV
<
_ 25 ns
<
_25 ns
125A gL/gG
100A gL/gG
25kArms
25kArms
580V / 5 sec.
900V / 5 sec.
-KEMA
Type 2
Class II
Withstand
-40°C to +80°C
Green (good) / Red (replace)
1
1.5mm2/14AWG solid/flexible
35mm2/2AWG stranded-25mm2/4AWG flexible
35mm DIN rail per EN 60715
Thermoplastic, UL 94V0
Indoor
IP20
3 Mods., DIN 43880
KEMA
Five Years*
Remote Contact Signaling
Remote Contact Signaling Type
AC Switching Capacity (Volts/Amps)
DC Switching Capacity (Volts/Amps)
Conductor Ratings and Cross-Sectional Area for
Remote Contact Signal Terminals
Ordering Information
Changeover Contact
250V/0.5A
250V/0.1A; 125V/0.2A; 75V/0.5A
60/75°C Max. 1.5mm2/14AWG Solid/Flexible
Order from Catalog Numbers Above
* See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge.
Recommended Cooper Bussmann Back Up Fuse
DIN Fuse Size
NH Fuse Part Number
100NHG00B-690
00
125NHG00B-690
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2011 Cooper Bussmann
www.cooperbussmann.com
0211
BU-SB11186
Page 2 of 2
Data Sheet 2094
Download