Catching up with 2014 NC Electrical Code Updates from Part One – 2014 Enactment, 2014 NC Amendments and NFPA TIAs and Errata Currently we have been advised by NCDOI that the 2014 NC Electrical Code will go into effect on April 1st, 2016. NCDOI: http://www.ncdoi.com/OSFM/Engineering_and_Codes/Documents/2014% 20Edition%20-%20Effective%20April%201%202016.pdf ; 2014 NC Electrical Code NFPA: http://www.nfpa.org/codes-and-standards/free-access ; 2011 NEC, 2011 TIAs, 2011 Errata, 2014 NEC, 2014 TIAs, 2014 Errata Date: December 31, 2015 To: All customers From: Jim Bartl, Director of Code Enforcement Re: 2014 NC Electrical Code effective date In the NC Building Code Council (BCC) meeting of December 15, the Council adopted the new 2014 NC Electrical Code. In doing so, the BCC set an effective date of April 1, 2016, subject to the NC Rule Review Commission offering no changes to the BCC approved 2014 NC Electrical Code. Department policy on the transition period as applied to the 2014 NC Electrical Code The Department maintains a code transition policy dating to 1997, which allows a 90-day grace period for projects under review, provided they gain a permit within 90 days of the code effective date. We will apply this policy to the new 2014 NC Electrical Code. Consequently, projects with permit applications prior to April 1, 2016 may use the current 2011 NC Electrical Code, provided they gain a permit by June 30, 2016. All other projects must use the new 2014 NC Electrical Code for project permit applications on or after April 1, 2014. The Department’s 1997 policy provides two exceptions to the above transition period, which also apply here. Exception 1: if a project requires lengthy review by City, State or Federal agencies, the Code Enforcement Director or his designee will select the appropriate year code to apply to the project. Exception 2: if a project is multi-phased, with construction time in excess of twelve (12) months, the applicable year code will be selected by the Code Enforcement Director or his designee at the preliminary code review meeting. It is very important that professionals monitor their work closely to carefully determine when a project’s design basis must switch to the new 2014 NC Electrical Code to comply with the above transition period and the Department’s related policy. While state law requires us to issue a permit on any project compliant with the effective code, the burden is on the owner’s team to estimate when your permit will be issued. Projects not covered by Exception 1 or Exception 2 above, and not permitted by June 30, 2016 must comply with the 2014 NC Electrical Code, regardless of when they entered the system for permitting. Feel free to contact me, Director of Plan Review & Permitting Patrick Granson or Electrical Code Administrator Gary Mullis, if you have questions on the 2014 NC Electrical Code effective dates. Item 6.1: Retain language from 2011 NEC for 110.26 (E) (2) – No Cost Impact (NEW AMENDMENT) AMENDMENT 110.26(E)(2) Amend NEC 2014, page 41: (2) Outdoor. (a) Installation Requirements. Outdoor electrical equipment shall be installed in suitable enclosures and shall be protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems. The working clearance space shall include the zone described in 110.26(A). No architectural appurtenance or other equipment shall be located in this zone. (b) Deleted. Item 6.2: Retain Existing NC Electrical Code Amendment to 210.8(A) (3) – No Cost Impact Amend NEC 2014, page 54: (3) Outdoors Exception No. 1 to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snowmelting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable. Exception No. 2 to (3): A single outlet receptacle supplied by dedicated branch circuit which is located and identified for specific use by a sewage lift pump. Item 6.3: Retain language from 2011 NEC for 210.8(A) (7) {residential GFCI requirements} – No Cost Impact (NEW AMENDMENT) AMENDMENT 210.8(A)(7) Amend NEC 2014, page 54: (7) Sinks — located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft.) of the outside edge of the sink. Item 6.4: Remove GFCI requirement for kitchen dishwasher branch circuit. This was not a requirement in the 2011 NEC. – No Cost Impact (NEW AMENDMENT) AMENDMENT 210.8(D) Amend NEC 2014, page 55: 210.8(D) Kitchen Dishwasher Branch Circuit. Deleted Item 6.5: Retain location requirements from 2011 NEC for AFCI Protection and remove term “readily”. – No Cost Impact (NEW AMENDMENT) Amend NEC 2014, page 56: 210.12 Arc-Fault Circuit-Interrupter Protection. Arc-fault circuitinterrupter protection shall be provided as required in 210.12(A) (B), and (C). The arc-fault circuit interrupter shall be installed in an accessible location. (A) Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6): Item 6.7: Revise to reflect NC Electrical Code Amendment with January 1, 2015 effective date. - No Cost Impact (NO CHANGE) Amend NEC 2014, page 62: 210.52 (I) Foyers. Foyers that are not part of a hallway in accordance with 210.52(H) and that have an area that is greater than 5.6 m2 (60 ft2) shall have at least one receptacle. Item 6.8: Retain Existing NC Electrical Code Amendment to 250.50 – No Cost Impact (NO CHANGE) Amend NEC 2014, page 117: 250.50 Grounding Electrode System. All grounding electrodes as described in 250.52(A)(1) through (A)(7) that are available at each building or structure served shall be bonded together to form the grounding electrode system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. Item 6.9: Modify 250.53 (A) (2) to match D-1 Agenda Item – No Cost Impact (NO CHANGE) Amend NEC 2014, page 118: (2) Supplemental Electrode Required. Exception No. 1: If a single, rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental electrode shall not be required. Exception No. 2: The supplemental ground electrode shall not be required at temporary electrical service installation (saw service pole) at construction site for one and two-family residences, provided the temporary electrical service does not exceed 150 volts to ground or 100A. Item 6.10: Retain Table and Language of 2011 NEC related to sizing of Dwelling Services and Feeders – No Cost Impact (NEW AMENDMENT) AMENDMENT 310.15(B)(7) Amend NEC 2014, page 160: (7) 120/240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders. For individual dwelling units of one-family, two-family, and multifamily dwellings, conductors, as listed in Table 310.15(B)(7), shall be permitted as 120/240-volt, 3-wire, single-phase service-entrance conductors, service-lateral conductors, and feeder conductors that serve as the main power feeder to each dwelling unit and are installed in raceway or cable with or without an equipment grounding conductor. For application of this section, the main power feeder shall be the feeder between the main disconnect and the panelboard that supplies, either by branch circuits or by feeders, or both, all loads that are part or associated with the dwelling unit. The feeder conductors to a dwelling unit shall not be required to have an allowable ampacity rating greater than their service-entrance conductors. The grounded conductor shall be permitted to be smaller than the ungrounded conductors, provided the requirements of 215.2, 220.61, and 230.42 are met. Table 310.15(B)(7) Conductor Types and Sizes for 120/240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders. Conductor Types RHH, RHW, RHW-2, THHN, THHW, THW, THW-2, THWN, THWN-2, XHHW, XHHW-2, SE, USE, USE-2 Service or Feeder Rating (Amperes) Copper Aluminum or CopperClad Aluminu m 100 4 2 110 3 1 125 2 1/0 150 1 2/0 175 1/0 3/0 200 2/0 4/0 225 3/0 250 250 4/0 300 300 250 350 350 350 500 400 400 600 Item 6.11: Retain Existing NC Electrical Code Amendment to 334.15 (C) – No Cost Impact (NO CHANGE) Amend NEC 2014, page 204: (C) In Unfinished Basements. Where cable is run at angles with joist in unfinished basements it shall be permissible to secure cables not smaller than two 6 AWG or three 8 AWG conductors directly to the lower edges of the joists. Smaller cables shall be run either through bored holes in joists or on running boards. Nonmetallic-sheathed cable installed on the wall of an unfinished basement shall be permitted to be installed in a listed conduit or tubing or shall be protected in accordance with 300.4. Conduit or tubing shall be provided with an insulating bushing or adapter at the point the cable enters the raceway. The sheath of the nonmetallic-sheathed cable sheath shall extend through the conduit or tubing and into the outlet or device box not less than 6 mm (1/4 in.). The cable shall be secured within 300 mm (12 in.) of the point where the cable enters the conduit or tubing. Metal conduit, tubing, and metal outlet boxes shall be connected to an equipment grounding conductor complying with the provisions of 250.86 and 250.148. Item 6.12: Revise to reflect NC Electrical Code Amendment with January 1, 2015 effective date. – No Cost Impact (NO CHANGE) AMENDMENT 404.2(C)(8) Amend NEC 2014, page 278: (8) Where installed in residential one- and two- family dwellings. Item 6.13: Remove term “readily” from 406.4 (D) and add new exception – No Cost Impact (NEW AMENDMENT) Amend NEC 2014, page 282: (D) Replacements. Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Arc-fault circuit-interrupter type and ground-fault circuit-interrupter type receptacles shall be installed in an accessible location. (4) Arc-Fault Circuit-Interrupter Protection. Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuitinterrupter protection as specified elsewhere in this Code, a replacement receptacle at this outlet shall be one of the following: (1) A listed outlet branch-circuit type arc-fault circuit-interrupter receptacle (2) A receptacle protected by a listed outlet branch-circuit type arc-fault circuit-interrupter type receptacle (3) A receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker This requirement becomes effective January 1, 2014. Exception: Non-grounding type receptacles. Item 6.14: For one- and two-family residences, remove term “readily” from 422.5 – No Cost Impact (NEW AMENDMENT) Amend NEC 2014, page 303: 422.5 Ground-Fault Circuit-Interrupter (GFCI) Protection. The device providing GFCI protection required in this article shall be readily accessible. Exception: For one- and two-family residences, the device providing the GFCI protection required in this article shall be accessible. Article 10 - ADMINISTRATIVE SECTION 10.1 TITLE These Administrative Regulations along with the requirements included in the 2014 Edition of the National Electrical Code (NFiPA70 - 2014) as adopted by the North Carolina Building Code Council on December 15, 2015, to be effective April 1, 2016, with the following amendments: (1) 110.26(E)(2), (2) 210.8(A)(3) (Exception No. 2), (3) 210.8(A)(7), (4) 210.8(D), (5) 210.12(A), (6) 210.52(I), (7) 250.50, (8) 250.53(A)(2) (Exception No. 2), (9) 310.15(B)(7), (10) 334.15(C), (11) 404.2(C)(8), (12) 406.4(D), (13) 422.5 shall be known as the North Carolina Electrical Code, and may be cited as such or as the State Electrical Code; and will be referred to herein as “the code” or “this code”. 10.2 SCOPE Article 80 Administration and Enforcement of the code is hereby not adopted and does not apply for this code. For Scope and Exceptions to Applicability of Technical Codes, refer to the North Carolina Administrative Code and Policies. 10.3 PURPOSE The purpose of the code is to provide minimum standards, provisions and requirements of safe and stable design, methods of construction and uses of materials in buildings or structures hereafter erected, constructed, enlarged, altered, repaired, moved, converted to other uses of demolished and to regulate the electrical systems, equipment, maintenance, use and occupancy of all buildings or structures. All regulations contained in this code have a reasonable and substantial connection with the public health, safety, morals, or general welfare, and their provisions shall be construed liberally to those ends. 10.4 ADMINISTRATION For administrative regulations pertaining to inspection (rough-ins and finals), permits and Certificates of Electrical Compliance, see When the provisions of other codes are determined to be contrary to the requirements of this code, this code shall prevail. local ordinances and the North Carolina Administrative Code and Policies. TIAs Reference: 516.3(A)(1)(a) and 516.10(A) TIA 14-1 (SC 13-8-16/TIA Log #1096) Note: Text of the TIA issued and incorporated into the text of 516.3(A)(1)(a) and 516.10(A), therefore no separate publication is necessary. 1. Remove the indication that 516.3(A)(1)(a) is to be deleted and renumber as needed. This is an error in ROC Comment 14-67 to read as follows: (A) Zone Classification of Locations. (1) For the purposes of this Article, the Zone system of electrical area classification shall be applied as follows: (a) The inside of open or closed containers or vessels shall be considered a Class I, Zone 0 location. (b) A Class I, Division 1 location shall be permitted to be alternatively classified as a Class I, Zone 1 location. (c) A Class I, Division 2 location shall be permitted to be alternatively classified as a Class I, Zone 2 location. (d) A Class II, Division 1 location shall be permitted to be alternatively classified as a Zone 21 location. (e) A Class II, Division 2 location shall be permitted to be alternatively classified as a Zone 22 location. [33: 6.2.2] 2. Change the second to last sentence of 516.10(A) and add an informational note as shown in ROC Comment 14-67 to read as follows: The installation of electrostatic spraying equipment shall comply with 516.10(A)(1) through (A)(10). Spray equipment shall be listed except as otherwise permitted. All automatic electrostatic equipment systems shall comply with 516.4(A)(1) through (A)(9). Informational Note: For more information on listing and approval of electrostatic spray equipment, see NFPA 332011, Standard for Spray Application Using Flammable or Combustible Materials, Section 11.5. NFPA 33 permits certain electrostatic spray equipment to be approved for use when additional mitigation equipment is employed. Issue Date: August 1, 2013 Effective Date: August 20, 2013 TIAs Reference: 445.20 TIA 14-2 (SC 13-10-5/TIA Log #1117) 1. Revise 445.20 to read as follows: 445.20 Ground-Fault Circuit Interrupter Protection for Receptacles on 15 kW or Smaller Portable Generators. All 125-volt, single-phase, 15-and 20-ampere receptacle outlets that are a part of a 15-kW or smaller portable generator either shall have ground-fault circuit-interrupter protection for personnel integral to the generator or receptacle or shall not be available for use when the 125/250-volt locking-type receptacle is in use. If the generator was manufactured or remanufactured prior to January 1, 2015, listed cord sets or devices incorporating listed ground-fault circuit-interrupter protection for personnel identified for portable use shall be permitted. If the generator does not have a 125/250-volt locking-type receptacle, this requirement shall not apply. Issue Date: October 22, 2013 Effective Date: November 11, 2013 TIAs Reference: Table 820.154(a) TIA 14-3 (SC 14-3-8/TIA Log #1120) Revise Table 820.154(a) as follows: (PRINT COPY FROM NFPA WEBSITE) TIAs Reference: 520.45 TIA 14-4 (SC 14-8-16 / TIA Log #1151) 1. Revise 520.45 to read as follows: 520.45 Receptacles. Receptacles for electrical equipment on stages shall be rated in amperes. Conductors supplying receptacles shall be in accordance with Articles 310 and 400. Section 406.15 shall not apply. TIAs Reference: 530.21(A) TIA 14-5 (SC 14-8-17 / TIA Log #1152) 1. Revise 530.21(A) to read as follows: 530.21 Plugs and Receptacles. (A) Rating. Plugs and receptacles, including cord connectors and flanged surface devices, shall be rated in amperes. The voltage rating of the plugs and receptacles shall be not less than the nominal circuit voltage. Plug and receptacle ampere ratings for ac circuits shall not be less than the feeder or branch-circuit overcurrent device ampere rating. Table 210.21(B)(2) shall not apply. Section 406.15 shall not apply. TIAs Reference: 590.6(A)(1) TIA 14-6 (SC 14-8-15 / TIA Log #1133) 1. Revise 590.6(A)(1) to read as follows: 590.6 Ground-Fault Protection for Personnel. (A) Receptacle Outlets. (1) Receptacle Outlets Not Part of Permanent Wiring. All 125-volt, single-phase, 15, 20-, and 30-ampere receptacle outlets that are not a part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. In addition to this required ground-fault circuit-interrupter protection, listed cord sets or devices incorporating listed ground-fault circuit-interrupter protection for personnel identified for portable use shall be permitted. TIAs Reference: 517.41(E) TIA 14-7 (SC 14-10-2 / TIA Log #1157) 1. Revise Article 517.41(E) to read as follows: (E) Receptacle Identification. The cover plates for the electrical receptacles or the electrical receptacles themselves supplied from the essential electrical system shall have a distinctive color or marking so as to be readily identifiable. [99:6.5.2.2.4.2] TIAs Reference: 625.17(B) TIA 14-8 (SC 15-4-5 / TIA Log #1162) 1. Revise Section 625.17(B) to read as follows: (B) Output Cable to the Electric Vehicle. The output cable to the electric vehicle shall be Type EV, EVJ, EVE, EVJE, EVT, or EVJT flexible cable as specified in Table 400.4. The output cable shall have an ampacity as specified in Table 400.5(A)(1) or, for 8 AWG and larger, in the 60°C columns of Table 400.5(A)(2). ERRATA Reference: Various Errata No.: 70-14-1 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. How to Use this Errata Sheet This is a list of errata to the first printing of the 2014 NEC®. 1. In Section 200.7, remove shading from the first line of the title. Add shading to “or Gray” in the second line. 2. In Table 220.3, on list item “Electric vehicle charging system branch-circuit and feeder calculations,” change the section reference to 625.41. 3. Revise the title of Table 220.44 as follows: “Table 220.44 Demand Factors for Non-Dwelling Receptacle Loads” ERRATA 4. In Section 400.4, insert as first sentence “Flexible cords and flexible cables shall conform to the description in Table 400.4.” 5. In heading above 400.30, Part II should be Part III. 6. In 422.51(A), delete “identified for portable use”. 7. Replace Section 490.48 with the following: 490.48. Substation Design, Documentation, and Required Diagram. (print from NFPA website) (A) Design and Documentation. Substations shall be designed by a qualified licensed professional engineer. Where components or the entirety of the substation are listed by a qualified electrical testing laboratory, documentation of internal design features subject to the listing investigation shall not be required. The design shall address but not be limited to the following topics and the documentation of this design shall be made available to the authority having jurisdiction. ERRATA (1) Clearances and exits (2) Electrical enclosures (3) Securing and support of electrical equipment (4) Fire protection (5) Safety ground connection provisions (6) Guarding live parts (7) Transformers and voltage regulation equipment (8) Conductor insulation, electrical and mechanical protection, isolation, and terminations (9) Application, arrangement, and disconnection of circuit breakers, switches, and fuses (10) Provisions for oil filled equipment (11) Switchgear (12) Surge arrestors ERRATA (B) Diagram. A permanent single-line diagram of the switchgear shall be provided in a readily visible location within the same room or enclosed area with the switchgear and this diagram shall clearly identify interlocks, isolation means, and all possible sources of voltage to the installation under normal or emergency conditions, and the marking on the switchgear shall cross-reference the diagram. Exception: Where the equipment consists solely of a single cubicle or metal enclosed unit substation containing only one set of high-voltage switching devices, diagrams shall not be required. 8. Section identifier at the top of page 390 should read “500.9”. 9. Change the references in 506.9(C)(2), Exception, from various sections in 506.9 (D) to 506.9(C) to read as follows: Exception: Associated apparatus NOT suitable for installation in a hazardous (classified) location shall be required to be marked only with 506.9(C)(2)(2), (3), and (5), but BOTH the symbol AEx in 506.9(C)(2)(2) and the symbol for the type of protection in 506.9(C)(2)(3) shall be enclosed within the same square brackets; for example, [AEx iaD] or [AEx ia] IIIC. ERRATA 10. Revise title of Article 516 to read as follows: Spray Application, Dipping, Coating, and Printing Processes Using Flammable or Combustible Materials 11. Replace Figure 516.3(D)(2) with the following: (PRINT FROM NFPA WEBSITE) 12. In Section 625.17(A)(1), change the cross-reference from 625.17(B)(1) to 625.17(B). 13. In Section 645.15, delete the second sentence, which reads: “Power systems derived within listed information technology equipment that supply information technology systems through receptacles or cable assemblies supplied as part of this equipment shall not be considered separately derived for the purpose of applying 250.30.” 14. Delete Section 690.7(F). 15. Change reference in last line of Section 690.56(A) to 690.31(G) 16. Delete Figure 700.2 and text reference in definition of Emergency Systems. 17. Delete Figure 701.2 and text reference in definition of Legally Required Standby Systems. 18. Delete Figure 702.2 and text reference in definition of Optional Standby Systems. 19. Delete Figure 708.2 and text reference in definition of Critical Operations Power Systems. 20. At top of page 664, upper left hand corner, change “(C)” to “705.12” ERRATA Reference: Various Errata No.: 70-14-2 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. 1. In 210.8, change the reference in the first sentence from “210.8(A) through (C)” to “210.8(A) through (D).” 2. In 225.36, Article 250, change the cross-reference to read “250.32(B) Exception No. 1.” 3. In 300.3(C)(2), change the cross-reference from “C(300.3)(2)(a) through (C)(2)(d)” to “300.3(C)(2)(a) through (C)(2)(d).” 4. In 230.62(B), change “110.27 (1)” to “110.27 (A)(1).” 5. In 250.102(C)(2), the Informational Note referencing Chapter 9 should appear at the end of Table 250.102(C)(1). 6. In 310.10(E), change the first word to “Nonshielded.” 7. Revise the first sentence in 314.15 to read as follows: “Boxes, conduit bodies, outlet box hoods, and fittings installed in wet locations shall be listed for use in wet locations.” 8. In 368.2, change “copper aluminum” to “copper or aluminum.” ERRATA 9. In 386.10(3), change the cross-reference from “645.29(1)” to “645.5(E)(2).” 10. In 392.80(A)(3)(2), delete the cross-reference to “392.22(D).” 11. In 404.3(A), Exception No. 2, change “110.27(1)” to “110.27(A)(1).” 12. In 409.3, delete the second “409.” 13. In the Title of Article 411, delete the hyphen between “Class” and “2.” 14. In 450.5, the cross-reference to “250.32(B) Exception” should read “250.32(B) Exception No. 1.” 15. In 480.9(C), change the cross-reference from “110.27” to “110.26.” 16. Revise 501.15(B)(2), Exception No. 2(1), as follows: (1) The unclassified location is outdoors, located or the unclassified location is indoors and the conduit system is entirely in one room. 17. In 501.130(B)(4,) Exception, change the cross-reference from “B(501.130)(1)” to “501.130(B)(1).” 18. In 502.140(A)(2), change the cross-reference from “A(502.10)(2)” to “502.10(A)(2).” ERRATA 19. In 505.9(D)(1), Exception No. 2, change “Class 1” to “Class I.” 20. In 506.6(A), change the cross-reference from “506.6(B)(1)” to “500.6(B)(1).” 21. In 506.6(B), change the cross-references from “506.6(B)(2) and 506.6(B)(3)” to “500.6(B)(2) and 500.6(B)(3).” 22. In 514.3(C)(2), change the cross-references from “Tables 514.3(B)(1)(1) and 514.3(B)(2)(2)” to “Table 514.3(B)(1) and Table 514.3(B)(2).” 23. In 514.3(D)(1), change the cross-reference from “Table 514.3(B)(1)(1)” to “Table 514.3(B)(1).” 24. In 516.3(C)(7), change the cross-reference from “Figure 516.3(D)(4)” to “Figure 516.3(D)(5).” 25. In 517.19(C)(2), shade the entire section and change the cross-reference to “517.19(C)(1).” 26. In 553.8(C), change the cross-references from “250.119(A)(2)(2) and (A)(2)(3)” to “250.119(A)(2)(b) and (A)(2)(c).” 27. In 620.21(A)(1)(c), Exception, change “A(620.21)(1)(c)(1)” to “620.21(A)(1)(c)(1).” 28. In 645.3(B), change the cross-reference from “820.113(C)(C)” to “820.113(C)” and delete shading of the “(C).” ERRATA 29. In 645.4, change the cross-reference from “Parts I and V of Article 725” to “Parts I and V of Article 770.” 30. In 646.19, change cross-references from “646.20(1) and (2)” to “646.19(1) and (2).” 31. Delete the Exception in 680.25(A)(1). 32. Revise 680.25(B) to read as follows: (B) Grounding. An equipment grounding conductor shall be installed with the feeder conductors between the grounding terminal of the pool equipment panelboard and the grounding terminal of the applicable service equipment or source of a separately derived system. For other than (1) existing feeders covered in 680.25(A), exception, or (2) feeders to separate buildings that do not utilize an insulated equipment grounding conductor in accordance with 680.25(B)(2), this equipment grounding conductor shall be insulated. 33. In Table 690.7, first column, change the fifth entry from “4” to “0.” 34. In 690.47(C)(2), change the cross-reference from “250.64(C)(C)(2)” to “250.64(C)(2).” 35. At the end of 694.18(C), after the label, add the following: “The warning sign(s) or label(s) shall comply with 110.21(B).” 36. In 725.179(D), Informational Note, delete the coding text before the word “Informational.” 37. In 725.179(F)(1), delete the cross-references to “725.154(D)(1) and (E).” 38. In 725.179(F)(2), delete the cross-references to “725.154(D)(1) and (E) and (F)(1).” ERRATA 39. In 770.100(A)(4), Exception, change the cross-reference from “B(770.100)(3)(2)” to “770.100(B)(3)(2).” 40. In 770.179(E)(2), change the cross-reference from “E(770.179)(1)” to “770.179(E)(1).” 41. In 770.179, delete the following: In addition, the overall covering of a field-assembled optical fiber cable shall have a surface marking indicating the specific optical fiber conductors with which it is listed and the optical fiber conductors shall have a permanent marking such as a marker tape indicating the overall covering with which they are listed. The overall covering of a field-assembled optical fiber cable shall meet the listing requirements for optical fiber raceways. 42. Replace 770.179(F) with the following: 770.179(F) Field-Assembled Optical Fiber Cables. Field-assembled optical fiber cable shall comply with 770.179(F)(1) through (4). (1) The specific combination of jacket and optical fibers intended to be installed as a fieldassembled optical fiber cable shall be listed in accordance with 770.179(A), (B), or (D) and shall be marked in accordance with Table 770.179. (2) The jacket of a field-assembled optical fiber cable shall have a surface marking indicating the specific optical fibers with which it is listed for use. ERRATA (3) The optical fibers shall have a permanent marking, such as a marker tape, indicating the jacket with which they are listed for use. (4) The jacket without fibers shall meet the listing requirements for communications raceways in 800.182(A), (B), or (C) in accordance with the cable marking. 43. In 800.44(B), Informational Note; 820.44(E)(3), Informational Note; 830.44, Informational Note before 830.44(A); and 840.44(B), Informational Note, change the title of the reference to “National Electrical Safety Code.” Issue Date: December 3, 2013 ERRATA Reference: Various Errata No.: 70-14-3 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. 1. 210.19(A), Informational Note No. 4. Change the reference in the last sentence to “Informational Note 2 of 215.2(A)(1)(b).” 2. Table 310.15(B)(3)(c). Revise second entry in the first column to read “Above roof 13 mm (1⁄2 in.)–90 mm (31⁄2 in.).” 3. 406.9(B)(1). Revise the first sentence by inserting “, 125 and 250 volts” after “amperes”. 4. 409.1, Informational note. Change the reference to read: ANSI/UL 508A. 5. 600.33(A). Revise first sentence to read “Listed Class 2 cable that complies with Table 725.154…” 6. 690.12(4). Change the reference to 690.56(C) 7. 690.15(D). Delete entire section. This is a duplicate of 690.13(D) 8. 725.154(A). Revise first sentence as follows: The substitutions for Class 2 and Class 3 cables listed in Table 725.154(A) and illustrated in Figure 725.154(A) shall be permitted. ERRATA 9. Add table as follows: Table 725.154(A) Cable Substitutions (PRINT FROM NFPA WEBSITE) 10. Table C.9(A) Change the third trade size from 1 3/4 to 3/4. Change the metric equivalent from (2) to (21). Issue Date: April 21, 2014 ERRATA Reference: 517.18(A), Exception No. 2 and 690.13(A) Exception Errata No.: 70-14-4 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. 1. 517.18(A), Exception No. 2. Change second cross reference from 517.18(B)(2) to 517.10(B(2). 2. 690.13(A), Exception. Change cross reference from 690.31(F) to 690.31(G). Issue Date: July 29, 2014 ERRATA Reference: 517.18(A), Exception No. 2 and 690.13(A) Exception Errata No.: 70-14-4 The National Electrical Code Correlating Committee notes the following errors in the 2014 edition of NFPA 70, National Electrical Code. 1. 517.18(A), Exception No. 2. Change second cross reference from 517.18(B)(2) to 517.10(B(2). 2. 690.13(A), Exception. Change cross reference from 690.31(F) to 690.31(G). Issue Date: July 29, 2014 PART TWO – SIGNIFICANT CHANGES OF THE NCEC 2014 THROUGH ARTICLE 285 CODE WIDE CHANGES were approximately 3,745 proposals and 1,625 public comments submitted for modifications to the 2014 edition of the NEC. There Field-Applied Hazard Markings. 110.21(B) was added to include specific requirements for warning labels and similar markings where required or specified elsewhere in the Code. Lockable Disconnecting Means. New 110.25 was added to deliver a “one-stop” location providing consistent requirements for a lockable disconnecting means. Requirements for dc Systems Integrated Throughout NEC. Direct current (dc) applications are experiencing a re-emergence because of such things as electric vehicle charging, solar photovoltaic (PV) systems, microgrids, wind-generated electric systems, etc. Barnes “Switchgear” Incorporated Throughout the NEC. The previous definition for “Metal-Enclosed Power Switchgear” was modified and retitled to simply “Switchgear” to make it inclusive of all types of switchgear under the purview of the NEC. Definitions Relocated to Article 100. Several existing definitions which appeared in the definitions of a particular article have been relocated to Article 100 as these terms are also found in other articles, not just the article where the previous definition was located. 600 Volts to 1000 Volts. Numerous changes throughout the NEC from the 600 volts threshold to 1000 volts. New Articles. Four new articles added to the 2014 NEC. CODE-WIDE CHANGES (CONT.) The 2014 code in 110.16 now refers us to 110.21 B for labeling and ANSI Z535.4 compliance is noted as a standard. This requires the extensive labeling we now have to be comparable to a uniform to a national standard. As with many issues previously the hope is now that all have a reliable standard. Some who skirted their responsibilities before now have a clear standard to follow. Kale indicates a hazardous situation which, if not avoided, will result in death or serious injury. DANGER indicates a hazardous situation which, if not avoided, could result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Per changes to 110.26 C 3 we now have the following. The ampere value related to provisions for “Personnel Doors” for “Entrance to and Egress from Working Space” was lowered to 800 amperes from 1200 amperes. The term “listed panic hardware” replaces the previous list of specific hardware provided at this requirement. Serious injury and fatalities have occurred involving electrical equipment rated at below 1200 amperes. This same panic hardware change occurred at 110.33(A)(3) for equipment with a voltage rating over 600 volts. Rains 200.4 B has been added. New provisions added requiring grouping the common neutral conductor for multiple circuits with its associated ungrounded conductors when contained in the same enclosure. New exceptions were also added to relax this grouping requirement where the grouping is obvious or where looped conductors or conductors simply pass through the enclosure. Neutral conductors are typically terminated on a common neutral terminal bar making tracing these neutral conductors more difficult than tracing the ungrounded conductors. West 200.6(A)(3) Means of Identifying Grounded Conductors has changed. Revision permits three continuous white “or gray” stripes along the grounded conductor’s entire length (on other than green insulation) for identification of sizes 6 AWG or smaller. Gray coloring for grounded conductors is frequently requested for 277/480 volt circuits. White “or gray” stripes will offer more choices to installers. Same change occurred at the following locations: 200.6(B)(3) 200.7(A)(2) 200.6(E) 200.7(C) 200.7 200.7(C)(1) 200.7(C)(2) Barnes 210.5(C)(2) Branch Circuits Supplied From Direct Current Systems New branch circuit identification requirements added for dc systems. For sizes 6 AWG and smaller, red for positive dc conductors and black for negative dc conductors. For branch circuits supplied from a dc system operating at more than 50 volts, each ungrounded conductor of 4 AWG or larger is to be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means. Direct current (dc) applications are experiencing a reemergence in the electrical industry because of such things as electric vehicle charging, solar photovoltaic (PV) systems, Kale microgrids, wind generated electric systems, etc. NEC 210.8(A)(7) GFCI: Dwelling Unit Sinks GFCI protection required for all 125-volt, single-phase, 15- and 20ampere receptacles installed within 1.8 m (6 ft) of all dwelling unit sinks (including kitchen sinks). Revision removes the term “located in areas other than kitchens.” Rule will now include the garbage disposal receptacle located in the cabinet under a kitchen sink, receptacle located behind a refrigerator, or a general lighting branch circuit living room receptacle located on the back side of a kitchen sink bar area if they are located within 1.8 m (6 ft) of the kitchen sink. NC 210.8(A) (7) Sinks — located in areas other than kitchens where receptacles are installed within 1.8 m (6 ft) of the outside edge of the sink. NEC 210.8(D) Dwelling Unit Kitchen Dishwasher Branch Circuit GFCI protection now required for all outlets that supply dishwashers installed in dwelling units. Includes both receptacle and hard-wired outlet for dishwasher. Modern-day electronically controlled dishwashers can experience “end of life” failures that can result in increased risk of electrical shock. GFCI protection for outlets supplying dishwashers can mitigate these increased risk of electrical shock. NC Item 6.4: Remove GFCI requirement for kitchen dishwasher branch circuit. This was not a requirement in the 2011 NEC. – No Cost Impact (NEW AMENDMENT) 210.8 (D) Kitchen Dishwasher Branch Circuit. GFCI protection shall be provided for outlets that supply dishwashers installed in dwelling unit locations. 210.8(A)(9) Dwelling Unit Bathtubs or Shower Stalls GFCI protection now required where receptacles are installed within 1.8 m (6 ft) of the outside edge of dwelling unit “Bathtubs or Shower Stalls.” Bathtubs or shower stalls are not always located in an area that meets the Article 100 definition of a “bathroom.” Bathroom is “an area including a basin with one or more of the following: a toilet, a urinal, a tub, a shower, a bidet, or similar plumbing fixtures.” Example: a room or area connected to a dwelling unit bedroom with a bathtub or shower stall as the only plumbing fixture in that particular room or area with a basin sink and toilet provided in another common area of the dwelling. West 210.8(A)(10) GFCI: Laundry Areas All dwelling unit “Laundry Areas” now require GFCI protection for 125-volt, single phase, 15-and 20-ampere receptacles (regardless of presence of a sink or distance from same). A laundry room sink is no longer the driving factor whether GFCI protection is required or not. GFCI protection in laundry areas addresses increased shock hazard risk and is consistent with other NEC requirements for GFCI protection of receptacles in areas in close proximity of water. Increased usage of GFCI protection for personnel at receptacles of residential homes is a highly effective means of further reducing the potential for electrical shock hazards. West 210.8(B)(8) GFCI: Garages, Service Bays, and Similar Areas GFCI protection required for all 125-volt, single-phase, 15- and 20ampere receptacles installed in all non-dwelling unit garages, service bays, and similar areas (other than vehicle exhibition halls and showrooms). The phrase, “where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used” was deleted. Many commercial garages have receptacles installed for purposes other-than the use of hand tools such as electric engine block heaters or battery charging equipment. Does not apply to such things as auto, power equipment (lawn mowers), or recreational vehicle dealership showrooms. Barnes NEC 210.12 AFCI Protection New provision added to require all AFCI devices required by 210.12 to be installed in a readily accessible location. Aligns with the “readily accessible” requirements for GFCI devices covered at 210.8. Primarily related to occupant or user accessibility to the monthly testing and reset features of AFCI devices. Will aid and facilitate the ability to reset the AFCI device in the event the AFCI detects an arcing event. NC Item 6.5: Retain location requirements from 2011 NEC for AFCI Protection and remove term “readily”. – No Cost Impact (NEW AMENDMENT) 210.12 Arc-Fault Circuit-Interrupter Protection. Arc-fault circuit-interrupter protection shall be provided as required in 210.12(A) (B), and (C). The arc-fault circuit interrupter shall be installed in an readily accessible location. (A) Dwelling Units. All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1) through (6): Kale 210.12(A)(1) – (6) AFCI Protection AFCI protection methods were expanded and language put into a list format. Provisions for outlet branch circuit (OBC) AFCI devices were expanded. The first two previous exceptions were revised to positive language and put into a list format of six provisions for providing AFCI protection. Rains 210.12(B) Ex. Branch Circuit Extensions or Modifications Dwelling Units Existing branch circuit conductors can be extended up to 1.8 m (6 ft.) without AFCI protection where no additional outlets or devices are installed for when modified or extended. Examples where situation does not require an AFCI device to be installed: Extending branch circuit conductors within an enclosure for the purposes of replacing a device or utilization equipment. Extending a branch circuit a short distance to a panelboard being replaced or upgraded. West 210.12(C) AFCI: DORMITORY UNITS All 120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets installed in dormitory unit bedrooms, living rooms, hallways, closets, and similar rooms are now required to be provided with AFCI protection. These confined living quarter conditions can lead to damage or misuse of the extension cords which in many cases are undersized for the applied load such as a microwave oven. Dorm occupants should be afforded the same level of AFCI protection provided to those who reside in a dwelling unit. Barnes 210.13 GFPE: BRANCH CIRCUITS GFP of equipment now required for branch circuit disconnects meeting provisions described at 230.95. New section requires each branch circuit disconnect rated 1000 amperes or more and installed on solidly grounded wye electrical systems of more than 150 volts to ground (but not exceeding 600 volts) to be provided with GFPE. New language for branch circuits was crafted after the existing language at 215.10 for feeders. Exceptions were also added for GFP provisions: creating additional or increased hazards already provided on the supply side of branch circuit Kale 210.17 ELECTRIC VEHICLE BRANCH CIRCUIT Outlet(s) installed for the purpose of charging electric vehicles required to be supplied by a separate branch circuit with no other outlets. Charging an electric vehicle (EV) with an existing 120 volt receptacle outlet will typically overload an existing general purpose branch circuit. It should be noted that this new requirement does not demand that an outlet(s) for the specific and sole purpose of charging EV equipment be installed. A new I-Note was also added giving guidance to 625.2 for the Rains definition of an “Electric Vehicle.” 210.52(E)(1) AND (E)(2) OUTDOOR OUTLETS The requirements for outdoor receptacles at dwellings have been revised to permit the required receptacle outlets to be “readily accessible from grade.” This provision was revised by removing the “while standing at grade level” requirement. This change will allow the deck or porch receptacle outlet to serve as one of the required outdoor receptacle outlets if it is “readily accessible from grade” with the deck or porch permitted to serve as “grade.” Same revision to individual units of multifamily dwellings (with individual exterior entrance/egress). West 210.52(E)(3) BALCONIES, DECKS AND PORCHES The requirement for a receptacle located at “Balconies, Decks, and Porches” has been revised to require the balcony, deck or porch to be attached to the dwelling. Requirements for the outdoor receptacle outlet to be installed “within the perimeter” of the balcony, deck or porch have been eliminated. “Detached” decks and such do not pose the same threat of extension cords being ran through windows and doorways as their “attached” counterparts. Barnes 210.52(G) BASEMENTS, GARAGES, AND ACCESSORY BUILDINGS “Basements, Garages, and Accessory Buildings” receptacle provisions revised into list format. 210.52(G)(1) Garages 210.52(G)(2) Accessory Buildings 201.52(G)(3) Basements Branch circuit supplying garage receptacle(s) to supply only the garage. Receptacle required for each car space in a garage. This is an effort to recognize the possibility of electric vehicle (EV) and plugin hybrid electric vehicle (PHEV) charging in these garages. Kale 210.64 ELECTRICAL SERVICE AREAS New provision requiring 125 volt, single-phase, 15-or 20-ampere receptacle outlet to be installed at “Electrical Service Areas.” At least one 125 volt, single-phase, 15-or 20-ampere receptacle outlet is now required to be installed within 15 m (50 ft) of all electrical service areas. Test equipment such as portable electrical data acquisition equipment is often needed for monitoring and servicing electrical equipment in service areas. Exception was added for one- and two-family dwelling services. Rains Table 220.3 Additional Load Calculation References New line item added to Table 220.3 for “Electric Vehicle Charging Equipment” and a reference to 625.14. This will help clarify the load calculation requirements for electric vehicle (EV) charging loads (considered as continuous). Electric vehicles and their charging stations are a growing trend in the electrical industry. This will give a direct and necessary link from Article 220 (calculations) to Article 625 for EV charging systems. West EATON CHARGERS 225.52(A) Disconnecting Means Location The requirements pertaining to the disconnecting means for services rated over 1000 volt have been incorporated into the requirements for the disconnecting means of outside branch circuits and feeders. 225.52(A) applies to the location of the disconnecting means for an outside branch circuit of feeder. Growing trend in the electrical industry to utilize more branch circuits and feeder rated over 1000 volts. Revision incorporates the same language at 230.205(C) dealing with a service disconnecting means ability to be electrically operated by a readily accessible, remote-control device. Barnes 230.30 Installation and Wiring Methods (Underground Service Conductors) 230.30 was divided into two subsections: (A) “Insulation” (B) “Wiring Methods” List of acceptable wiring methods for “Underground Service Conductors” was added. List includes all the cables and conductors that are identified in Chapter 3 as suitable for use as both service conductors and for direct burial. This section is referring to the conductors from the service point to the service disconnecting means, which is the definition of Kale “Service Conductors.” 230.44 Cable Trays Containing Service-Entrance Conductors Cable Trays containing service-entrance conductors required to include warning labels with these labels spaced at intervals not to exceed 3.0 m (10 ft.). This requirement is very similar to the requirement at 392.18(H) for warning label at cable trays containing conductors rated over 600 volts. Warning label spacing is reasonable as service-entrance conductors do not have overcurrent protection ahead of these conductors. This warning label spacing requirement will aid in the ability to trace the service-entrance conductors throughout the building. Rains 230.82(3) Equipment Connected to the Supply Side of Service Disconnect Provisions for a meter disconnect switch was revised by adding a label requirement to indicate: METER DISCONNECT - NOT SERVICE EQUIPMENT 230.82 lists several items that the Code permits to be installed ahead of or on the line side of a service disconnecting means. A meter disconnect switch is permitted ahead of the service disconnect but is not the service disconnecting means. Meter disconnect switches are often times confused with the service disconnecting means. The service disconnect marking is sometimes placed at the meter disconnecting switch in error. West 240.21(B)(1) Feeder Taps Not Over 3 m (10 ft.) Long Tap conductor ampacity for feeder taps [not over 3 m (10 ft.) long] required to be not less than the rating of the equipment containing an overcurrent device(s). “Equipment containing an overcurrent device(s)” replaces “device.” A new exception was also added for listed equipment, such as surge protective devices, power monitoring equipment and metering equipment, etc. allowed to be supplied with tap conductors without overcurrent protection. This same change also occurred at 240.21(C)(2) for transformer Barnes secondary conductors not over 3.0 m (10 ft.) long. 240.21(B)(1) Feeder Taps Not Over 3 m (10 ft.) Long Conductors are permitted to be tapped, without overcurrent protection at the tap, if the length of the tap conductors does not exceed 3 m (10 ft.) and the tap conductors comply with all the following: Ampacity cannot be less than the combined calculated loads on the circuits supplied by the tap conductors. Ampacity cannot be less than the rating of the equipment containing an overcurrent device(s) supplied by the tap conductors. Do not extend beyond the panelboard, etc. they supply. Generally, required to be enclosed in a raceway. If the tap conductors leave the enclosure in which the tap is made, the ampacity of the tap conductors cannot be less than one-tenth of the rating of the overcurrent device protecting the feeder conductors. Kale 240.87 Arc Energy Reduction Title was changed from “Non instantaneous Trip” to “Arc Energy Reduction” and section was revised for usability and formatted into subdivisions. Revision clarifies that this rule applies only to circuit breakers that are intentionally delayed under short-circuit conditions and that these circuit breakers do not have an instantaneous trip settings. No override setting higher than the potential arc current. A limitation to the size of breaker (1200 ampere) required to comply with this section was added. Two additional methods for reducing arc energy were added to the list of methods: Energy-reducing active arc-flash mitigation system. An approved equivalent means. Rains 250.21(C) Marking - Ungrounded Systems Ungrounded systems required to be legibly marked "Caution Ungrounded System Operating -____ Volts Between Conductors.“ Coincides with similar provisions at 408.3(F)(2) for a switchboard, switchgear, or panelboard. Marking requirements for ungrounded systems were added in two separate places in the 2011 NEC [250.21(C) and 408.3(F)(2)]. These two provisions for marking of ungrounded systems need to contain the same labeling requirements. West 250.64(D)(1) Common GEC: Multiple Disconnecting Means Revision was added to address busbar specifications and where buildings or structures are supplied by a feeder (not just services). Title of 250.64(D) was changed from “Services with Multiple Disconnecting Means Enclosures” to “Building or Structure with Multiple Disconnecting Means in Separate Enclosures.” Multiple disconnecting means can occur at a separate building or structure supplied by a feeder(s), not just at a building or structure supplied by a service. Text was also revised to include some specifications for a common GEC busbar for making the conductor taps [not less than 6 mm thick × 50 mm wide (¼ in. thick × 2 in. wide)]. Common GCE busbar must be “of sufficient length to accommodate the number of terminations necessary for the installation.” Barnes 250.68(C) Grounding Electrode Connections The title of 250.68(C) has been changed to “Grounding Electrode Connections.” Provisions for metal structure steel used to as a conductor to interconnect electrodes have been revised (prescriptive language has been removed). An above-grade structural metal frame of a building can serve as a conductor without having to be connected directly to a grounding electrode or qualify as a grounding electrode as previously required. Structural metal frame of a building should be treated the same as metallic water piping without having to meet qualifying conditions of a grounding electrode. Interior metal water piping and the metal structural frame of a building are permitted as a means of interconnecting electrodes that are part of the grounding electrode system. Kale Table 250.102(C) Sizing Grounded Conductors, Main Bonding Jumpers, Etc. New Table 250.102(C) added for sizing grounded conductors, main bonding jumpers, system-bonding jumpers, and supplyside bonding jumpers (rather than Table 250.66). References to this new table were revised throughout Article 250. Table 250.66 is titled for GECs with a max. required conductor of 3/0 copper or 250 kcmil aluminum. Table 250.122 will continue to be used for sizing fault-return carrying conductors, such as equipment grounding conductors, if the supply conductors have overcurrent protection on the Rains supply side. 250.130(C) Nongrounding Receptacle Replacement or Branch Circuit Extensions Connection to an equipment grounding conductor that is part of another branch circuit that originates from the enclosure where the branch circuit for the receptacle or branch circuit originates is permitted for replacement of non-grounding-type receptacles with grounding-type receptacles and for branch-circuit extensions. This is simply an extension of the present list item (3) that allows connecting to the equipment grounding terminal bar in the related panelboard. Allowing a connection back to the same enclosure or panelboard that serves the receptacle branch circuit will typically provide a shorter, more effective equipment grounding or ground-fault return path. West 250.166 Size of Direct-Current Grounding Electrode Conductor A maximum size requirement of 3/0 copper or 250 kcmil aluminum for grounding electrode conductor of dc systems was added at 250.166. This correlates with the maximum size requirements for ac system grounding electrode conductor as specified at 250.66 and Table 250.66. No maximum size was provided at 250.166 except for grounding electrode conductors that are the sole connection to grounding electrodes. This new provision is intended to provide practical sizing requirements for larger dc systems with large neutral conductors as is the case with an ac system. Barnes 250.167 Direct-Current Ground-Fault Detection New section added for “Direct-Current Ground-Fault Detection” requiring ground-fault detection on dc ungrounded systems. New requirements address grounded systems, ungrounded systems, and marking rules for each. These new provisions require ground-fault detection for ungrounded dc systems and permits ground-fault detection for grounded dc systems. New marking requirements call for system to be legibly marked to indicate the type of grounding provisions provided at the dc Kale source or the first disconnecting means of the dc system. Digital Ground Fault Monitor/ Ground Detector for Ungrounded AC/DC Systems Courtesy of Bender Inc. Digital Ground Fault Monitor/ Ground Relay for Grounded AC/DC Systems 250.186 Ground-Fault Circuit Conductor Brought to Service Equipment New 250.186 to require services (over 1000 volts) to have a grounded conductor to be brought to the service for a grounded system. Ungrounded systems (over 1000 volts) will require a supply-side bonding jumper brought to the service. Same requirements as 250.24(C) for services 1000 volts or below. Primary concern is to provide a very low impedance ground-fault return path from any point on the wiring system where a ground fault may occur to the electrical supply source. West 250.194 Grounding and Bonding of Fences and Other Metal Structures New section added for bonding and grounding metal fences and other metal structures around substations. These fences are accessible to the general public and must be grounded to limit the rise of hazardous voltage potential on the fence to the surrounding earth. For situations where step and touch voltage potential considerations indicate additional grounding and bonding design is necessary, alternate designs performed under engineering Barnes supervision is permitted. 285.13 Type 4 and Other Component Type Surge Protective Devices Type 4 component assemblies and Type 5 SPDs are incomplete devices that are only acceptable when provided as part of listed equipment. This section provides clarity that component SPD(s) are not to be installed in the field. PART THREE – SIGNIFICANT CHANGES OF THE NCEC 2014 CHAPTER THREE 300.22(C)(1) Wiring Methods for Environmental Air Spaces (Plenums) Cable ties used to secure cables in plenums must be listed as having fire resistant and low smoke producing characteristics. A new informational note was also added that will provide pertinent information related to low smoke and heat release properties for nonmetallic cable ties. Plenum grade nonmetallic cable ties are readily available in the marketplace today that can achieve compliance with this new provision. Kale 300.38 Raceways in Wet Locations Above grade Interior of raceways installed in wet locations above grade are now considered to be a wet location for installations of over 1000 volts, nominal. This will bring aboveground installation requirements for over 1000 volts consistent with the requirements in 300.9 for 1000 volts and under. The mere existence of condensation alone should render the interior of these raceways a wet location when these raceways are installed in wet locations, above grade or below, regardless of the voltage involved. Enclosures and raceways installed in wet location installations must have conductors and cables installed that are listed and identified for wet locations. Table 310.15(B)(3)(a) More Than Three Current-Carrying Conductors Title of 310.15(B)(3)(a) and corresponding table was changed to “More Than Three Current-Carrying Conductors in a Raceway or Cable.” Note to Table 310.15(B)(3)(a) was revised to make it clear that table applies to spare conductors but does not apply to conductors that cannot be simultaneously energized. Ampacity adjustment correction factor is required for three or more current carrying conductors that are installed or bundled together without maintaining spacing as well as those in a Rains raceway or cable. 310.15(B)(3)(C) RACEWAYS AND CABLES EXPOSED TO SUNLIGHT ON ROOFTOPS The title and parent text at 310.15(B)(3)(c) has been revised for clarity from “Circular Raceways Exposed to Sunlight on Rooftops” to “Raceways and Cables Exposed to Sunlight on Rooftops.” Provisions for cables installed on or above rooftops have been added as well [previous language indicated that the cable(s) had to be installed in a raceway]. new exception was also added allowing Type XHHW-2 conductors (thermoset insulated conductor) to be installed in raceways or cables on rooftops without having to apply an ambient temperature adjustment correction factor for these conductors. West A 314.15 Damp or Wet Locations All “outlet box hood” covers are required to be listed for use in a wet location, not just “extra duty” outlet box hood covers installed in a wet locations. The term “outlet box hoods” was added at this section, making boxes, conduit bodies, outlet box hoods, and fittings installed in wet locations to now be required to be listed for use in wet locations. Previous language at 406.9(B)(1) required “extra duty” outlet box hoods installed in a wet location to be listed for use in a wet location. 314.15 only required boxes, conduit bodies, and fittings installed in wet locations to be listed for use in wet locations. Barnes 314.15 Damp or Wet Locations Approved drainage openings permitted to be installed in the field in boxes or conduit bodies listed for use in damp or wet locations in accordance with manufacturer’s instructions. These weep holes cannot be larger than 6 mm (1/4 in.). Weep holes in the bottom of boxes installed in wet locations improves the safety and durability of electrical installations. Without these weep holes, the inside of cast aluminum boxes and other metallic enclosures can degrade over time due to moisture condensation. Kale 314.25 Covers and Canopies Drywall screws are not permitted to be used to attach box covers or other equipment fastened to a box. Screws used for this purpose are now required to be either machine screws matching the thread gauge or of a size that is integral to the box (in accordance with the manufacturer’s instructions). The use of drywall screws is unacceptable and can result in damage to the box and inadequate support of the attached luminaire or equipment itself. Similar provisions have been introduced at 404.10(B) for mounting of switches and 406.5 for mounting of receptacles. Rains 314.27(A)(1) Vertical Surface Luminaire Outlets The title was changed from “Wall Outlets” to “Vertical Surface Outlets” as not all vertical surfaces where luminaire or lampholders are mounted are necessarily in or on a “wall.” New language was also added to reflect that luminaires or lampholders can be mounted “on” a vertical service as well as “in” a vertical service. The previous language only addressed boxes mounted “in a wall.” An example of a “vertical” surface-mounted luminaire would be a luminaire mounted on the side of a square post in the middle of a large room or area. 314.27(A)(2) Boxes at Ceiling-Mounted Luminaire Outlets Outlet boxes used to support ceiling-mounted luminaires that weigh more than 23 kg (50 lb.) are now required to be marked with the maximum weight the box will support on the “interior of the box.” Allows the installer and the electrical inspector an opportunity to review this information at the time of installation without having to climb into the attic to retrieve this information. In some cases, the exterior of the outlet box is not accessible after a certain point in the building construction process. Ceiling-mounted outlet box supporting a luminaire weighing more than 23 kg (50 lb.) is required to be listed and marked for the maximum weight that particular outlet box is designed to support. 324.41 FLOOR COVERINGS (FLAT CONDUCTOR CABLE) The maximum size modular carpet square permitted to be cover floor-mounted flat conductor cable (Type FCC cable) has been increased from 914 mm (36 in.) square to 1.0 m (39.37 in.) square. This will allow the use of standard-sized modular carpet products sized based on the International System of Units (SI units) of measure. This revision will not disqualify the use of the readily available smaller 914 mm (36 in.) carpet squares [based on the (US) Customary Units of measurement (foot, pound, inches, etc.)]. A flat conductor cable system is designed to provide a completely accessible, flexible wiring system for installation West under carpet squares. 330.30(B) Securing (Type MC Cable) Type MC cable is now permitted to be secured in intervals not exceeding 3 m (10 ft.) for vertical installations when listed and identified for such use and containing ungrounded conductors 250 kcmil and larger. Type MC cables are generally required to be secured at intervals not exceeding 1.8 m (6 ft.). Type MC cable with integral conductor supports offers the installer an alternative and productive method for commercial vertical installs in high-rise buildings. Barnes 330.30(D)(3) Unsupported Type MC Cable MC cable permitted to be unsupported where the cable is made of the interlocked armor type in lengths not exceeding 900 mm (3 ft.) from the last point of support. Type This would apply where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation. This new allowance brings Type MC cable in line with other similar flexibility provisions for other wiring methods such as Type AC cable, flexible metal conduit (Type FMC), liquidtight flexible metal conduit (Type LFMC), and liquidtight flexible nonmetallic conduit Barnes (Type LFNC). 334.40(B) Devices of Insulating Material (Type NM Cable) Nonmetallic-sheathed cable interconnectors have been recognized to be used without a box and concealed where used for “repair wiring” rather than “rewiring” in existing buildings. Listed “nonmetallic sheathed cable interconnector devices” replaces the term “tap devices” to zero in on the specific type of device permitted in this application. When using Type NM cable, 300.15 generally requires a box to be installed at each conductor splice point, outlet point, switch point, junction point, termination point, or pull point. Type NM cable interconnectors are insulating enclosures which when connected to Type NM cable form both a mechanical Kale and electrical connection. 334.40(B) DEVICES OF INSULATING MATERIAL (TYPE NM CABLE) (CONT.) Further revision made a clear distinction between “rewiring” and “repair wiring” in existing buildings. Rewire is typically defined as replacing existing wiring with new wiring. If an electrician has the accessibility and availability to replace existing wiring with new wiring, there would be no need for a device such as a nonmetallic-sheathed cable interconnector. “Repair wiring” seems to be justified for the application of a nonmetallic-sheathed cable interconnector. An example of an area where these concealed nonmetallic sheathed cable interconnectors might be used would be in flooded areas. 356.12 Uses Not Permitted - LFNC Previous List Item (4) for “Uses Not Permitted” for liquidtight flexible nonmetallic conduit (LFNC) has been deleted. This will allow LFNC as an acceptable wiring method for applications where the voltage involved is greater than 600 volts. UL Certification Guide Information (White Book), DXOQ, does not limit LFNC to 600 volts. LFNC is an acceptable wiring method for signs with voltage ratings over 600 volts [see 600.32(A)]. Permitted as a wiring method enclosing leads to a motor from a separated junction box for all voltage applications [see Rains 430.245(B)]. Liquidtight flexible nonmetallic conduit (LFNC) 376.22 Number of Conductors and Ampacity (Metal Wireways) Ampacity adjustment factors for more than three currentcarrying conductors in a raceway shall only apply to metal wireways where the number of current-carrying conductors exceeds 30 at any cross section of the wireway. Does not apply to simply 30 or more current-carrying conductors total in the wireway. It was never intended for the adjustment factors of 310.15(B)(3)(a) to apply once there were more than 30 conductors total in the wireway as opposed to at a cross sectional area. West 376.56(B)(1) and (B)(5) Power Distribution Blocks (Wireways) Power distribution blocks (PDB) installed in wireways ahead of the service main (line side) must be "listed for the purpose.“ PDBs are generally listed for and required to be used only on the load side of service equipment. Conductors in wireways required to be arranged so that power distribution block terminals are unobstructed after their installation. This new PDB unobstruction provision will bring consistency with the provisions for PDBs installed in pull or junction boxes. Barnes 392.18(H) Ex. Cable Tray Marking Marking requirement for cable trays containing conductors rated over 600 volts has been relaxed for industrial establishments with maintenance, supervision, and qualified persons servicing the installation. Main requirement is for a cable tray contains conductor rated over 600 volts to have permanent and legible warning labels located in a readily visible location at least every 3 m (10 ft.). The existence of trained, qualified persons at supervised industrial establishments, makes it not always necessary to provide warning labels at cable trays containing conductors rated over 600 volts. Some of these industrial cable tray installations may be at elevated locations where the warning labels cannot even be seen from the floor. Kale Article 393 Low Voltage Suspended Ceiling Power Distribution Systems A new article was added to address low-voltage Class 2 ac and dc volt supplied equipment (lighting and power) connected to ceiling grids, floors and walls built for this purpose. New article addresses equipment with similar features to track lighting but includes the wiring and power supply requirements. New article provides specific requirements for safe installations of low voltage, power limited power distribution, for power to lighting and nonlighting loads. The growing interest in alternative energy sources (e.g. PV, wind turbines, batteries, fuel cells, etc.) and the increase of low voltage, low power devices (sensors, LV lighting, IT equipment, AV equipment, etc.), has created a significant need this new article. Rains 399.2 DEFINITIONS: OUTDOOR OVERHEAD CONDUCTORS Outdoor Overhead Conductors - Single conductors, insulated, covered, or bare, installed outdoors on support structures in free air. Definition of “Outdoor Overhead Conductors” was revised to include the term “in free air” to ensure that the definition clearly indicated that wiring installed under the scope of Article 399 is not installed in raceways, etc. This revised definition should clarify the conductors that Article 399 represent as being the conductors outside (in free air) used for transmission and distribution of electrical power to utilization equipment that transition from traditional indoor wiring methods such as wireways, raceways, busway conduit systems, etc. West Thank you for your partnership to build a safe and thriving community! Gary Mullis, Electrical Code Administrator Mecklenburg County Code Enforcement 2145 Suttle Ave., Charlotte, NC 28208 980-314-3098 gary.mullis@mecklenburgcountync.gov