(Code Enforcement) Land Use and Environmental Service Agency

advertisement

Land Use and Environmental Service Agency

(Code Enforcement)

NC Mechanical Code 2011

Attention:  Denotes a new question!

 Denotes a revised/revisited question. March 2011

Chapter 1 Administration

Chapter 3 General Regulations

Chapter 5 Exhaust Systems

Chapter 7 Combustion Air

Chapter 9 Specific Appliances

Chapter 11 Refrigeration

Chapter 13 Fuel Oil Piping

POLICY

Table of Contents

0 Chapter 2 Definitions

3 Chapter 4 Ventilation.

1 Chapter 6 Duct Systems

0 Chapter 8 Chimneys & Vents

0 Chapter 10 Boilers, Water Htrs

0 Chapter 12 Hydronic Piping

0 Chapter 14 Solar Systems

1 OTHER

0

1

0

0

0

0

0

0

Chapter 3 General Requirements:

1) (Q) What are the requirements for systems installed in a flood plain?

(A) Section 301.13 states:

301.13 Flood hazard. For structures located in flood hazard areas, mechanical

systems, equipment and appliances shall be located at or above the design flood

elevation. Exception: Mechanical systems, equipment and appliances are permitted

to be located below the design flood elevation provided that they are designed and

installed to prevent water from entering or accumulating within the components

and to resist hydrostatic and hydrodynamic loads and stresses, including the

effects of buoyancy, during the occurrence of flooding to the design flood elevation

in compliance with the flood-resistant construction requirements of the

International Building Code.

301.13.1 High-velocity wave action. In flood hazard areas subject to high-velocity

wave action, mechanical systems and equipment shall not be mounted on or

penetrate walls intended to break away under flood loads.

See section 602.4 for similar the requirements covering the duct system.

2) (Q) Would the discharge line of an appliance condensate pump need to be protected

from freezing temperatures?

(A) Chapter 307 does not address the protection of condensate discharge lines

Installed areas subject to freezing temperatures however we would be remiss if

we did not require this protection in areas such as a ventilated attic space. Other

areas of concern would be where the line exits the foundation wall. We would

“recommend” that these installations be sloped downward and increased in pipe

size to limit blockages.

Land Use and Environmental Service Agency

(Code Enforcement)

NC Mechanical Code 2011

Attention:  Denotes a new question!

 Denotes a revised/revisited question. March 2011

3) (Q) What type of access would be required on a boiler installation where the device

may be subject to vandalism or component theft?

(A) Chapter 306 covers the typical installation of equipment. Section 105.1

Would allow us the flexibility to allow alternative access on a case by case basis.

Chapter 4 Ventilation:

1) (Q) What is the minimum ventilation required for toilet rooms?

(A) Toilet rooms are not considered to be habitable space and so their ventilation requirements would be found in table 403.3 which would require mechanical exhaust and not natural ventilation.

Note:

We have allowed natural ventilation in the past and we will begin enforcing the mechanical ventilation requirement on permits obtained after April 1, 2011.

Chapter 5 Exhaust Systems:

1) (Q) Does Mecklenburg County allow an alternative method for type I hood clearances?

(A) Mecklenburg County allows the use of NFPA 96 , Chapter 4.2.3.2 based on an interpretation by DOI dated 2/2/2004.

2) (Q) In an automotive repair garage with a vehicle exhaust source capture system

per NCMC 502.14, is it permitted to have one (1) –exhaust capture connection

for every two (2) bays or is one connection only allowed per bay?

(A) The Mechanical Code is silent on this question, however the code language

gives the inference that it requires a singular; “a source capture system”

for each vehicle or service bay. One per bay is required. Ref: 502.14

3)

(Q) Even though the code requirements have been met for the installation of the

grease duct the contractor wants to add several more cleanout openings because he

also has the maintenance contract on the grease duct system. The duct is only 10

inches by 10 inches and the code access door manufacturer informs him the

smallest door approved for grease duct installation per code is 12 inches by 12

inches. Can the contractor make his own door to access the grease duct?

(A) Yes. Where the duct is smaller than the 12 by 12 minimum the mechanical

contractor may provide cleanouts approved by the mechanical official at least

equivalent to the minimum requirements of the code for manufactured access

doors. Ref: 506.3.9

Land Use and Environmental Service Agency

(Code Enforcement)

NC Mechanical Code 2011

Attention:  Denotes a new question!

 Denotes a revised/revisited question. March 2011

Chapter 6 Duct Systems:

1) (Q) What method can be used to protect the opening in a floor/ceiling or

roof/ceiling assembly where supply duct from the HVAC unit penetrates

the assembly? NOTE: There is not a fire damper currently manufactured that

is approved for this application when the multi-story building is classified as an

R2 occupancy with type V construction.

(A) The current code approval for this application requires a smoke detector to be installed in the same room as the HVAC unit that will shut down the unit

if smoke is detected. The smoke detector shall tie in to the smoke detector circuit provided for the apt/condo unit. A static damper is required at the ceiling penetration of the HVAC duct penetrations from the unit. This method

of protecting the ceiling penetrations is only approved until a Fire Damper is

manufactured that provides adequate protection for the openings.

2)

(Q) What are the minimum requirements for plenum rated materials within an

open air plenum space?

(A) Not required. See plenum definition. Open air returns are typically in

habitable areas and do not have to conform to the material requirements of

enclosed plenums.

Example: Home Depot. Ref: Chapter 2 plenum definition. & 602.2.1

Policy: Includes Energy Conservation and Re-Hab Codes

1) (Q) When is a refrigeration permit required?

(A) A refrigeration permit is required for any refrigeration equipment needing

to be assembled (excluding the walk-in cooler box) OR any equipment needing to be hard wired electrically (not plug type).

2)

(Q) Is the outside air make-up air duct located on the non-insulated side of an

attic in a single family dwelling required to be insulated?

(A) No. The temperature difference between the air in the make-up air duct and the air temperature in the attic are not sufficient to cause condensate that would require insulating the duct.

Ref: 503.2.7, Exception #2, North Carolina Energy Conservation Code

Land Use and Environmental Service Agency

(Code Enforcement)

NC Mechanical Code 2011

Attention:  Denotes a new question!

 Denotes a revised/revisited question. March 2011

3) (Q) When does a Mechanical Inspector enforce the Carbon Monoxide Alarm

requirements adopted by the NC Department of Insurance in

One-and-Two-Family Dwellings and Townhouses? Effective date:

January 1, 2011

(A ) 2009 NC Residential Code revisions to Section R313 as provided below:

R313.1.1 Carbon Monoxide alarms. In new construction, dwelling units shall be provided with an approved carbon monoxide alarm installed outside of each separate sleeping area in the immediate vicinity of the bedroom(s) as directed by the alarm manufacturer.

R313.1.2 Where required-existing dwellings. In existing dwellings, where interior alterations, repairs, fuel-fired appliance replacements, or additions requiring a permit occurs, or where one or more sleeping rooms are added or created, carbon monoxide alarms shall be provided in accordance with

Section 313.1.1.

R313.1.3 The required carbon monoxide alarms shall be audible in all bedrooms over background noise levels with all intervening doors closed.

Single station carbon monoxide alarms shall be listed as complying with

UL 2034 and shall be installed in accordance with this code and the manufacturer’s installation instructions.

4)

(Q) Can R-4 insulated Flex be used in Icynene insulated attics where a thermal

Barrier is above the ductwork?

(A) Yes. It can be used as long as the attic is now part of the thermal envelope

and properly sealed. Ref: 503.2.7, NC Energy Conservation Code

Land Use and Environmental Service Agency

(Code Enforcement)

NC Mechanical Code 2011

Attention:  Denotes a new question!

 Denotes a revised/revisited question. March 2011

Color code below denotes the calendar year quarter of the question. Colors are left

to right; Brown-first quarter, Blue-Second Quarter, Green-third quarter & Red-forth quarter.

Download