ABBREVIATIONS PIPE AND FITTING MATERIALS PERMITTED GENERAL NOTES: APPX APPROXIMATE ARCH ARCHITECTURAL BFP BACKFLOW PREVENTER BTU BRITISH THERMAL UNIT BTUH BTU/HOUR CO CLEANOUT CWS COLD WATER SUPPLY °F DEGREES (FAHRENHEIT) DN PIPE DOWN, THROUGH FLOOR DROP PIPE DOWN, NOT THROUGH FLOOR DWH DOMESTIC WATER HEATER DWV DRAIN, WASTE, AND VENT 5. CONTRACTOR RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING PERMITS, INSPECTIONS, ETC. (E) EXISTING 6. THE INSTALLING CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT. CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT. HANGER SCHEDULE (2015 NSPC, CHAPTER 8) ELEV ELEVATION MATERIAL MAX. VERTICAL SPACING (FT) FD FLOOR DRAIN FS FLOOR SINK FCO FLOOR PLATE CLEANOUT GAS LOW PRESSURE GAS (BELOW 0.5 PSI) GPM GALLONS PER MINUTE HWR DOMESTIC HOT WATER RETURN HWS DOMESTIC HOT WATER SUPPLY UNDERGROUND BUILDING DRAINAGE AND VENT PIPE MATERIAL CAST IRON PIPE PIPE STANDARD FITTING STANDARD ASTM A 74; ASTM A 888; CISPI 301 ASTM B 16.4; ASTM B 16.12; ASTM A 74; ASTM A 888; CISPI 301 ABOVE-GROUND BUILDING DRAINAGE AND VENT PIPE MATERIAL CAST IRON PIPE PIPE STANDARD FITTING STANDARD ASTM A 74; ASTM A 888; CISPI 301 ASTM A 74; ASTM A 888; CISPI 301 1. THESE GENERAL PLUMBING NOTES SHALL APPLY TO ALL P SERIES DRAWINGS, IN COORDINATION WITH DIVISION 22 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE P SERIES DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS. 2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE OWNER (AND/OR OWNER'S REPRESENTATIVE) AND THE ARCHITECT/ENGINEER THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE OWNER AND ARCHITECT, AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS. 3. CONTRACT DRAWINGS FOR THE PLUMBING WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE OWNER RESERVES THE RIGHT TO MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION. • THE CONTRACTOR SHALL INSTALL ALL PIPING, EQUIPMENT, FIXTURE, ETC. IN A WORKMAN MANNER WITH QUALIFIED PLUMBERS. 4. ALL PLUMBING WORK SHALL BE INSTALLED PER LOCAL PLUMBING CODE, HEALTH CODE, FIRE CODE, ENERCY CONSERVATION CODE, AND BUILDING CODE. ALL WORK SHALL COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING JURISDICTION. NATIONAL STANDARD PLUMBING CODE, 2015, IS IN EFFECT FOR THIS PROJECT. SEALED: MAX. HORIZONTAL SPACING (FT) CAST IRON PIPE 5 AT BASE AND EACH STORY HEIGHT COPPER TUBING, 1-1/4" DIAMETER AND SMALLER 6 10 COPPER TUBING, 1-1/2" DIAMETER AND LARGER 10 10 CPVC TUBING, 1" DIAMETER AND SMALLER NOTES 1,2 NOTES 1,3 CPVC TUBING, 1-1/4" DIAMETER AND LARGER NOTES 1,2 NOTES 1,3 PVC PIPE NOTES 1,2 NOTES 1,3 STEEL PIPE, 3/4" DIAMETER AND SMALLER 10 AT EVERY OTHER STORY STEEL PIPE, 1" DIAMETER AND LARGER 12 15 7. ALL PLUMBING EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER. N/A NOT APPLICABLE NTS NOT TO SCALE PSI POUNDS PER SQUARE INCH PRV PRESSURE REDUCING VALVE RISE PIPE UP, NOT THROUGH FLOOR ABOVE SAN SANITARY 8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED". • FOR RENOVATIONS: THE CONTRACTOR REQUIRING CUTTING SHALL BE RESPONSIBLE FOR HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES. • FOR NEW CONSTRUCTION: ALL CUTTING AND PATCHING THROUGH ALL WALL, CEILING, ETC. SHALL BE PROVIDED BY PLUMBING CONTRACTOR IN COORDINATION WITH THE GENERAL WORK. ALL PAINTING AND FINISHING SHALL BE DONE BY GENERAL CONTRACTOR. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH GENERAL CONTRACTOR. • OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION, DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC PLUMBING WORK AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION. • UNDERGROUND PIPING (NEW CONSTRUCTION): TRENCHING SHALL BE BY GENERAL CONTRACTOR. PIPE INSTALLATION WITH APPROPRIATE BEDDING MATERIAL SHALL BE BY THE PLUMBING CONTRACTOR. BACKFILL ABOVE PIPE AND BEDDING SHALL BE BY THE GENERAL CONTRACTOR BASED ON REQUIREMENTS OF THE STRUCTURAL PLANS AND SPECFICATIONS. • UNDERGROUND PIPING FINISHED FLOORS OTHER THAN CONCRETE: UNLESS OTHERWISE NOTED, TRENCHING, EXCAVATION, BACKFILLING, COMPACTION AND RESTORATION OF THE FLOORING SUBSTRATE SHALL BE PERFORMED BY THIS CONTRACTOR. FINAL FINISHED FLOOR SHALL BE BY OTHERS. • EQUIPMENT OPENINGS: OPENINGS REQUIRED FOR REMOVAL OF EXISTING EQUIPMENT OR INSTALLATION OF NEW EQUIPMENT SUPPLIED UNDER THIS CONTRACT SHALL BE CUT AND PATCHED BY THIS CONTRACTOR. CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: TYP TYPICAL V VENT PIPING 10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE PLUMBING CONTRACTOR SHALL GUARANTEE ALL SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. • THE CONTRACTOR SHALL PROVIDE OWNER WITH ALL NECESSARY OPERATION AND MAINTENANCE MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE PROJECT. 11. THE CONTRACTOR SHALL LOCATE ACCESS PANEL IN NON-ACCESSIBLE CEILING AND WALLS FOR ALL VALVES, SHOCK ABSORBERS, CLEANOUTS AND ALL OTHER ITEMS THAT REQUIRE ACCESS TO PROPERLY MAINTAIN OR SERVICE. 12. THE CONTRACTOR IS RESPONSIBLE FOR TESTING, AND ADJUSTING ALL PLUMBING EQUIPMENT INDICATED IN THE PLUMBING DRAWINGS. 13. THE MINIMUM SLOPE OF ALL INTERIOR SEWER LINES SHALL BE 1/4 INCH PER FOOT FOR SIZES 2-1/2" AND SMALLER, 1/8 INCH PER FOOT FOR SIZES 3"-6", AND 1/16 INCH PER FOOT FOR SIZES 8" AND GREATER. SEE SCHEDULE LOCATED ON DRAWING FOR CONNECTION SIZES FOR SANITARY, VENT, COLD, AND HOT WATER PIPING. SEE SCHEDULE FOR PIPING MATERIALS. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 14. ALL PIPING PENETRATIONS THROUGH EXPOSED WALLS SHALL BE PROVIDED WITH CHROME ESCUTCHEONS AND SEAL TO WALL OR CEILING. P TRAP BALL VALVES 16. ALL NATURAL GAS PIPING SHALL BE TESTED PER THE LIST BELOW. ALL TESTING SHALL CONFORM TO INTERNATIONAL STATE FUEL GAS CODE. • PRESSURE UP TO AND INCLUDING 12" W.C.: 15 PSI FOR ONE (1) HOUR. • PRESSURE ABOVE 12" W.C.: 1-1/2 TIMES THE WORKING PRESSURE, OR 50 PSI (MINIMUM) FOR ONE (1) HOUR. • COATED OR WRAPPED PIPING: 100 PSIG FOR ONE (1) HOUR 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS 18. UPON COMPLETION OF PROJECT, THE CONTRACTOR SHALL FLUSH AND SANITIZE THE DOMESTIC HOT, RECIRCULATION AND COLD WATER PIPING IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION. 1 PIPE DOWN/DROP PIPE UP/RISE PIPE UNION POINT OF NEW CONNECTION/DISCONNECTION xx DCA COMMENTS 3.14.2016 19. EQUIPMENT CONNECTIONS: • ALL EQUIPMENT SHALL BE PROVIDED WITH UNIONS AND SHUT-0FF VALVES WHETHER DETAILED OR NOT. • ALL PLUMBING FIXTURES SHALL BE PROVIDED WITH SHUT OFF VALVES. 20. NATURAL GAS REGULATOR VENT PIPING SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE IN ACCORDANCE WITH NFPA 54 AND/OR NFPA 58. EXTERIOR PIPING SHALL BE PAINTED WITH TWO COATS OF PRIMER AND ONE COAT OF FINISH PAINT. COLOR TO BE DETERMINED BASED COLOR OF SURROUNDING SURFACES. 21. FOR PROJECTS WITH APPROVED USE OF PVC AND CPVC PIPING, SUCH PIPING SHALL BE PROHIBITED IN THE FOLLOWING LOCATIONS. • AREAS OF ASSEMBLY. • RETURN AIR PLENUMS. • EXIT DISCHARGE CORRIDORS. • STAIRS. KEYED NOTE SYMBOL DRAWN BY: DAS CHECKED BY: MAE 22. RODENTPROOFING - IN OR ON STRUCTURES WHERE OPENINGS HAVE BEEN MADE IN FLOORS CEILINGS, OR WALLS FOR THE PASSAGE OF PIPE, SUCH OPENINGS SHALL BE CLOSED AND PROTECTED WITH APPROVED METAL COLLARS THAT ARE SECURELY FASTENED TO THE ADJOINING STRUCTURE. 23. STRUCTURAL SAFETY - IN THE PROCESS OF INSTALLING OR REPAIRING ANY PART OF A PLUMBING OR DRAINAGE SYSTEM, THE FINISHED FLOOR, WALLS, CEILINGS, TILE OR ANY OTHER PART OF THE BUILDING OR PREMISES THAT MUST BE CHANGED OR REPLACED SHALL REMAIN IN A STRUCTURALLY SAFE CONDITION. 24. PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS - PIPING AND OTHER SYSTEM COMPONENTS SHALL BE INSTALLED IN SUCH A MANNER SO AS TO PREVENT CORROSION, BREAKAGE, FREEZING, AND PHYSICAL DAMAGE BY OTHER BUILDING COMPONENTS. 25. PROTECTION OF WATER QUALITY - A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN SUCH A MANNER SO AS TO PREVENT CONTAMINATION FROM NON-POTABLE LIQUIDS, SOLIDS, OR GASES BEING INTRODUCED INTO THE POTABLE WATER SYSTEM THROUGH CROSS-CONTAMINATION OR ANY OTHER PIPING CONNECTIONS TO THE SYSTEM. 26. FLOODPROOFING - PLUMBING SYSTEMS AND EQUIPMENT IN STRUCTURES ERECTED IN AREAS PRONE TO FLOODING SHALL BE CONSTRUCTED IN SUCH A MANNER THAT THE COMPONENTS OF THE SYSTEM SHALL BE CAPABLE OF RESISTING HYDROSTATIC LOADS AND STRESSES IN THE EVENT OF FLOODING. ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: P-000 18031.00 DESCRIPTION 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 SYMBOLS 15. ALL NATURAL GAS PIPING SHALL BE INSTALL PER INTERNATIONAL FUEL GAS CODE AND AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL PROVIDE SHUT OFF GAS VALVE FOR ALL EQUIPMENT UTILIZING GAS. CONTRACTOR SHALL PROVIDE 6" DIRT LEG (MINIMUM) FOR ALL EQUIPMENT UTILIZING GAS. RCNJ No. 201437-01C PHASE 2 : ALTERATIONS PLUMBING LEGEND RAMAPO COLLEGE OF NEW JERSEY NOTES: 1. PLASTIC DRAIN, WASTE, AND VENT PIPE SHALL BE INSTALLED AND SUPPORTED AS RECOMMENDED BY THE MANUFACTURER'S INSTRUCTIONS. 2. MAXIMUM HORIZONTAL SUPPORT SPACING SHALL BE BASED ON THE PIPE SCHEDULE OR WALL THICKNESS, THE PIPE SIZE, THE SYSTEM OPERATING TEMPERATURE, THE AMBIENT TEMPERATURE, AND ANY CONCENTRATED LOADS. 3. VERTICAL PIPE SHALL BE MAINTAINED IN STRAIGHT ALIGNMENT WITH SUPPORTS AT EACH STORY HEIGHT. INTERMEDIATE SUPPORTS SHALLBE PROVIDED WHERE REQUIRED FOR STABILITY. 9. ALL PIPING PENETRATING ALL FIRE-RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. SHALL BE FIRE STOPPED IN ACCORDANCE WITH DIVISION 7. PLUMBING - CODES AND GENERAL NOTES 3/23/2016 10:51:53 AM NJDCA ELECTRONIC SUBMITTAL STAMP: 3/23/2016 10:51:54 AM NJDCA ELECTRONIC SUBMITTAL STAMP: GENERAL NOTES: ABBREVIATIONS 1. THESE GENERAL PLUMBING NOTES SHALL APPLY TO ALL P SERIES DRAWINGS, IN COORDINATION WITH DIVISION 22 SECTIONS, AND FRONT END (DIVISION 0 AND 1) REQUIREMENTS. ALL WORK ASSOCIATED WITH THE P SERIES DRAWINGS SHALL BE COORDINATED WITH ALL OTHER TRADES TO AVOID CONFLICTS. APPX APPROXIMATE ARCH ARCHITECTURAL BFP BACKFLOW PREVENTER BTU BRITISH THERMAL UNIT BTUH BTU/HOUR CO CLEANOUT CWS COLD WATER SUPPLY °F DEGREES (FAHRENHEIT) 4. ALL PLUMBING WORK SHALL BE INSTALLED PER LOCAL PLUMBING CODE, HEALTH CODE, FIRE CODE, ENERCY CONSERVATION CODE, AND BUILDING CODE. ALL WORK SHALL COMPLY TO ACCORDANCE OF LOCAL, STATE AND FEDERAL REGULATIONS AND OTHER AUTHORITIES HAVING JURISDICTION. NATIONAL STANDARD PLUMBING CODE, 2015, IS DN PIPE DOWN, THROUGH FLOOR IN EFFECT FOR THIS PROJECT. DROP PIPE DOWN, NOT THROUGH FLOOR DWH DOMESTIC WATER HEATER DWV DRAIN, WASTE, AND VENT 6. THE INSTALLING CONTRACTOR SHALL BE LICENSED IN THE LOCAL JURISDICTION PRIOR TO BIDDING ON PROJECT. CONTRACTOR TO CONTACT CITY/TOWNSHIP TO VERIFY LICENSE TO ENSURE THEY ARE CURRENT. (E) EXISTING ELEV ELEVATION 7. ALL PLUMBING EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS. ANY CONFLICTS WITH INSTALLATION AND MANUFACTURER RECOMMENDATIONS SHALL BE REPORTED TO ENGINEER. FD FLOOR DRAIN FS FLOOR SINK FCO FLOOR PLATE CLEANOUT GAS LOW PRESSURE GAS (BELOW 0.5 PSI) GPM GALLONS PER MINUTE HWR DOMESTIC HOT WATER RETURN HWS DOMESTIC HOT WATER SUPPLY 2. ALL WORK SHALL BE PERFORMED IN COOPERATION WITH THE OWNER (AND/OR OWNER'S REPRESENTATIVE) AND THE ARCHITECT/ENGINEER THE CONTRACTOR SHALL COORDINATE ALL WORK WITH THE CONSTRUCTION SCHEDULE ESTABLISHED BY THE OWNER AND ARCHITECT, AND SHALL IMMEDIATELY REPORT ANY DELAYS IN MATERIALS RECEIPT INCLUDING CIRCUMSTANCES CAUSING DELAYS. N/A NOT APPLICABLE NTS NOT TO SCALE 3. CONTRACT DRAWINGS FOR THE PLUMBING WORK ARE DIAGRAMMATIC, INTENDED TO CONVEY THE SCOPE OF WORK AND TO INDICATE THE GENERAL ARRANGEMENT AND APPROXIMATE LOCATION OF EQUIPMENT, PIPING, AND ACCESSORIES. THE INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING AND VERIFYING ALL CONDITIONS, DIMENSIONS, AND LOCATIONS PRIOR TO BIDDING PROJECT. CHECK PROJECT DRAWINGS PRIOR TO INSTALLATION FOR INTERFERENCES WITH OTHER TRADES. SHOULD THE CONTRACTOR FIND SUCH INTERFERENCES, THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING HIS WORK WITH OTHERS. THE OWNER RESERVES THE RIGHT TO MAKE REASONABLE CHANGES PRIOR TO ROUGH-IN WITHOUT ADDED EXPENSE. DIMENSIONS INDICATED ARE SUBJECT TO VERIFICATION OF EXACT SITE CONDITIONS AT THE TIME OF INSTALLATION. • THE CONTRACTOR SHALL INSTALL ALL PIPING, EQUIPMENT, FIXTURE, ETC. IN A WORKMAN MANNER WITH QUALIFIED PLUMBERS. 5. CONTRACTOR RESPONSIBLE FOR PAYING FOR ALL FEES ASSOCIATED WITH OBTAINING PERMITS, INSPECTIONS, ETC. 8. CUTTING AND PATCHING - ALL NOTES BELOW HOLD THE COMMON CONDITION "UNLESS OTHERWISE NOTED". • FOR RENOVATIONS: THE CONTRACTOR REQUIRING CUTTING SHALL BE RESPONSIBLE FOR HIS/HER OWN WORK WHETHER DESCRIBED IN THE CONTRACT DOCUMENTS OR NOT. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING CUTTING AND PATCHING REQUIREMENTS WITH OTHER TRADES. • FOR NEW CONSTRUCTION: ALL CUTTING AND PATCHING THROUGH ALL WALL, CEILING, ETC. SHALL BE PROVIDED BY PLUMBING CONTRACTOR IN COORDINATION WITH THE GENERAL WORK. ALL PAINTING AND FINISHING SHALL BE DONE BY GENERAL CONTRACTOR. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH GENERAL CONTRACTOR. • OPENINGS MADE POST-FINISH: IF AN OPENING IS REQUIRED IN A FINISHED SURFACE, AFTER COMPLETION, DUE TO LACK OF COORDINATION OR PROPER SCHEDULE MAINTENANCE, THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CUTTING AND PATCHING REQUIRED TO FINISH SPECIFIC PLUMBING WORK AND RESTORE THE FINISHED SURFACE TO PREVIOUS CONDITION. • UNDERGROUND PIPING (NEW CONSTRUCTION): TRENCHING SHALL BE BY GENERAL CONTRACTOR. PIPE INSTALLATION WITH APPROPRIATE BEDDING MATERIAL SHALL BE BY THE PLUMBING CONTRACTOR. BACKFILL ABOVE PIPE AND BEDDING SHALL BE BY THE GENERAL CONTRACTOR BASED ON REQUIREMENTS OF THE STRUCTURAL PLANS AND SPECFICATIONS. • UNDERGROUND PIPING FINISHED FLOORS OTHER THAN CONCRETE: UNLESS OTHERWISE NOTED, TRENCHING, EXCAVATION, BACKFILLING, COMPACTION AND RESTORATION OF THE FLOORING SUBSTRATE SHALL BE PERFORMED BY THIS CONTRACTOR. FINAL FINISHED FLOOR SHALL BE BY OTHERS. • EQUIPMENT OPENINGS: OPENINGS REQUIRED FOR REMOVAL OF EXISTING EQUIPMENT OR INSTALLATION OF NEW EQUIPMENT SUPPLIED UNDER THIS CONTRACT SHALL BE CUT AND PATCHED BY THIS CONTRACTOR. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. 9. ALL PIPING PENETRATING ALL FIRE-RATED WALLS, CEILINGS, FLOORS, ROOFS, ETC. SHALL BE FIRE STOPPED IN ACCORDANCE WITH DIVISION 7. ARCHITECT: PSI POUNDS PER SQUARE INCH PRV PRESSURE REDUCING VALVE RISE PIPE UP, NOT THROUGH FLOOR ABOVE 10. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE COMPLETE AND OPERABLE SYSTEMS, INCLUDING OPERATIONAL PROPERTIES TO THE EXTEND NECESSARY TO LINK MULTIPLE COMPONENTS OF THE SYSTEMS TOGETHER AND TO INTERFACE WITH SYSTEMS PROVIDED BY OTHERS. THE PLUMBING CONTRACTOR SHALL GUARANTEE ALL SYSTEMS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. • THE CONTRACTOR SHALL PROVIDE OWNER WITH ALL NECESSARY OPERATION AND MAINTENANCE MANUALS, SHOP DRAWINGS, WIRING DIAGRAMS, AND WARRANTY PAPERWORK UPON COMPLETION OF THE PROJECT. SAN SANITARY 11. THE CONTRACTOR SHALL LOCATE ACCESS PANEL IN NON-ACCESSIBLE CEILING AND WALLS FOR ALL VALVES, SHOCK ABSORBERS, CLEANOUTS AND ALL OTHER ITEMS THAT REQUIRE ACCESS TO PROPERLY MAINTAIN OR SERVICE. ST STORM TYP TYPICAL UP PIPE UP THROUGH FLOOR 12. THE CONTRACTOR IS RESPONSIBLE FOR TESTING, AND ADJUSTING ALL PLUMBING EQUIPMENT INDICATED IN THE PLUMBING DRAWINGS. 13. THE MINIMUM SLOPE OF ALL INTERIOR SEWER LINES SHALL BE 1/4 INCH PER FOOT FOR SIZES 2-1/2" AND SMALLER, 1/8 INCH PER FOOT FOR SIZES 3"-6", AND 1/16 INCH PER FOOT FOR SIZES 8" AND GREATER. SEE SCHEDULE LOCATED ON DRAWING FOR CONNECTION SIZES FOR SANITARY, VENT, COLD, AND HOT WATER PIPING. SEE SCHEDULE FOR PIPING MATERIALS. ENGINEER: 14. ALL PIPING PENETRATIONS THROUGH EXPOSED WALLS SHALL BE PROVIDED WITH CHROME ESCUTCHEONS AND SEAL TO WALL OR CEILING. V 15. ALL NATURAL GAS PIPING SHALL BE INSTALL PER INTERNATIONAL FUEL GAS CODE AND AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL PROVIDE SHUT OFF GAS VALVE FOR ALL EQUIPMENT UTILIZING GAS. CONTRACTOR SHALL PROVIDE 6" DIRT LEG (MINIMUM) FOR ALL EQUIPMENT UTILIZING GAS. VENT PIPING 16. ALL NATURAL GAS PIPING SHALL BE TESTED PER THE LIST BELOW. ALL TESTING SHALL CONFORM TO INTERNATIONAL STATE FUEL GAS CODE. • PRESSURE UP TO AND INCLUDING 12" W.C.: 15 PSI FOR ONE (1) HOUR. • PRESSURE ABOVE 12" W.C.: 1-1/2 TIMES THE WORKING PRESSURE, OR 50 PSI (MINIMUM) FOR ONE (1) HOUR. • COATED OR WRAPPED PIPING: 100 PSIG FOR ONE (1) HOUR PLUMBING LEGEND DESCRIPTION SYMBOLS 18. UPON COMPLETION OF PROJECT, THE CONTRACTOR SHALL FLUSH AND SANITIZE THE DOMESTIC HOT, RECIRCULATION AND COLD WATER PIPING IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION. P TRAP DRINKING FOUNTAIN SCHEDULE MANUFACTURER MODEL MANUFACTURER MODEL MANUFACTURER 20. NATURAL GAS REGULATOR VENT PIPING SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE IN ACCORDANCE WITH NFPA 54 AND/OR NFPA 58. EXTERIOR PIPING SHALL BE PAINTED WITH TWO COATS OF PRIMER AND ONE COAT OF FINISH PAINT. COLOR TO BE DETERMINED BASED COLOR OF SURROUNDING SURFACES. PIPE DOWN/DROP MODEL CWS SIZE DRAIN SIZE VENT SIZE MINIMUM SUPPLY PRESSURE ( PSI ) 21. FOR PROJECTS WITH APPROVED USE OF PVC AND CPVC PIPING, SUCH PIPING SHALL BE PROHIBITED IN THE FOLLOWING LOCATIONS. • AREAS OF ASSEMBLY. • RETURN AIR PLENUMS. • EXIT DISCHARGE CORRIDORS. • STAIRS. PIPE UP/RISE PIPE UNION ADA, WITH BOTTLE FILLER STAINLESS STEEL WALL ELKAY LZS8WSVRLP MCGUIRE 8872 MCGUIRE H2166CC 1/2" 1-1/4" 1-1/4" 25 22. RODENTPROOFING - IN OR ON STRUCTURES WHERE OPENINGS HAVE BEEN MADE IN FLOORS CEILINGS, OR WALLS FOR THE PASSAGE OF PIPE, SUCH OPENINGS SHALL BE CLOSED AND PROTECTED WITH APPROVED METAL COLLARS THAT ARE SECURELY FASTENED TO THE ADJOINING STRUCTURE. POINT OF NEW CONNECTION TAG DESCRIPTION ACCESS DESIGNATION MANUFACTURER MODEL NUMBER CWS SIZE HWS SIZE HB-1 HOSE BIBB, MILD CLIMATE, WITH WALL BOX N/A WATTS HY-330 3/4" N/A WHA-X WATER HAMMER ARRESTER N/A PRECISION PLUMBING PRODUCTS SC-SERIES VARIES N/A FS (E) FLOOR SINK (EXISTING) 25. PROTECTION OF WATER QUALITY - A POTABLE WATER SUPPLY SYSTEM SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN SUCH A MANNER SO AS TO PREVENT CONTAMINATION FROM NON-POTABLE LIQUIDS, SOLIDS, OR GASES BEING INTRODUCED INTO THE POTABLE WATER SYSTEM THROUGH CROSS-CONTAMINATION OR ANY OTHER PIPING CONNECTIONS TO THE SYSTEM. NOTES PRESSURE RANGE ( PSI ) NICKEL BRONZE BOX FACE (-X) SUFFIX ON PLANS CORRESPONDS TO PDI SIZE OF UNIT 0-200 FD (E) FLOOR DRAIN (EXISTING) FCO (E) FLOOR CLEANOUT (EXISTING) 1i KITCHEN EQUIPMENT TAG xx KEYED NOTE SYMBOL 26. FLOODPROOFING - PLUMBING SYSTEMS AND EQUIPMENT IN STRUCTURES ERECTED IN AREAS PRONE TO FLOODING SHALL BE CONSTRUCTED IN SUCH A MANNER THAT THE COMPONENTS OF THE SYSTEM SHALL BE CAPABLE OF RESISTING HYDROSTATIC LOADS AND STRESSES IN THE EVENT OF FLOODING. SANITARY/STORM DRAINAGE ACCESSORIES TAG DESCRIPTION MANUFACTURER MODEL DRAIN SIZE FD-1 FLOOR DRAIN WATTS FD-100-A5 SEE PLANS FS-1 FLOOR SINK WATTS FS-740-175 4" 2 FLOOR CLEANOUT WATTS CO-1200-R SEE PLANS, 4" MAX 1 LINE CLEANOUT CHARLOTTE PVC PART 105X SEE PLANS, 4" MAX WALL CLEANOUT WATTS CO-460-RD SEE PLANS, 4" MAX FCO-1 CO-1 WCO-1 NOTES NOTES: 1. PROVIDE LINE SIZE FLOOR CLEANOUT UP TO 4" PIPE SIZE. FOR PIPE SIZE GREATER THAN 4", TRANSITION TO 4" PIPE AT RISER TO FCO. 2. PROVIDE WITH 3/4 GRATE. WATER CLOSET SCHEDULE GENERAL TAG BOWL MOUNTING ACCESS DESIGNATION FLUSH VALVE MANUFACTURER SEAT MODEL COLOR MANUFACTURER MODEL MANUFACTURER UNIT CONNECTIONS MODEL COLOR FLUSH SUPPLY VOLUME SIZE (GPF) NOTES DRAIN SIZE VENT SIZE MINIMUM SUPPLY PRESSURE ( PSI ) WC-1 FLOOR TOP SPUD ADA AMERICAN STANDARD MADERA 3034.001 WHITE SLOAN OPTIMA 111-1.28-ES-S PROFLO PFTSCOF2000WH WHITE 1.6 1" 3" 2" 25 WC-2 FLOOR TOP SPUD NON-ADA AMERICAN STANDARD MADERA 3451.001 WHITE SLOAN OPTIMA 111-1.28-ES-S PROFLO PFTSCOF2000WH WHITE 1.6 1" 3" 2" 25 URINAL SCHEDULE GENERAL BOWL TAG MOUNTING U-1 WALL TOP SPUD U-2 WALL TOP SPUD ACCESS DESIGNATION FLUSH VALVE MANUFACTURER CARRIER UNIT CONNECTIONS COLOR MANUFACTURER MODEL MANUFACTURER MODEL WHITE SLOAN OPTIMA 186-1.0 ES-S MIFAB MC-32 1.0 SLOAN OPTIMA 186-1.0 ES-S MIFAB MC-32 1.0 AMERICAN STANDARD WASHBROOK 6590.001 NON-ADA AMERICAN STANDARD WASHBROOK 6590.001 WHITE VENT SIZE MINIMUM SUPPLY PRESSURE ( PSI ) 3/4" 2" 1-1/2" 25 HANGER SCHEDULE 3/4" 2" 1-1/2" 25 MATERIAL LAVATORY SCHEDULE GENERAL TAG L-1 BOWL ACCESSIBILITY DESIGNATION ALL MATERIAL VITREOUS CHINA FAUCET MOUNTING UNDERMOUNT MANUFACTURER AMERICAN STANDARD MODEL OVALYN 0495.221 COLOR WHITE MANUFACTURER SLOAN MAE/PP NOTES DRAIN SIZE FLUSH SUPPLY VOLUME SIZE (GPF) MODEL ADA CHECKED BY: 24. PROTECTION OF PIPES AND PLUMBING SYSTEM COMPONENTS - PIPING AND OTHER SYSTEM COMPONENTS SHALL BE INSTALLED IN SUCH A MANNER SO AS TO PREVENT CORROSION, BREAKAGE, FREEZING, AND PHYSICAL DAMAGE BY OTHER BUILDING COMPONENTS. DOMESTIC WATER SUPPLY ACCESSORY SCHEDULE UNIT PERFORMANCE MAE 23. STRUCTURAL SAFETY - IN THE PROCESS OF INSTALLING OR REPAIRING ANY PART OF A PLUMBING OR DRAINAGE SYSTEM, THE FINISHED FLOOR, WALLS, CEILINGS, TILE OR ANY OTHER PART OF THE BUILDING OR PREMISES THAT MUST BE CHANGED OR REPLACED SHALL REMAIN IN A STRUCTURALLY SAFE CONDITION. POINT OF DISCONNECTION GENERAL DRAWN BY: CARRIER MODEL ETF-80 MANUFACTURER BRADLEY NOTES: 1. NUMBER OF FAUCETS, TRAPS, DRAINS, SUPPLY SETS, AND COVERS SHALL MATCH THE NUMBER OF BOWLS. 2. CARRIER SHALL MATCH LAVATORY MANUFACTURER'S RECOMMENDATIONS. NUMBER OF ARMS SHALL MATCH THE NUMBER OF MOUNTING SLEEVES IN THE DECK. TRAP MODEL S59-4000A MANUFACTURER PROFLO SUPPLIES/STOPS MODEL PFPTB107 MANUFACTURER PROFLO INSULATION/COVERS MODEL PFXCAZ32CLKL12 MANUFACTURER TRUEBRO TAILPIECE MODEL LAV GUARD 2 102-EZ MANUFACTURER PROFLO UNIT CONNECTIONS MODEL PFGD100 CWS SIZE 1/2" HWS SIZE 1/2" DRAIN SIZE 1-1/2" NOTES VENT SIZE 1-1/4" MINIMUM SUPPLY PRESSURE ( PSI ) MAX. HORIZONTAL SPACING (FT) MAX. VERTICAL SPACING (FT) NOTES CAST IRON PIPE 5 15 1 COPPER TUBING, 1-1/4" DIAMETER AND SMALLER 6 10 COPPER TUBING, 1-1/2" DIAMETER AND LARGER 10 10 CPVC TUBING, 1" DIAMETER AND SMALLER 3 10 2 CPVC TUBING, 1-1/4" DIAMETER AND LARGER 4 10 2 STEEL PIPE 12 15 PVC PIPE 4 10 ISSUED: 3.24.2016 DESCRIPTION: 2 BID DOCUMENTS 25 NOTES: 1. MAXIMUM HORIZONTAL SPACING OF CAST IRON HANGERS SHALL BE INCREASED TO 10 FEET WHERE 10-FOOT LENGTHS OF PIPE ARE INSTALLED. 2. MID-STORY GUIDE FOR SIZES 2" AND SMALLER. SHEET: P-001 18031.00 MOUNTING NOTES 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 MATERIAL UNIT CONNECTIONS RCNJ No. 201437-01C PHASE 2 : ALTERATIONS EWC-1 ACCESSIBILITY DESIGNATION SUPPLIES/STOPS RAMAPO COLLEGE OF NEW JERSEY TAG TRAP REVISIONS 19. EQUIPMENT CONNECTIONS: • ALL EQUIPMENT SHALL BE PROVIDED WITH UNIONS AND SHUT-0FF VALVES WHETHER DETAILED OR NOT. • ALL PLUMBING FIXTURES SHALL BE PROVIDED WITH SHUT OFF VALVES. BALL VALVES BOWL 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com PLUMBING - CODES, GENERAL NOTES, AND SCHEDULES GENERAL 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 3/23/2016 10:52:08 AM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. 2. 3. 4. 5. 6. 7. 8. E G J N QQ.1 Q.2 Q.3 IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: B C D 21 KEYED NOTES 20 D1. DISCONNECT, REMOVE, AND DISCARD AREA DRAIN AND ASSOCIATED PIPING. 19 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: D2. DISCONNECT, REMOVE, AND DISCARD GUTTERS AND DOWNSPOUTS. D3. EXCAVATE, REMOVE, AND DISCARD 4" ST PIPING. RESTORATION IS NOT REQUIRED SINCE AREA IS BEING EXPANDED UPON. 18 D4. EXCAVATE, REMOVE, AND DISCARD CLEAN OUT, ELBOWS, AND WYES UP TO TRENCH DRAIN CONNECTION. D5. EXISTING AREA DRAIN TO REMAIN. WYE/TEE CONNECTION AT 4" LATERAL MAIN TO BE REMOVED. 17 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS D6. TRENCH DRAIN AND CONCRETE ENCASEMENT TO REMAIN. PREPARE OUTLET OF TRENCH DRAIN FOR CONNECTION TO NEW LATERAL. D7. EXCAVATE, REMOVE, AND DISCARD 4" ST PIPE. MAINTAIN EXCAVATION FOR NEW LATERAL INSTALLATION. DRAWN BY: Author CHECKED BY: Checker 14 10.3 10" ST (1/8" / 12") 10.9 10.8 A.4 B.7 10.2 10 9 8 D2 7.1 7 4" ST D1 6 5 4 D3 RAMAPO COLLEGE OF NEW JERSEY 11 PLUMBING DEMOLITION 12 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 13 3 2.9 2.1 1.9 2 1 D6 D8 4" ST 4" ST D2 4" ST (1/8" / 12") A F D4 H D7 I K L D5 M O ISSUED: 3.24.2016 DESCRIPTION: 10" ST (1/8" / 12") BID DOCUMENTS SHEET: 1 PLUMBING DEMOLITION - EXTERIOR/UNDERGROUND 1/8" = 1'-0" PD-100 18031.00 15 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 16 D8. REMOVE EXISTING 4"X10" WYE AND MAINTAIN FOR NEW LATERAL TIE-IN. 3/23/2016 10:52:12 AM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. 2. E G J N QQ.1 Q.2 Q.3 3. 22 4. 5. 6. 7. B C D 8. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. 21 3/4" HWR 1 1/2" HWS 1 1/2" CWS SEALED: DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: 20 4" GAS 19 2 1 PD-111 PD-111 KEYED NOTES 0 0 ALTERNATE #1 3/4" HWR 3/4" HWS 1 1/2" CWS FS (E) 18 1 2 2 1/2" GAS 1 PD-112 1 FS (E) FS (E) 1 1/2" CWS 1 1/2" HWS 3/4" HWR FCO (E) 1. DISCONNECT DRAIN FROM HOT/COLD WELL TO ALLOW FOR WELL AND COUNTER REMOVAL. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 2. DISCONNECT SUPPLIES AND DRAIN FROM SINK TO ALLOW FOR COUNTERTOP REMOVALS. 17 1 FCO (E) 1 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com FD (E) 16 FS (E) FS (E) 1 1 1/2" CWS 1 1/2" HWS FD (E) 3/4" HWR 1 1/2" HWS 1 1/2" CWS 3/4" HWR 1/2" CWS 3/4" HWS 3/4" HWR REVISIONS 15 14 10.3 1 FS (E) FS (E) D 13 DRAWN BY: MAE CHECKED BY: MAE/PP 1 2 1 CA BIN ET, ND BATTER NA 01050F KR A BREAD 10.9 10.8 FS (E) 1 1 A.4 B.7 10.2 10 9 8 7.1 7 6 5 4 2.9 3 2.1 1.9 2 1 A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: 1 SCALE, IN FEET PARTIAL DEMOLITION PLAN - GROUND FLOOR 1/8" = 1'-0" 0 8 16 24 NORTH PD-110 18031.00 11 00 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS FS (E) 12 FCO (E) RAMAPO COLLEGE OF NEW JERSEY FS (E) PLUMBING DEMOLITION FIRST FLOOR FCO (E) FD (E) 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 1 1 3/23/2016 10:52:14 AM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION GENERAL NOTES 1. 2. 3. 4. 5. 6. 7. 8. IDENTIFICATION AND/OR ABATEMENT OF HAZARDOUS MATERIALS IS NOT PART OF THIS SCOPE OF WORK. IF ASBESTOS OR OTHER HAZARDOUS MATERIALS ARE ENCOUNTERED, THE CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY. REFER TO SPECIFICATIONS FOR RECYCLING, CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL REQUIREMENTS. OPENING IN THE EXISTING STRUCTURE SMALLER THAN 12" IN ANY DIRECTION ARE NOT IDENTIFIED ON THESE DRAWINGS. SUBCONTRACTORS SHALL BE RESPONSIBLE FOR PROVIDING OPENINGS SMALLER THAN 12" AS REQUIRED FOR INSTALLATION OF THEIR WORK. OPENINGS IN THE EXISTING STRUCTURE SHALL NOT BE MADE WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. DO NOT REMOVE ITEMS WHICH JEOPARDIZE THE STRUCTURAL INTEGRITY OF THE BUILDING. IF HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. PROTECT ADJACENT AREAS AND ITEMS "TO REMAIN" DURING DEMOLITION/CONSTRUCTION. REPAIR/REPLACE ITEMS DAMAGED DURING CONSTRUCTION. IF UNANTICIPATED HIDDEN ELEMENTS OR DETERIORATED ELEMENTS ARE ENCOUNTERED, NOTIFY THE OWNERS REPRESENTATIVE IMMEDIATELY. REFER TO CONSULTANT DRAWINGS FOR ADDITIONAL DEMOLITION WORK. REVIEW w/ OWNER TO DETERMINE WHAT, IF ANYTHING, WILL BE REMOVED BY OWNER AND WHAT, IF ANYTHING, IS TO BE SALVAGED & TURNED OVER TO OWNER. SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: KEYED NOTES D1. DISCONNECT, REMOVE, AND DISCARD WATER CLOSET, FLUSH VALVE, AND CARRIER. TYPICAL FOR 6 IN THIS ROOM. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: D2. DISCONNECT, REMOVE, AND DISCARD LAVATORY, FAUCET, SUPPLIES, DRAIN, AND CARRIER. TYPICAL FOR 6 IN THIS ROOM. D3. DISCONNECT, REMOVE, AND DISCARD WATER CLOSET, FLUSH VALVE, AND CARRIER. TYPICAL FOR 2 IN THIS ROOM. D4. DISCONNECT, REMOVE, AND DISCARD URINAL, FLUSH VALVE, AND CARRIER. TYPICAL FOR 2 IN THIS ROOM. D5. DISCONNECT, REMOVE, AND DISCARD LAVATORY, FAUCET, SUPPLIES, DRAIN, AND CARRIER. TYPICAL FOR 3 IN THIS ROOM. 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS D6. DISCONNECT, REMOVE, AND DISCARD FLOOR DRAIN STRAINER AND BODY. D7. MAINTAIN SUPPLY PIPING TO UPPER FLOOR CHASE. D8. DISCONNECT 2" SAN AT ELBOW. MAINTAIN VERTICAL PIPING TO SECOND FLOOR FOR NEW CONNECTION. REMOVE HORIZONTAL PIPING ABOVE CEILING TO FIRST FLOOR CHASE. D9. DISCONNECT 6" ST AT ELBOW. MAINTAIN VERTICAL PIPING TO SECOND FLOOR FOR NEW CONNECTION. REMOVE HORIZONTAL PIPING ABOVE CEILING TO FIRST FLOOR CHASE. DRAWN BY: MAE CHECKED BY: MAE/PP D10. DISCONNECT, REMOVE AND DISCARD DRINKING FOUNTAIN. REMOVE PIPING SUPPLY AND VENT PIPING IN WALL TO CEILING. CONTINUE VENT REMOVAL TO WATER CLOSET CHASE. REMOVE SAN PIPING TO FLOOR. D16. REMOVE SAN PIPING IN CHASE THROUGH FLOOR SLAB. REMOVE VENT PIPING TO TEE CONNECTION ABOVE CEILING. MAINTAIN TEE FOR NEW CONNECTION. REMOVE SUPPLY PIPING TO CEILING AND MAINTAIN FOR NEW CONNECTION. D17. REMOVE SAN, CWS, AND VENT PIPING WITHIN CHASE SERVING FIRST FLOOR FIXTURES. PIPING SERVING SECOND FLOOR FIXTURES SHALL BE REMOVED TO THE CEILING LEVEL AND REMOVAL CONTINUED AS DIRECTED BY OTHER KEYED NOTES. SAN PIPING THROUGH FLOOR SHALL BE REMOVED. D18. REMOVE SAN, CWS, HWS AND VENT PIPING WITHIN CHASE SERVING FIRST FLOOR FIXTURES. PIPING SERVING SECOND FLOOR FIXTURES SHALL BE REMOVED TO THE CEILING LEVEL AND REMOVAL CONTINUED AS DIRECTED BY OTHER KEYED NOTES. SAN PIPING THROUGH FLOOR SHALL BE REMOVED. --- D19. MAINTAIN 3" ST PIPING FROM SECOND FLOOR, THROUGH GROUND FLOOR, TO BELOW GROUND. D16 D20. TERMINATION POINT OF PIPING REMOVAL. D21. REMOVE AND DISCARD P-TRAP AND PIPING ASSOCIATED WITH FLOOR DRAIN. D1 D15 D2 D12 FCO (E) 24 D7 D27 4" SAN D21 D25 2 1/2" CWS 1 1/4" HWS 3/4" HWR 2" N SA 2" CWS 2" D7 D27. REMOVE AND DISCARD 4" SAN RISER TO CHASE ABOVE AND ASSOCIATED LATERAL PIPING UP TO SANITARY WYE. CAP BRANCH OF WYE. 3" ST 1 1/2" CWS D28. REMOVE AND DISCARD 4" SAN RISER TO FLOOR CLEANOUT. CAP RISER BRANCH OF WYE. D19 2" CWS D29. REMOVE AND DISCARD 4" RISER TO CHASE AND CONTINUE REMOVAL TO MAIN SANITARY LATERAL. 3/4" HWS --- - 4" SAN 6" ST --- 4" SAN 10" ST 6" ST N SA D26. REMOVE AND DISCARD 2" SAN RISER TO CHASE ABOVE AND ASSOCIATED LATERAL PIPING UP TO SANITARY WYE. CAP BRANCH OF WYE. 2" V D6 - 3" ST D22 D14 4" SAN 3" V -2" V --- 1 1/2" V 3" SAN 8" ST D25. REMOVE AND DISCARD 4" SAN RISER TO CHASE ABOVE AND ASSOCIATED LATERAL PIPING, UP TO AND INCLUDED SANITARY WYE. FCO (E) 4" SA N 2" SAN D13 D24. REMOVE AND DISCARD P-TRAP AND PIPING ASSOCIATED WITH FLOOR DRAIN UP TO WYE CONNECTION TO MAIN. CAP BRANCH OF WYE. D11 2" V 4" SAN D23. REMOVE AND DISCARD 2" SAN FROM DRINKING FOUNTAIN UP TO AND INCLUDING WYE CONNECTION TO MAIN. D5 D6 4" SAN D18 D3 4" SAN 4" SAN D20 2" D22. REMOVE AND DISCARD 6" ST PIPING TO WYE AT UNDERGROUND MAIN. CAP BRANCH OF WYE. 1/2" CWS 1/2" HWS D26 N SA 1 1/4" CWS 2" V D28 4" SAN 4" SAN 10" ST 3/4" HWR 1 1/4" HWS 2 1/2" CWS D17 D20 D29 1/2" CWS 1/2" HWS D8 1 1/2" V 1/2" CWS D4 2" SAN 2" V D23 3" ST (1/8" / 12") 2" V D9 D10 ISSUED: 3.24.2016 2" V 3" ST (1/8" / 12") 2" V DESCRIPTION: --- BID DOCUMENTS CO SHEET: 1 SCALE, IN FEET TOILET ROOM DEMOLITION - UNDERGROUND 2 1/4" = 1'-0" SCALE, IN FEET TOILET ROOM DEMOLITION - GROUND FLOOR 1/4" = 1'-0" 0 4 8 12 NORTH 0 4 8 12 NORTH PD-111 18031.00 D15. REMOVE SUPPLY PIPING BACK TO ELBOW AT 3/4" HWS AND 3/4" HWS SERVING CHASE. PIPING AND VALVE UPSTREAM OF ELBOWS TO REMAIN. REMOVE ALL SAN PIPING TO FLOOR STUB. REMOVE VENT PIPING IN CHASE TO ELBOW AT HORIZONTAL PIPE AT ENTRY TO CHASE. SAN STUB AT FLOOR TO BE REUSED FOR NEW CONNECTION. SUPPLY AND VENT PIPING AT CEILING TO BE REUSED FOR NEW CONNECTION. 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 D14. DISCONNECT 4" SAN AT ELBOW TO VERTICAL. MAINTAIN HORIZONTAL PIPING FOR NEW CONNECTION. RAMAPO COLLEGE OF NEW JERSEY D13. MAINTAIN CWS AND SAN PIPING UP TO SECOND FLOOR CHASE. PLUMBING DEMOLITION TOILET ROOMS D12. DISCONNECT 4" SAN AT ELBOW. MAINTAIN VERTICAL PIPING TO SECOND FLOOR FOR NEW CONNECTION. REMOVE HORIZONTAL PIPING ABOVE CEILING TO FIRST FLOOR CHASE. MAINTAIN 3" V RISER AND HORIZONTAL PIPING ABOVE CEILING. RCNJ No. 201437-01C PHASE 2 : ALTERATIONS D11. DISCONNECT, REMOVE, AND DISCARD FLOOR CLEANOUT COVER AND BODY. 3/23/2016 10:52:16 AM NJDCA ELECTRONIC SUBMITTAL STAMP: DEMOLITION KEYED NOTES D1. DISCONNECT SINK AND REMOVE SUPPLIES BACK TO STOPS AT WALL. PIPING AT WALL TO REMAIN FOR NEW CONNECTION. REMOVE AND DISCARD INDIRECT WASTE PIPING. D2. DISCONNECT, REMOVE, AND DISCARD HAND SINK. MAINTAIN SUPPLY AND DRAIN PIPING AT WALL FOR NEW CONNECTION. D3. DISCONNECT GRIDDLE. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. GAS SIZING BASED ON 450' MAXIMUM DEVELOPED LENGTH FROM 2011 PROJECT WHICH ESTABLISHED MAXIMUM LENGTH TO EQUIPMENT ON THE ROOF. (INTERNATIONAL FUEL GAS CODE, 2015, TABLE 402.4(1), PRESSURE LESS THAN 2.0 PSI, 0.5 PSI DROP). G 2-1/2" GAS 2-1/2" GAS 2" GAS 1-1/4" GAS EXISTING GAS SOLENOID VALVE 1-1/4" GAS EXISTING GRIDDLE 105 MBH G 2" GAS G 1-1/2" GAS 1-1/4" GAS EXISTING CHARBROILER 90 MBH G D5. DISCONNECT STEAMER. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. 1-1/4" GAS 1-1/4" GAS EXISTING STEAMER 125 MBH G D4. DISCONNECT CHARBROILER. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. 1-1/4" GAS EXISTING CONVECTION OVEN 110 MBH G 1-1/4" GAS EXISTING FRYER 110 MBH D6. DISCONNECT CONVECTION OVEN. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. EXISTING RANGE 155 MBH G SEALED: D7. DISCONNECT FRYER. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. D8. DISCONNECT RANGE. SEE GAS PIPING SCHEMATIC ON THIS PAGE FOR EXTENT OF REMOVAL. EXISTING ARRANGEMENT 2 GAS PIPING SCHEMATIC - RESIDENTIAL SERVERY EXISTING/DEMO NOT TO SCALE E CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. C D ARCHITECT: 4" GAS B 21 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 20 ENGINEER: 4" GAS 19 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS 4" GAS 1 1/2" CWS 1 1/2" HWS 3/4" HWR 2 1/2" GAS 4" GAS MAE/PP 15 4" SAN D3 4" SAN 3" SAN 4" SAN FD (E) D4 1/2" CWS 3/4" HWR 1 1/2" HWS 1 1/2" CWS D5 FS (E) 3" SAN 14 D6 FS (E) D7 4" SAN 3" V 13 1/2" CWS 3/4" HWS 3/4" HWR D8 3" V 3" SAN 3" V FS (E) 4" SAN FD (E) 4" SAN 3" SAN 4" SAN 3" SAN 12 4" SAN 11 FCO (E) FS (E) FCO (E) FS (E) ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS A F SHEET: 1 SCALE, IN FEET SERVERY - DEMOLITION - ALTERNATE 1/4" = 1'-0" 0 8 16 24 NORTH PD-112 18031.00 16 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS FS (E) FS (E) RAMAPO COLLEGE OF NEW JERSEY FD (E) PLUMBING DEMOLITION SERVERY - ALTERNATE #1 3" V 4" SAN 4" SAN D2 1 1/2" CWS 1 1/2" HWS 3/4" HWR 3/4" CWS 4" SAN 2 1/2" GAS 3" V 4" SAN 17 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 4" SAN FS (E) FCO (E) 3/4" HWR 3/4" HWS CHECKED BY: D1 3" SAN 4" SAN MAE FS (E) FS (E) 1 1/4" CWS DRAWN BY: 4" SAN 3" SAN 4" SAN 1 1/2" GAS 3" SAN 3/4" HWR 3/4" HWS 1 1/2" CWS 2" GAS 3/4" HWR 1 1/2" HWS 1 1/2" CWS 3" V 4" SAN 1/2" CWS 1/2" HWS 3/4" HWR 1 1/2" HWS 1 1/2" CWS 3/23/2016 10:51:55 AM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION GENERAL NOTES SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: KEYED NOTES P1. PROVIDE 6" ST RISER TO FUTURE FIRST FLOOR WALL/CHASE. SAWCUT, TRENCH, AND EXCAVATE FOR HORIZONTAL INSTALLATION. BACKFILL, COMPACT, AND PATCH CONCRETE SUBSTRATE TO MATCH EXISTING ADJACENT AREAS. REFER TO A-SERIES DRAWINGS FOR FLOOR FINISH. E G J N QQ.1 Q.2 Q.3 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: P2. CONNECT 4" ST TO EXISTING OUTLET FROM TRENCH DRAIN. P3. CONNECT 4" ST FROM AREA DRAIN TO 6" ST LATERAL. P4. PROVIDE 6" ST IN EXCAVATION LEFT BY 4" ST REMOVAL. BACKFILL AND COMPACT EXCAVATION. RESTORE PAVER SYSTEM TO ORIGINAL CONDITION. B C P5. PROVIDE 6"x10" WYE/TEE TO CONNECT 6" ST LATERAL TO EXISTING 10" ST. D 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS 21 20 19 DRAWN BY: MAE CHECKED BY: MAE/PP 10" ST (1/8" / 12") A.4 11 10.9 10.8 B.7 10.2 10 9 8 7.1 7 6 5 4 P1 3 6" ST (1/8" / 12") 2.9 2.1 1.9 2 1 P5 P2 A 4" ST (1/8" / 12") 6" ST (1/8" / 12") 6" ST (1/8" / 12") 4" ST (1/8" / 12") F H P4 I K L P3 M O ISSUED: 3.24.2016 DESCRIPTION: 10" ST (1/8" / 12") BID DOCUMENTS SHEET: 1 PARTIAL UNDERGROUND PLAN 1" = 10'-0" P-100 18031.00 12 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 14 10.3 13 RAMAPO COLLEGE OF NEW JERSEY 15 10" ST (1/8" / 12") 16 PLUMBING UNDERGROUND PLAN 17 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 18 3/23/2016 10:51:57 AM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION GENERAL NOTES SEALED: E G J N QQ.1 Q.2 Q.3 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. B C ARCHITECT: D 21 20 19 KEYED NOTES P1. PROVIDE 4" CLEANOUT PLUG (CO-1) AT OPEN WYE/TEE. P2. PROVIDE 4" ST UP TO ROOF DRAIN (RD-1, 4"). 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: P3. PROVIDE 6" ST DOWN IN LOCATION OF FUTURE INTERIOR WALL. PROVIDE WALL CLEANOUT (WCO-1) 12" A.F.F. 0 0 P4. PROVIDE 3" ST UP TO ROOF DRAIN (RD-1, 3"). 18 P5. PROVIDE 3" CLEANOUT PLUG AT OPEN WYE/TEE. P6. PROVIDE 3" ST CONNECTION TO EXISTING 6" ST DROP IN CHASE. P6 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com REVISIONS 17 3" ST (1/8" / 12") 3" ST (1/8" / 12") P5 BIN ET, 11 ND BATTER A NA 01050F BREAD KR 10.9 10.8 A.4 B.7 10.2 10 9 8 7.1 MAE/PP 7 6 5 4 P3 3 2.9 P2 P2 6" ST (1/8" / 12") P1 6" ST (1/8" / 12") 2.1 1.9 6" ST (1/8" / 12") A P1 2 1 F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS 1 PARTIAL FIRST FLOOR 1/8" = 1'-0" SHEET: P-101 18031.00 CA CHECKED BY: 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 D P4 00 MAE 14 10.3 13 12 DRAWN BY: RCNJ No. 201437-01C PHASE 2 : ALTERATIONS P5 15 RAMAPO COLLEGE OF NEW JERSEY 3" ST (1/8" / 12") PLUMBING GROUND FLOOR PLAN 16 3/23/2016 10:51:59 AM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION GENERAL NOTES SEALED: CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. ARCHITECT: B C D E G J N QQ.1 Q.2 Q.3 KEYED NOTES 19 P1. NOTE DELETED. P2. DETAIL OF DRAIN/DOWNSPOUT FROM ROOF C TO ROOF D SHOWN ON A-SERIES DRAWINGS. 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: 18 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 17 16 REVISIONS 15 DRAWN BY: MAE CHECKED BY: MAE/PP 14 10.3 P2 11 10.9 10.8 Roof C. DESIGN AREA 270 SF. DISCHARGES TO Roof D. A.4 B.7 10.2 10 9 8 7.1 7 6 5 4 Roof A, DESIGN AREA 4200 SF. INCLUDES Roof B. 3 2.9 RD-1, 4" 2.1 1.9 RD-1, 4" 2 1 Roof Area B, DESIGN AREA 400 SF. DISCHARGES TO Roof A. A F H I K L M O ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: 1 PARTIAL ROOF PLAN 1/8" = 1'-0" P-102 18031.00 12 RAMAPO COLLEGE OF NEW JERSEY Roof D. DESIGN AREA 566 SF. INCLUDES Roof D. PLUMBING ROOF PLAN RD-1, 3" 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 13 3/23/2016 10:52:02 AM NJDCA ELECTRONIC SUBMITTAL STAMP: ADDITION/ALTERATION GENERAL NOTES 3" GAS GAS SIZING BASED ON 450' MAXIMUM DEVELOPED LENGTH FROM 2011 PROJECT WHICH ESTABLISHED MAXIMUM LENGTH TO EQUIPMENT ON THE ROOF. (INTERNATIONAL FUEL GAS CODE, 2009, TABLE 402.4(1), PRESSURE LESS THAN 2.0 PSI, 0.5 PSI DROP). G 2-1/2" GAS G 2-1/2" GAS SEALED: ITEM #27 GRIDDLE 100 MBH G ITEM #11 CHARBROILER 136 MBH 1-1/4" GAS 1" GAS 2" GAS ITEM #11 CHARBROILER 136 MBH G 1-1/4" GAS TENSION CABLE VALVE PROVIDED WITH EXHAUST HOOD #2 (PER MECHANICAL DWGS) ITEM #16 FRYER 150 MBH G G 1-1/4" GAS G G G 1-1/4" GAS ITEM #20 FRYER 360 MBH TENSION-CABLE VALVE PROVIDED WITH EXHAUST HOOD #2 (PER MECHANICAL DWGS) 2 1-1/4" GAS G 1-1/4" GAS G 1-1/4" GAS 2-1/2" GAS G 2" GAS G 2-1/2" GAS G 2-1/2" GAS ITEM #21 WOK/RANGE 120 MBH FUTURE GAS FIREPLACE 90 MBH TENSION-CABLE VALVE PROVIDED WITH EXHAUST HOOD #1 (PER MECHANICAL DWGS) GAS PIPING SCHEMATIC - FIREPLACE CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. NOT TO SCALE DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. E B C G J N QQ.1 Q.2 Q.3 ARCHITECT: D KEYED NOTES 1. PROVIDE 1-1/2" INDIRECT WASTE FROM REINSTALLED SINK TO EXISTING FLOOR SINK BELOW COUNTER. 21 ENGINEER: 2. RECONNECT SUPPLIES AND DRAIN TO SINK AFTER COUNTER INSTALLATION. 20 3. PROVIDE 1" GAS CONNECTION TO EXISTING PIPING. PROVIDE GAS VALVE AND PIPE DROP GAS FIREPLACE. 19 1/ 2" 1 1/2" CWS 1 1/2" HWS 3/4" HWR G A S 3" GAS 1/2" CWS 1/2" HWS 1 1/2" GAS 2 1 P-111 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 2 P-111 REVISIONS 0 0 3" V 4" GAS 2 1/2" GAS 1 1/2" CWS 1 1/2" HWS 3/4" HWR FS (E) 16 FS (E) 1 14 10.3 1 3/4" HWR FS (E) 13 D 1 1 3" V FD (E) 3" V 12 1 FCO (E) 2 11 00 CA ND BATTER A NA 01050F BREAD KR BIN ET, FCO (E) FS (E) 1 10.9 10.8 FS (E) FS (E) 1 1 1 1/4" GAS A.4 B.7 10.2 10 9 8 7.1 1 1/4" GAS 7 6 5 4 1 1/4" GAS FIREPLACE, SPECIFIED AND DETAILED ON I-SERIES DRAWINGS 3 2.9 3 2.1 1.9 2 1 ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS A F H I K L M O SHEET: 1 SCALE, IN FEET PARTIAL GROUND FLOOR RENOVATION 1/8" = 1'-0" 0 8 16 24 NORTH P-110 18031.00 3/4" HWR 1 1/2" CWS 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 1 1/2" HWS RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 1 1/2" HWS 1 1/2" CWS 3/4" HWS MAE/PP 3/4" HWR 3" V 1/2" CWS FD (E) 3" ST 1 CHECKED BY: 15 3" ST 1 MAE RAMAPO COLLEGE OF NEW JERSEY FS (E) DRAWN BY: PLUMBING ALTERATIONS FIRST FLOOR FD (E) 17 2 1/2" GAS 1 FS (E) FS (E) 3" V 1 P-112 FCO (E) 18 1 1/2" CWS 3/4" HWR 1 1/2" HWS 2 3/4" CWS 3/4" HWS 3/4" HWR FS (E) 2 1/2" GAS ALTERNATE #1 1 1/2" CWS 3/4" HWS 3/4" HWR 3/23/2016 10:52:03 AM NJDCA ELECTRONIC SUBMITTAL STAMP: 3/4" HWS 2" CWS 1-1/4" HWS SECOND FLOOR 3/4" HWS 2" CWS KEYED NOTES 2" CWS 3/4" HWS 3/4" CWS 1-1/2" CWS 3/4" HWS 3/4" HWS 2" CWS 3/4" HWS 1/2" CWS WHA-AA L-1 L-1 L-1 L-1 1/2" CWS 3/4" HWS L-1 3. PROVIDE 4" SAN DOWN IN CHASE THROUGH FLOOR. 1-1/2" CWS WHA-A 1-1/4" CWS L-1 2. PROVIDE 2" V DOWN INTO CHASE THROUGH FLOOR. 1-1/2" CWS WHA-AA (ONE ON 3/4" HWS, ONE ON 3/4" CWS) 3/4" CWS 3/4" CWS 2" CWS 3/4" HWS 2" CWS WHA-AA (ONE ON 3/4" HWS, ONE ON 3/4" CWS) 1. PROVIDE 1" CWS DROP IN CHASE TO WATER CLOSET. PROVIDE 2" V DOWN IN CHASE THROUGH FLOOR. CONNECT EACH TO EXISTING PIPING AT CEILING. 1-1/2" CWS 1" CWS 1" CWS 2" CWS 2" CWS WHA-B 1-1/2" CWS WHA-AA 4. PROVIDE 1" CWS DROP IN WALL TO WATER CLOSET. WHA-AA 5. PROVIDE 2" V DOWN IN WALL THROUGH FLOOR. L-1 3/4" CWS L-1 L-1 1/2" HWS, TYP FOR (7) L-1 THIS RISER U-1 1" CWS HB-1 DFC-1 7. CONNECT NEW VENT LINES TO EXISTING 2" V AT CEILING. 1" CWS 1" CWS WC-1 U-2 HB-1 3/4" HWS HEADER, ENTIRE LENGTH OF CHASE 3/4" CWS HEADER, ENTIRE LENGTH OF CHASE GROUND FLOOR 6. CONNECT 4" SAN FROM CHASE ABOVE TO NEW 4" SAN AT CEILING. L-1 1" CWS 1/2" CWS, TYP FOR (7) L-1 THIS RISER 3/4" CWS 1/2" HWS, TYP. FOR (3) L-1 THIS RISER WC-2 1" CWS 1" CWS SEALED: MS 8. CONNECT 4" SAN LATERAL ABOVE CEILING TO NEW 4" LATERAL MAIN. WHA-AA WC-2 WC-2 WC-2 WC-1 WC-2 WC-1 9. PROVIDE 1/2" CWS AND 1-1/4" V DROPS IN WALL TO DRINKING FOUNTAIN. PROVIDE 1-1/4" SAN DOWN IN WALL, EXPANDING TO 2" SAN AT FLOOR. 1/2" CWS, TYP. FOR (3) L-1 THIS RISER 3/4" HWS, ENTIRE LENGTH OF HEADER 10. CONNECT NEW 1/2" CWS TO EXISTING PIPING ABOVE CEILING. SUPPLY PIPING DIAGRAM 11. CONNECT 3" SAN TO NEW LATERAL ABOVE CEILING. 12. PROVIDE 3/4" HWS BRANCH FROM EXISTING MAIN TO SERVE MEN'S ROOM LAVATORIES. 13. CONNECT 6" ST RISER FROM SECOND FLOOR TO NEW 8" ST LATERAL ABOVE CEILING. 14. CONNECT 2" SAN RISER FROM SECOND FLOOR TO NEW 2" SAN LATERAL ABOVE CEILING. 15. CONNECT 1-1/2" CWS BRANCH TO EXISTING MAIN TO SERVE MEN'S ROOM COLD WATER FIXTURES. 2" SAN SECOND FLOOR 2" V 2" V 2" V 2" V 3" V 2" V 2" V WCO-1 WCO-1 2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 1-1/2" SAN 2" SAN 2" V WC-1 WC-1 FCO-1 WC-2 WC-2 1-1/2" V 1-1/2" V U-1 WC-2 19. CONNECT 1-1/2" V FROM LAVATORIES NORTH OF COLUMN TO EXISTING 1-1/2" V AT CEILING. PROVIDE 2" V FROM FLOOR DRAIN UP TO CEILING AND EXTEND TO 2" V MAIN. 4" SAN U-2 4" SAN 1-1/2" SAN 1-1/2" SAN 2" SAN 1-1/2" SAN 2" SAN 2" SAN 20. COMBINE SAN FROM LAVATORIES TO COMMON 2" SAN DROP AND CONNECT TO EXISTING DROP THROUGH FLOOR. 1-1/4" V 2" V 2" SAN WC-2 L-1 4" SAN WCO-1 2" V 2" SAN FD-1 2" SAN GROUND FLOOR 2" V L-1 1-1/2" V 1-1/4" V L-1 2" V 1-1/4" V L-1 1-1/4" V L-1 2" V FROM KITCHEN STAFF TOILETS 1-1/4" V L-1 1-1/4" V L-1 1-1/4" V L-1 1-1/4" V L-1 1-1/4" V 1-1/4" V 1-1/4" V L-1 1-1/2" V 18. PROVIDE 8" ST DOWN IN WALL THROUGH FLOOR. PROVIDE WALL CLEANOUT 12" A.F.F. 2" V 2" V 1-1/2" V 2" V 1-1/2" V 1-1/2" V DFC-1 MS 2" SAN WC-2 FCO-1 2" SAN WC-2 WC-1 FCO-1 1-1/4" SAN FD-1 4" SAN 4" SAN 4" SAN 4" SAN 4" SAN ENGINEER: 22. PROVIDE 2" V UP TO THROUGH FLOOR. 2" SAN 4" SAN 2" V 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com 21. PROVIDE 3" SAN UP TO WATER CLOSET. 2" V 2" SAN 23. CONNECT 4" SAN RISER TO EXISTING 4" SAN. FCO (E) 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com 24. CONNECT 4" SAN LATERAL TO EXISTING 4" SAN. 2" SAN ARCHITECT: 17. CONNECT 1-1/2" V FROM LAVATORIES NORTH OF COLUMN TO EXISTING 1-1/2" V AT CEILING. 1-1/2" V 2" V FROM LOBBY DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. 16. CONNECT 2" V FROM CHASE TO EXISTING 3" V ABOVE CEILING. 3" V 2" V CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. 4" SAN 2" SAN 25. CONNECT 4" SAN FROM FLOOR DRAIN TO EXISTING 4" SAN. 3" SAN 4" SAN 4" SAN 4" SAN 4" SAN REVISIONS 26. CONNECT 2" SAN FROM DRINKING FOUNTAIN TO EXISTING 4" SAN. 4" SAN 27. PROVIDE 2" SAN UP THROUGH FLOOR. 28. PROVIDE 2" SAN UP THROUGH FLOOR TO CHASE. SAN/VENT PIPING DIAGRAM 29. PROVIDE 2" V UP TO LAVATORY CHASE. 30. PROVIDE 6" ST UP TO LAVATORY CHASE. 3 TOILET ROOM RISERS 31. PROVIDE 4" P-TRAP CONNECTION TO FLOOR DRAIN AND CONTINUE 4" SAN AS SHOWN. DRAWN BY: MAE CHECKED BY: MAE/PP NOT TO SCALE 1 1/4" CWS L-1 20 21 21 21 22 21 4" SAN L-1 4" SAN 3" SAN WC-2 WC-2 10" ST 21 2" V L-1 26 4" ST (1/4") 2" V 3" SAN 21 2" V 2" V 5" ST (1/4") RD (E) 2040 SF 5" ST 6" ST 4" ST 5" ST 5338 SF L-1 WC-2 13 11 12 2" SAN 4" SAN L-1 1/2" CWS 2" V 17 22 10" ST WC-2 14 4" SAN RD (E) 2040 SF 1/2" HWS 3" ST 28 RD (E) 3150 SF 3/4" HWS 4" SAN 8" ST RD (E) 2204 SF 3" ST (1/8" / 12") L-1 21 RD (E) 2204 SF 2" CWS 1 1/2" V 31 30 1/2" CWS L-1 L-1 18 25 RD (E) 930 SF 1 1/2" CWS 10 HB-1 6" ST 7230 SF 1 1/4" V 4" SAN 4" SAN 21 FD-1 2" CWS 2" SAN 3/4" HWS 8" ST (1/8" / 12") 28 3" SAN 4" SAN 2 1/2" CWS 1 1/4" HWS 3/4" HWR L-1 3" SAN U-1 24 3" SAN 31 32 FD-1 1 1/2" V 4" SAN 2" V 8 7 15 4" SAN 21 6 3 U-2 L-1 19 WC-1 16 2" V 4" SAN 29 WC-2 WC-2 RD (E) 330 SF RD ADDITION 566 SF SECOND FLOOR 2" V 2" V 3" ST (1/8" / 12") DFC-1 8" ST 7886 SF 9 3" ST 27 ISSUED: 3.24.2016 4" SAN GROUND FLOOR DESCRIPTION: 8" ST 8216 SF 3" ST 330 SF BID DOCUMENTS 10" ST 13554 SF 1 SCALE, IN FEET ENLARGED TOILET ROOMS - NEW UNDERGROUND 2 1/4" = 1'-0" SCALE, IN FEET ENLARGED TOILET ROOMS PLANS - NEW 4 1/4" = 1'-0" 0 4 8 12 NOT TO SCALE 0 NORTH STORM RISERS - TOILET ROOMS 4 8 12 NORTH SHEET: P-111 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 18031.00 4 1" CWS 3" ST (1/8" / 12") 28 1 1/2" CWS 2" V 23 WC-1 2" V 2" V HB-1 5 RAMAPO COLLEGE OF NEW JERSEY 4 3/4" HWR 1 1/4" HWS 2 1/2" CWS 22 2 PLUMBING ALTERATIONS TOILET ROOMS 1 WC-1 RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 32. COMBINE SAN FROM LAVATORIES AND URINALS TO COMMON 2" SAN DN. 3/23/2016 10:52:06 AM NJDCA ELECTRONIC SUBMITTAL STAMP: KITCHEN EQUIPMENT SCHEDULE GAS SIZING BASED ON 450' MAXIMUM DEVELOPED LENGTH FROM 2011 PROJECT WHICH ESTABLISHED MAXIMUM LENGTH TO EQUIPMENT ON THE ROOF. (INTERNATIONAL FUEL GAS CODE, 2015, TABLE 402.4(1), PRESSURE LESS THAN 2.0 PSI, 0.5 PSI DROP). 1-1/4" GAS EXISTING GAS SOLENOID VALVE G ITEM #4 GRIDDLE 81 MBH G 1-1/2" GAS 1-1/2" GAS ITEM #3 CHARBROILER 102 MBH Phase Amps Cycle Hp 1 1 Sandwich / Salad Preparation Refrigerator Continental Refrig SW72-30M-FB 115 1 60 1-1/4" GAS EXISTING FRYER 150 MBH G G 1-1/2" GAS EXISTING FRYER 110 MBH G Cord & Plug 5-15P Gas Conn. Gas Size(in) Height (in) Gas MBTU 1 Range, 36", 6 Open Burners Vulcan 36S-6B 3/4" 215.0 Charbroiler Vulcan VACB36 3/4" 102.0 4 1 Countertop Griddle Vulcan 948RX 120 1 3/4" 108.0 5 1 Equipment Stand, Refrigerated Base Vulcan ARS84 115 1 12.0 60 6 1 Carving Station / Shelf Hatco DCSB400-3624-2 120 1 10.83 60 7 1 Fryer Vulcan LG500 3/4" 150.0 8 1 Work Table Advance Tabco KSS-305 9 1 Dual Temp Food Well, Drop-In Wells HRCP-7300 115 1 5.6 60 Wells HRCP-7300 208/240 1 14.4/16.7 60 10 1 Drop-In Sink Advance Tabco DI-1-2012 11 1 Microwave Oven ACP RCS10TS 120 1 12 1 Conveyor Toaster Adcraft CVYT-120 120 1 13 1 Reach-In Freezer True STG1F-1S 115 1 6.8 60 1/2 Cord & Plug 5-15P 14 1 Reach-In Refrigerator True STG1R-1S 115 1 4.8 60 1/3 Cord & Plug 5-15P 15 1 Heated Shelf Food Warmer Hatco GRS-72-L 120 1 5-15P 1.0 60 1/2 1.3 1/3 Cord & Plug 5-15P Cord & Plug 5-15P Cord & Plug 5-15P Direct 3.8/5.0 Direct 1-1/2" 15 60 1 60 1.7 Cord & Plug 5-15P 5-15P 60 1.45 Cord & Plug 0.45 Direct SEALED: Spare Number 17 2 Drop-In Hot Well Wells SS-10 120 1 3.75 60 18 1 Display Freezer Entree OFL-40 115 1 1.0 60 19 1 Dipper Well AllPoints 56-1462 20 1 L-Shaped Work Table Advance Tabco KTMS-307 21 4 120 1 2.08 60 115 1 8.2 Decorative Lamp 4 22 1 Reach-In Undercounter Refrigerator Advance Tabco TA-11A-2 Hatco DL-775-CL Hatco DL-SWITCH-16AMP Beverage Air UCR60A 1/8 Cord & Plug 5-15P (2) 1-1/2" .25 Direct 16.0 60 1/4 CONNOR ARCHITECTURE ACCEPTS NO RESPONSIBILITY FOR UNAUTHORIZED REPRODUCTION OR UNAUTHORIZED USE OF THIS DOCUMENT. GAS PIPING SCHEMATIC - RESIDENTIAL SERVERY - ALTERATION EXISTING EQUIPMENT SCHEDULE NOT TO SCALE B C D 21 20 EQ11 11 12 16 EQ13 1 12 EQ12 16 16 EQ10 19 3/4" HWR 1 1/2" HWS 1 1/2" CWS 3" V 4" SAN 2 14 3" V 3/4" HWR 3/4" HWS 1 1/2" CWS EQ22 4" SAN EQ14 7 20 6 EQ9 3" V EQ21 10 4" GAS 2 1/2" GAS FS (E) 4" SAN 4" GAS 13 1 1/2" CWS 1 1/2" HWS 3/4" HWR 3" V 1 1/2" CWS 1 1/2" HWS 3/4" HWR FS (E) 4" SAN 4" SAN 4" SAN 4" SAN EQ8 FCO (E) 4" SAN 8 9 EQ23 FD (E) 6 EXISTING COLD WELL EXISTING HOT WELL EXISTING HOT WELL EXISTING FRYER EXISTING CONVECTION OVEN EXISTING HOT WELL EXISTING REFRIDGERATOR EXISTING WALL MOUNTED SINK 1656 Massachusetts Ave. | Lexington, MA 02420 Tel: 781-652-0114 | connorarchitecture.com ENGINEER: EXISTING HOT WELL EXISTING HOT WELL EXISTING IMPINGER EXISTING PAN RACK EXISTING PIZZA MAKE TABLE 49 Court Street | P.O. Box 1980 | Binghamton, NY 13902 Tel: 607-723-9421 | mjinc.com EXISTING COLD WELL EXISTING COLD WELL REVISIONS EXISTING COLD WELL EXISTING HAND SINK EXISTING HOT WELL EXISTING HOT WELL EXISTING SINK EXISTING UNDERCOUNTER REFRIDGERATOR EXISTING UNDERCOUNTER REFRIDGERATOR EXISTING HOT WELL FS (E) FS (E) EQ15 15 4 5 4" SAN EQ5 3" SAN 4" SAN 1/2" CWS 3" V UP 5 3 5 EQ7 FS (E) 3" SAN EQ4 4" SAN FD (E) 5 V1 14 FS (E) EQ16 EQ3 5 7 5 EQ6 5 2 ADDITION/ALTERATION 13 GENERAL NOTES FS-1 4" SAN 3 ARCHITECT: 17 16 V1 DESSERT EQ16 GRILL EQ3 EQ4 EQ6 EQ7 HOMETOWN EQ5 EQ8 EQ9 MEDITERRANEAN EQ1 EQ2 PIZZA EQ10 EQ11 EQ12 SALAD EQ17 EQ18 SANDWICH EQ19 EQ20 WOK EQ14 EQ15 EQ21 EQ22 EQ23 BREAKFAST EQ13 DRAWINGS ARE FOR GENERAL PURPOSES ONLY. NO MEASUREMENTS SHALL BE SCALED OFF DRAWINGS. ALL MEASUREMENTS SHALL BE VERIFIED IN FIELD. DRAWN BY: MAE CHECKED BY: MAE/PP 1 1/2" CWS 1 1/2" HWS 3/4" HWR 3/4" HWR 1 1/2" HWS 1 1/2" CWS FS-1 4" SAN 3" SAN 3/4" HWR 3/4" HWS 2 NEMA 1 1 NEW ARRANGEMENT Connection Type Direct Waste Conn. Height(in) 2 16 ITEM #2 RANGE 215 MBH 7.6 Kw Direct Waste Size 3 1 1-1/2" GAS 1-1/4" GAS Voltage Indirect Waste Size 4" N SA EQ20 FS (E) KEYED NOTES 22 EQ17 3" V 3" SAN 3" V 19 4" SAN EQ2 4" SAN 3" SAN 4 4" SAN 1. PROVIDE 1-1/2" INDIRECT WASTE PIPING FROM ITEM EQ-13 TO FLOOR SINK (FS-1, 3") INSTALLED BELOW CABINET. PROVIDE 3" PTRAP AND EXTEND 3" SAN TO EXISTING VENTED 4" SAN PIPING BELOW FLOOR. FD (E) 12 11 4" SAN FCO (E) FCO (E) EQ18 FS (E) 3. PROVIDE 1-1/2" INDIRECT WASTE PIPING FROM ITEM EQ-16 TO FLOOR SINK (FS-1, 4") INSTALLED BELOW CABINET. PROVIDE 3" PTRAP AND EXTEND 4" SAN TO EXISTING VENTED 4" SAN PIPING BELOW FLOOR. FS (E) 17 2. PROVIDE 1/2" CWS AND 1/2" HWS FROM PIPING AT STRUCTURE ABOVE, DOWN IN WALL AND CONNECT TO ITEM #10. EXTEND 11/4" INDIRECT WASTE FROM ITEM #10 TO EXISTING FLOOR SINK BELOW ADJACENT COOKING STATION. EQ1 4. EXTEND 1/2" CWS FROM ADJACENT SINK TO ITEM #19 INLET. PROVIDE 1-1/2" INDIRECT WASTE FROM ITEMP #19 TO FLOOR SINK BENEATH EXISTING COOKING STATION. 17 EQ19 5. SEE GAS PIPING SCHEMATICS ON THIS SHEET FOR PIPING MODIFICATIONS TO EQUIPMENT BELOW EXHAUST HOOD. 1 6. CONNECT ITEM #8 TO EXISTING SUPPLY AND DRAIN PIPING IN WALL SERVING PREVIOUS HAND SINK. 7. CONNECT ITEM #20 TO EXISTING SUPPLY PIPING IN WALL SERVING PREVIOUS SINK. EXTEND 1-1/2" INDIRECT WASTE (QTY 2) TO EXISTING FLOOR SINK BELOW COUNTER. ISSUED: 3.24.2016 DESCRIPTION: BID DOCUMENTS SHEET: 1 SCALE, IN FEET SERVERY - RENOVATION - ALTERNATE 1/4" = 1'-0" 0 4 8 12 NORTH F H P-112 18031.00 2" GAS Model Hot Water Conn. Height(in) 505 RAMAPO VALLEY RD. MAHWAH, NJ 07430 2" GAS Mfr Hot Water (in) RCNJ No. 201437-01C PHASE 2 : ALTERATIONS 2-1/2" GAS Category Cold Water Conn. Height(in) RAMAPO COLLEGE OF NEW JERSEY 2-1/2" GAS Quantity Cold Water (in) PLUMBING ALTERATIONS SERVERY - ALTERNATE #1 G ItemNo Electrical Connection Height