High speed fuses 6 Contents Description Page General applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 North American fuses and accessories . . . . . . . . . . . . . . . . . . . . 6-4 DFJ - high speed Class J fuse . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5 Square body fuses and accessories . . . . . . . . . . . . . . . . . . . . . 6-22 BS 88 fuses and accessories . . . . . . . . . . . . . . . . . . . . . . . . . . 6-94 Ferrule fuses and accessories. . . . . . . . . . . . . . . . . . . . . . . . . 6-103 TM High speed fuses BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-1 High speed fuses 6 General applications Rated voltage The AC voltage rating of Eaton fuses is given in volts rms. Fuses tested to IEC are tested at 5% above their rated voltage. British Style BS 88 fuses are tested at 10% above its rated voltage. UL recognition tests are performed at the rated voltage. Rated current Rated current is given in amps rms. Eaton fuses can continuously carry the rated current. Power factor For other power factor values, the total clearing integral can be calculated as a multiple of the clearing integrals, the correction factor K and the correction factor X. X 1.0 0.9 0.8 Melting characteristic Clearing integrals 104 6-2 This curve gives the peak arc voltage, U L , which may appear across the fuse during its operation as a function of the applied working voltage, E g , (rms) at a power factor of 15%. 2 103 6 4 2 102 6 4 2 101 6 4 2 100 6 4 Power losses 2 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 10–4 The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 0.7 Arc voltage 6 4 2 101 4 6 8 102 2 4 6 8 103 Prospective Current In Amperes RMS 1.5 1.0 K 0.3 0.4 0.5 COS w 103 9 8 7 6 5 4 3 200 300 1.0 Kp 0.8 400 500 Eg 600 660 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 70 Ib 80 90 100% 105 0.3 Eg 100 200 300 400 500 600 660 BUSSMANN SERIES FULL LINE CATALOG 1.4 1.2 UL 0.2 A fuse operation relating to short-circuits only. When a fuse operates in its current-limiting range, it will clear a short- 0.5 0.4 0.2 0.1 Cut-off current Peak Let-Through Current Time In Seconds The melting characteristic shows the virtual melting time in seconds as a function of the prospective current in amps rms. The fuses are specially constructed for short-circuit protection against high level fault currents. Loading and operation of the fuse in the noncontinuous/dashed section of the melt curve must be avoided. The curve can also be read as the real melting time as a function of the RMS value of the pre-arc current. 104 103 A B 2 ≈ 10 2 102 103 104 Prospective Current in Amps RMS 105 106 circuit in less than 1⁄2 cycle. Also, it will limit the instantaneous peak let-through current to a value substantially less than 1007—July 2015 Eaton.com/bussmannseries High speed fuses 6 General applications that obtainable in the same circuit if that fuse were replaced with a solid conductor of equal impedance. A asymmetrical current B symmetrical current Parallel connection When fuses are connected in parallel it is recommended that the applied voltage does not exceed 0.9 UN (the rated voltage of the fuse). This is due to the fact that the energy released within the fuses may be unevenly shared between the parallel connected barrels. When fuses are connected in parallel, one must take into account that the current sharing is not necessarily equal. And it must be checked, that the maximum load current is not exceeded. Series connection Fuses in series may not equally divide the applied voltage. It is recommended that series connected fuses should only be operated at fault currents that yield melting times less than 10 ms and a recovery voltage per fuse of less than or equal to 0.9 UN (the rated voltage of the fuse). Mounting guidance The recommendations below have to be followed when mounting a Bussmann series fuse with end plate threaded holes. 1. Screw in studs: 5 N•m Max, 3 N•m Min 2. Attachment of the fuse to bussbar by means of nut and washer: Torque (N•m)* max min 25 20 45 40 45 40 65 50 65 50 Overloads The design of Eaton fuses is such that they can be operated under rather severe operating conditions imposed by overloads (any load current in excess of the maximum permissible load current). In applications, there will be a maximum overload current, Imax, which can be imposed on the fuse with a corresponding duration and frequency of occurrence. Time durations fall into two categories: 1. Overloads longer than one second 2. Overloads less than one second termed “impulse” loads. The following table gives general application guidelines which, in the expression Imax < (% factor) x It. It is the Frequency of Occurrence Less than once per month Less than twice per week Several times per day Overloads (> 1 sec) Imax < 80% x It Imax < 70% x It Imax < 60% x It Impulse Loads (< 1 sec) Imax < 70% x It Imax < 60% x It — When impulse loads are an intrinsic/normal parameter of the load current either as single pulse or in trains of pulses or when their level is higher than the melting current at 0.01 seconds (per time-current curve), contact Eaton for application assistance. In addition to the parameters set forth in the preceding table, the RMS value of the load current as calculated for any period of 10 minutes or more should not exceed the maximum permissible load current. Furthermore, it is important that a fuse should not be applied in the non-continuous/dashed portion of the associated time-current curve. Any time-current combination point which falls in the non-continuous/dashed portion of the time-current curve is beyond the capability of the fuse to operate properly. DC operation Depending upon the short-circuit time constant and the magnitude of the prospective short-circuit current, the dc voltage at which a fuse can be applied may be less than its ac rating. Long time constants require a lower dc voltage. Conversely, however, higher available prospective shortcircuit currents result in faster fuse openings and thus permit a fuse to be operated at a higher DC voltage. Consult Eaton for additional information and application assistance when fuses have to operate under DC conditions. Load current versus conductor cross section Reduction Factor 1 .0 High speed fuses Thread configuration 5 ⁄16” – 18, M8 3 ⁄8” – 16, M10 3 ⁄8” – 24 1 ⁄2” – 13, M12 1 ⁄2” – 20 *1 N•m = 0.7375 lb-ft melting current corresponding to the time “t” of the overload duration as read from the time-current curve of the fuse. The guidelines in the table below determine the acceptability of the selected fuses for a given Imax. 0 .9 0 .8 Reduction of permissible ≈ (IEC cross section) load current when the conductor cross section is less than that given in IEC Publication 269-1 and 4 valid for Bussmann series high speed fuses. 0 .5 0 .6 0 .7 0 .8 0 .9 1 .0 Application assistance If you have application problems or need a fuse outside our standard program, please contact the nearest Eaton representative. BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-3 High speed fuses 6 North American Introduction General information North American contents Catalog number DFJ FWA FWA FWX FWH KAC KBC FWP FWJ Accessories Fuse bases Amps 1000-4000 70-1000 35-2500 35-1600 1-1000 5-1200 40-600 35-2000 Amp range 1-600 1000-4000 70-1000 35-2500 35-1600 1-1000 35-800 5-1200 35-2000 Volts 600 130 150 250 500 600 600 700 1000 Volts 130 150 250 500 600 700 800 1000 AC X X X X X X — X North American fuse ranges 6-4 DC X X X X — X X — BUSSMANN SERIES FULL LINE CATALOG Page 6-5 6-6 6-8 6-10 6-12 6-14 6-15 6-16 6-19 Eaton offers a complete range of North American blade and flush-end style fuses and accessories. Their design and construction were optimized to provide: • Low energy let-through (I2t) • Low watts loss • Superior cycling capability • Low arc voltage • Excellent DC performance 6-21 North American style fuses provide an excellent solution for medium power applications. While there are currently no published standards for these fuses, the industry has standardized on mounting centers that accept Bussmann series fuses. Voltage rating All Eaton North American style fuses are tested at their rated voltage. Eaton should be consulted for applications exceeding those values. Accessories External and internal open fuse indication is available for selected portions of the North American line. Fuse blocks are available for most applications. 1007—July 2015 Eaton.com/bussmannseries High speed fuses Drive fuse 6 Catalog numbers (amps) DFJ Class J Specifications Description: High speed, current-limiting fuse. The Bussmann series DFJ drive fuse will provide maximum protection for AC and DC drives and controllers and meet NEC® branch circuit protection requirements. The drive fuse has the lowest I2t of any branch circuit fuse to protect power semiconductor devices that utilize diodes, GTOs, SCRs and SSRs. Dimensions: See page 1-5 for Class J dimensions. Construction: Melamine tube with silver fuse element. Ratings: Volts — 600Vac (or less), 450Vdc (or less, 15-600A) Amps — 1-600A IR — 200kA RMS Sym., 100kA DC Agency information: CE, UL Listed, Std. 248-8, Class J, Guide JDDZ, File E4273, CSA Certified, Class 1422-02, File 53787. Features and benefits • Easily coordinated with existing and new variable speed drives and electric controllers. • Standard Class J dimensions allowing the use of readily available fuse blocks, holders, and switches. • Allows the lowest let-thru energy of any branch circuit overcurrent protective device. Typical applications • Protection of AC and DC drives • Equipment using power semiconductor devices Catalog number DFJ-1 DFJ-2 DFJ-3 DFJ-4 DFJ-5 DFJ-6 DFJ-8 DFJ-12 DFJ-15 DFJ-20 DFJ-25 DFJ-30 DFJ-35 DFJ-40 DFJ-45 DFJ-50 DFJ-60 DFJ-70 DFJ-80 DFJ-90 DFJ-100 DFJ-110 DFJ-125 DFJ-150 DFJ-175 DFJ-200 DFJ-225 DFJ-250 DFJ-300 DFJ-350 DFJ-400 DFJ-450 DFJ-500 DFJ-600 Rated current RMS amps 1 2 3 4 5 6 8 12 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600 I2t (A2 Sec) @ 600Vac / 100kA Pre-arc Clearing – – – – – – – – – – – – – – – – 4 110 8 365 12 610 20 1000 55 1100 90 1900 90 1900 140 2800 290 6000 450 3100 650 4600 1010 7200 1460 10500 1710 9500 3580 20000 5080 28000 6310 35000 9850 54500 11420 51000 17000 74500 23500 103000 38800 170000 62200 272000 44600 270000 79500 480000 138000 830000 Watts loss – – – – – – – – 4.1 4.0 4.9 5.5 6.8 8.6 8.6 8.7 8.5 12 13 13 13 17 15 19 23 24 29 30 36 39 40 56 52 57 Time-current characteristic curves—average melt Current limitation curves High speed fuses Data Sheet: 1048 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-5 High speed fuses 6 North American FWA 130V: 1000-4000A Arc voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style flush-end high speed fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 130Vac Amps: — 1000-4000A IR: — 200kA RMS Sym. — 50kA @130Vdc Agency information: CE, UL Recognized JFHR2.E91958 on 1000-2000A fuses The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). Catalog number FWA-1000AH-2000AH FWA-2500AH-3000AH FWA-4000AH Dimensions - in 1mm = 0.0394˝ / 1˝ = 25.4mm Fig. 1 1 2 B 2.0 3.0 3.5 1.5 1.0 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. K 0.5 0.15 26 C 1.0 1.5 1.5 65 D — — 1.5 Fig. 1: 1000-3000A 104 Catalog numbers FWA-1000AH FWA-1200AH FWA-1500AH FWA-2000AH FWA-2500AH FWA-3000AH FWA-4000AH Eg 130 Thread depth Tapped 3⁄8”-24 x 1⁄2” Tapped 1⁄2”-20 x 1⁄2” Tapped 1⁄2”-20 x 1⁄2” • • • • • • • • 1.875 C B Typical applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters C Data Sheet: 720001 6-6 BUSSMANN SERIES FULL LINE CATALOG 100 1007—July 2015 Eaton.com/bussmannseries Eg 150 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 70 Features and benefits Excellent DC performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability D B 1.0 Kp 0.8 50 • Watts loss provided at rated current. Fig. 2: 4000A 1.875 100 Electrical characteristics I2t (A2 Sec) Rated current Clearing RMS-amps Pre-arc at 130V 1000 170000 460000 1200 270000 730000 1500 520000 1400000 2000 860000 2400000 2500 1500000 4100000 3000 2100000 5700000 4000 3400000 9200000 Catalog numbers 0.3 0.2 200 Power losses Electrical characteristics Total Clearing I2t 300 UL Ib 80 90 100% Watts loss 60 70 78 108 130 150 257 High speed fuses North American 6 FWA 1000-4000A: 130V Time-current curve 104 6 4 2 103 6 4 FWA-1000AH FWA-1200AH FWA-1500AH FWA-2000AH FWA-2500AH FWA-3000AH FWA-4000AH 2 102 6 4 Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 0 10 6 4 2 10–1 6 4 2 10–2 6 4 2 10–3 6 4 2 2 103 4 6 8 2 4 104 Prospective Current In Amps RMS 6 8 High speed fuses 10–4 105 Peak let-through curve 2 105 6 Peak Let-Through Current 4 2 FWA-4000AH FWA-3000AH 104 FWA-2500AH FWA-2000AH FWA-1500AH 6 FWA-1200AH FWA-1000AH 4 2 103 103 2 4 6 104 2 4 6 105 2 4 6 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785301 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-7 High speed fuses 6 North American FWA 150V: 70-1000A Arc voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 150Vac/dc* Amps: — 70-1000A IR: — 100kA Sym. (70-400A) — 200kA Sym. (450-1000A) — 20kA @150Vdc (70-800A) — 100kA @ 80Vdc (70-1000A) *1000A rated @ 80Vdc. Agency information: CE, UL Recognized JFHR2.E91958 Electrical characteristics Total clearing I2t The total clearing I t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 2 Dimensions - in Fig. 1: 70-400A 1.5 1.0 0.3 0.2 0.15 22 1) 70 102 1.936 1.156 Eg 150 0.125 1.000 Fig. 2: 500-1000A 0.438 3.500 2.438 1.250 1.000 Catalog number FWA-70B FWA-80B FWA-100B FWA-125B FWA-150B FWA-200B FWA-250B FWA-300B FWA-350B FWA-400B FWA-500A FWA-600A FWA-700A FWA-800A FWA-1000A 1) 500-1000A Range 2) 70-400A Range 2.656 2.188 0.750 0.312 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. Catalog numbers 2) 0.250 1.500 Rated current RMS-amps 70 80 100 125 150 200 250 300 350 400 500 600 700 800 1000 • • • • • • • • Typical applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Data Sheet: 720002 1007—July 2015 1.0 Kp 0.8 50 100 Eaton.com/bussmannseries Eg 150 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 70 Ib 80 90 100% Watts loss 6.9 7.7 9.0 11.2 13.5 17.6 22.5 27.0 30.6 35.2 35.0 47.0 49.0 58.0 60.0 Features and benefits Excellent DC performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability 0.406 BUSSMANN SERIES FULL LINE CATALOG 100 Electrical characteristics I2t (A2 Sec) Clearing Pre-arc at 150V 470 4000 670 6000 1200 12000 1870 18000 2700 26000 4780 45000 7470 70000 10760 100000 15700 140000 20300 180000 39000 120000 46000 140000 75000 220000 92000 280000 170000 510000 • Watts loss provided at rated current. • See accessories on page 6-21. 1mm = 0.0394” / 1” = 25.4mm 6-8 200 Power losses K 0.5 300 UL High speed fuses North American 6 FWA 70-1000A: 150V Time-current curve 104 6 4 2 103 6 4 FWA-500A FWA-600A FWA-700A FWA-800A FWA-1000A 2 102 6 4 Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 100 6 4 2 10–1 6 4 FWA-70A FWA-80A FWA-100A FWA-125A FWA-150A 2 10–2 6 4 2 10–3 6 4 FWA-200A FWA-250A FWA-300A FWA-350A FWA-400A 2 –4 10 2 102 4 6 8 2 4 6 103 Prospective Current In Amps RMS 8 104 High speed fuses Peak let-through curve 106 6 4 FWA-400A FWA-350A 2 FWA-300A FWA-250A 104 FWA-200A Peak Let-Through Current FWA-150A 6 FWA-100A 4 2 3 10 6 FWA-80A 4 FWA-70A 2 102 2 4 6 102 2 103 4 6 2 104 4 6 2 105 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785310 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-9 High speed fuses 6 North American FWX 250V: 35-2500A Arc voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount and flush-end fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 250Vac/dc Amps: — 35-2500A IR: — 200kA RMS Sym. 50kA@250Vdc (35-800A) Agency information: CE, UL Recognized JFHR2.E56412 and CSA Component Acceptance file Class 1422-30, (53787) on 35-800A fuses (50kA IR @250Vdc). Electrical characteristics Total clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). 1.5 K 1.0 1) 0.5 Catalog numbers 0.15 Fig. 1: 35-800A D 2.59 2.44 2.94 3.03 — 1.50 75 125 200 250 E 2.25 2.19 2.25 2.28 — — F 0.34 0.34 0.41 0.41 — — G 0.63 1.00 1.00 1.50 — — H 0.13 0.19 0.25 0.25 — — J 0.52 0.47 0.75 0.78 — — 300 Tapped thread depth — — — — 3 ⁄8”-24 x 1⁄2” 3 ⁄8”--24 x 1⁄2” Fig. 3: 1500-2500A A A A D E C C B Rated current RMS-amps 35 40 45 50 60 70 80 90 100 125 150 175 200 225 250 275 300 350 400 450 500 600 700 800 1000 1200 1500 1600 2000 2500 C F G H Data Sheet: 720005 6-10 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 800 600 500 400 1) 300 200 50 1.0 Kp 0.8 100 2) 150 200 Eg 1) 35-800A Range 2) 1000-2500A Range 250 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 70 Ib 80 90 100% Watts loss 4.2 5.2 5.7 6.0 8.1 7.2 8.1 9.0 10.0 12.5 15.7 18.5 22 24 27 31 32 39 44 49 54 62 72 84 100 103 140 140 151 163 • See accessories on page 6-21. Features and benefits • Excellent DC performance • Low arc voltage and low energy let-through (I2t) • Superior cycling capability B UL 103 Electrical characteristics I2t (A2 Sec) Clearing Pre-arc at 250V 50 230 60 310 80 390 100 520 140 740 330 1400 430 1850 570 2450 740 3150 1130 4850 1620 6950 2170 9300 2790 12000 3210 14700 3960 18100 4720 21600 6000 27300 10600 48600 14500 66100 22100 101000 28000 128000 41100 188000 48800 190000 59000 230000 44000 360000 92000 750000 120000 880000 160000 1200000 320000 2300000 670000 4700000 • Watts loss provided at rated current. D B Eg 1) 35-800A Range 2) 1000-2500A Range Fig. 2: 1000-1200A J Catalog number FWX-35A FWX-40A FWX-45A FWX-50A FWX-60A FWX-70A FWX-80A FWX-90A FWX-100A FWX-125A FWX-150A FWX-175A FWX-200A FWX-225A FWX-250A FWX-275A FWX-300A FWX-350A FWX-400A FWX-450A FWX-500A FWX-600A FWX-700A FWX-800A FWX-1000AH FWX-1200AH FWX-1500AH FWX-1600AH FWX-2000AH FWX-2500AH 2) 0.3 0.2 Dimensions - in Amp range Fig. A B C 35-60 1 3.19 0.81 1.59 70-200 1 3.13 1.22 1.59 225-600 1 3.84 1.50 1.59 700-800 1 3.84 2.00 1.59 1000-1200 2 2.59 3.00 1.50 1500-2500 3 2.59 3.50 1.50 1mm = 0.0394” / 1” = 25.4mm Power losses Watts loss at rated current is given in the electrical char acteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, K p , is given as a function of the RMS load current, Ib , in % of the rated current . 1.4 1.2 • • • • Typical applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High speed fuses 6 North American FWX 35-800A: 250V FWX 1000-2500A(H): 250V Time-current curve Time-current curve 104 6 4 104 2 103 FWX-200A FWX-350A FXW-400A FWX-500A FWX-600A FWX-800A 102 2 FWX-1000AH FWX-1200AH FWX-1500AH FWX-1600AH FWX-2000AH FWX-2500AH 2 10 101 6 4 2 100 Virtual Pre-Arcing Time In Seconds Virtual Pre-arcing Time In Seconds 103 6 4 FWX-35A FWX-40A FWX-60A FWX-70A FWX-100A FWX-150A 10–1 10–2 10–3 10–4 102 2 103 Prospective Current In Amps RMS 104 101 6 4 2 0 10 6 4 2 10–1 6 4 2 10–2 6 4 Peak let-through curve 2 105 B 10–3 6 4 FWX-800A FWX-600A FWX-400A FWX-300A FWX-200A 2 Peak Let-Through Current 103 4 6 8 2 4 6 104 Prospective Current In Amps RMS 8 105 High speed fuses 104 2 10–4 Peak let-through curve 105 6 FWX-2500AH FWX-150A FWX-100A FWX-70A FWX-60A FWX-45A FWX-35A A 102 102 4 103 104 Prospective Short-Circuit Current Symmetrical RMS Peak Let-Through Current 10 3 105 FWX-2000AH FWX-1600AH FWX-1500AH FWX-1200AH 2 FWX-1000AH 104 6 4 2 103 103 2 4 6 104 2 4 6 105 2 4 6 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 359 Data Sheet: 35785299 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-11 High speed fuses 6 North American FWH 500V: 35-1600A This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of theapplied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 500Vac/dc (35-800A only) Amps: — 35-1600A IR: — 200kA Sym. — 50kA @ 500Vdc (35-800A) Agency information: CE, UL Recognized JFHR2.E91958 FWH-_B (35-200A, 1000-1200A), JFHR2.E56412 FWH-_A (225-600A), CSA Component Acceptance Class 1422-30, File 53787 (35-1600A). Electrical characteristics Total clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). Amp Range 35-60 70-100 125-200 225-400 450-600 700-800 1000-1200 1400-1600 Dimensions - in Fig. 1 1 1 1 1 1 1 2 A B 3.188 0.813 3.625 0.947 3.625 1.156 4.340 1.500 4.340 2.000 6.340 2.500 6.969 3.000 See Drawing 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-1200A C 1.593 1.736 1.836 2.090 2.090 2.090 3.219 1.5 1.0 0.5 0.3 0.2 Catalog numbers 2) 250 400 1) 35-800A Range 2) 1000-1600A Range E 2.193 2.807 2.768 2.750 2.780 3.440 4.475 F 0.344 0.352 0.344 0.410 0.410 0.530 0.625 G 0.719 0.750 1.000 1.000 1.500 2.000 2.375 Catalog numbers FWH-35B FWH-40B FWH-45B FWH-50B FWH-60B FWH-70B FWH-80B FWH-90B FWH-100B FWH-125B FWH-150B FWH-175B FWH-200B FWH-225A FWH-250A FWH-275A FWH-300A FWH-325A FWH-350A FWH-400A FWH-450A FWH-500A FWH-600A FWH-700A FWH-800A FWH-1000A FWH-1200A FWH-1400A FWH-1600A Eg 500 H 0.125 0.125 0.188 0.250 0.250 0.380 0.438 J 0.518 0.375 0.406 0.750 0.780 1.300 1.120 H G F 0.125 1) 0.15 100 D 2.541 2.853 2.892 3.440 3.530 4.970 5.465 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. B J 0.5 10.219 0.625 3.219 3.5 BUSSMANN SERIES FULL LINE CATALOG 103 800 600 2) 500 400 300 100 1.0 Kp 0.8 1007—July 2015 Eaton.com/bussmannseries 1) 200 300 400 Eg 500 1) 35-200 and 1000-1600A Range 2) 225-800A Range 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 70 Ib 80 90 100% Watts loss 8 7.5 7.5 7.5 9.9 10.6 12.7 15 17 25 30 35 40 39 41 46 51 53 58 65 74 84 108 120 129 145 180 210 230 • See accessories on page 6-21. Features and benefits • Excellent DC performance • Low arc voltage and low energy let-through (I2t) • Superior cycling capability Data Sheet: 720007 6-12 1.2 Electrical characteristics I2t (A2 Sec) Clearing Pre-arc at 500V 34 150 76 320 105 450 135 670 210 900 210 900 305 1400 360 1600 475 2000 800 3500 1100 4600 1450 6200 1900 8500 4600 23300 6300 32200 7900 40300 9800 49800 13700 63800 14500 72900 19200 96700 24700 127000 29200 149000 41300 206000 55000 298000 76200 409000 92000 450000 122000 600000 200000 1000000 290000 1400000 • Watts loss provided at rated current. 1.625 1.750 0.75 4.25 6.219 8.969 Rated current RMS-amps 35 40 45 50 60 70 80 90 100 125 150 175 200 225 250 275 300 325 350 400 450 500 600 700 800 1000 1200 1400 1600 UL 1.6 Power losses K A D E C Fig. 2: 1400-1600A 2.0 Arc voltage • • • • Typical applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High speed fuses 6 North American FWH 35-200A(B) and 900-1600A(A): 500V Time-current curve FWH 250-800A: 500V Time-current curve 103 104 6 4 2 103 6 4 102 FWH-300A FWH-400A FWH-500A FWH-600A FWH-800A 2 102 6 4 101 6 4 Virtual Pre-Arcing Time In Seconds Virtual Pre-Arcing Time In Seconds 101 FWH-900A FWH-1000A FWH-1200A FWH-1400A FWH-1600A 2 2 100 6 4 FWH-80B FWH-90B FWH-100B FWH-125B FWH-150B FWH-175B FWH-200B FWH-35B FWH-40B FWH-45B FWH-50B FWH-60B FWH-70B 2 10–1 6 4 2 10–2 6 4 100 10–1 10–2 2 10–3 6 4 10–3 2 10 –4 2 4 6 8 2 4 6 8 2 103 Prospective Current In Amps RMS 102 4 6 8 104 10–4 102 105 High speed fuses Peak let-through curve 103 104 Prospective Current In Amps RMS Peak let-through curve 105 105 B FWH-1600A FWH-1400A 6 FWH-1200A FWH-1000A 4 2 104 Peak Let-Through Current Peak Let-Through Current 104 6 4 2 103 FWH-800A FWH-600A FWH-500A FWH-400A FWH-300A FWH-250A 103 FWH-200B 6 FWH-150B FWH-125B 4 A FWH-100B FWH-80B FWH-60B FWH-50B 2 FWH-40B FWH-35B 102 102 102 2 4 6 103 2 4 6 104 2 4 6 105 2 102 103 104 Prospective Short-Circuit Current Symmetrical RMS 105 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785304 Data Sheet: 360 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-13 High speed fuses 6 North American KAC 600V: 1-1000A KAC-1 KAC-2 KAC-3 KAC-4 KAC-5 KAC-6 KAC-7 KAC-8 KAC-9 KAC-10 KAC-12 KAC-15 KAC-17.5 KAC-20 KAC-25 KAC-30 KAC-35 KAC-40 KAC-45 KAC-50 KAC-60 KAC-70 KAC-80 KAC-90 KAC-100 KAC-110 KAC-125 KAC-150 Catalog numbers (amps) Specifications Description: North American style stud-mount fuses. These 600V fuses are supplied as replacements only. For new installations, Eaton recommends the 700V FWP fuse. Dimensions: See dimensions illustrations. Ratings: Volts: — 600Vac Amps: — 1-1000A IR: — 200kA RMS Sym. Agency information: CE, UL Recognized JFHR2.E56413 on 1-600A only. See accessories on page 6-21. KAC-175 KAC-200 KAC-225 KAC-250 KAC-300 KAC-350 KAC-400 KAC-450 KAC-500 KAC-600 KAC-700 KAC-800 KAC-1000 Features and benefits • Low arc voltage and low energy let-through (I2t) • Low watts loss • Superior cycling capability Typical applications • Power converters/rectifiers • Reduced voltage starters Dimensions - in Amp range 1-30A 35-60A 70-100A 110-200A 225-400A 450-800A 1000A Fig. 1 2 2 2 2 1 1 A 2.875 4.375 5.000 5.140 6.182 6.250 7.250 1mm = 0.0394˝ / 1˝ = 25.4mm B1 2.500 – – – – 4.750 4.750 B2 – 3.750 4.063 4.390 4.815 – – B3 – 3.500 3.656 3.766 4.565 – – C 1.875 2.750 2.750 2.906 3.000 3.063 3.063 D 0.406 0.625 0.750 1.000 1.625 2.000 2.750 E – 0.343 0.406 0.406 0.562 – – F 0.563 0.813 1.000 1.500 2.000 2.500 3.500 G 0.063 0.094 0.125 0.188 0.250 0.250 0.375 H 0.257 0.468 0.609 0.718 0.687 0.563 0.563 Fig. 1: 1-30 and 450-1000A A B1 C G D F H Fig. 2: 35-400A A B2 B3 C D G F E H Data Sheet: 720009 6-14 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries High speed fuses North American KBC 600V: 35-800A Specifications Description: North American style stud-mount and flush-end fuses. These 600V fuses are supplied as replacements only. For new installations, Eaton recommends the 700V FWP fuse. Dimensions: See dimensions illustrations. Ratings: Volts: — 600Vac Amps: — 35-800A IR: — 200kA RMS Sym. Agency information: CE, UL Recognized JFHR2.E56412 on 35-600A only. Amp range 35-60A 70-100A 110-200A 225-400A 450-600A 800A Dimensions - in Fig. 1 2 1 1 1 3 A B C 4.375 3.750 3.500 See Drawing 4.406 3.719 3.594 5.125 4.188 3.563 5.125 4.389 3.687 See Drawing 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-60 and 110-600A E KBC-35 KBC-40 KBC-45 KBC-50 KBC-60 KBC-70 KBC-80 KBC-90 KBC-100 KBC-110 KBC-125 KBC-150 KBC-175 KBC-200 KBC-225 KBC-250 Catalog numbers (amps) 6 KBC-300 KBC-350 KBC-400 KBC-450 KBC-500 KBC-600 KBC-800 Features and benefits • Low arc voltage and low energy let-through (I2t) • Low watts loss • Superior cycling capability Typical applications • Power converters/rectifiers • Reduced voltage starters D E F G H I 2.750 0.343 0.625 0.813 0.094 0.468 2.906 0.312 0.875 1.219 0.187 0.375 2.906 0.406 1.000 1.500 0.250 0.719 2.875 0.406 1.500 2.000 0.250 0.757 A B C D H F G High speed fuses I 0.312 0.750 1.000 2.906 3.656 0.125 4.406 Fig. 2: 70-100A Fig. 3: 800A 2.859 2.500 ‹/•" - 24 ≈ ⁄/™" 0.750 3.750 4.000 4.000 0.750 3.750 Data Sheet: 720010 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-15 High speed fuses 6 North American FWP 700V: 5-1200A Arc voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount fuses. Dimensions: See dimensions illustrations. Ratings: Volts: — 700Vac/dc Amps: — 5-1200A IR: — 200kA RMS Sym. — 50kA @700Vdc Agency information: CE, UL Recognized JFHR2.E91958 FWP-_B (5-100A, 700-1200A), JFHR2.E56412 FWP-_A (125-600A) and CSA Component Acceptance file Class 1422-30, (53787) on 5-800A 1.5 Electrical characteristics Total clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). Amp range Fig. 5-30 1 35-60 1 70-100 1 125-200 1 225-400 1 450-600 1 700-800 1 900-1000 2 1200 3 Dimensions - in A B 2.870 0.563 4.375 0.813 4.406 0.947 5.090 1.500 5.090 2.000 7.090 2.500 6.630 2.000 See Drawing See Drawing C 1.855 2.750 2.594 2.840 2.840 2.840 2.844 1.0 0.5 0.3 0.2 Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current. K 2) 1) 0.15 316 D 2.477 3.708 3.625 4.190 4.280 5.720 5.562 Power losses E 2.477 3.312 3.563 3.500 3.530 4.190 5.062 Catalog numbers Catalog numbers FWP-5B FWP-10B FWP-15B FWP-20B FWP-25B FWP-30B FWP-35B FWP-40B FWP-50B FWP-60B FWP-70B FWP-80B FWP-90B FWP-100B FWP-125A FWP-150A FWP-175A FWP-200A FWP-225A FWP-250A FWP-300A FWP-350A FWP-400A FWP-450A FWP-500A FWP-600A FWP-700A FWP-800A FWP-900A FWP-1000A FWP-1200A 3) 460 604 1) 35-100A Range 2) 125-600A Range 3) 700-1200A Range F 0.250 0.344 0.344 0.410 0.410 0.530 0.625 G 0.405 0.725 0.750 1.000 1.500 2.000 1.500 700 H 0.063 0.125 0.125 0.250 0.250 0.380 0.250 Eg I 0.250 0.542 0.375 0.750 0.780 1.300 0.875 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 5-800A Fig. 2: 900-1000A Fig. 3: 1200A 3.500 1.375 J 5.966 7.594 A D E C 9.590 6.840 3.844 5.154 0.625 F B 3.500 H 2.750 0.5 3.844 10.844 0.625 1.031 G 0.125 0.500 1.625 1.750 4.250 0.750 Rated current RMS-amps 5 10 15 20 25 30 35 40 50 60 70 80 90 100 125 150 175 200 225 250 300 350 400 450 500 600 700 800 900 1000 1200 BUSSMANN SERIES FULL LINE CATALOG UL 1.6 1.4 1.2 103 1) 8 6 5 4 3 300 400 2) 500 1007—July 2015 Eaton.com/bussmannseries Eg 700 1.0 Kp 0.8 0.6 0.5 0.4 0.3 0.2 0.1 30 40 50 60 Electrical characteristics I2t (A2 Sec) Clearing Pre-arc at 700V 1.6 10 3.6 20 10 75 26 180 44 340 58 450 34 160 76 320 135 600 210 950 305 2000 360 2400 415 2700 540 3500 1800 7300 2900 11700 4200 16700 5500 22000 7700 31300 10500 42500 17600 71200 23700 95600 31000 125000 36400 137000 45200 170000 66700 250000 54000 300000 78000 450000 91500 530000 120000 600000 195000 1100000 Features and benefits • Excellent DC performance • Low arc voltage and low energy let-through (I2t) • Superior cycling capability 600 1) 125-600A range 2) 35-100 & 700-1200A range • Watts loss provided at rated current. • See accessories on page 6-21. Data Sheet: 720012 6-16 2 • • • • 70 Ib 80 90 100% Watts loss 1.5 4 5.5 6 7 9 12 12 12 15.5 18 21 25 27 28 32 35 43 45 48 58 65 78 94 107 122 125 140 150 170 190 Typical applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters High speed fuses 6 North American FWP 5-30A(B): 700V FWP 35-100A(B) and 700-1200A(A): 700V Time-current curve Time-current curve 104 6 4 104 6 4 2 2 103 103 6 4 6 4 2 2 6 4 6 4 2 Virtual Pre-Arcing Time In Seconds Virtual Pre-Arcing Time In Seconds 2 101 6 4 2 100 6 4 FWP-5B FWP-10B FWP-15B FWP-20B FWP-25B FWP-30B 2 10–1 6 4 101 6 4 FWP-35B FWP-40B FWP-50B FWP-60B FWP-70B FWP-80B FWP-90B FWP-100B 2 100 6 4 2 10–1 6 4 2 2 10–2 10–2 6 4 6 4 2 2 10–3 10–3 6 4 6 4 2 2 10–4 FWP-700A FWP-800A FWP-900A FWP-1000A FWP-1200A 102 102 10–4 2 4 6 8 2 101 4 6 8 2 102 4 6 8 103 2 4 6 8 2 2 4 6 8 103 Prospective Current In Amps RMS 102 Prospective Current In Amps RMS Peak let-through curve 4 6 8 104 Peak let-through curve 106 104 FWP-1200A 6 FWP-1000A 6 4 High speed fuses FWP-800A 4 FWP-700A 2 FWP-30B FWP-25B 3 2 104 6 4 Peak Let-Through Current Peak Let-Through Current 10 2 FWP-20B FWP-15B FWP-10B FWP- 5B 2 10 6 4 6 4 2 3 10 2 6 FWP-100B 4 101 101 2 4 6 102 2 4 6 103 2 4 6 104 2 4 6 105 FWP-70B 2 FWP-60B Prospective Short-Circuit Current FWP-50B 2 FWP-40B FWP-35B 2 10 2 4 6 102 2 103 4 6 2 104 4 2 6 105 Prospective Short-Circuit Current Data Sheet: 35785316 Data Sheet: 35785308 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-17 High speed fuses 6 North American FWP 150-600A: 700V Peak let-through curve Time-current curve 10 3 105 B 102 FWP-150A FWP-200A FWP-300A FWP-400A FWP-600A 101 Virtual Pre-Arcing Time In Seconds Peak Let-Through Current 104 FWP-600A FWP-400A FWP-300A FWP-200A FWP-150A 103 100 A 102 102 103 10–1 10–2 10–3 10–4 102 103 104 105 Prospective RMS ProspectiveCurrent CurrentInInAmperes Amps RMS Data Sheet: 361 6-18 104 Prospective Short-Circuit Current Symmetrical RMS BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 105 High speed fuses 6 North American FWJ 1000V: 35-2000A Arc voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%. Specifications Description: North American style stud-mount fuses. Dimensions: See dimensions illustration. Ratings: Volts: — 1000Vac/800Vdc Amps: — 35-2000A IR: — 25kA (35-200A) — 100kA (250-2000A) — 50kA @ 800Vdc (35-200A, 450-600A) Agency information: CE, UL Recognized JFHR8.E91958 on 35-600A only. The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms). Dimensions - in B 0.940 1.125 1.526 2.000 2.500 3.500 1mm = 0.0394” / 1” = 25.4mm Fig. 1: 35-2000A C 3.110 3.085 3.261 3.500 3.465 3.312 1.0 Catalog numbers 0.5 0.3 0.2 0.15 200 D 4.235 4.266 4.803 4.811 5.984 5.472 1200 Watts loss at rated current is 1.0 given in the electrical characteristics. The curve 0.8 allows the calculation of the 0.6 0.5 power losses at load 0.4 currents lower than the 0.3 rated current. The correction factor, Kp, is 0.2 given as a function of the RMS load current, Ib, in % of the rated current. 0.1 K 500 E 4.180 4.156 4.055 4.150 4.706 4.962 F 0.352 0.352 0.445 0.433 0.562 0.625 800 G 0.750 1.000 1.000 1.500 2.000 2.750 A D E C H 0.125 0.188 0.250 0.250 0.375 0.500 Eg 1000 I 0.380 0.407 0.819 0.764 1.201 0.880 H G F B J Catalog numbers FWJ-35A FWJ-40A FWJ-50A FWJ-60A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-125A FWJ-150A FWJ-175A FWJ-200A FWJ-250A FWJ-300A FWJ-350A FWJ-400A FWJ-500A FWJ-600A FWJ-800A FWJ-1000A FWJ-1200A FWJ-1400A FWJ-1600A FWJ-1800A FWJ-2000A Rated current RMS-amps 35 40 50 60 70 80 90 100 125 150 175 200 250 300 350 400 500 600 800 1000 1200 1400 1600 1800 2000 • Watts loss provided at rated current. • See accessories on page 6-21. • • • • • • • • UL 800 400 Kp 200 30 40 50 600 60 Eg 1000 1400 1800 Electrical characteristics I2t (A2 Sec) Clearing Pre-arc at 1000V 210 2000 300 2500 470 3500 670 5000 1100 6900 1550 9700 1900 12000 2800 17500 4800 35000 6300 45000 7500 65000 11700 80000 16000 112000 23500 164000 33000 231000 47000 330000 39500 329000 61000 520000 87000 500000 190000 1100000 370000 2100000 470000 2700000 700000 4000000 925000 5300000 1330000 7600000 70 Ib 80 90 100% Watts loss 7 8 10 11 12 13 14 15 16 25 30 32 50 56 62 67 95 105 182 206 240 248 267 239 244 High speed fuses Amp range Fig. A 35-60 1 5.000 70-100 1 4.932 125-200 1 5.685 250-400 1 5.768 500-600 1 7.201 800-2000 1 6.811 1.5 1600 Power losses Electrical characteristics Total clearing I2t 2000 Features and benefits Excellent DC performance Low arc voltage and low energy let-through (I2t) Low watts loss Superior cycling capability Typical Applications DC common bus DC drives Power converters/rectifiers Reduced voltage starters Data Sheet: 720027 BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-19 High speed fuses 6 North American FWJ 35-600A: 1000V FWJ 800-2000A: 1000V Time-current curve 10 Time-current Curve 104 4 6 4 2 2 103 103 6 4 102 Virtual Pre-Arcing Time In Seconds 2 101 6 4 Virtual Pre-Arcing Time In Seconds FWJ-200A FWJ-250A FWJ-300A FWJ-350A FWJ-400A FWJ-500A FWJ-600A 6 4 2 100 6 4 101 6 4 2 10–3 FWJ-800A FWJ-1000A FWJ-1200A FWJ-1400A FWJ-1600A FWJ-1800A FWJ-2000A 6 4 2 100 6 4 2 10–1 10–2 6 4 2 10–1 2 2 6 4 2 2 102 6 4 6 4 6 4 2 FWJ-40A FWJ-50A FWJ-60A FWJ-70A FWJ-80A FWJ-90A FWJ-100A FWJ-125A FWJ-150A FWJ-175A 10–2 6 4 2 10–3 6 4 6 4 2 10–4 2 10–4 102 2 4 6 8 2 103 4 6 8 2 4 6 8 2 103 4 104 Prospective Current In Amps RMS Data Sheet: 35785309 Peak let-through curve 2 FWJ-2000A FWJ-1800A FWJ-1600A FWJ-1400A FWJ-1250A FWJ-1000A FWJ-600A FWJ-800A FWJ-400A FWJ-500A FWJ-350A FWJ-300A FWJ-250A FWJ-200A FWJ-175A FWJ-150A FWJ-125A FWJ-100A FWJ-90A FWJ-80A FWJ-70A FWJ-60A FWJ-50A FWJ-40A 5 10 6 4 Peak Let-Through Current 2 104 6 4 2 3 10 6 4 2 102 102 2 4 6 2 103 4 6 104 2 4 6 105 2 4 Prospective Short-Circuit Current Symmetrical RMS Data Sheet: 35785303 6-20 6 8 104 2 Prospective Current In Amperes Prospective Current in AmpsRMS BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6 4 6 8 105 High speed fuses 6 North American fuse accessories Fuse bases (blocks) Modular style Eaton offers a comprehensive line of fuse bases that provide the user with design and manufacturing flexibility. Two identical half bases make up a Bussmann series modular fuse base. These “split” units can be panel mounted any distance apart to accommodate any length fuse. Stud Type (not sold in pairs) The simpler design is the C5268 modular fuse base. With this design, the fuse terminal and cable (with termination) are mounted on the same stud, minimizing labor needed for installation. The stud type base is available in the configuration shown in the table below. Catalog Max fuse Stud Stud dia. number amp rating height (in) & threads 5 C5268-1 200 1.00 ⁄16˝-18 5 C5268-2 200 1.75 ⁄16˝-18 5 C5268-3 200 0.75 ⁄16˝-18 1 C5268-4 100 1.00 ⁄4˝-20 1 C5268-5 100 1.75 ⁄4˝-20 Connector type BS style Stud type Connector type High speed fuses Eaton also offers a modular style fuse base that utilizes a tin-plated connector (for wire termination and heat dissipation) and a plated-steel stud (for fuse mounting). The connector type fuse base is available in the configurations shown below. Consult Eaton for additional product details. Modular Max Max fuse Data sheet base style voltage amp rating number 1BS101 600 100 1206 1BS102 600 400 1207 1BS103 600 400 1208 1BS104 600 600 1209 BH-0xxx 700 100 1200 BH-1xxx 2500 400 1201 BH-2xxx 5000 400 1202 BH-3xxx 1250 700 1203 C5268 Refer to page 9-41 for BH holders. BUSSMANN SERIES FULL LINE CATALOG 1007—July 2015 Eaton.com/bussmannseries 6-21