7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com WESTGATE ELEMENTARY SCHOOL REPLACEMENT 2514 W. 4th Ave. Kennewick, WA 99336 ADDENDUM No. 2 March 28, 2016 GENERAL INFORMATION ITEM 1 DETAIL/DESCRIPTION NOTE: The Sign-in Sheet for the Pre-bid Meeting (3-24-16) is also available on Kennewick School District’s website: http://www.ksd.org/District/Departments/Capital-Projects. NOTE: The site survey (available for download on the Owner's website) does not show stockpiled material. Crushed brick, crushed asphalt and general fill quantities and approximate locations are shown on sheet C1.00. ELECTRICAL NOTE: All exposed cable located above the suspended acoustical tile ceilings shall be plenum rated. Cable installed in conduit can be non-plenum ELECTRICAL NOTE: All door position contact switches are provided with the hardware. Division 26 shall provide rough-in to door frame. Coordinate RI location (into frame) with the hardware installer ELECTRICAL NOTE: Provide cable and rough-in from all doors with electronic hardware and magnetic holders to the security access control system. All doors with electronic hardware shall lock and magnetic holders release upon lockdown activation. Exceptions: doors 152,153 & 158 IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH DESCRIPTION ADD 1.05 to read: 01 1000 1.05 CONTRACTOR USE OF SITE A. Time Restrictions: 1. Limit conduct to hours as per the City of Kennewick Municipal Code . 07 4213 2.01A ADD approved manufacturer: The Bryer Company, Symmetry Series C23 or C64 panels: www.thebryercompany.com 07 4213 2.02B REVISE 4 to read: 4. Panel Width: 12 or 16 inches. Addendum #2 Page 1 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 07 4264 2.01A DESCRIPTION ADD approved manufacturer: Larson by Alucoil; Product 6mm ACM panels: www.alucoilnorthamerica.com. 07 4264 2.01 ADD paragraph B to read: B. Wall Panel System Manufacturers: 1. Phoenix Panels: www.phoenixpanels.com. 2. Substitutions: See Section 01 6000 - Product Requirements. 07 4264 2.02A.1 08 7100 3.07 REVISE sheet thickness to be 4mm, minimum. ADD line to HW1 to read: Access control by others 08 7100 3.07 REVISE HW12 to: Add (1) Power Supply PS902, Delete (1) DPS 2757L 08 7100 3.07 DELETE (1) DPS 2757L from HW14. 08 7100 3.07 ADD line to HW21 to read: (1) DPS 2757L 08 7100 3.07 ADD line to HW25 to read: Access control by others (reader both sides) DELETE (1) key switch 653-04 L2 08 7100 3.07 REVISE HW26 to read: 3 ea Hinges TA2714 26D 4 ½ x 4 ½ 1 set Push/Pulls 110 x 73C/73CL 630 1 ea Roller Latch 594 626 (mt @ head) 1 ea Vertical Housing HVD-32 - 96 2 ea Mag Lock M32 1 ea Push Button 625RD 1 ea Power Supply PS902 1 ea Overhead Stop 9-036 630 1 ea Kickplate K1062 10 x 1 ½ LDW 630 B4E 3 ea Silencers 1 ea Wiring Diagram Wiring by elec contractor Addendum #2 Page 2 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 08 7100 3.07 DESCRIPTION ADD line to HW29 to read: Access control by others 08 7100 3.07 ADD line to HW30 to read: Access control by others 09 9123 3.07 REVISE H to read: H. P-8: Benjamin Moore, Woodcliff Lake 980 10 1400 2.01A ADD approved manufacturer: Meyer Architectural Signs; Product Nova Photopolymer: www.meyersignco.com. 10 1400 2.02C.6 ADD f to read: f. Music Room: One (1) occupant load sign. 10 2226.33 2.04C ADD 3 to read: 3. Cylinder cores to be keyed to School's keying system. 11 4000 2.03K.5 ADD subparagraphs c, d and e to read: c. Loose Parts: Beacon II smart controller. d. RRC (Remote Refrigeration Control). e. Provide wireless remote alarm system. 11 4000 2.03K.6 ADD subparagraph e to read: e. Provide wireless remote alarm system. 11 4000 2.03K DELETE paragraph 7. 11 4000 2.03K ADD item to read: Height: 8'-0" overall. Addendum #2 Page 3 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH 23 0900 2.02-F DESCRIPTION Add paragraph 2. and associated subparagraphs to read “Energy Monitoring and Reporting Display” A. The energy monitoring and display system shall include all necessary hardware, software and programming to display real-time and historical energy consumption data with the occupants of the building on a remote monitor provided and installed by others. This monitor will not be dedicated to the purpose of energy monitoring and reporting display as it may also be utilized for general communications. The controls contractor shall coordinate with the owner’s IT contractor and is responsible for network interfacing and cabling between the BAS workstation and the monitor system. B. The system shall display real-time consumption (water, gas, various electrical meters) and historical comparison graphs. The live information will be shown on a gauge and the historical information will be shown via a graph. This graph shall show daily, weekly, monthly and yearly totalization. 23 2315 Various Delete paragraphs 1.02-C, 1.04-C-2, 1.05-C, 1.07-C, 2.01-B, 2.01-C, 3.01-A-1-a, and 3.01-A-2 as aluminum piping is not allowed. 23 2500 2.07 Add equipment tags to title “2.07 Sidestream Filter (FLTR-1, FLTR-2)” 23 2500 2.07-B 23 2500 2.05-A Add statement “Provide additional 20 gallon recovery tank for boiler relief valves due to inability to pipe relief valve discharge to main tank location.” 23 3100 3.05 Delete paragraph and subparagraphs. Underground ducts not used. 23 3100 3.09-A Clarify paragraph to read “Contractor shall test all 25% of total duct area per NREC and all medium pressure ductwork (3” w.g. and above pressure class).” 23 3300 2.10-A 23 3300 2.06-H 23 3300 2.08-C-4 23 5216 2.02-I.3 23 7200 2.3-G-2d Addendum #2 Revise to read “Shelco Filters Model 4FQS1 FOS-80-4” Revise to read “…U.L. leakage class II” Delete paragraph Delete paragraph. Revise Safety Relief Valve Setting to 100-psig Revise paragraph to read “Where indicated, provide airflow monitoring device equal to TemFLO device…” Page 4 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE PROJECT MANUAL ITEM SECTION PARAGRAPH DESCRIPTION Revise all three paragraphs to read “Unless otherwise indicated and where EC motors are specified, a separate VFD is required for each fan motor in the unit and shall be factory mounted and wired to motor. See VFD specifications section 230926.” 23 7200 2.3-G-2e, Q-2, and R-2 23 7200 2.3.J.3 Revise paragraph to read “Flat plate aluminum air-to-air crossflow heat exchanger.” 23 7000 2.3.C.1 Revise last sentence of 1st paragraph to read “The color of AHU-1 thru -4 shall be custom and selected by architect.” 23 8226 2.01-H-1 26 2200 2.03 27 1500 2.02A 28 3100 2.06Q Revise paragraph to read “Provide with control transformer and/or relay for remote DDC thermostat by the control contractor. See Control Diagrams on drawings and Specification Section 23 0900” Delete paragraphs L-N in their entirety Delete sub-paragraphs 3-5. See 26 0533 for extra rough-in and 26 2726 for extra receptacles. Add the following: In addition to the floor plan (Zone Map) sheet provide type written instructions on how to reset the system. IN THE DRAWINGS ITEM SHEET L2.1/L2.2 DETAIL/DESCRIPTION REVISE scale on drawings per LA-2/1. 1/A2.11 CHANGE wall type from 10A to 11A (see attached drawing AA-2/10). 5/A4.11 Dimension soffit over casework @ south wall of Music 115 (see attached drawing AA-2/2). 1/A5.01 ADD 1'-0" handrail extension to top of ramp in RAMP 114. Relocate back stage curtain support from suspended ceiling to soffit in MUSIC 115. See attached drawing AA-2/6. 3/A5.01 CHANGE steel stud wall between Health 110 and RR 111 from 3 5/8" to 6" (see attached drawing AA-2/9). 4/A5.01 Decrease opening width by 12" to GIRLS 132/202. Swing non ADA stall doors inward. See attached drawing AA-2/1. Addendum #2 Page 5 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION 6/A5.01 Swing non ADA stall door inward (see attached drawing AA-2/11). 3/A5.02 DELETE 3'-4" dimension from door into Quiet 152. DELETE 1'-11 1/2" dimension @ casework between SP ED 150 and SP ED 153 ADD 1'-0" dimension to door into RR 151. ADD 1'-6" dimension from casework to door between SP ED 150 and SP ED 153 (verify). See attached drawing AA-2/12. A5.03 ADD (+/-) to dimensions that read, "3'-3/8"" and "2'-8 7/8"" on 2/A5.03. A6.00 Change note on 17/A6.00 to read, "PAINTED CMU (P-1), TYP." A6.00 Remove note that reads, "CHAIR RAIL, TYP." from detail 2/A6.00. A6.00 Remove note that reads, "IRP-1, TYP." from detail 2/A6.00. A6.00 Change note on 4/A6.00 to read, "PAINTED CMU (P-1), TYP." A6.00 ADD line to represent scheduled base to 10/A6.00. A6.00 ADD line to represent scheduled base to 14/A6.00. 7/A6.01 CMU lintel to be @ 8'-0" above music floor (see attached drawing AA-2/4). 4/A6.01 CMU lintel to be @ 8'-0" above music floor (see attached drawing AA-2/5). A6.01 CHANGE note on 1/A6.01 to read, "PAINTED CMU (P-1), TYP." A6.01 CHANGE note on 7/A6.01 to read "PAINTED CMU (P-1), TYP." A6.01 Fill in casework tag on 9/A6.01 to read, "15/A8.19". A6.01 ADD note reading, "LOCKING ALL CABINETS, THIS ROOM, TYP." to 14/A6.01. A6.02 ADD line to represent scheduled base to 6/A6.02. A6.02 MOVE arrow down on 7/A6.02 and 12/A6.02 to point to mop rack. A6.04 ADJUST wall hatch to fill entire wall on 2/A6.04 and 10/A6.04. A6.04 REMOVE SHOWER note from 11/A6.04. A6.04 REMOVE extraneous line work from 20/A6.04 and 1/A6.05. A6.05 ADD note that reads, "INTEGRAL COVE BASE, TYP. AS SCHEDULED" to 6/A6.05, 11/A6.05 and 15/A6.05. A6.06 ADD note that reads, "INTEGRAL COVE BASE, TYP. AS SCHEDULED" to 4/A6.06 and 14/A6.06. A6.06 CHANGE wall finish from P-1 to VWC-1 above chair rail in elevations 18,19,20 and 21 on sheet A6.06. A6.07 ADD note that reads, "(1) 8'-0" AND (2) 4'-0" MARKER BOARDS ON SLIDING TRACK IN FRONT OF STORAGE CABINET" to 2/A6.07. Addendum #2 Page 6 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION A6.07 ADD bookcase to 5/A6.07 to match adjacent bookcases. A6.08 ADD line to represent scheduled base to 10/A6.08. A6.08 ADD note that reads, "(1) 8'-0" AND (2) 4'-0" MARKER BOARDS ON SLIDING TRACK IN FRONT OF STORAGE CABINET" to 2/A6.08. A6.08 DELETE chair rail from 8/A6.08. A6.11 ADD line to represent scheduled base to 5/A6.11. A6.11 ADD line to represent scheduled base to 15/A6.11. A6.12 MOVE arrow on 2/A6.12 to point to pendant fixture. A6.13 CHANGE note on 1/A6.13 to read, "INSTALL TYPICAL WAINSCOT AT EAST AND WEST WALLS OF ALCOVE W/ VWC ABOVE, TYP." A6.16 DELETE elevations 14,15 and 16 from A6.16. A6.16/A9.0 CHANGE finish of east wall of Office 117 from "CMU" to "PAINTED CMU (P-1), TYP." in elevation 10/A6.16 and in Finish Schedule on A9.0. Varies Based on floor plan differences, classrooms on the north side of the building vary slightly from classrooms on the south side of the building. Each general classroom space has a consistent 16'-0" of marker board space. In addition to that, north classrooms have 10-0" of open shelving space (4 @ 30" wide; see 14/A8.19 for detail) and south classrooms have 8'-7 1/2" of open shelving space (2 @ 30" wide and 1 @ 3'-7 1/2" wide; see 14/A8.19 for detail). Additionally, Classrooms 163 and 241 have only 4'-7 1/2" of open shelving (2 @ 2'-3 3/4" wide; see 14/A8.19 for detail). Resource classroom 173 is configured like Computer Lab 231. See floor plans for additional information. Verify all dimensions in field. 1/A7.11 Center fixtures on both sides of opening between MULTI-PURPOSE 118 and MUSIC 115. Relocate back stage curtain support from suspended ceiling to soffit in MUSIC 115. Dimension south wall soffit in MUSIC 115. CMU lintel to be @ 8'-0" above music floor. See attached drawing AA-2/3. 1/A7.11 REMOVE detail callouts 20/A8.16 from soffits on east side of Commons 130. 1/A7.11 ADD light fixtures in PE OFFICE125 (see attached drawing AA-2/7). 1/A7.11 ADD light fixtures to wash soffit between GIRLS 132 and BOYS 133 (see attached drawing AA-2/8). 1/A7.21 ADD light fixtures to wash soffit between GIRLS 202 and BOYS 203 (see attached drawing AA-2/8). 1/A7.21 ADD note that reads, "PAINT CEILING AND STRUCTURE P-6, TYP" to Commons 130 ceiling. Addendum #2 Page 7 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION A8.01 REVISE door 119A type to "HM/FRP". A8.01 CHANGE frame depth of door 111 from 5 7/8" to 8 1/4". A8.01 CHANGE width of door 152 from 3'-0" to 3'-2". A8.16 CHANGE 3" dimension on 11/A8.16 to read, "6". S2.11 MOVE columns and rectangular footing on grid 10 1” to the east, as shown on attached drawing SA-2/1. Floor beams and roof beams above also move to maintain alignment with columns. S2.21 CHANGE the W14x22 floor beam, spanning in the north/south direction and located approximately 9’-6” east of the elevator shaft, to an 18LH4 bar joist. S2.42 CHANGE the 6’-9” plan dimension to 6’-8” to account for the beam line on grid 10 moving 1” to the east, as shown on attached drawing SA-2/2. S4.3 REDUCE the plan dimensions of the concrete pedestals at the exterior canopy columns as shown on attached drawing SA-2/3. S5.1 MOVE the floor beam located below the framed wall 1” to the east, as shown on attached drawing SA-2/4. M1.1 AHU-1 thru AHU-7 and FC-1 thru FC-6: Add sound data. See attached clarification drawing MA-2/1. M1.1 AHU-1, -2, -3, -4: Revise heat exchanger outdoor air winter leaving dry bulb (LDB) to 49 degrees F. Revise heating coil entering dry bulb (EDB) to 65 degrees F. Revise heating coil MBH to 150, 130, 130, and 140 respectively. M1.1 AHU-5, -6, -7: Remove note #9 referring to VFDs on supply and return fans. Add note #3 to read “Provide EC motors on supply and return fans with manual speed adjustment dials factory mounted in the control panel for use in TAB.” M1.1 AHU-5, -6, -7: Revise supply fan horsepower to 7.5 hp, 7.5 hp and 2.0 hp respectively. Overall electrical data does not change. M1.1 VAV-109: Revise maximum CFM to 1000 cfm M1.1 VAV-111: Revise maximum CFM to 1800 cfm M1.1 VAV-204, -205, -211, -212, -304, -305, -311, -312, -403, -404, -410: Revise minimum CFM to 600 cfm M1.1 VAV-408: Revise minimum CFM to 150 cfm M1.1 FC-1: Revise model to Destiny LAH005A. M1.2 Add dryer exhaust booster fan EF-9, Fantech Model DBF4XL, 115V. Provide with lint trap and factory pressure sensor to automatically turn the fan on when the dryer is on. M1.2 Add Sound Attenuator Schedule. See attached clarification MA-2/2. Addendum #2 Page 8 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION M1.2 Add AC-4 and CU-4 to ductless split system indoor and outdoor unit schedules respectively. All specifications are identical to AC-3 and CU-3. M1.3 Pumps P-1 and P-2: Revise head and rpm for to 90-ft and 1750 rpm respectively. M1.3 Hot Water Finned Tube Radiation Schedule: Remove EWT and LWT data as it varies depending on specific instance. M1.3 Hot Water Finned Tube Radiation Schedule: Revise duplicate FT-6 at end of schedule to FT-7. M1.3 Hot Water Finned Tube Radiation Schedule: Revise GPM for FT-1, FT-3 and FT-4 to 1.0 gpm. M2.11 Add dryer vent in Health-110 along with booster fan EF-9. See clarification MA2/3. M2.11 Add transfer grilles and duct between MPR and Kitchen. See MA-2/3. M2.11 Add DDC room temperature sensors in Freezer-119A and Cooler-119B for monitoring only as indicated by control diagram 4/M7.1. M2.11 Add a note at room temperature sensor in Machine-124 to state “DDC sensor for monitoring only as indicated on control diagram 10/M7.0.” M2.11 Revise keynote #29 to read “…duct riser serving the Gym…” M2.11 Add sound attenuators SA-7 and SA-8 at supply and return ducts respectively from AHU-7 in the kitchen. M2.11 Add 20x10 duct size callout on kitchen hood KH-1 exhaust duct. M2.11 Add keynote callout #23 at transfer grille at south wall of Mech-134. M2.12 Revise keynote #4 to read “8x8 type 5, 100 cfm” M2.12 Remove EUH-5 in Elec-156 (room under Stair-155). M2.12 Add ductless split indoor unit AC-4 above door in Elec-156 (room under Stair-155) and room sensor for monitoring only per control diagram 10/M7.0. M2.11 Add 44x18 duct size callout on return duct for AHU-5 above PE Off-125. M2.21 Add dryer vent and a couple notes. See clarification MA-2/4. M2.21 Add a note at room temperature sensor in Machine-201 and Data-200 to state “DDC sensor for monitoring only as indicated on control diagram 10/M7.0.” M2.21 Add keynote callout #10 on ducts from AHU-5 and AHU-6 where they turn upward between grids 3 and 5. M2.21 Add diffuser callout “48x48 Type 3 on top side of duct” on main return ducts from AHU-1 and AHU-2 where they turn up. M2.22 Revise CFM of the six north classroom displacement diffusers from 1200 cfm to 1300 cfm. Addendum #2 Page 9 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION M2.22 Revise keynote callout #2 on transfer grilles at SGIC-214 and SGIC-219 to keynote #1. M2.22 Add diffuser callout “48x48 Type 3 on top side of duct” on main return ducts from AHU-3 and AHU-4 where they turn up. M2.41 Add note “2-inch duct liner on exterior ductwork” at exterior supply ducts from AHU-5 and AHU-6. M2.41 Add dryer vent termination. See clarification MA-2/5. M2.42 Add ductless split outdoor unit CU-4 6-ft north of EF-6. M3.11 Revise HWS/HWR pipe size running south over Cust Office-135B from 1-1/2” to 2”. M3.11 Revise HWS/HWR runouts to CUH-1 to 3/4”. M3.11 Add reference to detail 4/M5.1 in keynotes #1 and #2. M3.11 Revise keynote #14 to read “Control valves for AHU-6 to be 3-way.” M3.11 Add 3/4" condensate drain line from AC-3 in Elec-124 to mop sing in RR-121. M3.11 Relocate keynote callouts #14 and #15 on runouts to AHU-5 above Com Stor-123 to AHU-6 runouts above kitchen. M3.11 Add line size callout of 2” on branch connections feeding AHU-6 and AHU-7 above Table Stor-122. M3.12 Revise equipment tag FT-1 at each classroom displacement ventilation diffuser to FT-5. The reading nook tags remain FT-1. M3.12 Remove panel heaters in restroom RR-151 and RR-154. See attached clarification MA-2/6. M3.12 Revise heating water runouts to CUH-2 to 3/4". M3.12 Add ductless split indoor unit AC-4 above door in Elect-156 (under Stair-155) and note “Refrigerant line set up to condensing unit on roof through common walls of Cust-157 and Cust-224. See sheet M2.41 for condensing unit location. See detail 8/M5.0.” M3.21 Replace detail callout 1/M5.0 at Library-226 with note that shall read “Fin-tube heater installed within book casework. See arch details.” M3.21 Add note at FC-4 and FC-6 to read “3-way heating and chilled water valves. See system diagram and details.” M3.21 Revise several pipe sizes and add detail callout 9/M5.1 at piping penetration through floor of Mech-205. See clarification MA-2/7. M3.21 Revise equipment tag FT-4 in Title-206 to FT-7. M3.21 Revise equipment tag FT-4 in Coun-204 to FT-3. M3.21 Add reference to detail 9/M5.1 in keynote #2. Addendum #2 Page 10 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION M3.22 Revise HWS/HWR line sizes at Grid 12-H from 3” to 2”. Revise HWS/HWR/CWS/CWR line sizes at Grid 14-H from 3” to 1.5”. Revise runouts to AHU-3 and AHU-4 to 1” HWS/HWR and 1.5” CWS/CWR. M3.22 Add reference to detail 9/M5.1 in keynote #2. M3.23 Add boiler relief tank, VFDs, BAS Panel and boiler EPO switch. See clarification drawing MA-2/8. M3.23 Add VFD’s, detail callouts on filters and boiler EPO switch. See clarification MA2/9. M5.0 Detail 2: Revise detail callout 3/M5.0 at roof penetration to 1/M5.0 M5.0 Detail 3: Add note “Mount to concrete curb at exterior wall with top of heater flush with top of curb in order to provide approx 3” clear below the heater.” M5.0 Detail 9: Revise detail callout 10/M-504 at roof penetration to 7/M5.0 M5.1 Detail 1: Revise factory relief pressures of both relief valves from 50-psig to 100psig. M5.1 Detail 3: Revise note to air vent to read “High capacity automatic air vent. Route discharge to glycol recovery tank.” M5.1 Detail 7: Revise “Pressure Independent Balancing Valve” on the heating water return line to “Venturi” and revise line designation from HWR to HWS. M5.1 Detail 8: See clarification MA-2/10. M5.2 Detail 5: See clarification MA-2/11. M5.2 Detail 9: Remove damper and add external duct insulation up into the curb. M5.3 Delete Detail 6 as it duplicates Detail 6 on M5.2. M5.4 Detail 9: Revise detail callout 7/M5.4 to 10/M5.4. M5.4 Detail 10: Revise reference to detail 6 at the platform to reference detail 9. M5.4 Delete Detail 7 as it duplicates Detail 2. M5.4 Delete Detail 6 as it duplicates Detail 3. M5.5 Detail 2: Revise title to read “Air Handler Details (AHU-5, -6, -7)” M5.5 Detail 2: Revise keynote #2 to read “Angle filter, 2-inch MERV-8 + 2” MERV-13” M5.5 Detail 2: Revise keynote #3 to read “Return fan, direct drive plenum type with ECM” M5.5 Detail 2: Revise keynote #8 to read “Supply fan, direct drive plenum type with ECM” M5.5 Detail 2: Revise keynote #15 to read “24-inch tall roof curb sloped to accommodate sound attenuators below and match roof slope. Curb footprint shall include piping vestibule.” Addendum #2 Page 11 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION M6.0 Re-issue entire sheet. M7.0 Detail 4: Clarify overlapping text “…cut-off mode. Under this mode, all air handling units shall be signaled to close outside air intake dampers…” M7.0 Detail 6: Clarify overlapping text “Peak Demand History: The controller shall monitor and record the peak (high and low) demand readings from the gas meter. Peak readings shall be recorded on a daily, month-to-date, and year-to-date basis. Usage history: The controller shall monitor and record gas meter readings so as to provide a gas consumption history. Usage readings shall be recorded on a daily, month-to-date, and year-to-date basis.” M7.1 Detail 4: Clarify overlapping text “Room temp sensor shall be suitable for freezing conditions and shall be flush mounted with a stainless steel cover plate. Coordinate with kitchen equipment.” M7.3 Detail 1: Revise title to “Multi-purpose Room AHU and Kitchen Pressure Control Diagram (AHU-6).” M7.3 Detail 1: Change all VFDs to EC Motors M7.3 Add pressure sensor in kitchen and associated analog input (AI) ad controller. M7.3 Detail 1: Revise exhaust fan numbers for Kitchen and Dishwasher Hoods to EF-7 and EF-8 respectively. M7.3 Detail 1: Add outdoor airflow measuring station at outdoor air intake and associated analog input (AI) at DDC controller. M7.3 Detail 2: Revise title to “ Gymnasium and Kitchen AHU Control Diagram (AHU-5, AHU-7)” M7.3 Detail 2: Change all VFDs to EC Motors M7.3 Detail 2: Add outdoor airflow measuring station at outdoor air intake and associated analog input (AI) at DDC controller. M7.3 Detail 2: Revise sequence of operations paragraph 3 to read “The CO2 sensor (not applicable to AHU-7) shall modulate the outside air damper…” P2.11 Revise reference to “food service drawings” in general notes #1 and #4 to reference “architectural drawings”. P2.11 Relocate 4” COTF shown in Freezer-119A approximately 18” south so it’s no longer in the freezer room. P2.11 Install rain leaders in wall per clarification drawing PA-2/1. P2.12 Add keynote #12 to read “1-inch CW DN” P2.12 Add keynote #13 to read “3-inch W up with P-trap and Primer” P2.12 Add keynote #14 to read “2-inch V up” P2.21 Revise note “4-inch Gas DN” to gas line at grid 5 to “3-inch Gas DN” Addendum #2 Page 12 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION P4.01 Detail 2: Revise “N.I.C.” notation at full size bypass valve to “N.C.” to indicate Normally Closed. E0.01 Delete OFOI & OFCI remarks in the Communications symbols note column E0.02 Change luminaire Type S20 and S20P to have 2 light engines and provide with dual switching. E0.03 Delete the electrical materials and connections to CUH-2, CUH-3, CUH-6 & CUH7 E0.03 Change the circuit number for EF-9 to A2-9 E0.03 Add split system AC-4/CU-4 to schedule. Same material and requirements as AC3/CU-3. Use circuit M-10,12 E1.01A Clarification: This drawing is informative only and is included to indicate the basis-of-design photometric performance. Approved equal fixtures shall meet or exceed the point by point photometry values. E2.11 Change LCM1 that control luminaire Type S20 to LCM2 in all locations. E2.12 Change LCM1 that control luminaire Type S20 to LCM2 in all locations. E3.11 Add a card access reader, electric door hardware rough-in, magnetic door holder connection, relay and 120V circuit/connections to power supplies for door 114 per drawing EA3.11A E3.11 Add magnetic door holder connection, relay and 120V circuit/connections to power supplies for door 118B per drawing EA3.11A E3.11 Add magnetic door holder connection, relay and 120V circuit/connections to power supplies for doors 118A & 127D per drawing EA3.11B E3.11 Add two card access readers, electric door hardware rough-in and 120V circuit/connections to power supplies for door 127B per drawing EA3.11B E3.11 Change power supply location for door 127D to flush enclosure as indicated on drawing EA3.11B E3.11 Add electric door hardware rough-in and 120V circuit/connections to power supply for door 118C per drawing EA3.11C E3.11 Delete rough-in for door position switches at 119A, 119C & 119D E3.11 Add a card access reader for the elevator located east of the elevator door in Commons 130. E3.11 Add 135 degree, 120VAC fixed temperature heat detectors in the elevator pit located within 18” of the sprinkler heads E3.11 Change the location of the receptacle located on the west wall of Conference Room 108 to be 6” south of the casework niche E3.11 Delete EF-1 connection from room 124 Addendum #2 Page 13 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION E3.11 Change the location of EUH-2 in room 174 to be west of door 174. Move the receptacle in that location to the adjacent west wall E3.11 Change the location of the mechanical equipment in room 134 to that shown on the mechanical drawings. See the mechanical addendum for the pump VFD locations E3.11 Add two 120V circuits and two data drops to the BAS panels located on the east wall of room 134. See mechanical addendum. Use spare circuits MA-11 & 13 E3.11 Add two security alarm motion sensors in multi-purpose room 118. Locate one on the north wall and one on the south wall facing doors 118A & 118B E3.12 Delete CUH-2 & CUH-3 E3.12 Delete EUH-5 E3.12 Add AC-4 in room 156 above door E3.12 Add electronic door hardware connections to doors 152, 153 & 158 per drawing EA3.12A. For door 152, provide a momentary contact switch that will manually engage the electronic lock as long as the switch is depressed E3.21 Add 135 degree, 120VAC fixed temperature heat detectors in the elevator machine room 201, located within 18” of the sprinkler heads E3.21 Add a fire alarm system smoke detector in elevator machine room 201 E3.21 Add a fire alarm system connection to the PMP to monitor the heat detector and shutdown operating voltage E3.21 Add a card access reader for the elevator located east of the elevator door in Corridor 225 E3.22 Delete CUH-6 & CUH-7 E3.30 Change EF-9 callout to EF-1 E3.30 Add CU-4 to plan, located 6’ north of EF-6 E5.01 Add the following note to K8: PROVIDE SWITCH WITH PILOT LIGHT AND ID TAG FOR EXHAUST FAN E5.01 Add a SPST switch with a pilot light to the south wall of the hood enclosure. Provide an ID tag stating EXHAUST FAN E6.01 Change MDS amp rating to 1,000A E6.01 Change service lateral between the BPUD transformer and MDS to (3) sets 31/2”C., 3#600 KCMIL (AL), #600 KCMIL (AL) N. E6.01 Change dry-type transformer XSDP to 300kVA E6.01 Change feeder between the MDS and transformer XSDP to (2) sets 3”C., 3#350 KCMIL (AL), #2G. Addendum #2 Page 14 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com IN THE DRAWINGS ITEM SHEET DETAIL/DESCRIPTION E6.01 Change feeder between transformer XSDP and SDP to (3) sets 3-1/2”C., 3#600 KCMIL (AL), #600 KCMIL (AL) N., #3/0G. E6.01 Change SDP main breaker and bus rating to 1,000A E6.01 Delete the main circuit breaker in PDP E6.01 Change the DS1 circuit breaker and DS1 bussing to 400A in MDS E6.01 Change panel C3 feeder to 2-1/2”C. 3#250 KCMIL (AL), #250 KCMIL (AL) N, #6G. E6.01 Change panel MC feeder to 1-1/2”C. 3#1/0 (AL), #1/0 (AL) N, #6G. E6.01 Change the AIC ratings for panels A1, A2, B1, B2, C1, C2, D1 & D2 to 10,000 E6.02 Replace panel schedules for MDS, DS1, PDP & SDP with the schedules issued in this addendum; drawings E6.02A & E6.02B E6.03 Change the AIC ratings for panels A1, A2, B1, B2 & C1 to 10,000 E6.03 Change MC-26-29 and MG-1 to SPARE E6.03 Add dryer booster fan EF-9 connection in room 112, south wall. E6.03 Add BAS panels to circuits MA11 & 13 E6.04 Change the AIC ratings for panels C2, D1 & D2 to 10,000 PRIOR APPROVALS ITEM SECTION DETAIL/DESCRIPTION This approval is an approval of quality only. No attempt has been made to check each material as to special features, capacities or physical dimensions especially required by this project. It shall be the responsibility of supplier, manufacturer and Contractor to check all requirements before submitting for final approval. Final approval of exact features, sizes, capacities, etc., all of which must match materials indicated/specified, will be determined when submitted during construction period. Certain approvals are subject to conditions as noted. Vibration Isolators – Vibro-Acoustics 230548 VFD’s – JCI (approved only for factory mounting in Air Handling Units) 230926 Flexible Pipe and Equipment Connections – Nexus 232115 Flexible Pipe and Equipment Connections – Griswold 232115 Y-Pattern Strainers – Nexus 232115 Venturis - Nexus 232115 Venturis - Griswold 232115 Duct Silencers – VAW Systems 233300 Addendum #2 Page 15 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com PRIOR APPROVALS ITEM SECTION 233600 233723 233723 233723 233723 235100 235216 237200 238226 238233 DETAIL/DESCRIPTION Single Duct VAV Units - JCI Roof Hoods – Twin City Fans Roof Hoods – Loren Cook Roof Hoods – Penn Barry Exterior Louvers – United Enertech Condensing Appliance Vents - Schebler Condensing Boilers – Fulton Outdoor Air Handling Units - Venmar Electric Heaters - Qmark Fin Tube Heaters - Modine 26 5100 A24 Lumenwerx VIA2 Series 26 5100 A28 Lumenwerx VIA2 Series 26 5100 C24 Lithonia ZL1DL48 3000LM FST WH 26 5100 C24E Lithonia ZL1DL48 3000LM FST E7W WH 26 5100 C26 Lithonia ZL1DL48 3000LM FST WH 26 5100 D01-4 Lumenwerx Reveal Series 26 5100 D01-8 Lumenwerx Reveal Series 26 5100 D01-8E Lumenwerx Reveal Series 26 5100 D01-12 Lumenwerx Reveal Series 26 5100 D10 Lumenwerx Quad Series 26 5100 D10E Lumenwerx Quad Series 26 5100 S03 LSI Xenm3 Series 26 5100 S11 ERCO Tesis Series 26 5100 S13 LSI Xenm3 Series 26 5100 S20 Spaulding TRP Series 26 5100 S20P Spaulding TRP Series 26 5100 S23 LSI Xenm3 Series 26 5100 S51 MP Lighting L22 Series 26 5100 T12 AFX ALV Series 26 5100 T20 ConTech CTL825 Series Addendum #2 Page 16 7601 W. Clearwater Ave., Ste 206 Kennewick, Washington 99336 1 N. Monroe, Ste. 200 Spokane, Washington 99201 www.mmecarchitecture.com PRIOR APPROVALS ITEM SECTION DETAIL/DESCRIPTION 26 5100 X01 DualLite SE Series 26 5100 X02 DualLite SE Series 26 5100 X03 DualLite SEWL Series 26 5100 G01 Kenall MLHA12 48 R MW PP 150L40K DCC 1 DV 26 5100 G02 Kenall MLHA12 24 R MW PP 45L40K DCC 1 DV W/EMERGENCY BATTERY PACK END OF ADDENDUM NO. 2 Addendum #2 Page 17 SCD SCD 5' - 0" 1' - 6" 5' - 0" 4' - 0 3/4" 17'-0" (FACE OF GWB TO FACE OF GAWB) CLR. 5' - 0" TPD 5' - 0" 1' - 6" TPD SNR 5' - 0 3/4" 9' - 3" CLR. 1' - 10" 10' - 3" TYP. 17' - 4 7/8" 2 SCD 2' - 11" 3' - 0" SCD SNR TPD 2 TPD 2 2 4' - 1 1/4" 2' - 11" SCD 2' - 11" 2 2 TPD SNR 5 A6.05 3 4 TPD SCD 2' - 11" 19 18 SNR SNR 6' - 1 1/4" A6.04 20 3' - 0" 2 3' - 0 1/8" 17 3' - 0" SCD TPD PTD SD SD 13' - 1 1/2" PTD 2 4' - 1 1/4" 1 A6.05 4 ENLARGED TOILET ROOM 132 & 202, 133 & 203 PLAN SCALE: 1/4" = 1'-0" REF. DWG. 4/A5.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/10/16 RMS DCM 1/4" = 1'-0" AA-2/1 N O 2 2' - 0" SOFFIT ASSEMBLY 8" TYPE A INSET 3/4" 2' - 0" TYPE A 8" TYPE A INSET 3/4" TYPE A 7' - 2" 1' - 8" 09 21 16.GB58 3' - 4" 09 21 16.SS358 8" FLOOR ASSEMBLY TYPE A INSET 3/4" 2' - 8" 3 A8.14 TYPE A 03 30 00.SL 05 31 00.SD Level 1 Level 1 0' - 0" 5 0' - 0" WALL SECTION SCALE: 1/2" = 1'-0" REF. DWG. 5/A4.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/16/16 RMS DCM 1/2" = 1'-0" AA-2/2 2 CENTER FIXTURE CENTER FIXTURE 2 K 6' - 0" L 1 A8.10 P-6, TYP. 26 P-6 2 MUSIC 115 STG 113 L 10' - 8" 10' - 0" P-6 8'-0" AB. MUSIC FLOOR M STG. M 20 A8.16 25 16' - 4" 116 6' - 0" RAMP 6' - 0" 16' - 0" 28 P-6 6' - 0" 2 N 20 A8.16 P-6 TYP. 114 P-6 O 6 1 PARTIAL LEVEL 1 REFLECTED CEILNG PLAN (WEST) SCALE: 1/8" = 1'-0" REF. DWG. 1/A7.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/16/16 RMS DCM 1/8" = 1'-0" AA-2/3 3' - 4" 3' - 4" P-2 P-3 P-5 4' - 0" P-4 8' - 0" OPEN TO RAMP 8" 2 7 MUSIC 115 SCALE: 1/4" = 1'-0" REF. DWG. 7/A6.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/17/16 RMS DCM 1/4" = 1'-0" AA-2/4 PAINTED CMU (P-1), TYP. 13 2 A8.15 OPEN TO MUSIC ROOM 16 P-3 P-2 P-4 P-5 P-2 P-3 P-5 TYP. A8.16 P-4 P-2 P-4 PARTIAL HEIGHT WALL, TYP. P-3 RAILING, TYP. P-3 P-5 P-2 GYP. BD. REVEAL, TYP. P-3 4 P-4 P-2 P-5 P-2 P-4 P-3 RAMP 114 SCALE: 1/4" = 1'-0" REF. DWG. 4/A6.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/17/16 RMS DCM 1/4" = 1'-0" AA-2/5 STG 7 5/8" 113 1' - 0" 11' - 0" 9' - 4" FIRE EXTINGUISHER CABINET (F.E.C.), TYP. UP 115 2 5 1' - 0" MUSIC 20' - 6 1/2" A6.01 6 2 A6.01 8 RAMP 10' - 0" 114 1 A6.01 17' - 8" 3' - 4 5/8" 1 1:12 MAX. SLOPED RAMP 3 2 4' - 1 3/8" 5 5/8" ENLARGED MUSIC ROOM PLAN SCALE: 1/4" = 1'-0" REF. DWG. 1/A5.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/18/16 RMS DCM 1/4" = 1'-0" AA-2/6 2 3 B B PE STOR 126 9' - 0" PE OFF 125 2 COM STOR 123 C C ELEC 124 2 1 PARTIAL LEVEL 1 REFLECTED CEILNG PLAN (WEST) SCALE: 1/8" = 1'-0" REF. DWG. 1/A7.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/21/16 RMS DCM 1/8" = 1'-0" AA-2/7 10 GIRLS BOYS 132 BOOKS 133 P-1 9'-0" A.F.F. 19 10' - 0" A8.16 28 9'-0" A.F.F. P-1 135A 10' - 0" 10' - 0" P-3 9' - 0" 2' - 0" 2 G 20 A8.16 G 10 1 PARTIAL LEVEL 1 REFLECTED CEILNG PLAN (WEST) SCALE: 1/8" = 1'-0" 10 GIRLS BOYS 9'-0" A.F.F. 202 19 P-1 10' - 0" A8.16 28 2 G P-6 9'-0" A.F.F. 203 P-1 10' - 0" P-3 2' - 0" 9' - 0" 20 A8.16 P-6 G 9'-0" A.F.F. 10 2 PARTIAL LEVEL 2 REFLECTED CEILING PLAN (WEST) SCALE: 1/8" = 1'-0" REF. DWG. 1/A7.11 & 1/A7.21 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/21/16 RMS DCM 1/8" = 1'-0" AA-2/8 SND 12 9 7 1/4" A6.04 6' - 1 1/4" PTD 1' - 6" 3' - 1" SD 3' - 2" 1' - 0" 10 RR 111 3' - 1" 11 TPD 3' - 4" 1 SNR 2 8' - 8" ENLARGED TOILET ROOM 111 PLAN SCALE: 1/4" = 1'-0" REF. DWG. 3/A5.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/25/16 RMS DCM 1/4" = 1'-0" AA-2/9 A6.02 1' - 4" 1' - 4" 6 5/8" 7 112 10' - 0 " 1' - 4" 112 H 10A 10E 10A 10A I 11D 10H 10A 10H RR 5 46 111 10E 10H 10E 10A 10E 10H 25' - 4" A4.23 108A CUST 111 2 K 11A 17 1' - 4" 1' - 1" 10A A6.00 10A 15 L HEALTH 16 2' - 8" 11A M 11E 14 110 6' - 0" 10A 11 101 U J 110 3' - 9 1/2" M 10A RECEPTION 101 8 1 PARTIAL LEVEL 1 FLOOR PLAN (WEST) SCALE: 1/8" = 1'-0" REF. DWG. 1/A2.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/25/16 RMS DCM 1/8" = 1'-0" AA-2/10 5/8" 160 7 1' - 6" 2 10' - 3 1/4" A6.06 GIRLS 6 SD 17 5' - 0" CLR. SNR TPD 5' - 0" 2' - 10 1/8" PTD A6.06 18 TPD SCD SCD SNR 5/8" 11' - 8" 4' - 0" 19 5/8" 3' - 10 3/4" 1' - 8" 5' - 0" SD A6.06 8 8' - 10" 20 SND 5' - 1" 5 PTD RR 15 162 4' - 0" SNR A6.06 1' - 6" 10 11 BOYS 161 5/8" TPD 12 TPD 9' - 8 3/4" 8' - 10" 14 SCD 9 5' - 0" SND 1' - 6" 7' - 6" PTD A6.06 5' - 0" CLR. 13 16 2' - 10 1/8" 5' - 0" 3' - 10 3/4" SD 4' - 6 1/2" 1' - 6" SCD 7' - 6" 6 1' - 8" 12' - 4" ENLARGED TOILET ROOM 160 & 242, 161 & 243, 162 & 244 SCALE: 1/4" = 1'-0" REF. DWG. 6/A5.01 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 RMS DCM 1/4" = 1'-0" AA-2/11 5' - 3 7/8" 7 1/4" 1' - 8" 3' - 11 3/4" 6' - 2 3/4" TPD 14 1' - 5 7/8" 7' - 2 1/8" 17 RR A6.05 15SD 16 SCD 4 A6.06 3 151 RR 154 1' - 0" 1' - 6" TPD 1' - 6" 2 2 9' - 9 1/4" 1 SP ED 150 STORAGE CABINETS BEHIND WHITEBOARDS SP ED 3' - 4" 2 1' - 6" 153 2 1/2" 6' - 1 1/4" 3 ENLARGED SPECIAL ED PLAN SCALE: 1/4" = 1'-0" REF. DWG. 3/A5.02 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 RMS DCM 1/4" = 1'-0" AA-2/12 O N M 2 CP A1 EAST ELEVATION 1 SCALE: 1/16" = 1'-0" D EF CH CG G CF CD H CE I 2 J CE K L M N O CD CC CB CA C 2 WEST ELEVATION SCALE: 1/16" = 1'-0" REF. DWG. 1 & 2/A3.00 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 RMS DCM 1/16" = 1'-0" AA-2/13 10 2 15'-7" 6'-7 1/2" 3" TYP 6 S4.1 C C5 C5 FTG 2'-0"x12" DP W/ 3-#4 CONT TYP, UNO C4 7 4 2'-6" C5 C5 10'-1 1/2" C5 10'-6" L S3.1 2'-6" 2 12'-0" 4 C5 10 REF DWG S2.11 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 JAQ LAH 1/8" = 1'-0" SA-2/1 10 W14x22 W14x22 W14x22 5 S6.8 7 S6.8 W18x40 G W16x26 11 S6.7 AHU 12,000# 3'-9" W21x44 2'-4" W16x26 2'-2" /8 3'-0" 1 SIM S6.7 GATE 24K8 W14x22 x S6 HS 10B S6.7 3 4x E OF A S I GA DE TE H 9'-1" 9'-0" W14x22 CH 7500# 6 S6.8 6'-8" 6'-3" 2'-10" 6'-3" 9'-0" 2 W16x26 9 S6.7 W16x26 F W14x22 2'-8" /8 x3 x4 O S 4 UN HS YP, T D 4'-8" 2'-0" 20K4 J 10 REF DWG S2.42 Westgate Elementary School Replacement 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 JAQ LAH 1/8" = 1'-0" SA-2/2 AIR E IN DIV 23 S. HOT WATER 2 SOUND DATA SUPPLY/RETURN SOUND POWERED LEVELS # NOTES 63 HZ 125 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ 8000 HZ AHU 1 94/81 94/82 94/86 97/88 96/82 93/81 88/77 84/73 1 3 AHU 2 94/81 94/82 94/86 97/88 96/82 93/81 88/77 84/73 1 3 AHU 3 94/81 94/82 94/86 97/88 96/82 93/81 88/77 84/73 1 3 AHU 4 94/81 94/82 94/86 97/88 96/82 93/81 88/77 84/73 1 3 AHU 5 74/67 71/73 81/79 83/78 78/72 84/73 82/71 77/69 1 3 AHU 6 74/67 72/73 81/79 84/78 84/72 85/73 85/71 79/69 1 3 AHU 7 66/67 62/64 74/77 73/77 75/73 72/73 68/73 64/71 1 3 FC 1 NL 77/80 72/79 69/79 73/81 70/79 65/76 66/71 2 3 FC 2 NL 77/80 72/79 69/79 73/81 70/79 65/76 66/71 2 3 FC 3 NL 73/80 78/78 66/75 64/71 67/75 63/71 72/70 2 3 FC 4 NL 72/76 70/71 60/72 60/69 64/71 57/66 64/60 2 3 FC 5 NL 77/80 72/79 69/79 73/81 70/79 65/76 66/71 2 3 FC 6 NL 81/83 74/82 71/83 71/81 70/78 66/76 70/70 2 3 PERFORMANCE DATA BASED ON 65F AIR AND 30% GLYCOL HEAT HOT WATE H SOUND NOTES: 1 SUPPLY / RETURN FAW FAN SOUND POWER LEVELS 2 RETURN INLET / SUPPLY OUTLET SOUND POWER LEVELS 3 SOUND DATA ARE CALCULATED +/-3 DB. MEASURED VALUES SHALL NOT EXCEED THESE. REF DWG M1.3 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/16" = 1'-0" MA-2/1 FT DIA MATERIAL SIZE FPI MATERIAL VELS 2 SOUND ATTENUATOR SCHEDULE INSERTION LOSS (DB) # MFR MODEL LOCATION TYPE WxH (IN) LENGTH (IN) CFM FPM IN.WG. 63 HZ 125 HZ 250 HZ 500 HZ 1000 HZ 2000 HZ 4000 HZ 8000 HZ SA 1 RUSKIN ELBMP5 AHU-1 RETURN RECT. ELBOW 50X28 30 UP 30 DN 13000 -1400 0.50 4 9 17 26 25 24 20 16 1 2 SA 2 RUSKIN ELBMP5 AHU-2 RETURN RECT. ELBOW 50X28 30 UP 30 DN 11600 -1200 0.35 4 9 17 26 25 24 20 16 1 2 RECT. ELBOW 50X28 30 UP 30 DN 11600 -1200 0.35 4 9 17 26 25 24 20 16 1 2 NOTES SA 3 RUSKIN ELBMP5 AHU-3 RETURN SA 4 RUSKIN ELBMP5 AHU-4 RETURN RECT. ELBOW 50X28 30 UP 30 DN 12600 -1350 0.40 4 9 17 26 25 24 20 16 1 2 TAPERD RECT. 44X18 36 5000 -1000 0.25 7 10 20 30 38 29 16 11 1 2 SA 5 RUSKIN A-36 AHU-5 RETURN SA 6 RUSKIN A-60 AHU-6 RETURN TAPERD RECT. 36X20 60 5500 -1200 0.28 9 14 32 44 51 47 27 16 1 2 SA 7 RUSKIN ELBMP5 AHU-7 SUPPLY RECT. ELBOW 26X16 30 UP 30 DN 1800 675 0.20 4 8 16 25 25 24 21 17 1 2 SA 8 RUSKIN ELBMP5 AHU-7 RETURN RECT. ELBOW 22X16 30 UP 30 DN 1800 -800 0.20 4 9 17 26 25 24 20 16 1 2 NOTES: 1 CONNECTION SIZES SHALL BE COORDINATED WITH AND MATCH DUCT SIZES. 2 PROVIDE ACOUSTICAL CALCULATIONS FOR AIR SYSTEM TO SHOW THAT NC-40 OR BETTER IS BEING ACHIEVED IN THE SPACES BELOW IF OTHER THAN BASIS-OF-DESIGN AIR HANDLER OR SOUND ATTENUATOR ARE INSTALLED. REF DWG M1.3 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/16" = 1'-0" MA-2/2 F 36x20 2 12Ф SA 24x30 6 6 5 25 26x16 KITCHEN 119 4 3 5 6 H 8x8 5 14 100 23 12Ф 12Ф 2 UP EF 15 111 8Ф 108 19 J 4'' DRYER VENT 12Ф K CONF 10Ф RR 12Ф 12Ф 8Ф I 1 19 9 16Ф 10Ф 112 16Ф CUST FC-3 T CORR 104 14 21 18 HEALTH 110 9 REF DWG M2.11 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/3 BOYS 203 GIRLS DATA 202 18x16 16x12 200 AC 10Ф 1 AC 1 202B 2 12Ф 2 (TYP 4) 4'' DRYER VENT UP 10x10 200 1 200 SPEECH PSYCH 228 229 12Ф 48x48 3 10Ф 200 (TYP) 4 4 M5.2 SA 1 12Ф SA 12x12 10Ф 13 J 1 WORK 227 I 10x10 SA H 18x18 (TYP 3) 4 10Ф 5 22x22 14Ф 14Ф 50x28 13 SA G ELEV SA LIBRARY 226 K REF DWG M2.21 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/4 8 9 2 H I 5 DRYER VENT M5.2 RH 10 3 M5.2 J REF DWG M2.41 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/5 FT 2 1 C RR 151 RR 154 D F SP ED SP ED 153 3/4" 150 REF DWG M3.12 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/6 10 F 4" CWR 4" CWS 4" HWS 4" HWR 4" UP TO CHILLER BOYS 203 3'' G 3/4" 3/4" 3/4" 3/4" 2 9 (TYP) M5.1 TITLE 206 MECH 205 2'' 2" HWR 3'' 2" HWS H 2 1'' HWS/HWR 1 1/2'' CWS/CWR (TYP. AHU-2,3,4) 3" CWS 3" CWR 3'' OT/PT 230 I REF DWG M3.21 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/7 C 3/4" HWS 3/4" HWR 2 P MECH 134 P 1 1 1/2" HWR 1 1/2" HWS B 1 D VFD 3 GIRLS 132 3 1" C D P F VFD 4 B 4 2 BAS BOILER RELIEF TANK 1" CD FC 5 ELEV 131 BOILER EPD, (TYP-2) SEE 1/M7.2. G REF DWG M3.23 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 Author Checker 1/4" = 1'-0" MA-2/8 4" HWS 2 GIRLS 132 VFD 2 4" CWS P P 2 5 4" CWR VFD 5 D P 6 BOYS VFD 1 VFD 6 133 F REF DWG M3.23 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 Author Checker 1/4" = 1'-0" MA-2/9 2 ISOLATION VALVE, TYP HWS RECESSED CABINET UNIT HEATER STRAINER PT PORT MANUAL AIR VENT, TYP HWR 3/4" FROM ABOVE PIPING WITHIN CABINET MANUAL BALANCING VALVE PRESSURE INDEPENDENT MODULATING CONTROL VALVE SUPPLY AIR THREADED HOSE CONNECTION AND CAP, TYPICAL FLEX, TYP UNION, TYP RETURN AIR 8 CABINET UNIT HEATER PIPING Scale: NOT TO SCALE REF DWG M5.1 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/10 2 REMOVABLE CAP FOR CLEANOUT STAINLESS STEEL VENT CAP WITH INTEGRAL BACKDRAFT DAMPER. SEIHO MODEL RCC-S. CAP SHALL BE REMOVABLE FOR CLEANING. MOUNT 18" ABOVE ROOF LEVEL SEAL WATERTIGHT WITH MASTIC SEE ARCH DWGS FOR FLASHING AND ROOFING ROOF BOOSTER FAN ASSEMBLY PRESSURE SENSOR TUBING 4" DUCTWORK ABOVE ROOF SHALL BE SEALED WATER TIGHT AT ALL JOINTS. MECH ACCESS AREA LOW VOLTAGE WIRING BY DIV. 23 REMOTE STATUS INDICATOR 120V POWER & PANEL DISCONNECT BY DIV. 26 WALL RESIDENTIAL TYPE CLOTHES DRYER 5 CLOTHES DRYER VENTING DETAIL Scale: NOT TO SCALE REF DWG M5.2 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com ADDENDUM #2 Date: Drawn by: Checked by: Scale: Sheet No: 03/23/16 MRH ASD 1/8" = 1'-0" MA-2/11 3/24/2016 1:10:12 PM REVISIONS AHU-6 AHU-1 FM AHU-5 AHU-7 INSERTION TYPE FLOW METER FOR INPUT TO EMCS. VENTURI, FLOW MEASURING STATION FOR TAB. (TYP AT ALL 3-WAY HEATING VALVES) 5 M5.0 AHU-4 1-1/2" ABV 1-1/2" 2" THERMOMETER (TYP), MOUNT WHERE VISIBLE 1" ABV ABV NC P/T PORTS, TYPICAL. NO AHU-3 NC NO (TYP AT ALL 3-WAY COOLING VALVES) ABV (TYP AT ALL 2-WAY VALVES) ABV VALVE, BUTTERFLY TYPE ABV MANUAL VALVE, SEE SPECS FOR VALVE TYPE 2" MANUAL BALANCING VALVE N0 ABV NC 2" N0 NC PRESSURE INDEPENDENT AUTO BALANCING VALVE 2" ABV ABV ABV ABV ASME RELIEF VALVE, RELIEF PRESSURE INDICATED. AUTOMATIC AIR VENTS AT TRAPPED HIGH POINTS. ROUTE TO RECOVERY TANK. HWS HWR CWS CWR 1-1/2" THERMOMETER WELL, COORDINATE LOCATION WITH CONTROLS CONTRACTOR 3" ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV VAV-405 GENERAL NOTES FC-2 3" 3/4", TYP FC-1 1. SEE TEMPERATURE CONTROL DIAGRAMS FOR LOCATIONS AND QUANTITIES OF TEMPERATURE SENSORS, PRESSURE SENSORS FLOW DEVICES, ETC. 2. PROVIDE ALL ADDITIONAL DRAINS & CONNECTIONS AS REQUIRED FOR SYSTEM FLUSHING, CLEANING AND FILLING. ABV ABV FC-3 FC-4 4" KEYNOTES 1" 1" ABV 1" 1 MECHANICAL ROOM PIPING ISOLATION VALVES AND DRAIN VALVES WITH HOSE CONNECTION. 2 TEMPERATURE & PRESSURE RELIEF VALVE PROVIDED BY BOILER MFR. 3 AIR AND DIRT SEPARATOR, PIPE DISCHARGE TO GLYCOL RECOVERY TANK. 4 SUCTION DIFFUSER W/ STRAINER, DRAIN VALVE, HOSE CONN., TYP. 5 (NOT USED) 6 GLYCOL FEEDER ASSEMBLY WITH DUAL PUMP AND LOW LEVEL SWITCH. ONE ASSEMBLY FEEDS BOTH HEATING AND CHILLED WATER SYSTEMS. 7 GLYCOL RECOVERY TANK (30 GAL). 8 CONCRETE HOUSEKEEPING PAD, TYPICAL. 9 PRESSURE GAUGE WITH STOP COCK AND SNUBBER. 10 CONCENTRIC REDUCER/INCRESE AT PUMP CONNECTIONS AS REQUIRED. 11 BYPASS POT FEEDER. 12 PUMP SUPPORT STAND SET ON HOUSEKEEPING PAD WITH NEOPRENE PADS. 13 SIDESTREAM CARTRIDGE FILTER. 14 CORROSION MONITORING COUPON RACK ASSEMBLY. 15 VENTURI FOR TAB 1" ABV HWS HWR CWS CWR ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV 3/4", TYP ABV ABV ABV ABV ABV ABV ABV 4" 3/4" ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV 1-1/4" 1" ABV ABV CU-2 CU-1 ABV 1/2" ABV 3/4", TYP 3/4", TYP 3/4" ABV ABV ABV VAV-411 ABV 1-1/4" FC-6 CU-1 HWS HWR CWS CWR ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV ABV FC-5 FIN-TUBE (TYP) PANEL HEATERS (TYP) CH 1 2 TO BUILDING DISTRIBUTION FS 4" 4" TO BUILDING DISTRIBUTION Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 4 M5.0 6 M5.0 MECHANICAL SYSTEM DIAGRAMS 2" AHU-2 ROOF LEVEL ABV MECHANICAL ROOM MECHANICAL ROOM 4" 3 UH-1 3" 3 1 4" CWR HWR 4" HWR 3" 1 4" 4" AS 1 HWS 4" 1 M5.1 AS 2 3 M5.1 4" FM 1 CWS FM 1 HWS 4" P 4 50 PSIG 50 PSIG 50 PSIG 1" 1" 50 PSIG 4" 15 15 4" 2 TYP 9 9 14 VFD 1 7 TYP VFD 2 10 10 10 TYP TYP VFD 5 1 GPM TYP 9 9 TYP 7 GPM TYP Spokane, Washington (509) 624-6800 2 VFD 6 10 10 10 TYP TYP 13 TYP 4 7 M5.1 B 1 HEATING WATER BOILER (TYP) B 2 8 TYP 4 4 12 12 8 P 1 8 P 2 2 M5.1 TYP 11 FLTR 1 5 M5.1 13 ET 1 8 6 7 ET 2 4 12 8 P 5 2 M5.1 TYP 11 12 FLTR 1 8 P 6 © 2015 Madsen Mitchell Evenson & Conrad pllc C:\Users\michael.MEULINK\Documents\Revit Local Projects\15-12 Westgate_ES V16\Westgate ES_Mech-V16 Mike.rvt 4" 4" 4" 15 3/4" VFD 4 3/4" P 3 15 4" 3" VFD 3 4" 4" Kennewick, Washington www.mmecarchitecture.com 4" 15 Date: Drawn by: Checked by: Scale: File No: 03/07/16 NAH WFM 1/8" = 1'-0" 14.05 Sheet No: M6.0 1 2 3 D TABLE STOR 122 ¾" 6"RDL UP F 6"ODL UP 6"DSN-1 @ 18"AFG 3"FS-1 1 1/4" FREEZER 119A 2" 6"ODL DN 2" 6"RDL DN 3"FS-1 KITCHEN 1 1/4" 2" 2" 1" 119 4 2" 5 1 9 3/4" ¾" 5 P12 P19 ¾" G9 3/4" 1" P2 3/4" 1 5 P6 1 2 OFFICE/STG. H 2" 3"FD-1 120 REF: DWG P2.11 Westgate Elementary School 2514 West 4th Ave. Kennewick, WA 99336 Spokane, Washington (509) 624-6800 Kennewick, Washington www.mmecarchitecture.com Unnamed Date: Drawn by: Checked by: Scale: Sheet No: 03/28/16 SSW WFM 1/8" = 1'-0" PA2/1