Electrical Signaling Electrical protective signaling systems are configurations of components used to produce alarm signals indicative of fire, smoke, sprinkler waterflow or other emergency and to produce supervisory signals indicative of conditions needing attention with respect to protection equipment or watch service. System configurations are classified according to where and how the signals are received. The categories are commonly designated as local, municipal, remote station, proprietary and central station. Auxiliary systems are either local or proprietary systems interconnected with a municipal system. This category presents the major system component categories and the integrated system configurations. The selection of components to form a hybrid system should be made only by those skilled in system design. Also, the suitability of any system application should be judged on the basis of the hazard(s) being protected. Emergency Voice/Alarm Communication Systems An emergency voice/alarm communication system consists of an Approved local alarm, remote station or proprietary signaling system incorporating dedicated manual and automatic facilities for the origination, control and transmission of verbal information and instructions pertaining to a fire alarm emergency to the occupants of a building. These systems meet the requirements of the NFPA Standard 72. Safepath4 Multi-Function Facility Communication System The Safepath4 Multi-Function Facility Communication System is a voice evacuation system intended to be used with an FM Approved 864 night edition FACP. The SafePath4 consists of the following: SP40S[E, BG, X, D, ED] is a single channel, 40 Watt emergency evacuation message system. The SP40S includes a synchronized 27.4Vdc, 2A strobe output Class B Style Y for Cooper Notification and Simplex compatible indicating devices max. 33 at 15cd. The SP40S also has a “synchronization pass through” synchronized pulse from another source to pass through; SP40S-D-PIK Conversion Kit AM-SP40S-SMK “standard "After Market" Message Kit AM-SP40S-PMK Programmed Message Kit SPB series of audio boosters provides added power for speakers and strobes. The audio output voltage is 25V, 70.7V or 100V. Audio input voltage is 1V, 25V, or 70.7V. SPB-160[E, BG] 160W. SPB-320[E, BG] 320W. SPB-80/4[E, BG, X] 80W and 4A strobe NAC power; SP4-RM[X] Remote Microphone Expansion; SP-APS intelligent Addressable Paging Splitter; SPRM[BG] Safepath Remote Microphone; SPRM-GP is for non-alarm general paging through an Audio Booster. [All emergency messaging will override the operation of the SPRM-GP]; SP4-A/B CLASS A/B SPLITTER; SP4-BCB Battery Cutoff Board; NACIM converts Notification Appliance Circuit (NAC) to an open collector circuit; SP-SVC Supervised Volume Control; SP4-LOC[SB, FB] console for remote location live emergency voice announcements; Supplementary use only - SP4-TZC and SP4-TZC-P SAFEPATH4 Telephone Zone Controller, and SP-COA Port Adapter; EOLK, EOLK-EM end of line resistors; BATC[BG] battery cabinet holds up to two pairs of 12V/24AH or one pair of 12V/33AH batteries. The enclosure is designed for indoor, dry use only; Model designations may include a suffix such as SIM to identify a Private Label product configuration. The following are compatible notification devices for SafePath4 system: Cooper Notification compatible speakers - ET-1010-R, ET-1080, ET70-R, ET80, ET90, RSS-24MCW, E70, E90, S8-70/25, STH-15SR, STH-4R, STH-3R, STH-2R, STH-2G. Cooper Notification compatible strobes - RSS-24MCWH, RSS-241575W, RSSWP-2475W, RSS-24MCC, RSS-24MCCH, RSS-24MCCHR, RSSP-24MCWH, RSSP-24MCW, RSSP-241575W, DC-MAXS. Cooper Notification compatible speaker/strobe combination - ET-1080-IS-24, ET80-241575W, S8-25/70MCCH, ET-1080-LS-24, © 2007-2012 FM Approvals. All rights reserved. 1 of 2 Cooper Notification compatible speaker/strobe combination - ET-1080-IS-24, ET80-241575W, S8-25/70MCCH, ET-1080-LS-24, ET90-24MCC, STH-2MSR, ET-1080-LSM-24, ET90-24MCCH, STH-3MSR, ET-1080-MS-24, E70-24MCW, STH-4MSR, ET-1080-SLM-24, E70-24MCCWH, STH-2R24MCCH, ET70-24MCW, E70-241575W, STH-3R24MCCH, ET70-24MCWH, E90-24MCC, STH-4R24MCCH, ET70-241575W, E90-24MCCH, STH-4M30WC, ET80-24MCW, S8-25/70MCC, STH-90-R24MCCH, ET80-24MCWH. Simplex compatible speakers - 4902-971, 4902-9717, 4902-9721, 4902-9716(CA), 4902-9717(CA), 4902-9721(CA). Simplex compatible strobes - 4906-9101, 4906-9102, 4906-9103, 4906-9104. Simplex compatible speaker/strobe combination - 4906-9151, 4906-9153, 4906-9154. Company Name: Cooper Notification Inc Company Address: 7246 16th Street East, Suite 105, Sarasota, Florida 34243, USA Company Website: http://www.cooperwheelock.com New/Updated Product Listing: No Listing Country: United States of America Certification Type: FM Approved © 2007-2012 FM Approvals. All rights reserved. 2 of 2