SC-RP – Universal Source Controllers – Feed Through iLumin Technical Data

iLumin
Technical Data
SC-RP – Universal Source Controllers –
Feed Through
Catalog#
Prepared by
Project
Date
Comments
Type
Overview
The Switched Relay Controllers are scalable to any size application.
The LCD graphical user interface and keypad permit programming
and monitoring for complete system control and integration. Each
Switched Relay Controller can control up to 48 relays per panel with
two discrete inputs for use with occupancy sensors or other input
devices. The Switch Relay Controller family can be networked with
other iLumin Source Controllers to provide both architectural and
non-dimmed control. Each panel has an onboard Ethernet and RS485
ports that may be used for ASCII integration to A/V or other third
party systems, a DMX interface for complete system integration and
optional support for up to 24, 0-10V dimming outputs. Variable Relay
Timing Technology automatically senses the optimal time to switch
lighting loads, based on the load attached to each output. This not
only extends the life of the relays but also reduces the switching
impact on the connected loads. Each output provides real-time
Power Metering data available from both the LCD graphical user
interface and via the Ethernet port.
Features
Capable of mixed load voltages (120/277/347 VAC)
Capable of mixed sources (normal and emergency power)
Manual control of individual relays
Programming stored in non-volatile memory
Individually replaceable relays with Variable Relay Timing
Technology
30 Amp relays are used on all 20A relay cards to extend relay life
RoHS compliant
Up to 24, 0-10V Dimming channels (optional)
Control receptacle loads with Latching Relay
SC-RP – Universal Source Controllers – Feed Through
July 2015
Mechanical
Dimensions
Wall mounted design
Surface mount enclosures
Low voltage input connections
Feed Through Panel
An LCD graphical user interface and keypad
for ease of programming and configuration.
The interface can be used for programming
single area systems there is no need to use a
PC. The GUI also allows programming of the
astronomical timeclock.
All SC-RP Source Controllers have RS485
and UDP over Ethernet connections to allow
for control by third party systems (Building
Management System, Audio/Visual, etc.)
through the use of open protocol ASCII
message commands
Two contact closure inputs for integration
with auxiliary equipment and emergency
lighting input
DMX512 input for control by entertainment
systems
Power metering information is available via
UDP over Ethernet through the use of open
protocol ASCII message commands
Programming
Interfacing
(Inches/mm)
SC-RP 18: 31”H X 24”W X 6”D (up to 18 relays)
SC-RP 36: 40”H X 24”W X 6”D (up to 36 relays)
SC-RP 48: 48.25”H X 24”W X 6”D (up to 48 relays)
24 in.
(609.6 mm)
6 in.
(152.4 mm)
31 in. (787.40 mm)
Specifications
24 in.
(609.6 mm)
Standards
24 in.
(609.6 mm)
6 in.
(152.4 mm)
Load Types
6 in.
(152.4 mm)
(All relay’s have a 25KA at 277 VAC SCCR)
Latching Relay Ratings:
20A, incandescent 120 VAC
20A, ballast 277 VAC
31 in. (787.40 mm)
Relay Ratings
40 in. (1219.20 mm)
24 in.
Each 0-10V output supports up to 50 ballasts/drivers that draw
(609.6 mm)
the standard 2mA each
48.25 in. (1225.55 mm)
Non-dim (Switched)
20A, ballast 347 VAC
Maximum wire size: 8 AWG
1HP @ 120 VAC, 2HP @ 277 VAC
24 in.
(609.6 mm)
Two Pole Relay Ratings:
24 in.
(609.6 mm)
Normally open
6 in.
(152.4 mm)
20A, ballast 480 VAC
Maximum wire size: 8 AWG
2
www.eaton.com/lightingsystems
48.25 in. (1225.55 mm)
40 in. (1219.20 mm)
1HP @ 120 VAC, 2HP @ 277 VAC
6 in.
(152.4 mm)
(1
SC-RP – Universal Source Controllers – Feed Through
July 2015
Wiring Diagram
Low voltage connections for iCANnet, DMX512, RS485, Ethernet, Contact
Closures, 0-10V Dimming come into the center top section of the enclosure
Relay connections to lighting loads (conduit
may enter through side or side top of the
enclosure)
31 in. (787.40 mm)
24 in.
(609.6 mm)
Latching Relay Receptacle Control
Sample System Topology
www.eaton.com/lightingsystems
3
SC-RP – Universal Source Controllers – Feed Through
July 2015
Ordering
SC - M - 18 - RP - MP - FT - 20 - S - 12 - 3 - HF1
Product
Interior Options
SC = Source Controller
0
= 0, 0-10V Dimming Channels (18, 36, 48)
HF1 = 12, 0-10V Dimming Channels (18, 36, 48)
HF2 = 24, 0-10V Dimming Channels (36, 48)
Voltage
M = Mixed
Number of Two Pole Relays (Two Pole
Relays count as 2, Single Pole Relays)
Number of Circuits
0-8 = 18 Size
0-18 = 36 Size
0-24 = 48 Size
18, 36, 48
Source Controller Type
RP = Relay Panel
Number of Single Pole Relays
0-18 = 18 Size
0-36 = 36 Size
0-48 = 48 Size
Phase
MP = Multi Phase
Panel Feed
Enclosure
FT = Feed Through
S
= Surface
Branch Breaker Rating (Amps)
20 = 20 Amps
SC-RP Additional Components
iBarrier
HF1
HF2
Individual Relay Barrier, Voltage and Power Source
Separation
Field Installable, 12, 0-10V Dimming Channels
(Only supported in the 18, 36 & 48 size panels)
Field Installable, 24, 0-10V Dimming Channels
(Only supported in the 36 & 48 size panels)
Ordering Examples
SC-M-18-RP-MP-FT-20-S-12-3-HF1
SC-M-36-RP-MP-FT-20-S-18-0-0
18 circuit surface mount feed through panel with 12 single pole relays, 3 two
pole relays, 12-10V dimming channels
36 circuit surface mount feed through panel with 18 single pole relays, no two
pole relays, no 0-10V dimming channels
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton
Lighting systems
203 Cooper Circle
Peachtree City, GA 30269
www.eaton.com/lightingsystems
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD503024EN
July 10, 2015
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.