MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement Electrical Consistency Meeting November 4TH, 2009 Code Consistency Questions 1. (Q)Does the requirement for AFCI protected receptacles being those listed in 210.52 mean that extra receptacles would not be required to be AFCI protected? (A)The code addresses all receptacles in those areas and they are to be AFCI protected. NEC 210.12 (B) Dwelling Units. All 120-volt, single phase, 15- and 20ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter, combination-type, installed to provide protection of the branch circuit. 2. (Q)We were turned down on a job for installing a track light installation because it was not listed. The main track was clearly listed but some pieces were not labeled. What was the reason for this? (A)Per the UL White Book page 149, certain manufactured pieces “are not acceptable for use with a listed track lighting system: 1) receptacle adaptors that when inserted into a track section will accommodate attachment plugconnected products and 2) power supply cord connectors that when inserted into the end of a track section enables the track system to serve as a power supply cord connected to its source of power” 3. (Q)We had a problem with a cover for a porch receptacle cover. Some are requiring the bubble covers and some are not. How can we get together on this issue? (A)Generally bubble covers are needed when the receptacle is in a wet location and where not protected from weather. NEC 406.8 Receptacles in Damp or Wet Locations. (A) Damp Locations. A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is weatherproof when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed). An installation suitable for wet locations shall also be considered suitable for damp locations. A receptacle shall be considered to be in a location protected from the w eather w here located under roofed open porches, canopies, m arquees, and the like, and w ill not be subjected to a beating rain or w ater runoff. All 15- and 20-ampere, 125- and 250-volt nonlocking receptacles shall be a listed weather-resistant type. FPN: The types of receptacles covered by this requirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2002, National Electrical Manufacturers Association Standard for Dimensions of Attachment Plugs and Receptacles. (B) Wet Locations. (1) 15- and 20-Ampere Receptacles in a Wet Location. 15- and 20-ampere, 125and 250-volt receptacles installed in a w et location shall have an enclosure that is w eatherproof w hether or not the attachm ent plug cap is inserted. All 15- and 20-ampere, 125- and 250-volt nonlocking receptacles shall be listed weather-resistant type. FPN: The types of receptacles covered by this requirement are identified as 5-15, 5-20, 6-15, and 6-20 in ANSI/NEMA WD 6-2002, National Electrical Manufacturers Association Standard for Dimensions of Attachment Plugs and Receptacles.] Exception: 15- and 20-ampere, 125- through 250-volt receptacles installed in a wet location and subject to routine high-pressure spray washing shall be permitted to have an enclosure that is weatherproof when the attachment plug is removed. (2) Other Receptacles. All other receptacles installed in a wet location shall comply with (B)(2)(a) or (B)(2)(b). (a) A receptacle installed in a w et location, w here the product intended to be plugged into it is not attended w hile in use, shall have an enclosure that is w eatherproof w ith the attachm ent plug cap inserted or rem oved. (b) A receptacle installed in a wet location where the product intended to be plugged into it will be attended while in use (e.g., portable tools) shall have an enclosure that is weatherproof when the attachment plug is removed. (C) Bathtub and Shower Space. Receptacles shall not be installed within or directly over a bathtub or shower stall. (D) Protection for Floor Receptacles. Standpipes of floor receptacles shall allow floor-cleaning equipment to be operated without damage to receptacles. (E) Flush Mounting with Faceplate. The enclosure for a receptacle installed in an outlet box flush-mounted in a finished surface shall be made weatherproof by means of a weatherproof faceplate assembly that provides a watertight connection between the plate and the finished surface. 4. (Q)We recently had a problem with the classification of a garage that affected the wiring methods and ventilation requirements. We were approaching the project as a minor garage and the inspector turned us down saying it was a major repair garage. (A)We hope to address this issue in plan review by requiring a statement from the designer of record as to the classification. It could be that the process was affected by incomplete info between the owner and his team as to what the actual procedures of the garage would be. The job must be installed for the correct usage as defined in the NEC. 511.2 Definitions. Major Repair Garage. A building or portions of a building where major repairs, such as engine overhauls, painting, body and fender work, and repairs that require draining of the motor vehicle fuel tank are performed on motor vehicles, including associated floor space used for offices, parking, or showrooms. [30A:3.3.12.1] Minor Repair Garage. A building or portions of a building used for lubrication, inspection, and minor automotive maintenance work, such as engine tune-ups, replacement of parts, fluid changes (e.g., oil, antifreeze, transmission fluid, brake fluid, air-conditioning refrigerants), brake system repairs, tire rotation, and similar routine maintenance work, including associated floor space used for offices, parking, or showrooms. [30A:3.3.12.2] 5. (Q)What wiring methods are acceptable to run across roofs to feed equipment located on the roof? (A)We need to consider the conditions that are present and probable. Per NEC 300.4 conductors are to be protected. Roofs of most commercial buildings would allow for the system to be subject to physical damage and possibly severe physical damage especially when re-roofed, and as such acceptable wiring methods would be: (1) rigid conduit 334.10, (2) intermediate conduit 342.10, (3) MI cable 332.10, (4) or the system could be put in other raceways suitable for the environment and with other suitable physical protection acting as a guard. 6. (Q) Explain what type of equipment is required to be listed and labeled and how these requirements can be met. Example: A machine shop has been in business for many years and has out grown its’ present location. The owner of the machine shop builds a new building and moves his existing equipment into the new building and the electrical inspector will not final the building because the machine shop equipment does not have a third party label or listing. The owner states he has been using this equipment for many years and feels the electrical contractor is responsible for this problem. (A)Per the General Statutes there are basically five methods to approve equipment. (1) The statutes allows the CEO to accept the listing of a NRTL, NEC 90.7 (2) The equipment could be wired to meet all the applicable NEC requirements (3) The CEO could approve the equipment per his own authority NEC 110.2, but most authorities would refer clients to acceptable NRTL field labeling services as they were not trained or experienced in these types of evaluations (4) The CEO can accept and approve the equipment per a certification report of a registered professional engineer (5) The owner can ask that the equipment be exempted per GS 143-138(b) which exempts industrial machinery from inspections by code enforcement officials 7. (Q) Are you required to provide arc-fault protection for an outside flood light circuit, which has a 3-way wall switch control in the bed room? (A)No. The arc fault requirement applies only to outlets and the switch is a device. NEC references are 210.12 and Article 100, definitions of outlet and device. 8. (Q)Do temporary construction pole services require the new “in use” covers for receptacles mentioned in NEC Section 406.8(B)? (A)No. NEC 406.8 (B) (2) (b) states that for attended use for portable equipment that the only weatherproof cover required is one that is weatherproof when the attachment plug is removed. 9. (Q)NEC Sections 110.10, 250.4(A)(5), the heading to Table 250.122 and a Note at the bottom of this Table, warn us that the equipment grounding conductor shall be large enough to provide a low impedance path so that in the event of a ground fault the overcurrent device will operate to limit damage to the equipment. How can the proper size be determined and how can these sections be complied with by contractors and electricians in the field? (A)In most cases where the grounding system is in average condition the Table 250.122 will suffice. The next step for increased capability of the grounding conductor is to size it equal to the current carrying conductors. Typically without extreme conditions of length or excessive fault current the return path is assured. In cases where distances of the return path are extremely long and the fault current is excessive the contractors project engineer may need to run a calculation to certify the grounding conductor’s capability. Additionally we need to remember that per NEC 250.122 (B) that if we increase the phase conductors for any reason that the grounding conductor shall be increased by the same proportional circular mill area. 10. (Q)Distributors continue to market equipment in our state that only has a CE mark of identification. They have sought help from the Chamber of Commerce, and other public officials in forcing the Inspection Departments to just accept this label. According to them, CE is the same mark as any other “third party label” placed on electrical equipment by a NRTL. After all, these are big companies and expensive equipment and they say we are wrong in our interpretation of third party listing and labeling and we are the “ only State in the Union” requiring evaluation of equipment for SAFETY . They insist there is no problem with unlisted equipment and all manufacturers and distributors must be reputable and would never sell a product in this country before it was rigorously tested. As a contractor, what can we do when we encounter these projects? (A)Probably the best we can do is to attempt to educate our customers. The CE label is not an indication of any nationally recognized testing lab. In their own charter the label has no effect outside the chartered nations of Europe. The NCBCC has not recognized the mark as an approved agency for NC. The manufactures in the CE program do not participate in a jointly standardized safety listing program and only guarantee their equipment’s safety by their own claim. We also need to inform them of the exemption of industrial equipment that was created by our General Assembly if applicable. 11. (Q)Several changes in the NEC have raised questions about the disconnecting means on an outdoor generator being used to serve as the disconnecting means for a building. Many Inspectors have claimed that to allow those disconnects at the generator only, they shall be rated for service and comply with NEC Article 225. Why are we directed to NEC Article 225? (A)225 is the feeder and branch circuit article. The conductors from the genset are generally feeders per definition in Article 100. Per Article 90.3 the code chapters 1 thru 4 applies to all installations where not amended by chapters 5 thru 7. Article 445 does not modify the requirements if the overcurrent device is installed at the genset. However this question says disconnect and does not specify overcurrent protection. 445.13 requires that the feeder now be sized for 115% of the rating of the genset output. There is an exception for this requirement and if load conditions are controlled by design and operation to prevent operation at more than 100%. Article 225 section II would tell us how to deal with disconnect requirements at the building or structure. 225.36 states that the disconnect shall be rated for use as service equipment. 12. (Q)As a contractor we are mainly doing commercial work. We install many 480/277-volt systems and know about the bonding requirements when eccentric or concentric knockouts are encountered. We maintain that as long as one end of the run meets the requirements in NEC Article 250 we should not be concerned about the other end when using metallic conduits such as rigid, intermediate, and EMT, even though at the other end we have concentric or eccentric knockouts. What is the interpretation of the NEC ? (A)NEC in 250.97 requires bonding of raceways for systems operating at over 250 volts. If concentric or eccentric knockouts are encountered we are to use the methods specified in NEC 250.92 (B) except (B) (1). 250.96 (A) states that metal raceways that serve as grounding conductors shall be effectively bonded where necessary to ensure electrical continuity and the capacity to conduct safely any fault current likely to be imposed on them. Additionally if the raceway is being used as the grounding conductor 250.120 applies and states that the grounding method shall be installed in accordance with the applicable provisions of this code and 250.120 (A) requires using fittings approved for the use and made tight with suitable tools. All of these references point to us that both ends would need to be bonded. 13. (Q) Please explain to me how to size disconnecting means for fire pumps. I ran a feeder from the service equipment panel over to a disconnect beside the fire pump controller. The fire pump has a FLA of 100-amperes. The Inspector is trying to make me install a 600-ampere disconnect. Why would he think I needed such a big disconnect? (A) Many installations we now see are feed from the utility directly to a listed controller for a given horsepower motor. This installation depicts the one additional overcurrent device that is allowed by NEC 695.4(B). NEC 695.4 (B) (1) states that the overcurrent device shall be capable of carrying indefinitely the locked rotor currents of the fire pump, maintenance pump and associated equipment. The locked rotor requirement is the reason for the 600 amp disconnect as the locked rotor current is generally six times the FLA of the motor. 14.(Q)I have an industrial warehouse condominium in a single story building divided into 20 tenants with 20 meters and 20 disconnect switches (6 mains or less). I would like to install the entire electrical service on a 6 feet high concrete wall which is approximately 20 feet long and located 6 feet away from the main building. Since the wall is not part of the building, is this an allowable installation or would this wall have to be connected to the main building such that it were considered part of the building? (A)First I believe we need to look in Article 100 at the definition of structure. It states, that which is built or constructed. The installation is allowable but requires that we now have to set a disconnect means at the entrance to the building per NEC 225.30, 31, and 32. Additionally we would have to reground at the building per NEC 250.32. I don’t believe that is what the author of the question desires to do. If the wall where made to be part of the building (generally in or on the footprint) then the price of the additional disconnects and grounding could be eliminated. 15. (Q)An electrical contractor has mounted a panelboard with the main installed vertically to one end. It seems though that the handle is now upside down. You must move the handle down to turn on the power and up to turn it off. To me this is in violation of the NEC . What is your interpretation? Yes it’s a violation per the NEC 404.7 Indicating. General-use and motor-circuit switches, circuit breakers, and molded case switches, where mounted in an enclosure as described in 404.3, shall clearly indicate whether they are in the open (off) or closed (on) position. Where these switch or circuit breaker handles are operated vertically rather than rotationally or horizontally, the up position of the handle shall be the (on) position. Exception No. 1: Vertically operated double-throw switches shall be permitted to be in the closed (on) position with the handle in either the up or down position. Exception No. 2: On busway installations, tap switches employing a centerpivoting handle shall be permitted to be open or closed with either end of the handle in the up or down position. The switch position shall be clearly indicating and shall be visible from the floor or from the usual point of operation. 16. (Q)I’m wiring a machine shop where the equipment is located in a generally open area. The only way to wire this equipment is from the bar joists to the equipment disconnect switch. I ran IMC with threaded couplings from a junction box on the bar joist to the disconnect. The Inspector says I have to support the conduit better. How do I do that, it is going to cost too much to add braces? (A)NEC 342.30 allows for this type installation in (B) (3) Exposed vertical risers from industrial machinery or fixed equipment shall be permitted to be supported at intervals not exceeding 6 m (20 ft) if the conduit is made up with threaded couplings, the conduit is supported and securely fastened at the top and bottom of the riser, and no other means of intermediate support is readily available. 17. (Q)If a single family residence has a single receptacle on its exterior for a water softener or chemical pump and it is a 120-volt, 15-ampere or 20-ampere, would this receptacle be acceptable as the one required for servicing the A/C equipment if it is within 20 feet of the A/C Unit? (A)NEC 210.63 requires an outlet for servicing the a/c units. It must be within 25 feet, on the same level, not on the load side of the disconnect means; and GFCI protected per NEC 210.8. The code does not require a dedicated circuit and therefore the outlet could be on the same circuit as the equipment as long as it does not violate the requirements of NEC 210.23 . 18.(Q)Is it permissible to use UF cable for interior wiring method instead of NM cable? (A)NEC 340.10 (4) allows this use; (4) Installed as nonmetallic-sheathed cable. Where so installed, the installation and conductor requirements shall comply with Parts II and III of Article 334 and shall be of the multiconductor type. EVENTS UPDATE • The re-org has been approved by the executive management team and we expect to implement by sometime in January