CTL8029(W/F)17 Catalog No. Optica ED17 Ceramic Metal Halide Track Fixture Type Specifications/Features Project Fixture Die cast aluminum housing with vertical ballast. Lockable, precision aiming adjustment. 360°+ Horizontal rotation, 180° vertical rotation. Integral ON/OFF switch and track polarity indicator are standard. Lamp CTL8029_1750M: (1) 50W ED17 CMH, E26 Medium Base CTL8029_1770M: (1) 70W ED17 CMH, E26 Medium Base Electrical Electronic Ceramic Metal Halide ballast, 120V operation. 50W Input power: 56W; Input current: 0.41A @ 120V. 70W Input power: 77W; Input current: 0.64A @ 120V. Harmonic distortion: <20%. Thermally and transient protected. Sound rated “A” for indoor applications. Warranty This fixture is covered by ConTech’s full one (1) year replacement guarantee after date of purchase. Ballast is covered by manufacturer’s five (5) year warranty. Listing cCSAus Certified. Suitable for dry locations. 8" Fixture Compatibility 7" Standard ConTech track fixtures are cCSAus certified as-is for use with ConTech’s many track systems, as well as with Juno®¹ Lighting track. By changing the prefix in the part number, ConTech can install inserts which make our fixtures compatible with other manufacturers. Replace “CTL” with “HTL” for Halo®² track, “LTL” for Lightolier®³ track, and “PTL” for Capri®4 track. For more information, please consult our factory. 6" Ordering Information Example Order: CTL8029 F1770M Track System P Fixture Beam Distribution Lamp Wattage Finish F - Flood W - Wide Flood 1750MH - 50W 1770MH - 70W B - Black P - White S - Silver 8029 CTL - ConTech HTL - Halo LTL - Lightolier PTL - Capri 8029 1. Juno is a registered trademark of Juno Lighting 2. Halo is a registered trademark of Cooper Lighting 3. Lightolier is a registered trademark of Philips Lighting 4. Capri is a registered trademark of Philips Lighting 1-847-559-5500 www.contechlighting.com Please Recycle All specifications subject to change without notice. CTL8029(W/F)17 Catalog No. Optica ED17 Ceramic Metal Halide Track Fixture Type Photometrics Project Flood Distribution: CTL8029F1770M Lamp: (1) 70W ED17 CMH Lumens: 5700 per lamp Spacing Criteria: 0.8 Test No.: 54376 Candela Curve 0 Candlepower Summary 90° 75° 1000 60° 2000 45° 3000 0° 15° 30° FROM 0 0 5 15 25 35 45 55 65 75 85 95 CANDELA 2893 2776 2177 1450 873 458 249 131 63 11 0 Coefficients of Utilization RC RW 0 1 2 3 4 5 6 7 8 9 10 80% 50% 30% 60 55 50 45 42 38 36 33 31 29 27 60 53 47 42 38 35 32 30 27 26 24 70% 50% 30% 59 54 49 45 41 38 35 33 31 29 27 59 52 46 42 38 35 32 29 27 25 24 50% 50% 30% 56 51 47 43 40 37 34 32 30 28 27 56 50 45 41 37 34 31 29 27 25 24 Wide Flood Distribution: CTL8029W1770M Lamp: (1) 70W ED17 CMH Lumens: 5700 per lamp Spacing Criteria: 0.6 Test No.: 54377 Candlepower Summary Candela Curve 0 90° 75° 1200 60° 2400 45° 3600 0° 15° 1-847-559-5500 30° FROM 0 0 5 15 25 35 45 55 65 75 85 95 CANDELA 3462 3193 2152 1351 748 287 99 31 5 0 0 www.contechlighting.com Coefficients of Utilization RC RW 0 1 2 3 4 5 6 7 8 9 10 80% 50% 30% 49 45 42 39 36 34 32 30 28 26 25 Please 49 44 40 37 34 31 29 27 25 24 22 70% 50% 30% 48 44 41 38 36 33 31 29 28 26 25 Recycle 48 43 40 36 33 31 29 27 25 24 22 50% 50% 30% 46 43 40 37 35 33 31 29 27 26 24 46 42 39 36 33 31 28 27 25 24 22 All specifications subject to change without notice.