SHUT-OFF VALVE #1 SHUT-OFF VALVE #2 INSULATED ENCLOSURE SHALL BE AS SPECIFIED IN CLT WATER ENCLOSURE INFORMATION - HEATED INSULATED ENCLOSURE IS RECOMMENDED. NO INSULATION SHALL BE WRAPPED AROUND BPA. 4. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL AND MUST BE OUTSIDE OF ZONING SET-BACK/ DIRECTLY BEHIND METER. 5. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 6. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 7. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. CHECK VALVE #2 CHECK VALVE #1 STRAINER RECOMMENDED FLOW TYPE K OR L COPPER TUBING PIPE OR GALVANIZED STEEL PIPE FOR MIN. OF 5' ON EACH END OF THE ASSEMBLY. SEE NOTE #2 TEST COCK #1 12" MIN. 30" MAX. HINGED ACCESS OR REMOVABLE INSULATED ENCLOSURE MEETING ASSE 1060 SPECIFICATIONS. ENCLOSURE TO INCLUDE DRAIN PORT(S) PER CLT WATER REQUIREMENT. LOWEST POINT OR RELIEF VALVE OUTLET SLOPE GROUND AWAY FROM COVER (TYP.) SLEEVE REQUIRED (TYP.) CLT WATER REQUIRED BPA ABOVE GROUND ZONING SETBACK 5.3.2016 3. VERSION DATE PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 1.1 2. 1 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. REDUCED PRESSURE PRINCIPLE REDUCED PRESSURE PRINCIPLE ASSEMBLY 1. VERSION NO. NOTES: SLEEVE REQUIRED (TYP.) SEE NOTE #4 & #5 PROPERTY LINE CLT WATER METER TYPICAL LOCATION REQUIREMENT FOR ABOVE GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT PUBLIC WATER MAIN ROAD R/W SUPPORT AS REQUIRED BY DESIGNER MIN. 4" THICK CONCRETE PAD REQUIRED PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS SPECIFICATION. ALL JOINTS SHALL BE RESTRAINED WITH MEGALUG RESTRAINTS OR APPROVED EQUAL. 4. SUPPORT OF ASSEMBLY SHALL BE DESIGNED BY OWNER, 8" - 12" SHALL BE SUPPORTED AT EACH VALVE AND SHALL NOT BLOCK RELIEF VALVE ON DRAIN PORT. 5. INSULATED ENCLOSURE SHALL BE AS SPECIFIED IN CLT WATER ENCLOSURE INFORMATION - HEATED INSULATED ENCLOSURE ARE REQUIRED FOR FIRE LINE SERVICES. NO INSULATION SHALL BE WRAPPED AROUND BPA. 6. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL AND MUST BE OUTSIDE OF ZONING SET-BACK DIRECTLY BEHIND METER. 7. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 8. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 9. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. SHUT-OFF VALVE #2 SEE NOTE #2 SHUT-OFF VALVE #1 SEE NOTE #2 6" MIN. CHECK VALVE #1 COVER MUST NOT OBSTRUCT VALVE BEING FULLY OPENED CHECK VALVE #2 TEST COCK #1 RESTRAINED JOINT SEE NOTE #3 HINGED ACCESS OR REMOVABLE INSULATED ENCLOSURE MEETING ASSE 1060 SPECIFICATIONS. ENCLOSURE TO INCLUDE DRAIN PORT(S) PER CLT WATER REQUIREMENT. SUPPORTS SEE NOTE #4 SUPPORTS SEE NOTE #4 FLOW 12" MIN. 30" MAX. DUCTILE IRON PIPE OR TYPE K OR L COPPER TUBING FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #3 RELIEF VALVE OUTLET SLOPE GROUND AWAY FROM COVER LOWEST POINT OR RELIEF VALVE OUTLET SLEEVE REQUIRED (TYP.) SLEEVE REQUIRED (TYP.) SUPPORT, PAD AND CONCRETE FOOTINGS AS REQUIRED BY SYSTEM DESIGNER CLT WATER REQUIRED BPA ABOVE GROUND MIN. 4" THICK CONCRETE PAD REQUIRED SEE NOTE #6 & #7 PROPERTY LINE CLT WATER METER PUBLIC WATER MAIN ROAD R/W RESTRAINED JOINT SEE NOTE #3 ZONING SETBACK TYPICAL LOCATION REQUIREMENT FOR ABOVE GROUND INSTALLATION N.T.S. 5.3.2016 3. REDUCED PRESSURE PRINCIPLE ASSEMBLY VERSION DATE FIRE LINE SERVICES SHALL HAVE OUTSIDE STEM AND YOKE (OS & Y) HANDWHEEL OPERATORS OR BUTTERFLY VALVES, AND LISTED ON APPROVED LIST AS FIRE APPROVED. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 1.2 2. 2 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. REDUCED PRESSURE PRINCIPLE 1. VERSION NO. NOTES: PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS SPECIFICATION. ALL JOINTS SHALL BE RESTRAINED WITH MEGALUG RESTRAINTS OR APPROVED EQUAL. 4. SUPPORT OF ASSEMBLY SHALL BE DESIGNED BY OWNER, 8" - 12" SHALL BE SUPPORTED AT EACH VALVE. 5. INSULATED ENCLOSURE SHALL BE AS SPECIFIED IN CLT WATER ENCLOSURE INFORMATION - HEATED INSULATED ENCLOSURE ARE REQUIRED FOR FIRE LINE SERVICES. NO INSULATION SHALL BE WRAPPED AROUND BPA. 6. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL AND MUST BE OUTSIDE OF ZONING SET-BACK DIRECTLY BEHIND METER. 7. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 8. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CHARLOTTE WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 9. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. SHUT-OFF VALVE #2 SEE NOTE #2 6" MIN. CHECK VALVE #1 TEST COCK #1 COVER MUST NOT OBSTRUCT VALVE BEING FULLY OPENED CHECK VALVE #2 RESTRAINED JOINT SEE NOTE #3 HINGED ACCESS OR REMOVABLE INSULATED ENCLOSURE MEETING ASSE 1060 SPECIFICATIONS. ENCLOSURE TO INCLUDE DRAIN PORT(S) PER CLT WATER REQUIREMENT. FLOW LOWEST POINT DUCTILE IRON PIPE OR TYPE K OR L COPPER TUBING FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #3 12" MIN. 30" MAX. SLOPE GROUND AWAY FROM COVER SEE NOTE #4 SLEEVE REQUIRED (TYP.) SLEEVE REQUIRED (TYP.) SUPPORT, PAD AND CONCRETE FOOTINGS AS REQUIRED BY SYSTEM DESIGNER RESTRAINED JOINT SEE NOTE #3 ZONING SETBACK CLT WATER REQUIRED BPA ABOVE GROUND MIN. 4" THICK CONCRETE PAD REQUIRED SEE NOTE #6 & #7 PROPERTY LINE CLT WATER METER PUBLIC WATER MAIN ROAD R/W SHUT-OFF VALVE #1 SEE NOTE #2 TYPICAL LOCATION REQUIREMENT FOR ABOVE GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT DOUBLE CHECK VALVE ASSEMBLY VERSION DATE 3. 05.03.2016 FIRE LINE SERVICES SHALL HAVE OUTSIDE STEM AND YOKE (OS & Y) HANDWHEEL OPERATORS OR BUTTERFLY VALVES, AND LISTED ON APPROVED LIST AS FIRE APPROVED. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 1.2 2. 4 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. DOUBLE CHECK VALVE ASSEMBLY (DC) 1. VERSION NO. NOTES: STRAINER RECOMMENDED VAULT, DOORS OR COVERS AND SUPPORT OF ASSEMBLY SHALL BE DESIGNED BY OWNER AND AS REQUIRED. 4. DRAIN INLET MAY BE PROVIDED AS SHOWN OR AS FLOOR DRAIN. 5. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 6. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 7. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 8. INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. FLOW 4" MIN. 4" MIN. SLEEVE REQUIRED (TYP.) 12" MIN. 30" MAX. SHUT-OFF VALVE #1 CHECK VALVE #2 MIN. 4" THICK #67 WASHED STONE OR VAULT BOTTOM TYPE K OR L COPPER TUBING PIPE, 1" MIN. GALVANIZED STEEL PIPE OR SCH. 40 PVC PIPE WITH SCH. 80 PVC FITTINGS. SEE NOTE #2 SEE NOTE #3 2" MIN. DIA. DRAIN BY GRAVITY TO ATMOSPHERE AS REQUIRED BY CLT WATER SPECIFICATIONS. SEE NOTE #4 SUPPORT AS REQUIRED BY DESIGNER ELEVATION VIEW TEST COCK #1 8" MIN. DOUBLE CHECK VALVE ASSEMBLY 4" MIN. SHUT-OFF VALVE #2 FLOW 4" MIN. SHUT-OFF VALVE #1 8" MIN. CHECK VALVE #1 DRAIN ZONING SETBACK 2" MIN. DRAIN TO ATMOSPHERE PLAN VIEW CLT WATER REQUIRED BPA BELOW GROUND. SEE NOTE #5 & #6 PROPERTY LINE CLT WATER METER PUBLIC WATER MAIN TOP OF DISCHARGING STORM PIPE STORM PIPE DRAIN ALTERNATIVE: TIE INTO CATCH BASIN OR STORMWATER MANHOLE PER DETAIL SHOWN ABOVE. NO TIE IN TO STORMWATER PIPE WILL BE ACCEPTED. TYPICAL LOCATION REQUIREMENT FOR BELOW GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT DRAIN FROM BACKFLOW VAULT CATCH BASIN WITH GRATE ROAD R/W SEE NOTE #6 5.3.2016 3. 5 PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. VERSION DATE SLEEVE REQUIRED (TYP.) 2. 1.1 DOUBLE CHECK VALVE ASSEMBLY CHECK VALVE #1 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. VERSION NO. 15" MAX. 6" MIN. 1. DOUBLE CHECK VALVE ASSEMBLY (DC) 3/4" & 1" BELOW GROUND VAULT TEST COCK #1 NOTES: FINISHED GRADE TO BE SLOPED AWAY FROM COVER SHUT-OFF VALVE #2 PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. DOUBLE CHECK VALVE ASSEMBLY STRAINER RECOMMENDED 15" MAX. 6" MIN. SLEEVE REQUIRED (TYP.) 3. VAULT, DOORS OR COVERS AND SUPPORT OF ASSEMBLY SHALL BE DESIGNED BY OWNER AND AS REQUIRED. 4. DRAIN INLET MAY BE PROVIDED AS SHOWN OR AS FLOOR DRAIN. FLOW 5. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 4" MIN. 4" MIN. 6. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. SHUT-OFF VALVE #1 12" MIN. 30" MAX. CHECK VALVE #2 SEE NOTE #3 7. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 8. INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. 2" MIN. DIA. DRAIN BY GRAVITY TO ATMOSPHERE AS REQUIRED BY CLT WATER SPECIFICATIONS. SEE NOTE #4 SUPPORT AS REQUIRED BY DESIGNER ELEVATION VIEW TEST COCK #1 DOUBLE CHECK VALVE ASSEMBLY 12" MIN. SHUT-OFF VALVE #2 4" MIN. DRAIN ZONING SETBACK FLOW SHUT-OFF VALVE #1 COVER 4" MIN. 12" MIN. CHECK VALVE #1 2" MIN. DRAIN TO ATMOSPHERE PLAN VIEW DRAIN FROM BACKFLOW VAULT CLT WATER REQUIRED BPA BELOW GROUND. SEE NOTE #5 & #6 PROPERTY LINE CLT WATER METER PUBLIC WATER MAIN ROAD R/W SEE NOTE #6 CATCH BASIN WITH GRATE TOP OF DISCHARGING STORM PIPE STORM PIPE DRAIN ALTERNATIVE: TIE INTO CATCH BASIN OR STORMWATER MANHOLE PER DETAIL SHOWN ABOVE. NO TIE IN TO STORMWATER PIPE WILL BE ACCEPTED. TYPICAL LOCATION REQUIREMENT FOR BELOW GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT SLEEVE REQUIRED (TYP.) TYPE K OR L COPPER TUBING OR 1" MIN. GALVANIZED STEEL PIPE FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #2 5.3.2016 TEST COCK #1 SHUT-OFF VALVE #2 VERSION DATE 2. CHECK VALVE #1 1.1 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. 6 1. DOUBLE CHECK VALVE ASSEMBLY (DC) 1 1/ 2" & 2" BELOW GROUND VAULT FINISHED GRADE TO BE SLOPED AWAY FROM COVER VERSION NO. NOTES: COVER SEE NOTE #3 FIRE LINE SERVICES SHALL HAVE OUTSIDE STEM AND YOKE (OS & Y) HANDWHEEL OPERATORS OR BUTTERFLY VALVES, AND LISTED ON APPROVED LIST AS FIRE APPROVED. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 3. ASSEMBLIES SHALL BE INSTALLED UPRIGHT AND IN THE HORIZONTAL POSITION. 4. PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 5. VAULT AND SUPPORT OF ASSEMBLY SHALL BE DESIGNED BY OWNER, 8" - 12" SHALL BE SUPPORTED AT EACH VALVE. 6. ACCESS DOORS SHALL BE AS SPECIFIED IN CLT WATER WATER DETAILS #23, 25, OR 28 OR APPROVED EQUAL. 7. DRAINAGE INLET MAY BE PROVIDED AS SHOWN OR AS FLOOR DRAIN. 8. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 9. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. CHECK VALVE #1 CHECK VALVE #2 SHUT-OFF VALVE #2 SEE NOTE #2 6" MIN. SLEEVE REQUIRED (TYP.) FLOW DUCTILE IRON PIPE OR TYPE K OR L COPPER TUBING FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #4 LOWEST POINT SLEEVE REQUIRED (TYP.) 12" MIN. 30" MAX. TEST COCK #1 SEE NOTE #5 SHUT-OFF VALVE #1 SEE NOTE #2 4" MIN. DIA. DRAIN BY GRAVITY TO ATMOSPHERE AS REQUIRED BY CLT WATER SPECIFICATIONS. SEE NOTE #7 ELEVATION VIEW 6" MIN. CHECK VALVE #1 FLOW TEST COCK #1 CHECK VALVE #2 EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 11. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. 6" MIN. 6" MIN. SHUT-OFF VALVE #1 10. SHUT-OFF VALVE #2 24" MIN. 5.3.2016 6" MIN. WHEN VALVE IS FULLY OPEN VERSION DATE 2. DOUBLE CHECK VALVE ASSEMBLY 1.2 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. 7 1. DOUBLE CHECK VALVE ASSEMBLY (DC) 2 1/ 2" - 12" BELOW GROUND VAULT FINISHED GRADE TO BE SLOPED AWAY FROM COVER VERSION NO. NOTES: 4'x5', 5'x5' OR 4'x6' DOUBLE LEAF STEEL OR ALUMINUM DOORS HINGED AND LOCKABLE SEE NOTE #6 DRAIN ZONING SETBACK 4" DIA. DRAIN TO ATMOSPHERE COVER CLT WATER - REQUIRED BPA BELOW GRND. SEE NOTE #8 & #9 PROPERTY LINE PLAN VIEW CATCH BASIN WITH GRATE TOP OF DISCHARGING STORM PIPE PUBLIC WATER MAIN STORM PIPE DRAIN ALTERNATIVE: TIE INTO PRIVATE CATCH BASIN OR PRIVATE STORMWATER MANHOLE PER DETAIL SHOWN ABOVE. NO TIE IN TO STORMWATER PIPE OR PUBLIC CATCH BASIN / MANHOLE WILL BE ACCEPTED. TYPICAL LOCATION REQUIREMENT FOR BELOW GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT DRAIN FROM BACKFLOW VAULT ROAD R/W CLT WATER METER CHECK VALVE #2 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. FLOW LOWEST POINT OR RELIEF VALVE OUTLET 4" MIN. STRAINER RECOMMENDED SLEEVE PER NC BLDG. CODE (TYP.) RELIEF VALVE OUTLET SEE NOTE #6 12" MIN. 60" MAX. TYPE K OR L COPPER TUBING OR 1" MIN. GALVANIZED STEEL PIPE FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #4 3. ASSEMBLIES SHALL BE INSTALLED UPRIGHT AND IN THE HORIZONTAL POSITION. 4. PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 5. SUPPORT FOR ASSEMBLY SHALL BE DESIGNED BY OWNER AS REQUIRED. 6. AN AIR GAP DRAIN IS RECOMMENDED TO REDUCE SPLASHING OF MINOR DISCHARGES FROM THE RELIEF VALVE DRAIN PORT. FLOOR 7. INDOOR INSTALLATION OF RP'S SHOULD PROVIDE FOR DRAINAGE CAPABLE OF HANDLING IN EXCESS OF THE MAXIMUM DISCHARGE RATE EXPECTED BY THE BACKFLOW ASSEMBLY MANUFACTURER. 8. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 9. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. SEE NOTE #5 DRAIN BY GRAVITY SEE TABLE IN SPECIFICATIONS FOR MINIMUM DRAIN SIZES FOR RP INDOOR INSTALLATIONS. SEE NOTE #7 ELEVATION VIEW WALL 6" MIN. 10. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 11. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. 5.3.2016 2. SHUT-OFF VALVE #2 CHECK VALVE #1 VERSION DATE OUTSIDE WALL TEST COCK #1 1.1 INDOOR INSTALLATION SHALL ONLY BE PERMITTED IN CASES WHERE ADEQUATE SPACE FOR THE BACKFLOW PREVENTION ASSEMBLY IS NOT AVAILABLE OUTSIDE. CLT WATER WILL REVIEW ON A CASE BY CASE BASIS. 8 1. REDUCED PRESSURE PRINCIPLE ASSEMBLY REDUCED PRESSURE PRINCIPLE ASSEMBLY (RP) 3/4" - 2" INDOOR SHUT-OFF VALVE #1 VERSION NO. NOTES: REDUCED PRESSURE PRINCIPLE ASSEMBLY SHUT-OFF VALVE #2 4" MIN. CLT WATER REQUIRED BPA INSIDE EXTERIOR BUILDING WALL SHUT-OFF VALVE #1 CHECK VALVE #1 24" MIN. CLEAR SPACE DRAIN ZONING SETBACK PROPERTY LINE SEE NOTE #8 & #9 CLT WATER METER PUBLIC WATER MAIN PLAN VIEW TYPICAL LOCATION REQUIREMENT FOR INSIDE INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT TEST COCK #1 ROAD R/W OUTSIDE WALL FLOW SLEEVE PER NC BLDG. CODE (TYP.) CHECK VALVE #1 SHUT-OFF VALVE #2 SEE NOTE #3 FIRE LINE INSTALLATIONS SHALL HAVE OUTSIDE STEM AND YOKE (OS&Y) HANDWHEEL OPERATORS OR BUTTERFLY VALVES, AND LISTED ON APPROVED LIST AS FIRE APPROVED. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 4. ASSEMBLIES SHALL BE INSTALLED UPRIGHT AND IN THE HORIZONTAL POSITION. 5. PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 6. SUPPORT FOR ASSEMBLY SHALL BE DESIGNED BY OWNER, 8" - 12" SHALL BE SUPPORTED AT EACH VALVE AND SHALL NOT BLOCK RELIEF VALVE ON DRAIN PORT. 7. AN AIR GAP DRAIN IS RECOMMENDED TO REDUCE SPLASHING OF MINOR DISCHARGES FROM THE RELIEF VALVE DRAIN PORT. 8. INDOOR INSTALLATION OF RP'S SHOULD PROVIDE FOR DRAINAGE CAPABLE OF HANDLING IN EXCESS OF THE MAXIMUM DISCHARGE RATE EXPECTED BY THE BACKFLOW ASSEMBLY MANUFACTURER. 9. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 6" MIN. FLOW 6" MIN. RELIEF VALVE OUTLET SEE NOTE #7 DRAIN FLOOR LOWEST POINT OR RELIEF VALVE OUTLET 12" MIN. 60" MAX. SEE NOTE #6 SEE TABLE IN SPECIFICATIONS FOR MINIMUM DRAIN SIZES FOR RP INDOOR INSTALLATIONS SEE NOTE #8 ELEVATION VIEW CHECK VALVE #1 OUTSIDE WALL 11. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. 6" MIN. FLOW SHUT-OFF VALVE #1 THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 12. WALL 6" MIN. 10. CHECK VALVE #2 24" MIN. CLEAR SPACE DRAIN REDUCED PRESSURE PRINCIPLE ASSEMBLY TEST COCK #1 PLAN VIEW SHUT-OFF VALVE #2 CLT WATER REQUIRED BPA INSIDE EXTERIOR BUILDING WALL ZONING SETBACK PROPERTY LINE SEE NOTE #9 & #10 CLT WATER METER ROAD R/W SLEEVE PER NC BLDG. CODE (TYP.) DUCTILE IRON PIPE OR TYPE K OR L COPPER TUBING FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #5 5.3.2016 3. CHECK VALVE #2 1.2 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. 9 2. PUBLIC WATER MAIN TYPICAL LOCATION REQUIREMENT FOR INSIDE INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT OUTSIDE WALL TEST COCK #1 6" CLEAR OF OBSTRUCTIONS WHEN VALVE IS FULLY OPEN VERSION NO. REDUCED PRESSURE PRINCIPLE ASSEMBLY INDOOR INSTALLATION SHALL ONLY BE PERMITTED IN CASES WHERE ADEQUATE SPACE FOR THE BACKFLOW PREVENTION ASSEMBLY IS NOT AVAILABLE OUTSIDE. CLT WATER WILL REVIEW ON A CASE BY CASE BASIC. REDUCED PRESSURE PRINCIPLE ASSEMBLY (RP) 2 1/ 2" - 12" INDOOR SHUT-OFF VALVE #1 SEE NOTE #3 1. VERSION DATE NOTES: CHECK VALVE #1 STRAINER RECOMMENDED PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. LOWEST POINT STRAINER RECOMMENDED CHECK VALVE #2 12" MIN. 60" MAX. SEE NOTE #5 TYPE K OR L COPPER TUBING OR 1" MIN. GALVANIZED STEEL PIPE FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #4 5. SUPPORT FOR ASSEMBLY SHALL BE DESIGNED BY OWNER AS REQUIRED. 6. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 7. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 8. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 9. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. FLOOR DRAIN RECOMMENDED ELEVATION VIEW WALL 6" MIN. 4" MIN. DOUBLE CHECK VALVE ASSEMBLY SHUT-OFF VALVE #2 FLOW CLT WATER REQUIRED BPA INSIDE EXTERIOR BUILDING WALL TEST COCK #1 24" MIN CLEAR SPACE CHECK VALVE #1 ZONING SETBACK SEE NOTE #6 & #7 DRAIN RECOMMENDED PROPERTY LINE PLAN VIEW CLT WATER METER PUBLIC WATER MAIN TYPICAL LOCATION REQUIREMENT FOR INSIDE INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT SHUT-OFF VALVE #1 ROAD R/W OUTSIDE WALL VERSION DATE 4. 5.3.2016 ASSEMBLIES SHALL BE INSTALLED UPRIGHT AND IN THE HORIZONTAL POSITION. 1.1 3. 10 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. VERSION NO. 2. SHUT-OFF VALVE #2 TEST COCK #1 FLOW SLEEVE PER NC BLDG. CODE (TYP.) INDOOR INSTALLATION SHALL ONLY BE PERMITTED IN CASES WHERE ADEQUATE SPACE FOR THE BACKFLOW PREVENTION ASSEMBLY IS NOT AVAILABLE OUTSIDE. CLT WATER WILL REVIEW ON A CASE BY CASE BASIS. DOUBLE CHECK VALVE ASSEMBLY SHUT-OFF VALVE #1 4" MIN. 1. DOUBLE CHECK VALVE ASSEMBLY (DC) -3/4" - 2" --INDOOR OUTSIDE WALL NOTES: BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. 3. FIRE LINE INSTALLATIONS SHALL HAVE OUTSIDE STEM AND YOKE (OS&Y) HANDWHEEL OPERATORS OR BUTTERFLY VALVES, AND LISTED ON APPROVED LIST AS FIRE APPROVED. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 4. ASSEMBLIES SHALL BE INSTALLED UPRIGHT AND IN THE HORIZONTAL POSITION. 5. PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 6. SUPPORT FOR ASSEMBLY SHALL BE DESIGNED BY OWNER, 8" - 12" SHALL BE SUPPORTED AT EACH VALVE. 7. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL. 8. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 9. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. SHUT-OFF VALVE #2 SEE NOTE #3 6" MIN. FLOW DUCTILE IRON PIPE OR TYPE K OR L COPPER TUBING FOR MIN. OF 5' ON EACH END OF ASSEMBLY. SEE NOTE #5 LOWEST POINT 12" MIN. 60" MAX. FLOOR FLOOR DRAIN RECOMMENDED SEE NOTE #6 SLEEVE PER NC BLDG. CODE (TYP.) TEST COCK #1 ELEVATION VIEW 3. FIRE LINE INSTALLATIONS SHALL HAVE OUTSIDE STEM AND YOKE (OS&Y) HANDWHEEL OPERATORS. IF SERVING FIRE SPRINKLERS, TAMPER SWITCHES ARE REQUIRED. 10. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. WALL 6" MIN. CHECK VALVE #1 6" MIN. CLT WATER REQUIRED BPA INSIDE EXTERIOR BUILDING WALL SHUT-OFF VALVE #1 CHECK VALVE #2 24" MIN. CLEAR SPACE DRAIN RECOMMENDED DOUBLE CHECK VALVE ASSEMBLY TEST COCK #1 PLAN VIEW SHUT-OFF VALVE #2 ZONING SETBACK PROPERTY LINE SEE NOTE #7 & #8 CLT WATER METER ROAD R/W OUTSIDE WALL FLOW PUBLIC WATER MAIN TYPICAL LOCATION REQUIREMENT FOR INSIDE INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT 6" MIN. 5.3.2016 OUTSIDE WALL SLEEVE PER NC BLDG. CODE (TYP.) CHECK VALVE #1 VERSION DATE 2. CHECK VALVE #2 1.2 INDOOR INSTALLATION SHALL ONLY BE PERMITTED IN CASES WHERE ADEQUATE SPACE FOR THE BACKFLOW PREVENTION ASSEMBLY IS NOT AVAILABLE OUTSIDE. CLT WATER WILL REVIEW ON A CASE BY CASE BASIS. 11 1. DOUBLE CHECK VALVE ASSEMBLY (DC) 2 1/ 2" - 12" INDOOR 6" CLEAR OF OBSTRUCTIONS WHEN VALVE IS FULLY OPEN DOUBLE CHECK VALVE ASSEMBLY SHUT-OFF VALVE #1 SEE NOTE #3 VERSION NO. NOTES: VERSION DATE 5.3.2016 VERSION NO. 1.1 12 TEST COCK #2 #1 SHUT-OFF VALVE TEST COCK #3 CHECK VALVE #1 TEST COCK #4 CHECK VALVE #2 IF APPLICABLE REDUCE PRESSURE RELIEF VALVE & OUTLET #2 SHUT-OFF VALVE A CITY OF CHARLOTTE DEPARTMENT TEST COCK #1 TEST COCK LOCATION CMU APPROVED BACKFLOW PREVENTION (BPA) ASSEMBLY SHUT-OFF VALVE #2 4. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL AND MUST BE OUTSIDE OF ZONING SET-BACK DIRECTLY BEHIND METER. 5. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER-USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 6. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 7. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. CHECK VALVE #2 CHECK VALVE #1 STRAINER RECOMMENDED FLOW TEST COCK #1 12" MIN. 30" MAX. HINGED ACCESS OR REMOVABLE INSULATED ENCLOSURE MEETING ASSE 1060 SPECIFICATIONS. ENCLOSURE TO INCLUDE DRAIN PORT(S) PER CLT WATER REQUIREMENTS. LOWEST POINT OR RELIEF VALVE OUTLET TYPE K OR L COPPER TUBING PIPE. 1" MIN. GALVANIZED STEEL PIPE OR SCH. 40 PVC PIPE WITH SCH. 80 PVC FITTINGS. SEE NOTE #2 SLOPE GROUND AWAY FROM COVER (TYP.) CLT WATER REQUIRED BPA ABOVE GROUND ZONING SETBACK MIN. 4" THICK #67 WASHED STONE OR CONCRETE PAD SEE NOTE #4 & #5 PROPERTY LINE IF USING PVC PIPE, HORIZONTAL BRACING IS RECOMMENDED. CLT WATER METER PUBLIC WATER MAIN ROAD R/W IF USING PVC PIPE VERTICAL BRACING IS REQUIRED 5.3.2016 INSULATED ENCLOSURE SHALL BE AS SPECIFIED IN CLT WATER ENCLOSURE INFORMATION - HEATED INSULATED ENCLOSURE IS RECOMMENDED. NO INSULATION SHALL BE WRAPPED AROUND BPA. VERSION DATE 3. 1.1 PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. IF USING PVC PIPE / FITTINGS, VERTICAL SUPPORT IS REQUIRED AND HORIZONTAL BRACING IS RECOMMENDED. 13 2. TYPICAL LOCATION REQUIREMENT FOR ABOVE GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT SHUT-OFF VALVE #1 BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. REDUCED PRESSURE PRINCIPLE ASSEMBLY (RP) 3/4" - 1" ABOVE GROUND REDUCED PRESSURE PRINCIPLE ASSEMBLY 1. VERSION NO. NOTES: 4. ALL LOCATIONS FOR BPA'S REQUIRE CLT WATER APPROVAL AND MUST BE OUTSIDE OF ZONING SET-BACK DIRECTLY BEHIND METER. 5. THERE SHALL BE NO TAPS, PIPING BRANCHES, UNAPPROVED BYPASS PIPING, HYDRANTS, FIRE DEPT. CONNECTION POINTS, OR OTHER WATER - USING APPURTENANCES CONNECTED TO THE SUPPLY LINE BETWEEN ANY WATER METER AND ITS CLT WATER - REQUIRED BACKFLOW PREVENTER. 6. EACH CLT WATER-REQUIRED BPA IS REQUIRED TO BE TESTED BY A CLT WATER - APPROVED CERTIFIED TESTER PRIOR TO PLACING THE WATER SYSTEM IN SERVICE. TEST RESULTS SHALL BE SUBMITTED TO CLT WATER WITHIN 30 DAYS AND TESTED ANNUALLY THEREAFTER SUBMITTING RESULTS TO CLT WATER. 7. ALL INSTALLATIONS INTENDED FOR ADDRESSING CLT WATER REQUIREMENTS, REQUIRE PRIOR APPROVAL FROM THE APPROPRIATE CLT WATER BACKFLOW INSPECTOR. CHECK VALVE #1 TEST COCK #1 CHECK VALVE #2 SHUT OFF VALVE #2 HINGED ACCESS OR REMOVABLE INSULATED ENCLOSURE MEETING ASSE 1060 SPECIFICATIONS. ENCLOSURE TO INCLUDE DRAIN PORT(S) PER CLT WATER REQUIREMENT. FLOW 12" MIN. 30" MAX. STRAINER RECOMMENDED TYPE K OR L COPPER TUBING PIPE, 1" MIN. GALVANIZED STEEL PIPE OR SCH. 40 PVC PIPE WITH SCH. 80 PVC FITTINGS. SEE NOTE #2 LOWEST POINT SLOPE GROUND AWAY FROM COVER (TYP.) CLT WATER REQUIRED BPA ABOVE GROUND ZONING SETBACK SEE NOTE #4 & #5 PROPERTY LINE CLT WATER METER IF USING PVC PIPE, HORIZONTAL BRACING IS RECOMMENDED. PUBLIC WATER MAIN ROAD R/W IF USING PVC PIPE, VERTICAL BRACING IS REQUIRED 4" MINIMUM #67 WASHED STONE OR CONCRETE PAD 5.3.2016 INSULATED ENCLOSURE SHALL BE AS SPECIFIED IN CLT WATER ENCLOSURE INFORMATION - HEATED INSULATED ENCLOSURE IS RECOMMENDED. NO INSULATION SHALL BE WRAPPED AROUND BPA. VERSION DATE 3. 1.1 PIPE MATERIAL AND FITTINGS SHALL BE AS SPECIFIED IN CLT WATER STANDARDS & SPECIFICATIONS. 14 2. TYPICAL LOCATION REQUIREMENT FOR ABOVE GROUND INSTALLATION N.T.S. A CITY OF CHARLOTTE DEPARTMENT DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTION ASSEMBLIES (BPA's) SHALL CONFORM TO CLT WATER SPECIFICATIONS. SHUT-OFF VALVES ARE SPECIFIC TO EACH APPROVED BPA AND NO SUBSTITUTIONS OF SHUT-OFF VALVES ARE PERMITTED. REFER TO CLT WATER APPROVED LIST OF BPA's. DOUBLE CHECK VALVE ASSEMBLY (DC) 3/4" & 1" ABOVE GROUND SHUT OFF VALVE #1 1. VERSION NO. NOTES: