Using IED Data To Implement Substation Automation Functions Reducing Costs by Reusing Available Data Gerrit Dogger Product and Application Specialist Cybectec Inc. Objectives 2 Where are we and what is needed The benefits of using IED data Discussion of challenges and their solutions Discussion of future developments Real-world case study: Emergency power management and load restoration Substation Evolution 1/2 SCADA Existing situation IED RTU 3 PROTECTION METERING POWER QUALITY Substation Evolution 2/2 New situation: IEDs for protection, measurement and control Substation gateway/data concentrator for communication IED PROTECTION 4 METERING POWER QUALITY Automation Requirements Substation automation functions need – 5 Access to all substation data Control capability of substation switchgear A device with programming capability Introducing the Intelligent Gateway A communications gateway provides data access and control capabilities An intelligent gateway also provides automation capabilities Replaced by 6 Direct Benefits of the Intelligent Gateway 7 No PLC or other additional devices needed Fewer devices reduce administrative costs No additional cabling – IEDs are already connected Opportunity for optimized price/performance relay configuration Reinforced by the additional intelligence Simplified substation architecture – vendor independent Indirect Benefits of the Intelligent Gateway These might be more important in the long run – 8 Simpler diagrams because of reduced cabling Less maintenance on diagrams Fewer devices means Fewer spare parts Less training Challenges and Their Solutions Using intelligent gateways introduces new challenges – 9 Response times Exception handling Supporting redundancy Response Times – Issues Data acquisition delays due to communication between gateway and IED Delay in command execution Note: Immediate faults are handled by the IED. 10 Response Times – Solutions Modern protocols reduce data acquisition delays – 11 DNP3, IEC 60870-5-101, IEC 60870-5-104 use unsolicited reporting Response Times – Solutions Processor/task priority reduce the command delay – 12 High priority for Automation tasks Command handling IED command handling Exception Handling – Issues Special care needs to be taken for – 13 Invalid incoming data Command execution error handling Exception Handling – Solutions Data invalidity can be handled by – 14 Checking individual data point quality Checking the communication link status Exception Handling – Solutions For command execution – 15 Check the protocol command acknowledgement Check the corresponding indications Supporting Redundancy – Issues Redundancy introduces additional challenges – 16 Correct handling of failover situations Synchronization of data between the programs No or limited concurrent execution Supporting Redundancy – Solutions To ensure correct execution – 17 Plan redundancy from the start Use internal program indications Use external indications – binary inputs Supporting Redundancy – Solutions 18 Fast failover needs data synchronization Gateway must address this issue Supporting Redundancy – Solutions 19 Both synchronized gateways might execute the program. Highly undesirable Should be solved in the design Future Developments Some trends we see developing: 20 IEC 61850 – GOOSE messages can optimize interaction Communication availability Substations can share more data This enables region-wide automation Real-World Case Study: Emergency Power Management and Load Restoration Incomer #1 Incomer #2 EDG #1 EDG #2 EDG #3 52R-2 52L-3 52L-2 52L-1 52R-1 52L-R NO F1 21 F2 F16 F17 REDUNDANT CONTROL CENTERS REDUNDANT GATEWAYS EDG MCP INCOMER UNDERVOLTAGE PLCS GENERATOR BREAKER IEDS 22 FEEDER IEDS Start state Initialization and C: Start of SMP A: Initialize system IDLE state C: One or both incomers closed & C: `Permissive to syn and close EDG`s CBs` A: Reset `Permissive to syn and close EDG`s CBs IDLE C: Both incomers open & C: NOT `Permissive to syn and close EDG`s CBs` A: Open feeders C: Both incomers open & C: `Permissive to syn and close EDG`s CBs` Wait for feeders to open C: One or both incomers closed Blackout: open feeders C: (Both incomers open & C: All feeders open & C: Bus load less than 1 MW) OR C: FeederOpenTimer timout (10 sec) A: Set `Permissive to syn and close EDG`s CBs Wait for power from generators C: One or both incomers closed Feeders open: Start generators C: 1 or more EDG`s CB s closed A: Calculate power A: Determine next feeder C: All feeders Done & C: Retrycounter < 3 A: Retrycounter := Retrycounter + 1 Retry feeders that didn’t close C: One or both incomers closed Closing feeders C: Power is available A: Calculate power A: Close selected feeder Determine Close Fail Wait for close confirmation C: Feeders to retry deteminated A: Determine next feeder C: One or both incomers closed 23 C: (Feeder is closed || timeout (5sec)) & C: Not all feeder are closed A: Determine next feeder Power: Close feeders (priority based) Emergency Power Management and Load Restoration Basic facts 24 Put into service in November 2005 Normal conditions: restore power within 1 minute Mainly waiting for generators to come online Failover condition: restore power within 1.5 minutes Concluding Remarks Benefits 25 No additional hardware Uses existing data and wiring Fewer spare parts Lower administration costs – Minimal training needed Everything is available to implement it now Proven concept Concluding Remarks Development 26 Better interaction using IEC 61850 GOOSE messages Upcoming opportunities for region-wide automation Contact Information Gerrit Dogger Product and Application Specialist Cybectec Inc. Gerrit.Dogger@Cybectec.com 27 Questions? 28