Commercial Plan Review Land Use and Environmental Service Agency (Code Enforcement) Building Q&A 2009 Fourth Quarter 2009 General: 1. (Q) Table 508.3.3 indicates the separation requirements between occupancy types for mixed occupancy situations. Occupancies like “B” and “F-1” show a separation requirement of “N” (No separation requirement) and “B” and “F-2” as 1-hour if fire sprinklered and 2-hour if not fire sprinklered. Why is the fire separation requirement less for the “B” and “F-1” separation than for the “B” and “F-2” separation? (A) It is true that the separation requirement between “B” and “F-1” should be greater than for “B” and “F-2” as the code considers “F-1” a greater hazard than “F-2.” The 2006 NCBC did in fact provide a 3-hour separation between “B” and “F-1” and a 2-hour separation if the building was fully sprinklered. Table 508.3.3 unfortunately does not tell the whole story. You can provide “B” and “F-1” in the same building without separation, but the building is then unseparated mixed use and must be built to the more stringent occupancy type. If you want to design a building with separated mixed use for “B” and “F-1” you have to go to Table 706.3.9. This is because the code offers no other means of fire-resistance-rating such separation. Table 706.3.9 is intended to be used to separate like occupancies such as “B” and “B” into separate fire areas, but it is our only alternative for separated mixed use fire-resistance-ratings where Table 508.3.3 provides no rating. For “B” and “F-1” you would use the worst case scenario, and the required rating would be 3-hours. Note that Table 706.3.9 does not allow a reduction for fire sprinklers. Note: The 2009 IBC changes the section number from 706.3.9 to 707.3.9 and adds the following sentence to correct this issue: “The fire barriers or horizontal assemblies, or both, separating fire areas of mixed occupancies shall have a fire resistance rating of not less than the highest value indicated in Table 707.3.9 for the occupancies under consideration. All of the above was clarified in an interpretation from the NC Department of Insurance dated June 19, 2009. 2. (Q) Does Code Section 1008.1.3.3 apply to all sliding doors or just those entering a building or tenant suite required for egress in and out of the space? (A) Refer to Code Section 1008.1.2 for door swing. Egress doors shall be sidehinged swinging. Exception 1: Private garages, office areas, factory and storage areas with an occupant load of 10 or less. This exception would allow for a sliding door in an office area with an occupant load of 10 or less. Exception 6 in other than Group H occupancies, horizontal sliding doors complying with Section Fourth Quarter 2009 1008.1.3.3 are permitted in a means of egress. Section 1008.1.3.3 requires that the sliding door comply with 8 criteria with the first being: The door shall be power operated and shall be capable of being operated manually in the event of a power failure. Thus, a 400 sq. ft. conference room could have a sliding door but the door must comply with all 8 items in 1008.1.3.3. 3. (Q) If an accessory room, (such as a conference room, or a break room) of a tenant space has an exit access door opening directly onto the exit access corridor; is the occupant load of the accessory area required to be included as part of the total occupant load of the primary space in determining the egress requirements? (A) No, provided the accessory room (conference room, etc.) occupant load does not require egress through the primary space. The primary space must comply with the egress requirements for number and size of exits as well as remoteness of exits and may or may not utilize the accessory room in the exit path to satisfy the required remoteness of exits for the primary tenant space. 4. (Q) A tenant space may require two or more remotely located exits per 1015.1 and 101015.2 because of the space size, length of exit travel and/or number of occupants. If the limited length of exit access corridor does not provide sufficient distance to satisfy the remoteness rule along the corridor, is it acceptable to separate the space into two smaller tenant type areas (each small enough to require only one exit) and treat the two smaller areas as if they were separate tenants each required to provide single exits, thereby eliminating the need for remoteness? (A) Yes, provided all of the following conditions are met: a) Each space shall comply as a single exit space meeting Table 1015.1 b) The communicating access door must be located to meet the remoteness rule for the space and marked with an exit sign on each side c) The division wall shall be constructed consistent with the tenant separation requirements for the building, but not less than smoke-tight floor to ceiling d) Hard wired smoke detectors shall be installed in the corridor within 15 feet of the tenant space corridor doors with alarms that can be heard throughout the tenant space 5. (Q) Many listed and approved fire stop systems require that an item penetrating the rated wall or floor (pipes, conduit, wiring, etc.) be rigidly supported on both sides of the wall or floor being penetrated. What is required for these penetrating items to meet the “rigidly supported” condition? (A) Section 712, 712.3.1.1 and 712.4.1.1.1 require that when a building service system (electrical, plumbing, mechanical) penetrates a fire rated assembly it Fourth Quarter 2009 shall be protected by an approved fire stop system. The approved fire stop system must be installed consistent with the requirements of the listing. To ensure the penetrating item does not move at the point of penetration causing the fire stop system to be compromised, it requires adequate (or rigid) support on each side of the penetration. Minimum support for electrical, plumbing, and mechanical systems is addressed by various tables in the respective volumes of the North Carolina State Building Code. Unless the support requirements are specifically addressed by the approved listed test; building service systems, which are supported in accordance with the Code, shall be deemed adequately/rigidly supported. The support system should be designed based on the premise the fire stop system (point of penetration) provides no support. 6. (Q) Are secondary or miscellaneous structural members, such as a steel wall frame member, header or masonry lintel required to be fire protected if they are welded or bolted to a rated structural frame? (A) Yes, a minimum of 24 inches of the secondary member will need to be protected at the connection to the structural frame. Table 601 specifies the required fire protection of the structural frame based on the type of construction. Footnote (a) defines the structural frame as the columns, girders, beams, trusses and spandrels having direct connections to the columns and bracing members designed to carry gravity loads. The concern is that although a secondary structural member and its performance may not have a direct effect on the stability of the primary building frame, it could allow heat to transfer through the direct connection and cause the premature failure of the structural frame. Due to this potential heat transfer problem, in addition to structural members requiring full protection, any secondary structural members with direct connections to the structural frame shall be protected a minimum of 24 inches from the connection. Fourth Quarter 2009