Fast-Acting ⁄ ˝ x 1 ˝ (10x38mm) Midget Fuses,

advertisement
DCM
Series is discontinued.
13
1
Fast-Acting
⁄
3
2
˝
x
1
⁄
2
˝
(10x38mm)
Midget
Fuses,
For supplemental, control circuit
applications, see
KLM Series,
data sheet # 2020
1
For photovoltaic
600Vac/dc,
⁄10–30A applications, see PVM Series, data sheet # 2153
AMP
RATING
30 A
15 A
20 A
8A
10 A
100
5A
Time-Current Characteristic Curves–Total Clearing
3A
Dimensions - in (mm)
3/4 A
DCM Series
1.5"
Ⳳ0.031
(38.1mm)
10
0.41"
Catalog Symbol: DCM
Fast-Acting 1⁄10-30A
UL Listed: STD. 248-14, (FILE #E19180,
GUIDE #JDYX)
CSA Certified, C22.2 NO. 248. 14 (CLASS #1422-01,
FILE #53787)
Interrupting Ratings: 100kA at 600Vac
50kA at 600Vdc
Electrical Ratings (Catalog Symbol and Amps) IR 100kA AC
DCM-1⁄10
DCM-1⁄2
DCM-2
DCM-6
DCM-12
DCM-1⁄4
DCM-1-1⁄4
DCM-4
DCM-9
DCM-25
DCM-1-1⁄2
Designed To:
Fuses:
DCM 1⁄10 thru 30
DCM-2-1⁄2
DCM-3
DCM-5
0-30
DCM-8
DCM-10
DCM-15
DCM-20
DCM-30
Designed to:
Carry 110% of rating for 4 hours
AC Opens at 135% of rating within 1 hour
AC Maximum Interrupting Rating of 100kA at 600Vac
DC Maximum Interrupting Rating of 50kA at 600Vdc
DC Minimum Interrupting Rating of 200% rated current
at 600Vdc,
Carton Quantity and Weight
Ampere
Ratings
DCM-7
Carton
Qty.
10
Lbs.
0.187
• A full range DC midget fuse.
• Melamine tube.
• Nickel-plated brass endcaps.
Weight
.01
CURRENT IN AMPS
1,000
DCM-1
100
DCM-3⁄10
DCM-3⁄4
.1
10
DCM-2⁄10
1
1
DCM-1⁄8
TIME IN SECONDS
Ⳳ0.004
(10.3mm)
Recommended fuse blocks/fuse holders
See Data Sheets listed below
• Open fuse blocks - 1104, 2104
• Finger-safe fuse holders - 1109, 1102, 1103, 2053
• Panel-mount fuse holders - 2114, 2113, 2108,
2112, 2109, 2140
• In-line fuse holders - 2127, 2126
Kg.
0.088
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2010 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0310 BU-SB091066
Page 1 of 1
Data Sheet 2038
Download