Land Use and Environmental Service Agency (Code Enforcement) Attention: 3 Denotes a new question! z Denotes a revised/revisited question. Quarter Mechanical Q&A 2009 May 2009 3) 4)3 5)3 1 nd 2) (Q) What does a contractor/permit holder have to supply for an inspection? (A) Section 107.2 of the NC Administrative Code states that it is the duty of the permit holder “to provide access to and means for inspection of the work for any inspections that are required by this code.” (Q) An existing home with a package unit, installed prior to the requirement for lintels where the duct penetrates the foundation wall is being replaced with equipment and duct of the same size. Would a lintel have to be installed at this time? (A) No, provided there is no increase in size of the foundation opening. (Q) The Mecklenburg County inspection department preaches strongly about how hard it works to combat inconsistency in inspections and interpretations. When are you going to be consistent with other counties? (A) Mecklenburg County Code Enforcement prides itself on achieving a high level of consistency within the confines of Mecklenburg County. We however do not have authority over other counties or the decisions they render. We make interpretation recommendations and/or requests to the NC Department of Insurance from time to time and will continue to do so in and effort to provide consistent code enforcement within “Mecklenburg County”. (Q) What is the inspection department’s policy on wearing hard hats on construction sites? (A) We are to wear hard hats anywhere job sites are posted “Hard Hat Area”! (Q) Is a permit and inspection required when replacing or installing a free standing appliance? (A) Yes, if the appliance is directly connected to the building utilities and just plugged into an outlet. 2 1) st General: Land Use and Environmental Service Agency (Code Enforcement) Attention: 3 Denotes a new question! z Denotes a revised/revisited question. Quarter Mechanical Q&A 2009 May 2009 2)3 3)3 (Q) Are hinges required on roof mounted exhaust fans (506.5.3)? (A) If the exhaust system has code approved cleanouts and removal of the exhaust fan for duct cleaning is not necessary, then a hinge would not be required. (Q) Does equipment installed in an enclosure, accessed by a louvered door, have to be supplied with a high and low combustion air duct? (A) The louvered door can not be used to meet the combustion air requirements (per DOI). Transfer ducts or ducts to the outside are acceptable. (Q) Is a well acceptable to achieve the termination (clearance to grade) requirements on a downdraft exhaust for a domestic range? (A) In cases where there is no possible alternative to achieve the required clearance to grade, a well with positive drain to open air may be provided. 2 1)3 nd Equipment: Land Use and Environmental Service Agency (Code Enforcement) Attention: 3 Denotes a new question! z Denotes a revised/revisited question. Quarter Mechanical Q&A 2009 May 2009 4) 5) 6) 7)3 1 3) nd 2) (Q) May a contractor use the merchant coupling provided with each stick of gas pipe, to assemble the permitted gas piping system? (A) The NC Gas Code does not prohibit the use of all thread merchant couplings. (Q) How many gas tests are required for a single gas pipe installation? (A) The Code would require two tests. One before you cover the work and one on final inspection. We require an additional test if you would like “temporary heat” which would result in a total of three. (Q) Does gas piping have to be steel where the piping terminates at the meter? (A) The Code does not require a steel termination, but many gas utility providers (Piedmont Natural Gas) will refuse to connect to CSST or copper piping. (Q) May the valve for a free standing range be placed behind the range? (A) Yes. The valve is for servicing and does not have to be placed where it can be accessed without moving the appliance. (Q) Does the Code require a cut-off to be placed at the base of decorative gas yard lights? (A) Yes! The light is considered an appliance and would require a cut-off within 6 feet and accessible (box/vault). (Q) What is the minimum length for an appliance drip leg (sediment trap)? (A) Drip legs shall be a minimum of 3” long or per the equipment and/or regulator manufacturer’s installation instructions, whichever is greater. (Q) How do you test a new gas line extension or branch, added to an existing gas line within the structure? (A) Section 406.1.3 (2009 NC Gas Code) states that only the new branch has to be tested. Section 406.1.4 states that you must use two valves in series with a telltale piece, with valve, between the two valves to vent any pressure. 2 1) st Gas Piping: Land Use and Environmental Service Agency (Code Enforcement) Attention: 3 Denotes a new question! z Denotes a revised/revisited question. Quarter Mechanical Q&A 2009 May 2009 3)¹ 4) 1 nd 2) (Q) What does the new 2009 Energy Code require for duct insulation? (A) Section 403. of the NC Energy Code states residential supplies and returns shall be R8 in unconditioned areas. Duct running through the web of floor truss systems may be R6 to limit duct compression. Duct installed between conditioned floors need not be insulated provided there is no condensation. Commercial supplies and returns shall be R5 in unconditioned areas. Commercial outside duct shall be R8. (Q) The new 2009 NC Mechanical Code requires that grease duct be tested with a light. How will this be accomplished? (A) The contractor/installer shall call for an inspection after the job is ready for inspection. The ladders should be in place, the drop cord/light shall be fished through the duct and any obstacles such as fans or grills that might obscure the inspection shall be removed. The light inspection will commence upon arrival. Should the contractor have concerns about open duct or would like the inspector on the job for more time, the contractor may secure an inspection by appointment (Call J. Aidoo (704)353-1273). (Q) What are the new requirements for duct wrap on type I grease exhaust in lieu of shaft requirements? (A) In January 2009 UL, OPL and ICC-ES withdrew the listing and Legacy reports for enclosure materials that used UL1978 as the basis for approval instead of the more appropriate ASTM E2336 standard. Projects with permits issued on or after May 1, 2009 will be required to meet the ASTM E2336 standards. (Q) Is flex duct allowed in a residential garage? (A) HVAC systems whose equipment room is located within the garage shall be constructed of metal (26 gage, Minimum) for all portions located within or penetrating the rated floor or ceiling. Systems that serve the living area shall not supply or return from the garage. Systems dedicated to the garage with not portions penetrating the rated enclosure may be of duct board or flex duct. 2 1) st Duct: