The Industry’s Best Selective Coordination Solution Just Got Better The New Quik-Spec™ Coordination Panelboard with a Footprint up to 40% Smaller than other Fusible Panelboards is Now Available up to 1200A • Configurable panelboards with options for 600, 800 and 1200A mains and branches from 1-600A all rated 200kA SCCR at 600Vac • Smallest standard fusible panelboards in the industry • Featuring the finger-safe UL Class CF CUBEFuse™ with ampacity rejection features • Available with time-delay or UPS/critical application fast-acting fuses • UL listing makes it simple to address NEC® selective coordination system requirements in an all fused system For more information visit www.cooperbussmann.com/QSCP Fusible Branch Circuit Panelboards The Quik-Spec™ Coordination Panelboard (QSCP) simplifies selective coordination in a fully fused system by using published fuse ampacity ratio tables. This eliminates lengthy and costly studies required with circuit breakers. The large 1-600A branch disconnect fuse range enables closely matching fuse ampacity with UPS loads. Fault current events do not require the disconnect to be tested and recalibrated as is the Code requirement for circuit breakers. To enhance safety, the QSCP branch disconnects utilize a rejection feature that helps avoid overfusing. The QSCP offers all these advantages while having a footprint up to 40% smaller than other fusible panels. Quik-Spec Coordination Panelboard Compared to Traditional Fusible Circuit Panelboards. Panel Configuration SCCR Voltage Type Main Bus Rating Branch Fuse Type Size Quik-Spec Coordination Panelboard 50kA 200kA 600V 600V MLO MLO up to 1200A UL Class CF CUBEFuse* and UL Class J 27-38˝ Width Eaton (PRL4) GE (ADS) Square D (QMB) 200kA 600V MLO up to 1200A Circuit Breaker Panelboards 10kA-100kA 240V-480/277V MLO up to 1200A Class H, J, K, R & T N/A 36-44” Width 36-44” Width Design Features • Branch-circuit amp ratings • Branch amp rating rejection feature • Branch circuit disconnect • Short-circuit current study required • Ease of achieving selective coordination • Study is job specific • Study applicable if fault currents change Up to 600A (1-, 2- and 3-Pole) Rejection by fuse amp breaks UL 98 CCPB and UL 98 switches Rejection by fuse case size only UL 98 Fused disconnect Circuit Breaker No (if fault level <200kA) Simplest (use fuse ratios) Not specific (up to 200kA) Yes (up to 200kA) No (if fault level <200kA) Simplest (use fuse ratios) Not specific (up to 200kA) Yes (up to 200kA) Yes (at each point of use) Requires plotting time-current curves and proper interpretation. Yes (typically not transferable) No (must re-verify) Up to 1200A N/A N/A Safety Features • Branch disconnect with integrated lockout means • Interlock to prevent branch fuse removal while energized • Lockable main disconnect (main configuration) Cost * UL Class CF with Class J electrical performance. Yes Yes, but defeatable Yes Yes No N/A Yes (optional) $$-$$$ Yes (optional) $$$$ No $$-$$$$$ 1. Typical panelboard voltage ratings are 208Y/120 3-P, 4W, 120/240 1-P, 3W, & 480Y/277 3-P, 4W. 2. Multi-pole configurations may be available by special order. 3. Suitable for use on most systems up to 600Vac. This information is to provide a comparative analysis based upon the similarities and dissimilarities between Cooper Bussmann and competitive offerings. This does not replace specific product documentation for Cooper Bussmann products. Information in this document about other manufacturers’ products was collected from published materials. This document is a general guideline and is not all inclusive. © 2011 Cooper Bussmann www.cooperbussmann.com Reorder #3187 0611 Printed in USA