Commercial Consistency Land Use and Environmental Service Agency (Code Enforcement) January Q&A 2011 General: 1. (Q) Can egress doors in section 1008.1.3.4 be connected to a back up electrical supply? (A) No, the door locks should release on the failure of the primary electrical power to the building. 2. (Q) What does the 6’ height apply to in section 603 item 8? (A) Per an interpretation from DOI the 6’ only applies to the wood panels and similar light frame construction? 3. (Q) In B type units can the exception # 10 in the 2009 ANSI 117.1 section 1004.9 be used for counter heights? (A) Yes, the ANSI 117.1 2009 has been adopted by the NC Building Code Council to be effective Sept. 1st 2011, so it can be used at this time as an alternate method. Commercial Consistency Land Use and Environmental Service Agency (Code Enforcement) March Q&A 2011 General: 1. (Q) How are crematoriums to be treated under the Building Code? (A) Crematoriums are the same as incinerators and must meet secton 508.2 for incidental use. 2. (Q) Under section 1210 can vinyl wallpaper be used in restrooms. (A) Yes, provided that there are no joints within 24” of any fixture and the manufacture provides data that it meets the requirements non absorbent an it is installed over moisture resistant gyp board. 3. (Q) If a building is constructed per section 509.2 can the additional story and building height allowed in section 504.2 be taken? (A) Yes, section 509.2 refers you to section 503 and no longer to table 503. 4. (Q) Can a dutch door be used as an exit access door from a room or space? (A) Yes provided that the top and bottom latch together when in the closed position and open as a single unit from the closed position. 5. (Q) Are elevators required in a charter school 2 or more stories if it is publicly funded? (A) Yes 6. (Q) Can the field inspector require exit signs to be added or move even if they are already shown on the drawings. (A) Yes, conditions in the field my dictate additional signs or new locations not shown on the approve drawings. Commercial Consistency Land Use and Environmental Service Agency (Code Enforcement) February Q&A 2011 General: 1. (Q) With reinforced masonry walls are inspections required while they are under construction? (A) Yes, the inspector should make periodic inspections while the walls are under construction especially when there are no special inspections. Set the parameters with the contractor at the start of the job. 2. (Q) What happens toa TCO when the tenant moves out of a space or building? (A) The TCO is no longer valid and a new one must be obtained for the next tenant which may also require a ne permit. 3. (Q) Can the Building Inspector make a final inspection and accept a certification letter on the fire alarm before the Fire Inspector has made his inspection? (A) Yes. Building Consistency Meeting Residential Date02/09/2011 Recorder and minutes prepared by: Danny Wooten/Lon McSwain Staff present: On File Public present: Wayne Carter (J&B Development); Terry Cleary (Meeting Street Homes); Darrin Price; Greg Seaton (Seaton Builders); Charlie Carter (Remmington Homes); David Reynolds (BFS); Bob McKee (Ryan Homes); Allan McGee (McGee Brick); David Kost (True Homes); John Meeks(Appleblossom Energy); Topics/Subject Decisions/Conclusions/Actions Old Business None New Business No roof load is allowed on a cantilevered girder in deck construction. Girders can be set on a notched post in the following conditions. Minimum post size 6”X 6”. If both members of the girder rest on the notched post then 1 ½” of the post must be maintained to bolt through. If only one member rest on the notched post then 3 1/2” of the post must be maintained to bolt through. Can Lights in a Garage Sheathing Inspections. Sealed Crawl Bathroom Ventilation Section 316.4 Foam Insulation Stucco & Reroof Sill Plate Deck Footings Can Lights installed in the ceiling of a garage must be IC rated. Sheathing inspection is for sheathing only, not the roof. House should be dryed in. Plans are only required on the site if the house is brick veneer for bolt on lintels. A sealed crawl is not a conditioned crawl. The liner is lapped and runs up the wall with a 3’ gap at the top for termite inspection. There is a conflict between the Building Code and the Mechanical Code. Table 403.3 of the Mechanical requires the bathroom to be mechanically ventilated. Window will not meet the requirement. There are new ICC compliance reports for foam insulation. They must be supplied and followed for foam insulation installations. See attached reports. When a stucco house is re-roof a new certification letter for the stucco should be obtained. The required distance between the new roof and the bottom of the stucco needs to be maintained. 5/4 board is not acceptable to use as a sill plate, it is only 1” thick and does not provide the nailing depth as a 2X . Deck blocks are acceptable for deck footings for limited tributary area. 12X12 footing min 4” concrete. Bottom 12” below grade. Approved By ___Lon Mcswain_________ Date _______02/25/2011_______________ Building Consistency Meeting Residential Date01/05/2011 Recorder and minutes prepared by: Danny Wooten/Lon McSwain Staff present: On File Public present: Mike Kissel, Jack Glunt, Darrell Fribs, (Standard Pacific Homes); Wayne Carter (J&B Development); Terry Cleary (Meeting Street Homes); Charles Sofinowski (M/I Homes); Matthew Klaphcke (L & M Homes);Daniel Blackwelder (Barefoot & Company);A. Wynn Yates( Yates/Stranes Engineering); Jason Whitner(Southern Traditional Homes);Bob McKee (Ryan Homes); Allan McGee, Doc McGee (McGee Brick); Rob Merrill (Griffin Masonry);John Meeks(Appleblossom Energy); Topics/Subject Decisions/Conclusions/Actions Old Business Soil Reports Footing inspections that fail due to “need subgrade verification form” will have to produce that form at the next requested inspection. If the next inspection is a poured concrete wall or slab (concrete work) and the letter is not available this inspection will be failed as “previous list not complete” but inspection will be performed. If the only reason to fail that slab or foundation wall is because footers (subgrade form) have not passed then inspectors will note “pending footer/subgrade letter only, pour at own risk”. This failure will count against the GC or permit holder and will affect their defect rate. New Business Code Changes Effective 01/01/2011 See attached for new Code requirements effective Jan. 1, 2011 R602.6 Load bearing studs cannot be notched in the top or bottom 6” nor can they be drilled within 6” of another hole or notch. Putting another stud adjacent and attached in an “L” formation to the notched or drilled stud would be an acceptable fix. Mechanical rooms that are supplied with outside air must be insulated so that they are outside the buildings thermal envelope. Make sure that if they are located above conditioned space that the floor/ceiling space below is insulated also. Doors that swing out (other than an exterior storm or screen) cannot swing over steps or stairs, there must be a landing provided. The 2012 Residential code passed with the option of sprinklers in townhouses to reduce the 2 hr. wall to 1 hr. Chapter 11 passed with a total reduction of energy use of 15% not the 30% as submitted. Trade offs for the energy requirements will be heard at the March meeting. See attached guide for cold weather protection. Chapter 11 Section R311.4.3 December NCBCC Meeting. Cold Weather Concrete. Approved By ___Lon Mcswain_________ Date _______01/28/2011_______________ Residential code Changes effective Jan 1st, 2011 Building Consistency Meeting Residential Date03/02 /2011 Recorder and minutes prepared by: Danny Wooten/Lon McSwain Staff present: On File Public present: Wayne Carter (J&B Development);Charlie Sofinowski (M/I Homes);Bill Green (Barefoot & Co);Toby Brundage, Joe Stewart (Builders 1st Source); Bob McKee (Ryan Homes);Doc McGee, Allan McGee (McGee Brick);Matthew Klapheke (L&M Construction); David Schwieman(DR Schwieman, Inc); Darren Price;Daniel McBride (Cunnane Group);Dave Reynolds (BSF);Jason Whitener (Southern Tradition Homes);Bob McKee (Ryan Homes); Topics/Subject Decisions/Conclusions/Actions Old Business None New Business Section R408.1.2 Foundation vent wells are required when the bottom of the vent is located less than 4” above finish exterior grade. Vent wells would not be required if the grade under the vent is concrete and is sloped so that water will not run into the vent. Mud mats Mud mats cannot be poured until the an inspection has been made on the sub grade. Senate Bill 22 has passed the Senate And the House. Once it is signed by the Governor it becomes law. This law may prevent the adoption of the 2012 Residential Code, the 2012 Energy Code and the 2012 Electrical Code. Foundations cannot be backfilled until a foundation inspection has been made. Carbon Monoxide detectors are required to be installed in all new residential construction, in existing dwellings where interior alterations, repairs fuel-fired appliance replacement or additions requiring a permit occurs, or where one or more sleeping rooms are added or created. Effective January 1, 2011 Senate Bill 22 Foundations Carbon Monoxide Detectors Approved By ___Lon Mcswain_________ Date _______03/31/2011_______________ MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection at the generator, and it’s feeding a trough. Off this trough I am feeding two 200 Amp disconnecting means. 1) How do is size the conductors to the trough? 2) How do I size the conductors to my disconnects? See 445.13 and 19. 445.19 (2) first of all allows a generator to feed individual enclosures tapped from a single feeder for load separation and distribution. 1) 445.13 says if those feeder conductors to the trough don’t have overcurrent protection ahead of them, they shall be sized to carry 115% of the generator nameplate current rating. 2) We would then size the conductors to the disconnects per the appropriate tap rule found in 240.21 and load calculations per article 220. 2. Is a disconnect required within sight of a range hood controller? Yes – No - Maybe. 422.31 & 422.32 Exception & 422.34 (D). If the motor is 1/8 hp or less and 300 VA or less; the answer is no. (422.31(A)) If the motor is over 1/8 hp and there is no unit switch, then yes, there must be a disconnect within sight of the controller. (422.32) If the motor is over 1/8 hp and there is a unit switch, then the disconnect is permitted to be out of sight from the controller. (422.31(B) & 422.34(A-D)) NOTE: A unit switch(es) with a marked-off position that is a part of an appliance and disconnects all ungrounded conductors shall be permitted as the disconnecting means required by this article where other means for disconnection are provided in occupancies specified in 422.34(A) through (D). PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 2 of 6 3. I have a lug that is attached to the meter can (not to the neutral bar which is also attached to the can). Am I allowed to attach the grounding electrode conductor to this lug. (see attached picture) No. 200.2(B) states “The continuity of a grounded conductor shall not depend on a connection to a metallic enclosure, raceway, or cable armor.” 4. In a 120/240-volt 3-phase, 4 wire, delta-connected panelboard, are straight voltage rated 2-pole breakers (240-volts) required only when one pole is connected to the high leg (“B” phase); and are slash-rated 2-pole breakers (120/240-volts) permitted where connected to the “A” & “C” phases? See 240.85 that states, “A circuit breaker with a straight voltage rating, such as 240V or 480V, shall be permitted to be applied in a circuit in which the nominal voltage between any two conductors does not exceed the circuit breaker’s voltage rating. A circuit breaker with a slash rating, such as 120/240V shall be permitted to be applied in a solidly grounded circuit where the nominal voltage of any conductor to ground does not exceed the lower of the two values of the circuit breaker’s voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit breaker’s voltage rating. Therefore, a 240-volt circuit breaker can be connected between any two phases of a 120/240-volt, 3-phase panelboard supplied by a 120/240-volt delta 3-phase system. A 120/240-volt rated circuit breaker may service 120-volt line-to-ground circuits and/or 240-volt line-to-line circuits. A slash rated 120/240-volt circuit breaker may not be applied on a 208-volt line-to-ground circuit. There is no NEC prohibition in connecting a 2-pole, 120/240-volt rated circuit breaker between A and B or between B and C phases where the nominal voltage of any conductor to ground does not exceed the lower of the two values of the circuit breaker’s voltage rating and the nominal voltage between any two conductors does not exceed the higher value of the circuit breaker’s voltage rating. The UL panelboard marking guide states, “Some circuit breakers, like single-pole breakers for use with handle ties rated 120/240 colts, should not be connected to the phase that is 20-volts to ground. Also the UL panelboard marking guide goes on to state, “Generally, the B-phase is used only in conjunction with either the A- or Cphase for a 240 single-phase branch circuit or with both the A- and C-phase for a three-phase branch circuit. Circuit breakers or cartridge fuses rated for straight 240 volt systems are suitable for this use.” PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 3 of 6 5. Is a bonding jumper required around a water meter when the grounding electrode conductor is connected to the street side of the water meter? Maybe, see 250.53(D)(1) that states, “Continuity of the grounding path or the bonding connection to interior piping shall not rely on water meters or filtering devices and similar equipment.” If the street side of the meter has a metal water pipe that is in direct contact with the earth for 3.0 m (10 ft) or more and the grounding electrode conductor is connected to that pipe on the street side of a water meter, then that pipe is adequate as a metal underground water pipe electrode per 250.52(A)(1). However, the interior portion of the metallic water piping system on the house side of the water meter cannot benefit from that sole connection on the street side of the water meter, therefore either a bonding jumper needs to be installed around the water meter to provide continuity of the metal water piping system or a separate bonding conductor per 250.104(A) will be required to be installed to the interior water piping system that is on the house side of the water meter. See 250.104(A)(1) that states, “Metal water piping system(s) installed in or attached to a building or structure shall be bonded to the service equipment enclosure, the grounded conductor at the service, the grounding electrode conductor where of sufficient size, or to the one or more grounding electrodes used. The bonding jumper(s) shall be sized in accordance with Table 250.66 except as permitted in 250.104(A)(2) and (A)(3).” 6. Is the 10 AWG DC grounded conductor of a PV system required to have a white outer finish or can it being re-indentified? In accordance with 200.6(A), grounded conductors that are smaller than 6 AWG and used in PV source circuits are permitted to be marked at the time of installation with a white marking at all terminations. Also see 200.6(A)(2) that states “A single-conductor, sunlight-resistant, outdoor-rated cable used as a grounded conductor in photovoltaic power systems as permitted by 690.31 shall be identified at the time of installation by distinctive white marking at all terminations. See also 200.6(B) and 690.13. PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 4 of 6 7. I have a 5000 amp feeder with 12 parallel runs of 600 kcmil THHN copper ungrounded conductors installed in 12- 4" PVC conduits. What is the minimum size copper equipment grounding conductor required in each conduit? 600 kcmil or 700 kcmil? For a 5000 ampere overcurrent device Table 250.122 shows a 700 kcmil. While this might seem to qualify for the allowance in 250.122(A) where the EGC is not required to be larger than the phase conductor, it does not apply to these conductors that are in parallel. This EGC sizing requirement is in place because the majority of the ground fault current could be supplied by all the phase conductors but be returned to ground by only one EGC. 8. Can you explain why the DC conductors for PV systems are sized by multiplying 125% twice? Section 690.8(A) requires the photovoltaic source circuit maximum current to be the sum of parallel module rated short circuit currents multiplied by 125% (these are maximum short circuit currents). Section 690.8(B)(1) requires the dc circuit conductors and any overcurrent protective devices to be sized to carry the maximum short circuit currents figured at 125% in 690.8(A) plus an additional 125% for continuous use or a total of 156%. This 156% will ensure the conductors are large enough to handle both normal current plus the additional fault current at the point of fault from both the array at the fault site and any that are in parallel with the array. 690.8(B)(2) Overcurrent protection for photovoltaic output circuits with devices that will internally limit the amount of current from the photovoltaic output circuits (for example, where fuses are built into the system) are permitted to be rated less than 156%. These overcurrent protective devices can be rated at least at 125% of the limited current value. The conductors must still be rated at 156%. 690. 8(D) Where a single overcurrent device is used to protect a set of two or more parallel connected module circuits, the ampacity of each of the module interconnection conductors shall not be less than the sum of the rating of the single fuse plus 125% of the short-circuit current from the other parallel connected modules. PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 5 of 6 9. Is a disconnect mandatory both inside and outside for a mini-split system? Yes-No-Maybe . 424.19 There are so many different makers and combinations of make-ups of these systems that no one answer will cover them all. You will have to look at the installation instructions first and then apply the proper Code section. It should be noted, however, that in some cases it is allowable for the breaker in the panel to serve as the disconnect for these units per 424.19. 10. There is a GFCI protected 125 volt 15 amp receptacle outlet installed on the front porch of a single dwelling. I have to step up onto the porch slab 4 inches from grade to access the receptacle. Can this receptacle be recognized as the required outside receptacle on the front of the dwelling unit? As the question is written, no. See 210.52(E) that states “For a one-family dwelling and each unit of a two-family dwelling that is at grade level, at least one receptacle outlet accessible while standing at grade level and located not more than 2.0 m (6½ ft) above grade shall be installed at the front and back of the dwelling.” NEC 210.52(E)(3) requires a receptacle outlet within the parameter of the porch . A receptacle can be located to meet both of these requirements. 11. For a 240V to 208Y/120V transformer, is it better to bond the neutral to the metal frame at the transformer itself, at the panel, or at both locations? Better to bond at the source. There are three exceptions and one may bond the neutral at either point as long as the neutral does not carry parallel current. See 250.30(A)(1) that states “This connection shall be made at any single point on the separately derived system from the source to the first system disconnecting means or overcurrent device, or it shall be made at the source of a separately derived system that has no disconnecting means or overcurrent devices.” Also see Exception No. 2 that states “A system bonding jumper at both the source and the first disconnecting means shall be permitted where doing so does not establish a parallel path for the grounded conductor. Where a grounded conductor is used in this manner, it shall not be smaller than the size specified for the system bonding jumper but shall not be required to be larger than the ungrounded conductor(s). For the purposes of this exception, connection through the earth shall not be considered as providing a parallel path.” PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 6 of 6 12. I was recently turned down by an inspector for using HCF MC cable to wire recessed and lay-in fixtures in a hospital. I understand that non-flexible raceways are required for emergency system wiring; but does that include whips for light fixtures, headboards, custom office furniture and other items that are difficult to connect as well? See 517.30 (C) (3) 3 d. After consulting with DOI and other enforcement entities, the consensus was that lay-in fixtures (luminaires) ARE considered “necessary for flexible connection to equipment” and thus they, along with the other equipment mentioned above, are permitted to be installed with listed flexible metal raceways and listed metal sheathed cable assemblies; not because they are difficult to connect but because of the need for flexibility after connection. PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 1/12/11 ELECTRICAL CONSISTENCY MEETING The January Consistency Meeting was cancelled due to Office Closing for snow. PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 3/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Do all low voltage devices have to be installed to approve a final? Yes, No, and Maybe. There are so many varieties of low voltage installations that are going to be installed at so many different stages of construction that it is not feasible to say that ALL low voltage devices must be installed at the final inspection. The following is a guide to what is required: All code required low voltage systems must have devices and system fully installed. All systems or portions of systems that will be energized when power is turned on must have that system or portions fully installed All systems that have wiring un-terminated and for future use, must have that wiring protected and tagged for” future use.” All components that require grounding must be grounded per code. All installed components, devices, etc shall be labeled and listed 2. What is required for an Industrial Machinery exemption? First you must become completely familiar with the Department Directive on Industrial Machinery found on our website at: http://www.charmeck.org/mecklenburg/county/LUESA/CodeEnforcement/Inspections/trades/ Electrical/Documents/IMandFAQ.pdf Next a Declaration Letter described in the Directive must be submitted by the owner or officer of the business to the authority having jurisdiction and / or the inspector on the job for review and documentation. Finally the inspector will evaluate the machinery at the installation to see if it meets the intent of GS 143-138(b), and if so, inspect the job accordingly. PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 2 of 3 3. When does work have to be brought up to current code? This is an issue that for the most part has to be evaluated on a case-by-case basis; in general all work must meet the current code. Some specific replacement/repair work guidelines such as flood & fire damage, remodel jobs, kitchen cabinet replacement and existing bathroom remodels can be found in the Electrical Interpretation page of our website as follows: http://www.charmeck.org/mecklenburg/county/LUESA/CodeEnforcement/ CodeInterpretations/Pages/ElectricalInterpretations.aspx 4. The central vacuum system installer installed a bunch of their suction outlets onto existing electrical receptacle outlets. In some cases these existing outlets are 20 amp wire and breakers. The wire that comes from the assembly is a five foot length #14 AWG. He says UL allows this as the devices are listed. Is this correct? No. the items are a recognized component, not a “listed system”. UL White Book DMLW NEC 422.15(A) which references 210.23(A) and also 422.15(B) which states that the conductors cannot be less in size than the conductors they connect to. 5. I have a 3,000 amp service and two 2,000 amp services in the same room. The water main is located 400 feet away. A designer insists that I install either three separate 3/0 AWG copper grounding electrode conductors or two 300 kcmil conductors in parallel. May I run a single 3/0 AWG copper wire from a bus bar (1/4” x 2” x 12”) that is in the room containing these services to the water main to serve as the ground for all the services and connect each service to this bus bar? Yes, A common grounding electrode is acceptable. The 250.64(a) thru (F) of the 2008 NEC makes it clear that a common GEC must be a 3/0 cu conductor. While all three services could fail, they would not all fail at the same instance. The grounding electrode connection is not there to open an overcurrent device and when you look at an installation if there are just made (rod) type electrodes a #6 is the maximum size required. A separate grounding electrode conductor shall be run PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Page 3 of 3 from each electrical service to a grounding electrode or a common grounding electrode conductor. 250.58 requires the same electrode(s) be used as the common tie point for all services. 250.64(F) allows the installer to use a bus bar for connecting “(B) bonding jumpers from grounding electrodes “if there are more than one. Typically each service may be connected with a properly sized EGC to the closest steel framing member and the steel frame is grounded properly per 250.52(A) (2). 6. There have been several questions regarding CSST bonding come up, We need some clarification. Do we require # 6 per mechanical code or do we require bond per CSST installation instructions? Yes. 310.2 CSST Bonding of the Fuel Gas Code states: CSST Gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent. If the manufacturer’s instructions call for a size larger than #6, then it must be used, otherwise we use 310.2 PEOPLE ● PRIDE ● PROGRESS ● PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina 28202 • Phone (704) 336-3821• Fax (704) 336-3839 www.meckpermit.com Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. Quarter NC Fuel Gas Code 2011 March 2011 Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Chimneys & Vents Chapter 7 Gaseous Hydrogen S. POLICY 0 0 0 0 0 Chapter 2 Definitions Chapter 4 Gas Piping Install. Chapter 6 Specific Appliances. Chapter 8 Ind./Special Waste OTHER 2 0 0 0 0 Chapter 4 Gas Piping Installation: 1) (Q) When and where are sediment traps required? (A) Section 408 requires a sediment trap as close as practical to the inlet side of the equipment. This would include gas regulators. Regulators for individual appliances may utilize a single trap for both the regulator as well as the appliance. Illuminating appliances, ranges, clothes dryers, gas logs, log lighters and outdoor grills are exempt from traps. 2) (Q) May a flexible gas connector run through the appliance housing? (A) No! Per section 411.1.3.3 1) (Q) I am terminating a direct vent appliance on the exterior wall of a residential building. The fireplace I am venting is on the same wall as the porch. The porch is open on three sides and the termination cap provides adequate protection for the vent opening. Am I allowed to install this per code? (A) Yes. A venting system shall be designed and constructed so as to develop a positive flow adequate to convey flue or vent gases to the outdoor atmosphere. Once a deck is completely covered and/or screened in, it now could be an occupied space and would no longer be considered outdoors. We have to depend on the field Inspector to make an informed judgment. There are special circumstances where this would be allowed. If the manufacturer’s instructions allow the installation on an open porch (3 sides) and the termination vent is protected the installation may be allowed. Ref: 503.3 1st Chapter 5 Chimneys and Vents: NC Fuel Gas Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) March 2011 1) (Q) I want to install code approved unvented gas logs in a commercial restaurant that seats 100 people. Can this appliance be installed in an assembly occupancy? No. Unvented room heaters shall not be installed within Groups A, E, and I Occupancies. Ref: (FGC) 621.4 2) (Q) A new 5 million BTUH instantaneous water heater is being installed in an existing food processing plant. The water heater is located in an existing pump room that also contains electrical panels. The pump room area is 1000 square feet. Combustion and ventilation air openings are installed high and low and meet code sizing requirements. a. Does the pump room have to comply with the boiler room requirements of [B] 1015.3 for egress? (A) Yes. At 15.1 Boiler Horse Power it will require two remote exit doors per the building code. b. What is the BTUH conversion factor for BTUH to Boiler Horse Power? (A) One boiler horse power equal 330,000 BTUH. c. Are there other factors or trade requirements that may be effected by the installation of the boiler in the pump room? (A) Inspectors should be aware of clearance to combustibles. Ref: (FGC) 631.3. . 1st Chapter 6 Specific Appliances : NC Fuel Gas Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 4th 3rd 2nd 1st Note: The colored lines in the right margins identify the quarter of the calendar year questions were completed. Quarters color coded L to R, 1,2,3,4. Quarter Land Use and Environmental Service Agency (Code Enforcement) Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. Quarter NC Mechanical Code 2011 March 2011 Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Exhaust Systems Chapter 7 Combustion Air Chapter 9 Specific Appliances Chapter 11 Refrigeration Chapter 13 Fuel Oil Piping POLICY 0 3 1 0 0 0 0 1 Chapter 2 Definitions Chapter 4 Ventilation. Chapter 6 Duct Systems Chapter 8 Chimneys & Vents Chapter 10 Boilers, Water Htrs Chapter 12 Hydronic Piping Chapter 14 Solar Systems OTHER 0 1 0 0 0 0 0 0 Chapter 3 General Requirements: (Q) What are the requirements for systems installed in a flood plain? (A) Section 301.13 states: 301.13 Flood hazard. For structures located in flood hazard areas, mechanical systems, equipment and appliances shall be located at or above the design flood elevation. Exception: Mechanical systems, equipment and appliances are permitted to be located below the design flood elevation provided that they are designed and installed to prevent water from entering or accumulating within the components and to resist hydrostatic and hydrodynamic loads and stresses, including the effects of buoyancy, during the occurrence of flooding to the design flood elevation in compliance with the flood-resistant construction requirements of the International Building Code. 301.13.1 High-velocity wave action. In flood hazard areas subject to high-velocity wave action, mechanical systems and equipment shall not be mounted on or penetrate walls intended to break away under flood loads. See section 602.4 for similar the requirements covering the duct system. 2) (Q) Would the discharge line of an appliance condensate pump need to be protected from freezing temperatures? (A) Chapter 307 does not address the protection of condensate discharge lines Installed areas subject to freezing temperatures however we would be remiss if we did not require this protection in areas such as a ventilated attic space. Other areas of concern would be where the line exits the foundation wall. We would “recommend” that these installations be sloped downward and increased in pipe size to limit blockages. 1st 1) Land Use and Environmental Service Agency NC Mechanical Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. 3) Quarter (Code Enforcement) March 2011 (Q) What type of access would be required on a boiler installation where the device may be subject to vandalism or component theft? (A) Chapter 306 covers the typical installation of equipment. Section 105.1 Would allow us the flexibility to allow alternative access on a case by case basis. Chapter 4 Ventilation: 1) (Q) What is the minimum ventilation required for toilet rooms? (A) Toilet rooms are not considered to be habitable space and so their ventilation requirements would be found in table 403.3 which would require mechanical exhaust and not natural ventilation. Note: We have allowed natural ventilation in the past and we will begin enforcing the mechanical ventilation requirement on permits obtained after April 1, 2011. 1) (Q) Does Mecklenburg County allow an alternative method for type I hood clearances? (A) Mecklenburg County allows the use of NFPA 96 , Chapter 4.2.3.2 based on an interpretation by DOI dated 2/2/2004. 2) (Q) In an automotive repair garage with a vehicle exhaust source capture system per NCMC 502.14, is it permitted to have one (1) –exhaust capture connection for every two (2) bays or is one connection only allowed per bay? (A) The Mechanical Code is silent on this question, however the code language gives the inference that it requires a singular; “a source capture system” for each vehicle or service bay. One per bay is required. Ref: 502.14 3) (Q) Even though the code requirements have been met for the installation of the grease duct the contractor wants to add several more cleanout openings because he also has the maintenance contract on the grease duct system. The duct is only 10 inches by 10 inches and the code access door manufacturer informs him the smallest door approved for grease duct installation per code is 12 inches by 12 inches. Can the contractor make his own door to access the grease duct? (A) Yes. Where the duct is smaller than the 12 by 12 minimum the mechanical contractor may provide cleanouts approved by the mechanical official at least equivalent to the minimum requirements of the code for manufactured access doors. Ref: 506.3.9 1st Chapter 5 Exhaust Systems: Land Use and Environmental Service Agency NC Mechanical Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter (Code Enforcement) March 2011 Chapter 6 Duct Systems: 2) (Q) What method can be used to protect the opening in a floor/ceiling or roof/ceiling assembly where supply duct from the HVAC unit penetrates the assembly? NOTE: There is not a fire damper currently manufactured that is approved for this application when the multi-story building is classified as an R2 occupancy with type V construction. (A) The current code approval for this application requires a smoke detector to be installed in the same room as the HVAC unit that will shut down the unit if smoke is detected. The smoke detector shall tie in to the smoke detector circuit provided for the apt/condo unit. A static damper is required at the ceiling penetration of the HVAC duct penetrations from the unit. This method of protecting the ceiling penetrations is only approved until a Fire Damper is manufactured that provides adequate protection for the openings. (Q) What are the minimum requirements for plenum rated materials within an open air plenum space? (A) Not required. See plenum definition. Open air returns are typically in habitable areas and do not have to conform to the material requirements of enclosed plenums. Example: Home Depot. Ref: Chapter 2 plenum definition. & 602.2.1 Policy: Includes Energy Conservation and Re-Hab Codes 1) (Q) When is a refrigeration permit required? (A) A refrigeration permit is required for any refrigeration equipment needing to be assembled (excluding the walk-in cooler box) OR any equipment needing to be hard wired electrically (not plug type). 2) (Q) Is the outside air make-up air duct located on the non-insulated side of an attic in a single family dwelling required to be insulated? (A) No. The temperature difference between the air in the make-up air duct and the air temperature in the attic are not sufficient to cause condensate that would require insulating the duct. Ref: 503.2.7, Exception #2, North Carolina Energy Conservation Code 1st 1) Land Use and Environmental Service Agency NC Mechanical Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. 3) Quarter (Code Enforcement) March 2011 (Q) When does a Mechanical Inspector enforce the Carbon Monoxide Alarm requirements adopted by the NC Department of Insurance in One-and-Two-Family Dwellings and Townhouses? Effective date: January 1, 2011 (A ) 2009 NC Residential Code revisions to Section R313 as provided below: R313.1.2 Where required-existing dwellings. In existing dwellings, where interior alterations, repairs, fuel-fired appliance replacements, or additions requiring a permit occurs, or where one or more sleeping rooms are added or created, carbon monoxide alarms shall be provided in accordance with Section 313.1.1. R313.1.3 The required carbon monoxide alarms shall be audible in all bedrooms over background noise levels with all intervening doors closed. Single station carbon monoxide alarms shall be listed as complying with UL 2034 and shall be installed in accordance with this code and the manufacturer’s installation instructions. 4) (Q) Can R-4 insulated Flex be used in Icynene insulated attics where a thermal Barrier is above the ductwork? (A) Yes. It can be used as long as the attic is now part of the thermal envelope and properly sealed. Ref: 503.2.7, NC Energy Conservation Code 1st R313.1.1 Carbon Monoxide alarms. In new construction, dwelling units shall be provided with an approved carbon monoxide alarm installed outside of each separate sleeping area in the immediate vicinity of the bedroom(s) as directed by the alarm manufacturer. Land Use and Environmental Service Agency NC Mechanical Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter (Code Enforcement) March 2011 4th 3rd 2nd 1st Color code below denotes the calendar year quarter of the question. Colors are left to right; Brown-first quarter, Blue-Second Quarter, Green-third quarter & Red-forth quarter. Land Use and Environmental Service Agency (Code Enforcement) Attention: Denotes a new question! Denotes a revised/revisited question. Quarter NC Plumbing Code 2011 March 2011 Table of Contents Chapter 1 Administration Chapter 3 General Regulations Chapter 5 Water Heaters Chapter 7 Sanitary Drainage Chapter 9 Vents Chapter 11 Storm Drainage POLICY 0 0 0 0 0 0 0 Chapter 2 Definitions Chapter 4 Fixtures, Fau & Fit. Chapter 6 Water Supply & Dist. Chapter 8 Ind./Special Waste Chapter 10 Traps, Inter. & Sep. Appendix A-H OTHER 0 0 0 0 0 0 0 Chapter 3 General Regulations: 1) (Q) Is a check valve required on the water supply to a mobile home? No. Water supply piping shall be directly connected to the mobile home. The utility requirements are the same as any single family dwelling in Mecklenburg County. Ref: 301.3, 301.4 & North Carolina Mobile Home Code requirements. 1) (Q) What is the maximum height of the curb on a shower pan threshold? (A) There is not a maximum height for a non-handicap shower threshold. The requirement is; “the remaining side (threshold) shall wrap over the curb”. Ref: 417.4 (B) The maximum height for the threshold of a handicap shower, (either rollin or transfer type) is ½ inch. The exception is for existing facilities where structural reinforcement would be disturbed. If that is the case a maximum threshold of 2 inches would be allowed. Ref: ICC/ANSI A117.1- 2003 2) (Q) Can standard drywall coverings be used on the walls of a shower enclosure with shower head? (A) No. The wall area shall be constructed of smooth, non-corrosive, nonabsorbent, and water proof materials to a height of 6 feet. Ref: 417.4.1 3) (Q) I have an old existing apartment building three stories high that have no washer and dryer facilities. I can alter the plumbing piping to provide a 2 inch drain for the washers. I have no practical way to install a horizontal 3 inch drain for the washers. Will the re-hab code offer me any relief so these 1st Chapter 4 Fixturers, Faucets and Fixture Fittings: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 washers may be installed? (A) No. The Re-hab code offers the designer no relief from the horizontal 3 Inch drain requirement, however, the plumbing official may look at the existing DWV system to determine the feasibility of accommodating the washers before making a final determination. Ref: 406.3 4) Quarter Land Use and Environmental Service Agency (Code Enforcement) (Q) Is a drain required for an outside shower used on a pool deck that has only a cold water connection? (A) No. The shower is not used for bathing and has no hot water connection. The water could be considered clear water waste under normal circumstances and can drain into the same system that is used for the pool deck drainage. Similar in some respects to Emergency Showers and Eyewash Stations. Ref: 411 Chapter 5 Water Heaters: (Q) may a plastic safety pan be used for a gas fired instantaneous W/H? (A) Yes, provided that the water heaters minimum distance from combustible material is maintained. Ref: Manufacturers Instructions 1st 1) 2) (Q) What is the minimum size of a water heater pan drain per the current North Carolina Plumbing Code? (A) The plumbing code minimum in 504.7.1 requires a ¾ inch drain minimum This is incorrect and is a misprint in the code. The correct minimum size is 1 Inch. See DOI letter From Henry Webster Chief Plumbing Engineer for the State Department of Insurance Office of the State Fire Marshall. Chapter 6 Water Supply & Distribution: 1) (Q) What is the maximum distance a fixture supply pipe may be from the fixture it serves? (A) Section 604.5 states 72”. 2) (Q) When are water hammer arrestors required? (A) 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water- NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 hammer arrestor shall be installed where quick-closing valves (clothes washers and dishwashers) and metallic piping is used. The water-hammer arrestor shall not be required on any valves where plastic piping is used for water distribution. Water-hammer arrestors shall be installed in accordance with the manufacturer’s specifications. Water-hammer arrestors shall conform to ASSE 1010. 3) (Q) Does the Code require a water distribution system to be sanitized? (A) ? (No) 602.3.4 purged and disinfected, 610.1 purged of deleterious matter. 4) (Q) Is an expansion device required on a tankless water heater? (A) No. An expansion device is required only if there is a tank type water heater installed in the residence. An expansion device is not required if hot water distribution is from a tankless water heater. Ref: 607.3 Chapter 8 Indirect/Special Waste: 1) (Q) What is a sacristy and what special allowances apply? (A) It is one use where the drain is allowed to discharge directly into a drywell outside of the structure. 2) (Q) Can the tail piece of a lavatory or sink be used as a direct connection for the drainage from an ice maker or medical equipment? No. An air gap shall be provided and the waste shall discharge into an approved receptor to protect against backflow. Ref: Section 801.2, 802.1, and 802.1.6 3) (Q) Do all acid waste neutralization tanks require a monitoring device with alarm? (A) Yes. We require monitoring and alarms on all neutralization tanks installed in Mecklenburg County. Ref: Code Interpretation Letter & 702.5/803.2,803.5. 4) (Q) Can the discharge from a three compartment sink in a commercial Restaurant be pumped to an indirect waste receptor in a remote location? (A) Yes. The three compartment sink shall discharge through a flow control fitting and a point of use grease interceptor before terminating in the lift station. The lift station pumped discharge shall have a check valve and terminate over an indirect waste receptor which must be visible from the three compartment sink location. Ref: 802.1.1, 802.2.1 Quarter Land Use and Environmental Service Agency (Code Enforcement) NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) March 2011 Chapter 10 Traps, Interceptors & Seperators: 1) (Q) What is required for laundry drain protection for lint, buttons or strings? 1st (A) Laundries other than a single family residence, shall be equipped with a manufactured device (not field fabricated) that will limit lint, buttons or string larger than ½” from entering the drainage system. 2) (Q) Is a separate draw off storage tank allowed to be installed as part of an oil/water separator installation? Yes. When circumstances exist on a site that would not permit the full storage tank capacity calculated for an integral storage oil/water separator to be installed, an integral separator sized to meet the minimum capacity of the code may be installed with an additional draw off tank to store the remaining capacity calculated for the separator. All other requirements for oil/water separators installed in Mecklenburg County shall remain the same. Ref: 1003.1, 1003.2, 1003.4, & 1003.4.2 1) (Q) How do vertical walls affect roof drain calculations? (A) 1106.4 Vertical walls. In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that diverts rainwater to the roof shall be added to the projected roof area for inclusion in calculating the required size of vertical conductors, leaders and horizontal storm drainage piping. 2) (Q) I am attaching a handmade metal box I designed to a 4 inch overflow roof drain that terminates on the side wall of an apartment building. I am installing a screen in the box to restrict the flow so the water will not be pouring down the side of the building and staining the brick finish. Does this installation meet the code? No. The size of the drainage pipe is reduced in the direction of flow. The fitting is not approved and retards the direction of flow. The fitting has shoulders and/or reductions that retard flow. Strainers are allowed on roof surfaces only for overflow drains this is a side wall mounted fitting. Ref: 1101.5, 1101.6, 1102.7, 1105.1, 1107.2 1st Chapter 11 Storm Drainage: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. Quarter Land Use and Environmental Service Agency (Code Enforcement) March 2011 1) (Q) What is the maximum depth that a two-way C/O may be installed? (A) The maximum depth shall not exceed 24” below grade. If deeper depths are required, then an additional combination may be placed as close as possible downstream of the required building drain/sewer junction C/O. 2) (Q) A single family home is connected to a septic tank. Can a dishwasher or washing machine be connected to the drainage system of the house? Can the washing machine be connected to a dry well? (A)The homeowner would be required to contact the Environmental Health Department for Mecklenburg County. They regulate the installation, repair, and alteration of the septic tank systems in Mecklenburg County. 1st Policy: NC Plumbing Code 2011 Attention: Denotes a new question! Denotes a revised/revisited question. March 2011 4th 4th 3rd 3rd 2nd 2nd 1st1st Color code below denotes the calendar year quarter of the question. Colors are left to right; Brown-first quarter, Blue-Second Quarter, GreenThird quarter & Red-forth quarter. Quarter Land Use and Environmental Service Agency (Code Enforcement) MECKLENBURG COUNTY Land Use and Environmental Services Agency Code Enforcement Memo Date: April 19, 2011 TO: From: RE: All Contractors Jim Bartl Code Compliance Report For over fourteen years, the Department has collected data on inspection failures, based on a system of defect codes, which are recorded at the time of inspection. Those reports are summarized for presentation to the Building Development Commission on a quarterly basis. Attached is a copy of the most recent Code Compliance Report Data Summary for the period January 1, 2011 to March 31, 2011. This report highlights the most frequent code defects sighted in each of the trades. Since July 1, 2001, detailed contractor code defect data has been available on the Department web site (go to the contractor’s tool box at www.meckpermit.com). Questions on the data may be directed to Kathleen Batey: kathleen.batey@mecklenburgcountync.gov , (704-336-3545) or your project specific Code Enforcement Manager. Prior to July 1, 2002, we also held hard copies of individual contractor defect reports at the Building Development Center front desk for contractor pickup. Given the huge amount of paper involved, and the fact that the vast majority of these reports were not picked up, this service was discontinued. However, Hal Marshal administrative support staff will provide assistance to contractors on downloading their reports over the counter or by phone (call Documents 704-3363830). PEOPLE • PRIDE • PROGRESS • PARTNERSHIPS 700 North Tryon Street • Charlotte, North Carolina • Fax (704) 336-3839 www.meckpermit.com