Dr. RIYADH S. AL-TURAIHI POWER PLANT LEC.NO.(2) ____________________________________________________________________ Load Variation: What happens when load change on station ,say at particular point or instant the plant carries a steady load and energy input balances plant output of losses ,suddenly many lights are switched on the effect will be as follows: 1- This reduces over all resistance of the system and a greater current flows through the generator armature and connected circuit . 2- Reduces the turbine generated shaft speed. 3- Bring governor in to action which will open the throttle valve more for supplying more steam. 4-Reduction of steam pressure in the boiler . 5-Will give single to automatic combustion control system to speed up the forced draft and induced draft fan and also the fuel feed and water feed system. 6-Governnor spring tension helps in opening the throttle valve ,increase the flow of steam bring the shaft speed normal .The total time takes in this process from few second to few minutes. Dr. RIYADH S. AL-TURAIHI POWER PLANT LEC.NO.(2) ____________________________________________________________________ Distribution of Electricity: Demand Factor: demand factor=Maximum demand / connected load is the ratio of the maximum demand of a system or part of the a system to the total connected load of the system under consideration . Diversity factor: DF= is the ratio of the sum of the individual max demand of the various sub division of a system or part of a system to the max demand of the hole system or part of the system under consideration the partial subdivision may be one substation where there are several in a system or may be a group of residential customs .Supplied by one Transformer. Load factor= Dr. RIYADH S. AL-TURAIHI POWER PLANT LEC.NO.(2) ____________________________________________________________________ Average load= capacity factor= when applied to machine or equipment ,rating of the machine is capacity. when applied to power plant ,plant capacity is the capacity. Use Factor= = Ex(1):Given (70 Mw) power plant ( installed capacity ),Annual output=250,000,000 kw/h, having peak head=56700 kw,plant was not use for (500 hr) in one year, find the load factor ,capacity factor and use factor? Ex(2):Given :capacity (70 Mw),straight line (load variation curve)varies, from (50 Mw to 6 Mw) ,find load factor ,capacity factor and demand factor? Ex(3):Given: L.F=0.5,CF=0.3,use factor=0.37,Reverse of low peak load=20000 kw, find capacity and peak load? if capacity=Lp+ Reverse Dr. RIYADH S. AL-TURAIHI POWER PLANT LEC.NO.(2) ____________________________________________________________________ Plant location: 1- Transmission of energy. 2- Supply of fuel (transportation). 3- Supply of water. 4- Availability of land and its cost. Station performance of operation characteristics. I=input in million of kg/hr L=output in kws of mega watts Io=amount of energy required to keep the plant functioning (frictional of other losses). y=a+bx+cx2+dx3+……… I=a+bL+cL2+dL3+……… dI/dL=increment rate Heat rate= I/L (kJ/hr.kw) = Dr. RIYADH S. AL-TURAIHI POWER PLANT LEC.NO.(2) ____________________________________________________________________ = +b+cL+dL2 increase rate=dI/dL= 0+b+2cL+3dL2 Average heat rate= Ex(4):A 20 Mw station has an input -output curve defined by: I= 30+0.5L0.65L2+0.01L3 where I t is the in millions of kg/hr and L is in (Mw) ,find the increase output from (7Mw) to (9 Mw) by means of the input-output curve and also by the incremental rate curve? EX(5): The input -output curve of a (20Mw) generating station in defined by I= 30+0.5L0.65L2, where I is in millions of ( kJ/hr) and L is in (Mw) ,find the average heat rate of this station for a day when it was operating at load of (20Mw) for 12 hr ,and at (4 Mw )load for the remaining 12 hr?