Surge Protection Made Simple™ for Wind Power Applications IEC Class I Coordinated Lightning Current Arresters with High Follow Current for 400-690 Volt, TNC, TNS & IT Systems Description The Cooper Bussmann® IEC Class I 400 and 690 Volt, one-pole lightning current arresters feature local, easy ID™ visual indication and optional remote contact signaling. BSPS1400WE(R) BSPS1690WER 440V and 760V maximum continuous operating voltage arresters protect installations against surges and direct lightning strikes. System & Application TNC 400V/690V: 3x BSPS1400WE(R) TNS 400/690V: 4x BSPS1400WE(R) IT 690V: 3x BSPS1690WER Remote Signaling Contact The three-pole terminal remote signaling contact versions have a floating changeover contact for use as a break or make contact, according to circuit concept. Visual Status Indication Dimensions - mm Remote Signal Contact Available Circuit Diagrams - Shown with optional remote contact signaling Creepage Discharge Spark Gap Spark Gap Trigger BSPS1400WE(R) BSPS1690WER Shown with optional remote contact signaling www.cooperbussmann.com/Surge 0211 BU-SB11087 Page 1 of 2 Data Sheet 2091 Ordering Information System Voltage/Poles Max. Continuous Operating AC voltage (MCOV) [UC] Catalog Numbers: Without Remote Signaling With Remote Signaling 400V/1 440V BSPS1400WE BSPS1400WER 690V/1 760V -BSPS1690WER Specifications Line System Type Lightning impulse current (10/350 µs) [Iimp] Specific Energy [W/R] Nominal Discharge Current (8/20 µs) [In] Voltage Protection Level [UP] Follow Current Extinguishing Capability AC [Ifi] Follow Current Limitation / Selectivity Response Time [tA] Max. Backup Fuse (L) up to IK = 25kArms (ta < _ 5 s) Max. Backup Fuse (L) up to IK > 25kArms Max. Backup Fuse (L) up to IK = 50kArms (ta < _ 0.2 s) Max. Backup Fuse (L) up to IK = 50kArms (ta < _ 5 s) Max. Backup Fuse (L) for IK > 50kArms Max. Backup Fuse (L-L´) Short-Circuit Withstand Capability for Max. Mains-Side Overcurrent Protection Temporary Overvoltage (TOV) [UT] Cross-Sectional Area (L, L´, ) [min.] Cross-Sectional Area (L, L´, N/PEN) [min.] Cross-Sectional Area (L, N/PEN) [max.] Cross-Sectional Area (L, ) [max.] Cross-Sectional Area (L´) [max.] SPD According to EN 61643-11 SPD According to IEC 61643-1 TOV Characteristics Operating Temperature Range (parallel connection) [TUP] Operating Temperature Range (series connection) [TUS] Operating State/Fault Indication Number of Ports Mounting Enclosure Material Place of Installation Degree of Protection Capacity Product Warranty TNC, TNS, IT 35kA 306.25kJ/ohms 35kA < _ 2.5kV 50kArms no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.) < _ 100 ns --500A gL/gG 250A gL/gG 160A gL/gG 125A gL/gG TNC, TNS, IT 25kA 156.25kJ/ohms 25kA < _ 4kV 25kArms no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.) < _ 100 ns 250A gL/gG 100A gL/gG ---125A gL/gG 50kArms 25kArms 690V / 5 sec. 1000V / 5 sec. -10mm2 solid/flexible 2 10mm solid/flexible -50mm2/1AWG stranded/35mm2/2AWG flexible --50mm2/1AWG stranded/35 mm2/2AWG flexible 35mm2/2AWG stranded/25mm2/4AWG flexible 35mm2/2AWG stranded/25mm2/4AWG flexible Type 1 Class I Withstand -40°C to +80°C -40°C to +60°C Green (good) / Red (replace) 1 35mm DIN rail per EN 60715 Thermoplastic, UL 94V0 Indoor IP20 2 Mods., DIN 43880 Five Years* Remote Contact Signaling Remote Contact Signaling Type AC Switching Capacity (Volts/Amps) DC Switching Capacity (Volts/Amps) Conductor Ratings and Cross-Sectional Area for Remote Contact Signal Terminals Ordering Information Size 000 00 01 02 02 3 Changeover Contact 250V/0.5A 250V/0.1A; 125V/0.2A; 75V/0.5A 60/75°C Max. 1.5mm2/ 14AWG Solid/Flexible Order from Catalog Numbers Above Recommended Cooper Bussmann NH DIN Size Back Up Fuses NH Fuse Part Number 100NHG000B-690 (max L) up to IK > 25kArms 125NHG00B-690 (max L-L´) 160NHG01B-690 (max L) for IK > 50kArms 250NHG02B-690 (max L) up to IK = 25kArms (ta < _ 5 s) 250NHG02B-690 (max L) up to IK = 50kArms (ta < _ 5 s) 500NHG3B-690 (max (L) up to IK = 50kArms (ta < _ 0.2 s) * See Cooper Bussmann SPD Limited Warranty Statement (3A1502) for details at www.cooperbussmann.com/surge. The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. © 2011 Cooper Bussmann www.cooperbussmann.com 0211 BU-SB11087 Page 2 of 2 Data Sheet 2091