Lift Parks at Ground Floor Level (where appropriate) with Doors Open on Activation of Fire Alarm Laboratory Mains Gas Supply Solenoid Closes on Activation of Fire Alarm Panel Boiler Supply Gas Solenoid Closes and Boilers Shut Down on Fire Alarm Activation Laboratory Fume Cupboard Extraction Fans / Systems Must be Maintained on Activation of Fire Alarm Containment Laboratory AHU Fan Extract & Pressure Systems Must be Maintained on Activation of Fire Alarm BSU Area Plant Provided with Essential Power on Activation of Fire Alarm AHU's and Extract Fans Close Down / Disabled on Activation of Fire Alarm Atrium / Stair Smoke Vent Closes (if Open Under Temperature Control) on Activation of Fire Alarm Fire Signal (for 999 Action) - Raised at UCL Security Control Room Access Control Mechanisms on Doors Release on Activation of Fire Alarm (Except BSU) X X X X X X X X X X X X X X X X X X Break Glass (Manual Call Points) Provided In All Plant Rooms as per BS 5839-1 X X X X X X X X X X X X X X X X X X X X X X Weather Proofed Manual Call Points - Provided in External Roof Plant Areas as per BS 5839-1 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X Where buildings with separate Fire Alarm Systems join & occupants can move freely between the buildings preventative measures required to stop access when either building's fire alarm system has activated. X X X X X X X X X X X X Noisy or Very Quite Conditions (Sound Proof Rooms) Etc X X X X X X X X X Disability and MIP Requirements X X X X X X X Fireman's Switch for Atrium / Stair Smoke Vent - Open Position X Provide All Floors with Automatic Fire Detection (AFD) to a minimum of Life Risk 3 (L3) Standard as per BS5839-1 Provided Automatic Fire Detection (AFD) to an Enhanced Life Risk 1 or 2 (L1 / L2) Standard as per BS5839-1 Fireman's Switch Override for ALL AHU's & Extract Fans Off Position Fireman's Switch Override for ALL AHU's & Extract Fans All Extract Smoke Position X Fireman's Switch for ALL Boilers and Plant Systems - Off Position X Sprinkler or Gas Suppression System Activation X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X Requirements To Be Discussed with UCL Fire Officer X Automatic Extraction Fans for Basement Smoke Control X Fault Signal - Raised at UCL Security Control Room X Pre-Alarm Signal - Raised at UCL Security Control Room X Allow Certain Essential Building Services to Remain Active on Activation of Fire Alarm Break Glass (Manual Call Points) Provided on All Floors as per BS5839: Part1 UCL FIRE ALARM CONDITION GENERAL CAUSE (Down ) & EFFECT (Across ) SCHEDULE Provided All Mechanical Control Panel(s) with Fire Alarm Signal Interfaced from Fire Alarm Panel DDA Vibrating Pagers (where fitted) Operate on Activation of Fire Alarm Philip Payne Illuminated 'Do Not Enter' Warning Signs (where fitted) Operate on Activation of Fire Alarm Silent Tone Sounders (where fitted) Operate on Activation of Fire Alarm Flashing Beacons (where fitted) in Quiet / Noise Locations - Operate on Activation of Fire Alarm Activation of Fire Alarm System & Operation of Fire Evacuation Warning Sounders Emergency Escape Lighting (where provided) on Activated on Fire Alarm System UCL Fire Technical Note - TN063 UCL Fire Alarm Activation Condition - Suggested General Cause Effect Matrix X X X X This guide is to be regarded as a general statement of UCL local requirements, information or guidance only & supplements relevant British Standards or Manufacturers Instructions etc. Issued by the - Fire Safety Manager, UCL, Estates, Gower Street, London, WC1E 6BT Date Last Amended: Dec 15