High Performance Cover Clamps Installation Manual

High Performance Cover Clamps
Installation Manual
High performance
cover clamp
The high performance cover clamp is designed for any
application, including industrial high wind environments.
• Use with HPL, SDL, and HDL Series Cable Ladder
• Recommended for any covered cable ladder
application
• High wind rated up to 76 m/s (170 mph)
• Utilizes slots in ladder and cover for strength
• Helps reduce sagging and warping
• Available in mechanical zinc or stainless steel
• Raised clamp available for side ventilation
• Multiple installation options for fittings (pages 4-5)
Number of Clamps for Wind Speeds up to 76 m/s (170 mph)
Assembly
Cover Size
# of Clamps
Straight Section
1.5 M Length
3.0 M Length
All Radii
150 to 600 MM Radius
900 to 1200 MM Radius
All Radii
150 to 600 MM Radius
900 to 1200 MM Radius
150 to 600 MM Radius
900 to 1200 MM Radius
150 to 600 MM Radius
900 to 1200 MM Radius
150 to 600 MM Radius
900 to 1200 MM Radius
All Sizes
All Sizes
All Sizes
150 MM Reduction
300 to 900 MM Reduction
All Sizes
4
6
4
4
6
4
4
6
6
8
8
12
8
12
4
8
4
2
4
4
30-60 Degree Horizontal
90 Degree Horizontal
30-60 Degree Vertical Bend
90 Degree Vertical Bend
Horizontal Tee
Horizontal Cross
Vertical Tee Up
Vertical Tee Down
Cable Support Fitting
Left/Right Reducer
Straight Reducer
Horizontal WYE Left/Right
2
INSTALLATION INSTRUCTIONS
Straight section cover
installation
Step 1: Determine the total number of clamps required.
See table on page 2.
3
Step 2: Determine installation location for cover clamps.
This is the top slot adjacent to the edge of the splice plate.
Step 5: Install the serrated flange nut and tighten.
Repeat steps for all clamp locations.
Step 3: Place the clamp plate on the inside of the ladder into the
determined slot.
Step 6: Align the cover slots with the clamp studs and place cover
on ladder.
Step 4: Align the plate on the outside of the ladder with the clamp.
Step 7: Secure cover by installing serrated flange nut over each
clamp. Torque all nuts to 13 Newton meters.
INSTALLATION INSTRUCTIONS
Fitting cover installation
Option 1
Step 1: Determine the total number of clamps required.
See table on page 2.
4
Step 2: Determine installation location for cover clamps.
This is the top slot adjacent to the edge of the splice plate.
Step 5: Install the serrated flange nut & tighten to 13 Newton
meters. Repeat steps for all clamp locations.
Step 3: Place the clamp plate on the outside of the ladder into the
determined slot.
Step 6: Align the cover slots with the clamp studs and place cover
on ladder.
Step 4: Align the cover clamp on the inside of the ladder with the
clamp plate.
Step 7: Secure cover by installing serrated flange nut over each
clamp. Torque all nuts to 13 Newton meters.
INSTALLATION INSTRUCTIONS
Fitting cover installation
Option 2
Step 1: Determine the total number of clamps required.
See table on page 2.
5
Step 2: Determine installation location for cover clamps.
This is the top slot adjacent to the edge of the splice plate.
Step 5: Install the serrated flange nut. Repeat steps for all clamp
locations.
Step 3: Mate the cover clamp and clamp plate together.
Step 6: Align the cover slots with the clamp studs and place cover
on ladder.
Step 4: Place both the cover clamp and clamp plate on the inside of
the fitting.
Step 7: Secure cover by installing serrated flange nut over each
clamp. Torque all nuts to 13 Newton meters.
Eaton’s B-Line Business
United States
509 West Monroe Street
Highland, IL 62249
United States
Phone: 800-851-7415
www.cooperbline.com/contactus
Eaton’s B-Line Business
Canada
5925 McLaughlin Road
Mississauga, ON L5R 1B8
Canada
Phone: 800-569-3660
www.cooperbline.com/contactca
Eaton’s B-Line Business
United Kingdom
Walrow, Highbridge
Somerset, TA9 4AQ
United Kingdom
Phone: +44 (0) 1278 783371
www.cooperbline.com/contactuk
Eaton’s B-Line Business
Saudi Arabia
PO Box 70160 - Al Khobar - 31952
Kingdom of Saudi Arabia
Phone: 00966 3 812 2236
www.cooperbline.com/contactme
Eaton’s Cooper Singapore
No. 2 Serangoon North Ave. 5
#06-01 Fu Yu Building, 554911
Singapore
Phone: +65 (0) 62974849
Eaton’s Cooper Korea Co., Ltd.
13 Fl Vision Tower, 7072 Yeoksam-dong
Gangnam-gu
Seoul, 135-080
Korea
Phone: +44 (0) 1278 772600
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s B-Line Business
509 West Monroe Street
Highland, IL 62249
Eaton.com
© 2013 Eaton
All Rights Reserved
Printed in USA
Publication No. HPCC-13
August 2013
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.