MOTOR CONTROLLER AND FUSE SELECTION TABLE FOR TYPE 2 PROTECTION (SELF CERTIFIED) MAXIMUM THREE PHASE MOTOR HORSEPOWER 200V(FLC) 230V(FLC) 460V(FLC) 575V(FLC) C O O R D I N AT E D PROTECTION .5(2.2) .5(1.1) .75(1.6) 1(2.1) .75(1.3) 1(1.7) 1.5(3) 1.5(2.4) 2(2.7) .5(2.5) TYPE 2 PROTECTION BUSSMANN/ ALLEN-BRADLEY IEC .75(3.7) .75(3.2) 1(4.2) 2(3.4) 1(4.8) 1.5(6.9) 2(7.8) 1.5(6.0) 2(6.8) 3(4.8) 5(7.6) 3(3.9) 5(6.1) 7.5(9.0) 3(9.6) 3(11.0) 5(15.2) 7.5(11.0) 10(14.0) 10(11.0) 15(17.0) 7.5(22.0) Maximum ratings are sized based on the maximum tested value that offers Type 2 protection, or the maximum allowed by the 1996/1999 NEC®, whichever is lower. Refer to Bussmann Bulletin SPD, “Electrical Protection Handbook” for more information on Motor Circuit Protection. 12-28-98 SB98107 Rev. A 5(17.5) 7.5(25.3) 10(32.2) 15(48.3) 20(62.1) 25(78.2) 30(92.0) 40(120.0) 50(150.0) 60(177.0) 10(28.0) 15(42.0) 20(54.0) 25(68.0) 30(80.0) 40(104.0) 50(130.0) 60(154.0) 75(221.0) 75(192.0) 100(285.2) 100(248.0) 15(21.0) 20(22.0) 20(27.0) 25(34.0) 30(40.0) 40(52.0) 50(65.0) 60(77.0) 25(27.0) 30(32.0) 40(41.0) 50(52.0) 60(62.0) 75.(77.0) 75(96.0) 100(99.0) 100(124.0) 125(125.0) 125(156.0) 150(144.0) 150(180.0) 200(240.0) 200(192.0) 250(242.0) 250(302.0) 300(289.0) CONTACTOR(1) OLR LPJ CLASS J LP-CC CLASS CC 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A09 100-A12 100-A12 100-A18 100-A18 100-A24 100-A24 100-A18 100-A30 100-A38 100-A45 100-A60 100-A75 100-B110 100-B110 100-B110 100-B180 100-B180 100-B180 100-B250 100-B250 100-B300 193-BSB16 193-BSB22 193-BSB22 193-BSB30 193-BSB30 193-BSB30 193-BSB42 193-BSB42 193-BSB50 193-BSB60 193-BSB80 193-BSC10 193-BSC10 193-BSC15 193-BSC15 193-BSC24 193-BSC24 193-BSC24 193-BSC24 193-BSC32 193-CPC45 193-CPC45 193-CPC63 193-CPC75 193-HPD110 193-HPD110 193-HPD110 193-DPD200 193-DPD200 193-DPD200 193-EPD300 193-EPD300 193-EPD300 2 3 3 6 6 6 6 6 6 10 10 15 15 20 20 30 30 30 30 40 50 50 80 100 150 150 150 200 200 200 300 300 300 2 3 3 6 6 6 6 6 6 10 20 20 20 30 30 (1) Catalog number is not complete. Refer to Bulletin 100 Section of A-B Industrial Catalog to specify contractor number. Form No. T2-AB-BOTH Page 1 of 2 BIF #8109 MOTOR CONTROLLER AND FUSE SELECTION TABLE FOR TYPE 2 PROTECTION (UL & CSA VERIFIED) THREE PHASE MOTOR HORSEPOWER 200V(FLC) 230V(FLC) 460V(FLC) 575V(FLC) C O O R D I N AT E D PROTECTION 1.5 (6.9) 5 (6.1) 2(6.8) 5.(7.6) TYPE 2 PROTECTION 2(7.8) 3(9.6) 3(11.0) 7.5(9.0) BUSSMANN/ ALLEN-BRADLEY 7.5(11.0) 10(11.0) 10(14.0) 5(15.2) NEMA 5(17.5) 7.5(22.0) 15(21.0) 15(17.0) 20(22.0) 20(27.0) 25(27.0) 7.5(25.3) 10(28.0) 10(32.2) Maximum Maximumratings ratingsare are sized sizedbased basedon onthe the maximum maximumtested tested value valuethat thatoffers offers Type Type22protection, protection, ororthe themaximum maximum allowed allowedby bythe the 1996/1999 1996/1999NEC NEC®,®, whichever whicheverisislower. lower. Refer RefertotoBussmann Bussmann Bulletin BulletinSPD, SPD, “Electrical “ElectricalProtection Protection Handbook” Handbook”for formore more information informationon onMotor Motor Circuit CircuitProtection. Protection. 25(34.0) 15(42.0) 30(40.0) 30(32.0) 40(41.0) 20(54.0) 40(52.0) 50(52.0) 15(48.3) 20(62.1) 50(65.0) 25(68.2) 25(78.2) 30(80.0) 60(77.0) 75(96.0) 30(92.0) 60(62.0) 75(77.0) 100(99.0) 40(104.0) 40(120.0) 100(124.0) 50(130.0) 125(125.0) 150(144.0) 50(150.0) 60(177.1) 60(154.0) 125(156.0) 150(180.0) 75(192.0) 200(192.0) 75(221.0) 200(240.0) 100(248.0) STARTER (1) SIZE CAT. # 0 0 0 0 0 0 0 1 1 1 1 1 1 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 509-A 509-A 509-A 509-A 509-A 509-A 509-A 509-B 509-B 509-B 509-B 509-B 509-B 509-C 509-C 509-C 509-C 509-C 509-D 509-D 509-D 509-D 509-D 509-D 509-D 509-D 509-D 509-D 509-D 509-E 509-E 509-E 509-E 509-E 509-E 509-E 509-E 509-F 509-F 509-F 509-F 509-F 509-F 509-F 509-F HEATER ELEMENT W48 W47 W48 W49 W50 W52 W53 W51 W53 W53 W56 W57 W59 W58 W61 W63 W63 W64 W65 W66 W64 W66 W68 W69 W71 W72 W73 W75 W75 W71 W74 W77 W78 W79 W81 W82 W83 W35 W36 W37 W39 W40 W41 W42 W43 MAXIMUM LPN-RK/ LPS-RK/LPS CLASS RK1/J 15 12 15 15 15 20 20 20 20 20 30 30 30 35 45 50 60 60 60 60 70 90 100 100 100 100 100 150 150 100 125 175 175 175 200 200 200 200 200 200 250 300 350 400 400 (1) Catalog number is not complete. Refer to Bulletin 509 Section of A-B Industrial Control Catalog to specify complete catalog starter number. 12-28-98 SB98107 Rev. A The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Form No. T2-AB-BOTH Page 2 of 2 BIF #8109