Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. Quarter NC Plumbing Code 2011 March 2011 Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage POLICY 0 0 0 0 0 0 0 Chapter 2 Definitions Chapter 4 Fixtures, Fau & Fit. Chapter 6 Water Supply & Dist. Chapter 8 Ind./Special Waste Chapter 10 Traps, Inter. & Sep. Appendix A-H OTHER 0 0 0 0 0 0 0 Chapter 3 General Regulations: 1) (Q) Is a check valve required on the water supply to a mobile home? No. Water supply piping shall be directly connected to the mobile home. The utility requirements are the same as any single family dwelling in Mecklenburg County. Ref: 301.3, 301.4 & North Carolina Mobile Home Code requirements. 1) (Q) What is the maximum height of the curb on a shower pan threshold? (A) There is not a maximum height for a non-handicap shower threshold. The requirement is; “the remaining side (threshold) shall wrap over the curb”. Ref: 417.4 (B) The maximum height for the threshold of a handicap shower, (either rollin or transfer type) is ½ inch. The exception is for existing facilities where structural reinforcement would be disturbed. If that is the case a maximum threshold of 2 inches would be allowed. Ref: ICC/ANSI A117.1- 2003 2) (Q) Can standard drywall coverings be used on the walls of a shower enclosure with shower head? (A) No. The wall area shall be constructed of smooth, non-corrosive, nonabsorbent, and water proof materials to a height of 6 feet. Ref: 417.4.1 3) (Q) I have an old existing apartment building three stories high that have no washer and dryer facilities. I can alter the plumbing piping to provide a 2 inch drain for the washers. I have no practical way to install a horizontal 3 inch drain for the washers. Will the re-hab code offer me any relief so these 1st Chapter 4 Fixturers, Faucets and Fixture Fittings: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 washers may be installed? (A) No. The Re-hab code offers the designer no relief from the horizontal 3 Inch drain requirement, however, the plumbing official may look at the existing DWV system to determine the feasibility of accommodating the washers before making a final determination. Ref: 406.3 4) Quarter Land Use and Environmental Service Agency (Code Enforcement) (Q) Is a drain required for an outside shower used on a pool deck that has only a cold water connection? (A) No. The shower is not used for bathing and has no hot water connection. The water could be considered clear water waste under normal circumstances and can drain into the same system that is used for the pool deck drainage. Similar in some respects to Emergency Showers and Eyewash Stations. Ref: 411 Chapter 5 Water Heaters: (Q) may a plastic safety pan be used for a gas fired instantaneous W/H? (A) Yes, provided that the water heaters minimum distance from combustible material is maintained. Ref: Manufacturers Instructions 1st 1) 2) (Q) What is the minimum size of a water heater pan drain per the current North Carolina Plumbing Code? (A) The plumbing code minimum in 504.7.1 requires a ¾ inch drain minimum This is incorrect and is a misprint in the code. The correct minimum size is 1 Inch. See DOI letter From Henry Webster Chief Plumbing Engineer for the State Department of Insurance Office of the State Fire Marshall. Chapter 6 Water Supply & Distribution: 1) (Q) What is the maximum distance a fixture supply pipe may be from the fixture it serves? (A) Section 604.5 states 72”. 2) (Q) When are water hammer arrestors required? (A) 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water- NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 hammer arrestor shall be installed where quick-closing valves (clothes washers and dishwashers) and metallic piping is used. The water-hammer arrestor shall not be required on any valves where plastic piping is used for water distribution. Water-hammer arrestors shall be installed in accordance with the manufacturer’s specifications. Water-hammer arrestors shall conform to ASSE 1010. 3) (Q) Does the Code require a water distribution system to be sanitized? (A) ? (No) 602.3.4 purged and disinfected, 610.1 purged of deleterious matter. 4) (Q) Is an expansion device required on a tankless water heater? (A) No. An expansion device is required only if there is a tank type water heater installed in the residence. An expansion device is not required if hot water distribution is from a tankless water heater. Ref: 607.3 Chapter 8 Indirect/Special Waste: 1) (Q) What is a sacristy and what special allowances apply? (A) It is one use where the drain is allowed to discharge directly into a drywell outside of the structure. 2) (Q) Can the tail piece of a lavatory or sink be used as a direct connection for the drainage from an ice maker or medical equipment? No. An air gap shall be provided and the waste shall discharge into an approved receptor to protect against backflow. Ref: Section 801.2, 802.1, and 802.1.6 3) (Q) Do all acid waste neutralization tanks require a monitoring device with alarm? (A) Yes. We require monitoring and alarms on all neutralization tanks installed in Mecklenburg County. Ref: Code Interpretation Letter & 702.5/803.2,803.5. 4) (Q) Can the discharge from a three compartment sink in a commercial Restaurant be pumped to an indirect waste receptor in a remote location? (A) Yes. The three compartment sink shall discharge through a flow control fitting and a point of use grease interceptor before terminating in the lift station. The lift station pumped discharge shall have a check valve and terminate over an indirect waste receptor which must be visible from the three compartment sink location. Ref: 802.1.1, 802.2.1 Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) March 2011 Chapter 10 Traps, Interceptors & Seperators: 1) (Q) What is required for laundry drain protection for lint, buttons or strings? 1st (A) Laundries other than a single family residence, shall be equipped with a manufactured device (not field fabricated) that will limit lint, buttons or string larger than ½” from entering the drainage system. 2) (Q) Is a separate draw off storage tank allowed to be installed as part of an oil/water separator installation? Yes. When circumstances exist on a site that would not permit the full storage tank capacity calculated for an integral storage oil/water separator to be installed, an integral separator sized to meet the minimum capacity of the code may be installed with an additional draw off tank to store the remaining capacity calculated for the separator. All other requirements for oil/water separators installed in Mecklenburg County shall remain the same. Ref: 1003.1, 1003.2, 1003.4, & 1003.4.2 1) (Q) How do vertical walls affect roof drain calculations? (A) 1106.4 Vertical walls. In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that diverts rainwater to the roof shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping. 2) (Q) I am attaching a handmade metal box I designed to a 4 inch overflow roof drain that terminates on the side wall of an apartment building. I am installing a screen in the box to restrict the flow so the water will not be pouring down the side of the building and staining the brick finish. Does this installation meet the code? No. The size of the drainage pipe is reduced in the direction of flow. The fitting is not approved and retards the direction of flow. The fitting has shoulders and/or reductions that retard flow. Strainers are allowed on roof surfaces only for overflow drains this is a side wall mounted fitting. Ref: 1101.5, 1101.6, 1102.7, 1105.1, 1107.2 1st Chapter 11 Storm Drainage: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) March 2011 1) (Q) What is the maximum depth that a two-way C/O may be installed? (A) The maximum depth shall not exceed 24” below grade. If deeper depths are required, then an additional combination may be placed as close as possible downstream of the required building drain/sewer junction C/O. 2) (Q) A single family home is connected to a septic tank. Can a dishwasher or washing machine be connected to the drainage system of the house? Can the washing machine be connected to a dry well? (A)The homeowner would be required to contact the Environmental Health Department for Mecklenburg County. They regulate the installation, repair, and alteration of the septic tank systems in Mecklenburg County. 1st Policy: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 4th 4th 3rd 3rd 2nd 2nd 1st1st Color code below denotes the calendar year quarter of the question. Colors are left to right; Brown-first quarter, Blue-Second Quarter, GreenThird quarter & Red-forth quarter. Quarter Land Use and Environmental Service Agency (Code Enforcement)