NORMES DE FIABILITÉ DE LA NERC - INT (VERSION ANGLAISE) Demande R-3699-2009

advertisement
COORDONNATEUR
DE LA FIABILITÉ
Demande R-3699-2009
Direction Contrôle des mouvements d’énergie
NORMES DE FIABILITÉ DE LA NERC - INT
(VERSION ANGLAISE)
Original : 2013-03-27
HQCMÉ-8, Document 2.5
(En liasse)
Standard INT-001-3 — Interchange Information
A. Introduction
1. Title: Interchange Information
2. Number:
INT-001-3
3. Purpose:
To ensure that Interchange information is submitted to the NERCidentified reliability analysis service.
4. Applicability:
4.1. Purchase-Selling Entities.
4.2. Balancing Authorities.
5. Effective Date:
August 27, 2008 (U.S.)
NERC Board Approved: October 9, 2007
B. Requirements
R1. The Load-Serving, Purchasing-Selling Entity shall ensure that Arranged Interchange is
submitted to the Interchange Authority for:
R1.1. All Dynamic Schedules at the expected average MW profile for each hour.
R2. The Sink Balancing Authority shall ensure that Arranged Interchange is submitted to
the Interchange Authority:
R2.1. If a Purchasing-Selling Entity is not involved in the Interchange, such as
delivery from a jointly owned generator.
R2.2. For each bilateral Inadvertent Interchange payback.
C. Measures
M1. The Purchasing-Selling Entity that serves the load shall have and provide upon request
evidence that could include but is not limited to, its Interchange Transaction tags
operator logs, voice recordings or transcripts of voice recordings, electronic
communications, computer printouts or other equivalent evidence that will be used to
confirm that Arranged Interchange was submitted to the Interchange Authority for all
Dynamic Schedules at the expected average MW profile for each hour as specified in
Requirement 1.
M2. Each Sink Balancing Authority shall have and provide upon request evidence that
could include but is not limited to, Interchange Transaction tags operator logs, voice
recordings or transcripts of voice recordings, electronic communications, computer
printouts, or other equivalent evidence that will be used to confirm that Arranged
Interchange was submitted to the Interchange Authority as specified in Requirements
2.1 and 2.2.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organizations shall be responsible for compliance
monitoring.
Approved by Board of Trustees: October 9, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 1 of 3
Standard INT-001-3 — Interchange Information
1.2. Compliance Monitoring and Reset Time Frame
One or more of the following methods will be used to assess compliance:
- Self-certification (Conducted annually with submission according to
schedule.)
- Spot Check Audits (Conducted anytime with up to 30 days notice given to
prepare.)
- Periodic Audit (Conducted once every three years according to schedule.)
- Triggered Investigations (Notification of an investigation must be made
within 60 days of an event or complaint of noncompliance. The entity will
have up to 30 days to prepare for the investigation. An entity may request an
extension of the preparation period and the extension will be considered by
the Compliance Monitor on a case-by-case basis.)
The Performance-Reset Period shall be 12 months from the last finding of noncompliance.
1.3. Data Retention
The Purchasing-Selling Entity that serves load and Sink Balancing Authority shall
each keep 90 days of historical data (evidence).
If an entity is found non-compliant the entity shall keep information related to the
noncompliance until found compliant or for two years plus the current year,
whichever is longer.
Evidence used as part of a triggered investigation shall be retained by the entity
being investigated for one year from the date that the investigation is closed, as
determined by the Compliance Monitor,
The Compliance Monitor shall keep the last periodic audit report and all requested
and submitted subsequent compliance records.
1.4. Additional Compliance Information
None.
2.
Levels of Non-Compliance for Sink Balancing Authorities:
2.1. Level 1: One instance of not submitting Arranged Interchange to the Interchange
Authority as specified in R2.1 and R2.2.
2.2. Level 2: Two instances of not submitting Arranged Interchange to the Interchange
Authority as specified in R2.1 and 2.2.
2.3. Level 3: Three instances of not submitting Arranged Interchange to the
Interchange Authority as specified in R2.1 and 2.2.
2.4. Level 4: Four or more instances of not submitting Arranged Interchange to the
Interchange Authority as specified in R2.1 and 2.2.
3.
Levels of Non-Compliance for Purchasing-Selling Entities that Serve Load:
3.1. Level 1: One instance of not submitting Arranged Interchange to the Interchange
Authority as specified in R1.
Approved by Board of Trustees: October 9, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 2 of 3
Standard INT-001-3 — Interchange Information
3.2. Level 2: Two instances of not submitting Arranged Interchange to the Interchange
Authority as specified in R1.
3.3. Level 3: Three instances of not submitting Arranged Interchange to the
Interchange Authority as specified in R1.
3.4. Level 4: Four or more instances of not submitting Arranged Interchange to the
Interchange Authority as specified in R1.
E. Regional Differences
MISO Energy Flow Information Waiver effective on July 16, 2003.
1.
Version History
Version
Date
Action
Change Tracking
0
April 1, 2005
Effective Date
New
1
May 2, 2006
Adopted by Board of Trustees
Revised
2
November 1,
2006
Adopted by Board of Trustees
Revised
3
October 9,
2007
Adopted by Board of Trustees (Remove
WECC Waiver)
Revised
3
July 21, 2008
Regulatory Approval (Remove WECC
Waiver)
Revised
Approved by Board of Trustees: October 9, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 3 of 3
Standard INT-001-3 — Interchange Information
Appendix QC-INT-001-3
Provisions specific to the standard INT-001-3 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Interchange information
2.
Number:
INT-001-3
3.
Purpose:
No specific provision
4.
Applicability:
No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope: Main Transmission System (MTS)
B.
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance for Sink Balancing Authority:
No specific provision
3.
Levels of Non-Compliance for Purchasing-Selling Entities that Serve Load:
No specific provision
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
Page QC-1 of 2
Standard INT-001-3 — Interchange Information
Appendix QC-INT-001-3
Provisions specific to the standard INT-001-3 applicable in Québec
E.
Regional Differences
No specific provision
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
1
Date
Month xx, 201x
Action
Change Tracking
Effective Date
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
New
Page QC-2 of 2
S ta n d a rd INT-003-3 — In te rc h a n g e Tra n s a c tio n Im p le m e n ta tio n
A. Introduction
1.
Title:
Interchange Transaction Implementation
2.
Number:
INT-003-3
3.
Purpose:
To ensure Balancing Authorities confirm Interchange Schedules with Adjacent Balancing
Authorities prior to implementing the schedules in their Area Control Error (ACE) equations.
4.
Applicability
4.1. Balancing Authorities.
5.
Effective Date:
First day of first calendar quarter after applicable regulatory approval, or in
those jurisdictions where no regulatory approval is required, the first day of the first calendar
quarter after Board of Trustees adoption.
B. Requirements
R1.
Each Receiving Balancing Authority shall confirm Interchange Schedules with the Sending
Balancing Authority prior to implementation in the Balancing Authority’s ACE equation.
(Violation Risk Factor: Medium)
R1.1.
The Sending Balancing Authority and Receiving Balancing Authority shall agree on
Interchange as received from the Interchange Authority, including: (Violation Risk
Factor: Lower)
R1.1.1. Interchange Schedule start and end time. (Violation Risk Factor: Lower)
R1.1.2. Energy profile. (Violation Risk Factor: Lower)
R1.2.
If a high voltage direct current (HVDC) tie is on the Scheduling Path, then the
Sending Balancing Authorities and Receiving Balancing Authorities shall coordinate
the Interchange Schedule with the Transmission Operator of the HVDC tie. (Violation
Risk Factor: Medium)
C. Measures
M1. Each Receiving and Sending Balancing Authority shall have and provide upon request
evidence that could include, but is not limited to, interchange transaction tags, operator logs,
voice recordings or transcripts of voice recordings, electronic communications, computer
printouts, or other equivalent evidence that will be used to confirm that each Interchange
Schedule’s start and end time, and energy profile were confirmed prior to implementation in
the Balancing Authority’s ACE equation. (Requirement R1, R1.1, R1.1.1 & R1.1.2)
M2. Each Receiving and Sending Balancing Authority shall have and provide upon request
evidence that could include, but is not limited to, interchange transaction tags, operator logs,
voice recordings or transcripts of voice recordings, electronic communications, computer
printouts, or other equivalent evidence that will be used to confirm that it coordinated the
Interchange Schedule with the Transmission Operator of the HVDC tie as specified in
Requirement 1.2.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organizations shall be responsible for compliance monitoring.
Approved by the Board of Trustees: November 5, 2009
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
1
S ta n d a rd INT-003-3 — In te rc h a n g e Tra n s a c tio n Im p le m e n ta tio n
1.2. Compliance Monitoring and Reset Time Frame
One or more of the following methods will be used to assess compliance:
-
Self-certification (Conducted annually with submission according to schedule.)
-
Spot Check Audits (Conducted anytime with up to 30 days notice given to prepare.)
-
Periodic Audit (Conducted once every three years according to schedule.)
-
Triggered Investigations (Notification of an investigation must be made within 60
days of an event or complaint of noncompliance. The entity will have up to 30 days
to prepare for the investigation. An entity may request an extension of the
preparation period and the extension will be considered by the Compliance Monitor
on a case-by-case basis.)
The Performance-Reset Period shall be 12 months from the last finding of noncompliance.
1.3. Data Retention
Each Balancing Authority shall keep 90 days of historical data (evidence).
If an entity is found non-compliant the entity shall keep information related to the
noncompliance until found compliant or for two years plus the current year, whichever is
longer.
Evidence used as part of a triggered investigation shall be retained by the entity being
investigated for one year from the date that the investigation is closed, as determined by
the Compliance Monitor,
The Compliance Monitor shall keep the last periodic audit report and all requested and
submitted subsequent compliance records.
1.4. Additional Compliance Information
None.
Approved by the Board of Trustees: November 5, 2009
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
2
S ta n d a rd INT-003-3 — In te rc h a n g e Tra n s a c tio n Im p le m e n ta tio n
2.
R#
Violation Severity Levels:
Lower VSL
Moderate VSL
High VSL
R1
There shall be a separate Lower
VSL, if either of the following
conditions exists: One instance of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2. One instance of
not coordinating the Interchange
Schedule with the Transmission
Operator of the HVDC tie as
specified in R1.2
There shall be a separate Moderate
VSL, if either of the following
conditions exists: Two instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2. Two instances
of not coordinating the Interchange
Schedule with the Transmission
Operator of the HVDC tie as
specified in R1.2
There shall be a separate High
VSL, if either of the following
conditions exists: Three instances
of entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2. Three instances
of not coordinating the Interchange
Schedule with the Transmission
Operator of the HVDC tie as
specified in R1.2
There shall be a separate Severe
VSL, if either of the following
conditions exists: Four or more
instances of entering a schedule
into its ACE equation without
confirming the schedule as
specified in R1, R1.1, R1.1.1 and
R1.1.2. Four or more instances of
not coordinating the Interchange
Schedule with the Transmission
Operator of the HVDC tie as
specified in R1.2
R1.1
The Balancing Authority
experienced one instance of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced two instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced three instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced four instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
R1.1.1
The Balancing Authority
experienced one instance of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced two instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced three instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced four instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
R1.1.2
The Balancing Authority
experienced one instance of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced two instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced three instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
The Balancing Authority
experienced four instances of
entering a schedule into its ACE
equation without confirming the
schedule as specified in R1, R1.1,
R1.1.1 and R1.1.2.
R1.2
The sending or receiving
Balancing Authority experienced
The sending or receiving
Balancing Authority experienced
The sending or receiving
Balancing Authority experienced
The sending or receiving
Balancing Authority experienced
Approved by the Board of Trustees: November 5, 2009
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Severe VSL
3
S ta n d a rd INT-003-3 — In te rc h a n g e Tra n s a c tio n Im p le m e n ta tio n
R#
Lower VSL
one instance of not coordinating
the Interchange Schedule with the
Transmission Operator of the
HVDC tie as specified in R1.2
Moderate VSL
two instances of not coordinating
the Interchange Schedule with the
Transmission Operator of the
HVDC tie as specified in R1.2
Approved by the Board of Trustees: November 5, 2009
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
High VSL
three instances of not coordinating
the Interchange Schedule with the
Transmission Operator of the
HVDC tie as specified in R1.2
Severe VSL
four instances of not coordinating
the Interchange Schedule with the
Transmission Operator of the
HVDC tie as specified in R1.2
4
S ta n d a rd INT-003-3 — In te rc h a n g e Tra n s a c tio n Im p le m e n ta tio n
E. Regional Differences
MISO Energy Flow Information Waiver dated July 16, 2003.
Version History
Version
Date
Action
Change Tracking
0
April 1, 2005
Effective Date
New
1
May 2, 2006
Adopted by Board of Trustees
Revised
2
November 1, 2006
Adopted by Board of Trustees
Revised
3
November 5, 2009
Added approved VRFs and VSLs to document.
Revised
Removed MISO Scheduling Agent Waiver, and
MISO Enhanced Scheduling Agent Waiver
(Project 2009-18).
3
November 5, 2009
Approved by the Board of Trustees
3
January 6, 2011
Approved by FERC
Approved by the Board of Trustees: November 5, 2009
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
5
Standard INT-003-3 — Interchange Transaction Implementation
Appendix QC-INT-003-3
Provisions specific to the standard INT-003-3 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A. Introduction
1.
Title:
Interchange Transaction Implementation
2.
Number:
INT-003-3
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date :
5.1. Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2. Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3. Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope: Main Transmission System (MTS)
B. Requirements
No specific provision
C. Measures
No specific provision
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Authority
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with respect
to the reliability standard and its appendix that it adopts.
1.2. Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3. Data Retention
No specific provision
1.4. Additional Compliance Information
No specific provision
2.
Violation Severity Levels
No specific provision
Adopted by the Régie de l’énergie (Decision D-201x-xxxx) : Month xx, 201x
Page QC-1 de 2
Standard INT-003-3 — Interchange Transaction Implementation
Appendix QC-INT-003-3
Provisions specific to the standard INT-003-3 applicable in Québec
E. Regional Differences
No specific provision
F.Violation Risk Factor
No specific provision.
Version History of the Appendix
Version
Date
Action
Adopted by the Régie de l’énergie (Decision D-201x-xxxx) : Month xx, 201x
Change Tracking
Page QC-2 de 2
Standard INT-004-2 — Dynamic Interchange Transaction Modifications
A. Introduction
1.
Title:
Dynamic Interchange Transaction Modifications
2.
Number:
INT-004-2
3.
Purpose: To ensure Dynamic Transfers are adequately tagged to be able to
determine their reliability impacts.
4.
Applicability
4.1. Balancing Authorities
4.2. Reliability Coordinators
4.3. Transmission Operators
4.4. Purchasing-Selling Entities
5.
Effective Date:
August 27, 2008 (U.S.)
NERC Board Approval: October 9, 2007
B. Requirements
R1.
At such time as the reliability event allows for the reloading of the transaction, the
entity that initiated the curtailment shall release the limit on the Interchange
Transaction tag to allow reloading the transaction and shall communicate the release of
the limit to the Sink Balancing Authority.
R2.
The Purchasing-Selling Entity responsible for tagging a Dynamic Interchange Schedule
shall ensure the tag is updated for the next available scheduling hour and future hours
when any one of the following occurs:
R2.1.
The average energy profile in an hour is greater than 250 MW and in that hour
the actual hourly integrated energy deviates from the hourly average energy
profile indicated on the tag by more than +10%.
R2.2.
The average energy profile in an hour is less than or equal to 250 MW and in
that hour the actual hourly integrated energy deviates from the hourly average
energy profile indicated on the tag by more than +25 megawatt-hours.
R2.3.
A Reliability Coordinator or Transmission Operator determines the deviation,
regardless of magnitude, to be a reliability concern and notifies the PurchasingSelling Entity of that determination and the reasons.
C. Measures
M1. The Sink Balancing Authority shall provide evidence that the responsible Purchasing-
Selling Entity revised a tag when the deviation exceeded the criteria in INT-004
Requirement 2.
D. Compliance
1.
Compliance Monitoring Process
Periodic tag audit as prescribed by NERC. For the requested time period, the Sink
Balancing Authority shall provide the instances when Dynamic Schedule deviation
Approved by Board of Trustees: October 9, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 1 of 2
Standard INT-004-2 — Dynamic Interchange Transaction Modifications
exceeded the criteria in INT-004 R2 and shall provide evidence that the responsible
Purchasing-Selling Entity submitted a revised tag.
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
One calendar year without a violation from the time of the violation.
1.3. Data Retention
Three months.
1.4. Additional Compliance Information
Not specified.
Levels of Non-Compliance
2.
2.1. Level 1:
Not specified.
2.2. Level 2:
Not specified.
2.3. Level 3:
Not specified.
2.4. Level 4:
Not specified.
E. Regional Differences
None
1.
Version History
Version
Date
Action
Change Tracking
0
April 1, 2005
Effective Date
New
1
May 2, 2006
Board of Trustees Approval
Revised
2
October 9,
2007
Board of Trustees Approval (Removal
of WECC Waiver)
Revised
2
July 21, 2008
FERC Approval
Revised
Approved by Board of Trustees: October 9, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 2 of 2
Standard INT-004-2 — Dynamic Interchange Transaction Modifications
Appendix QC-INT-004-2
Provisions specific to the standard INT-004-2 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Dynamic Interchange Transaction Modifications
2.
Number:
INT-004-2
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope:
B.
Main Transmission System (MTS)
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
No specific provision
E.
Regional Differences
1.
No specific provision
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
Page QC-1 of 2
Standard INT-004-2 — Dynamic Interchange Transaction Modifications
Appendix QC-INT-004-2
Provisions specific to the standard INT-004-2 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
1
Date
Month xx, 201x
Action
Change Tracking
Effective Date
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
New
Page QC-2 of 2
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
A. Introduction
1.
Title:
Interchange Authority Distributes Arranged Interchange
2.
Number:
INT-005-3
3.
Purpose: To ensure that the implementation of Interchange between Source and
Sink Balancing Authorities is distributed by an Interchange Authority such that
Interchange information is available for reliability assessments.
4.
Applicability:
4.1. Interchange Authority.
5.
Effective Date:
July 1, 2010
B. Requirements
R1.
Prior to the expiration of the time period defined in the timing requirements tables in this
standard, Column A, the Interchange Authority shall distribute the Arranged Interchange
information for reliability assessment to all reliability entities involved in the Interchange.
R1.1.
When a Balancing Authority or Reliability Coordinator initiates a Curtailment to
Confirmed or Implemented Interchange for reliability, the Interchange Authority shall
distribute the Arranged Interchange information for reliability assessment only to the
Source Balancing Authority and the Sink Balancing Authority.
C. Measures
M1. For each Arranged Interchange, the Interchange Authority shall be able to provide evidence
that it has distributed the Arranged Interchange information to all reliability entities involved in
the Interchange within the applicable time frame.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last noncompliance to Requirement 1.
1.3. Data Retention
The Interchange Authority shall keep 90 days of historical data. The Compliance
Monitor shall keep audit records for a minimum of three calendar years.
1.4. Additional Compliance Information
Each Interchange Authority shall demonstrate compliance to the Compliance
Monitor within the first year that this standard becomes effective or the first year
the entity commences operation by self-certification to the Compliance Monitor.
Subsequent to the initial compliance review, compliance may be:
1.4.1
Verified by audit at least once every three years.
1.4.2
Verified by spot checks in years between audits.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 1 of 6
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
1.4.3
Verified by annual audits of noncompliant Interchange Authorities, until
compliance is demonstrated.
1.4.4
Verified at any time as the result of a specific complaint of failure to
perform R1. Complaints must be lodged within 60 days of the incident.
The Compliance Monitor will evaluate complaints.
Each Interchange Authority shall make the following available for inspection by
the Compliance Monitor upon request:
1.4.5
For compliance audits and spot checks, relevant data and system log
records for the audit period which indicate the Interchange Authority’s
distribution of all Arranged Interchange information to all reliability
entities involved in an Interchange. The Compliance Monitor may request
up to a three month period of historical data ending with the date the
request is received by the Interchange Authority.
1.4.6
For specific complaints, only those data and system log records associated
with the specific Interchange event contained in the complaint which
indicate that the Interchange Authority distributed the Arranged
Interchange information to all reliability entities involved in that specific
Interchange.
Levels of Non-Compliance
2.
One occurrence 1 of not distributing information to all involved
reliability entities as described in R1.
2.1. Level 1:
Two occurrences1 of not distributing information to all involved
reliability entities as described in R1.
2.2. Level 2:
Three occurrences1 of not distributing information to all involved
reliability entities as described in R1.
2.3. Level 3:
Four or more occurrences1 of not distributing information to all
involved reliability entities as described in R1 or no evidence provided.
2.4. Level 4:
E. Regional Differences
None
Version History
Version
Date
Action
Change Tracking
1
May 2, 2006
Approved by BOT
New
2
May 2, 2007
Approved by BOT
Revised
3
April 8, 2010
Approved by FERC, Effective July 1,
2010
1
This does not include instances of not distributing information due to extenuating circumstances approved by the
Compliance Monitor.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 2 of 6
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
Timing Requirements for all Interconnections except WECC
Request for
Interchange
Submitted
Ramp
Start
Interchange Timeline with Minimum
Reliability-Related Response Times
A
B
C
D
If Arranged
2
Interchange (RFI)
is Submitted
IA Assigned
Time
Classification
IA Makes Initial
Distribution of
Arranged Interchange
BA and TSP Conduct
Reliability Assessments
IA Compiles and
Distributes Status
>1 hour after the RFI
start time
ATF
< 1 minute from RFI
submission
Entities have up to 2 hours
to respond.
< 1 minute from receipt of
all Reliability Assessments
NA
<15 minutes prior to
ramp start and <1
hour after the RFI
start time
Late
< 1 minute from RFI
submission
Entities have up to 10
minutes to respond.
< 1 minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
<1 hour and > 15
minutes prior to
ramp start
On-time
< 1 minute from RFI
submission
< 10 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 3 minutes prior to
ramp start
>1 hour to < 4
hours prior to ramp
start
On-time
< 1 minute from RFI
submission
< 20 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 39 minutes prior to
ramp start
> 4 hours prior to
ramp start
On-time
< 1 minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from
IA
< 1 minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes
prior to ramp start
2
BA Prepares
Confirmed Interchange
for Implementation
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 3 of 6
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
Example of Timing Requirements for all Interconnections except WECC
Ramp
Start Time
RFI submit time
relative to start
time
5:55
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment
Interchange
Start Time
8:55
9:40
1 hour
before
ramp start
15
minutes
before
ramp start
20 minutes
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
9:55 10:00
10 minutes
11:00
2 hours
Page 4 of 6
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
Timing Requirements for WECC
A
B
IA Makes Initial
Distribution of
Arranged
Interchange
BA and TSP Conduct
Reliability Assessments
Entities have up to 2 hours to
respond.
If Arranged Interchange
(RFI) 3 is Submitted
IA Assigned
Time
Classification
>1 hour after the start time
ATF
< 1minute from RFI
submission
<10 minutes prior to ramp
start and <1 hour after the
start time
Late
< 1minute from RFI
submission
10 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
11 minutes prior to ramp
start
On-time
12 minutes prior to ramp
start
C
D
IA Compiles and
Distributes Status
BA Prepares Confirmed
Interchange for
Implementation
< 1minute from receipt of
all Reliability Assessments
NA
< 1minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
< 5 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
< 1minute from RFI
submission
< 6 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 7 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
13 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 8 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
14 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 9 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
<1 hour and > 15 minutes
prior to ramp start
On-time
< 1minute from RFI
submission
< 10 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
> 1hour and < 4 hours prior
to ramp start
On-time
< 1minute from RFI
submission
< 20 minutes from Arranged
interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 39 minutes prior to ramp
start
> 4 hours prior to ramp
start
On-time
< 1minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
Submitted before 10:00 PPT
with start time > 00:00 PPT
of following day
On-time
< 1minute from RFI
submission
By 12:00 PPT of day the
Arranged Interchange was
received by the IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
3
Entities have up to 10 minutes
to respond.
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 5 of 6
S ta n d a rd INT-005-3 — In te rc h a n g e Au th o rity Dis trib u te s Arra n g e d In te rc h a n ge
Example of Timing Requirements for WECC
Ramp
Start Time
9:35
RFI submit time
relative to start
time
5:50
9:40
8:50
9:50
10:00
11:00
1 hour
before
ramp start
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment*
Interchange
Start Time
20 minutes
*If submitted before 10:00 PPT with
start time >= 00:00 PPT of the
following day then assessment is
>= 2 hours and by 12:00 PPT
10 minutes
10 minutes
2 hours
Submittal &
Assessment
Times
9:35 - 10
9:36 - 9
9:37 - 8
9:38 - 7
9:39 - 6
9:40 - 5
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 6 of 6
Standard INT-005-3 — Interchange Authority Distributes Arranged Interchange
Appendix QC-INT-005-3
Provisions specific to the standard INT-005-3 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Interchange Authority Distributes Arranged Interchange
2.
Number:
INT-005-3
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope: Main Transmission System (MTS)
B.
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset TimeframeTime Frame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
No specific provision
E.
Regional Differences
No specific provision
Timing Requirements for all Interconnections except WECC
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-1 of 3
Standard INT-005-3 — Interchange Authority Distributes Arranged Interchange
Appendix QC-INT-005-3
Provisions specific to the standard INT-005-3 applicable in Québec
No specific provision
Example of Timing Requirements for all Interconnections except WECC
No specific provision
Timing Requirements for WECC
No specific provision
Example of Timing Requirements for WECC
No specific provision
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-2 of 3
Standard INT-005-3 — Interchange Authority Distributes Arranged Interchange
Appendix QC-INT-005-3
Provisions specific to the standard INT-005-3 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
0
Date
Action
Change Tracking
Month xx, 201x
Effective date
New
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-3 of 3
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
A. Introduction
1.
Title:
Response to Interchange Authority
2.
Number:
INT-006-3
3.
Purpose:
To ensure that each Arranged Interchange is checked for reliability before it is
implemented.
4.
Applicability:
4.1. Balancing Authority.
4.2. Transmission Service Provider.
5.
Effective Date:
July 1, 2010
B. Requirements
R1.
Prior to the expiration of the reliability assessment period defined in the timing requirements
tables in this standard, Column B, the Balancing Authority and Transmission Service Provider
shall respond to each On-time Request for Interchange (RFI), and to each Emergency RFI and
Reliability Adjustment RFI from an Interchange Authority to transition an Arranged
Interchange to a Confirmed Interchange. 1
R1.1.
Each involved Balancing Authority shall evaluate the Arranged Interchange with
respect to:
R1.1.1. Energy profile (ability to support the magnitude of the Interchange).
R1.1.2. Ramp (ability of generation maneuverability to accommodate).
R1.1.3. Scheduling path (proper connectivity of Adjacent Balancing Authorities).
R1.2.
Each involved Transmission Service Provider shall confirm that the transmission
service arrangements associated with the Arranged Interchange have adjacent
Transmission Service Provider connectivity, are valid and prevailing transmission
system limits will not be violated.
C. Measures
M1. The Balancing Authority and Transmission Service Provider shall each provide evidence that it
responded, relative to transitioning an Arranged Interchange to a Confirmed Interchange, to
each On–time Request for Interchange (RFI), and to each Emergency RFI or Reliability
Adjustment RFI from an Interchange Authority within the reliability assessment period defined
in the Timing Table, Column B. The Balancing Authority and Transmission Service Provider
need not provide evidence that it responded to any other requests.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last non-compliance to
Requirement 1.
1
The Balancing Authority and Transmission Service Provider need not provide responses to any other requests.
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 1 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
1.3. Data Retention
The Balancing Authority and Transmission Service Provider shall each keep 90 days of
historical data. The Compliance Monitor shall keep audit records for a minimum of three
calendar years.
1.4. Additional Compliance Information
The Balancing Authority and Transmission Service Provider shall demonstrate
compliance to the Compliance Monitor within the first year that this standard becomes
effective or the first year the entity commences operation by self-certification to the
Compliance Monitor.
Subsequent to the initial compliance review, compliance may be:
1.4.1
Verified by audit at least once every three years.
1.4.2
Verified by spot checks in years between audits.
1.4.3
Verified by annual audits of non-compliant Interchange Authorities, until
compliance is demonstrated.
1.4.4
Verified at any time as the result of a complaint. Complaints must be lodged
within 60 days of the incident. The Compliance Monitor will evaluate
complaints.
The Balancing Authority, and Transmission Service Provider shall make the
following available for inspection by the Compliance Monitor upon request:
2.
1.4.5
For compliance audits and spot checks, relevant data and system log records and
agreements for the audit period which indicate a reliability entity identified in R1
responded to all instances of the Interchange Authority’s communication under
Reliability Standard INT-005 Requirement 1 concerning the pending transition of
an Arranged Interchange to Confirmed Interchange. The Compliance Monitor
may request up to a three month period of historical data ending with the date the
request is received by the Balancing Authority, or Transmission Service
Provider.
1.4.6
For specific complaints, agreements and those data and system log records
associated with the specific Interchange event contained in the complaint which
indicates a reliability entity identified in R1 has responded to the Interchange
Authority’s communication under INT-005 R1 concerning the pending transition
of Arranged Interchange to Confirmed Interchange for that specific Interchange.
Levels of Non-Compliance
2.1. Level 1:
in R1.
One occurrence 2 of not responding to the Interchange Authority as described
2.2. Level 2:
Two occurrences1 of not responding to the Interchange Authority as
described in R1.
2.3. Level 3:
Three occurrences1 of not responding to the Interchange Authority as
described in R1.
2
This does not include instances of not responding due to extenuating circumstances approved by the Compliance
Monitor.
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 2 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
2.4. Level 4:
Four or more occurrences1 of not responding to the Interchange Authority as
described in R1 or no evidence provided.
E. Regional Differences
None.
Version History
Version
Date
Action
Change Tracking
1
May 2, 2006
Approved by BOT
New
2
May 2, 2007
Approved by BOT
Revised
3
April 8, 2010
Approved by FERC, Effective July 1,
2010
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 3 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
Timing Requirements for all Interconnections except WECC
Request for
Interchange
Submitted
Ramp
Start
Interchange Timeline with Minimum
Reliability-Related Response Times
A
B
C
D
If Arranged
3
Interchange (RFI)
is Submitted
IA Assigned
Time
Classification
IA Makes Initial
Distribution of
Arranged Interchange
BA and TSP Conduct
Reliability Assessments
IA Compiles and
Distributes Status
>1 hour after the RFI
start time
ATF
< 1 minute from RFI
submission
Entities have up to 2 hours
to respond.
< 1 minute from receipt of
all Reliability Assessments
NA
<15 minutes prior to
ramp start and <1
hour after the RFI
start time
Late
< 1 minute from RFI
submission
Entities have up to 10
minutes to respond.
< 1 minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
<1 hour and > 15
minutes prior to
ramp start
On-time
< 1 minute from RFI
submission
< 10 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 3 minutes prior to
ramp start
>1 hour to < 4
hours prior to ramp
start
On-time
< 1 minute from RFI
submission
< 20 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 39 minutes prior to
ramp start
> 4 hours prior to
ramp start
On-time
< 1 minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from
IA
< 1 minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes
prior to ramp start
3
BA Prepares
Confirmed Interchange
for Implementation
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 4 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
Example of Timing Requirements for all Interconnections except WECC
Ramp
Start Time
RFI submit time
relative to start
time
5:55
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment
Interchange
Start Time
8:55
9:40
1 hour
before
ramp start
15
minutes
before
ramp start
20 minutes
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
9:55 10:00
10 minutes
11:00
2 hours
Page 5 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
Timing Requirements for WECC
A
B
IA Makes Initial
Distribution of
Arranged
Interchange
BA and TSP Conduct
Reliability Assessments
Entities have up to 2 hours to
respond.
If Arranged Interchange
(RFI) 4 is Submitted
IA Assigned
Time
Classification
>1 hour after the start time
ATF
< 1minute from RFI
submission
<10 minutes prior to ramp
start and <1 hour after the
start time
Late
< 1minute from RFI
submission
10 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
11 minutes prior to ramp
start
On-time
12 minutes prior to ramp
start
C
D
IA Compiles and
Distributes Status
BA Prepares Confirmed
Interchange for
Implementation
< 1minute from receipt of
all Reliability Assessments
NA
< 1minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
< 5 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
< 1minute from RFI
submission
< 6 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 7 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
13 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 8 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
14 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 9 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
<1 hour and > 15 minutes
prior to ramp start
On-time
< 1minute from RFI
submission
< 10 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
> 1hour and < 4 hours prior
to ramp start
On-time
< 1minute from RFI
submission
< 20 minutes from Arranged
interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 39 minutes prior to ramp
start
> 4 hours prior to ramp
start
On-time
< 1minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
Submitted before 10:00 PPT
with start time > 00:00 PPT
of following day
On-time
< 1minute from RFI
submission
By 12:00 PPT of day the
Arranged Interchange was
received by the IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
4
Entities have up to 10 minutes
to respond.
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 6 of 7
S ta n d a rd INT-006-3 — Re s p o n s e to In te rc h a n g e Au th o rity
Example of Timing Requirements for WECC
Ramp
Start Time
9:35
RFI submit time
relative to start
time
5:50
9:40
8:50
9:50
10:00
11:00
1 hour
before
ramp start
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment*
Interchange
Start Time
20 minutes
*If submitted before 10:00 PPT with
start time >= 00:00 PPT of the
following day then assessment is
>= 2 hours and by 12:00 PPT
10 minutes
10 minutes
2 hours
Submittal &
Assessment
Times
9:35 - 10
9:36 - 9
9:37 - 8
9:38 - 7
9:39 - 6
9:40 - 5
Ad o p te d b y NERC Bo a rd o f Tru s te e : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 7 of 7
Standard INT-006-3 — Response to Interchange Authority
Appendix QC-INT-006-3
Provisions specific to the standard INT-006-3 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Response to Interchange Authority
2.
Number:
INT-006-3
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope:
B.
Main Transmission System (MTS)
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time Fframe
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
2.2 to 2.4: Refer to footnote #2 instead of footnote #1.
E.
Regional Differences
No specific provision
Timing Requirements for all Interconnections except WECC
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-1 of 3
Standard INT-006-3 — Response to Interchange Authority
Appendix QC-INT-006-3
Provisions specific to the standard INT-006-3 applicable in Québec
No specific provision
Example of Timing Requirements for all Interconnections except WECC
No specific provision
Timing Requirements for WECC
No specific provision
Example of Timing Requirements for WECC
No specific provision
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-2 of 3
Standard INT-006-3 — Response to Interchange Authority
Appendix QC-INT-006-3
Provisions specific to the standard INT-006-3 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
0
Date
Action
Change Tracking
Month xx, 201x
Effective date
New
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-3 of 3
Standard INT-007-1 — Interchange Confirmation
A. Introduction
1.
Title:
Interchange Confirmation
2.
Number:
INT-007-1
3.
Purpose:
To ensure that each Arranged Interchange is checked for reliability before it is
implemented.
4.
Applicability
4.1. Interchange Authority.
5.
Effective Date:
January 1, 2007
B. Requirements
R1.
The Interchange Authority shall verify that Arranged Interchange is balanced and valid prior to
transitioning Arranged Interchange to Confirmed Interchange by verifying the following:
R1.1.
Source Balancing Authority megawatts equal sink Balancing Authority megawatts
(adjusted for losses, if appropriate).
R1.2.
All reliability entities involved in the Arranged Interchange are currently in the NERC
registry.
R1.3.
The following are defined:
R1.3.1. Generation source and load sink.
R1.3.2. Megawatt profile.
R1.3.3. Ramp start and stop times.
R1.3.4. Interchange duration.
R1.4.
Each Balancing Authority and Transmission Service Provider that received the
Arranged Interchange information from the Interchange Authority for reliability
assessment has provided approval.
C. Measures
M1. For each Arranged Interchange, the Interchange Authority shall show evidence that it has
verified the Arranged Interchange information prior to the dissemination of the Confirmed
Interchange.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last noncompliance to
Requirement 1.
1.3. Data Retention
The Interchange Authority shall keep 90 days of historical data. The Compliance
Monitor shall keep audit records for a minimum of three calendar years.
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 1 of 3
Standard INT-007-1 — Interchange Confirmation
1.4. Additional Compliance Information
Each Interchange Authority shall demonstrate compliance to the Compliance Monitor
within the first year that this standard becomes effective or the first year the entity
commences operation by self-certification to the Compliance Monitor.
Subsequent to the initial compliance review, compliance may be:
1.4.1
Verified by audit at least once every three years.
1.4.2
Verified by spot checks in years between audits.
1.4.3
Verified by annual audits of noncompliant Interchange Authorities, until
compliance is demonstrated.
1.4.4
Verified at any time as the result of a complaint. Complaints must be lodged
within 60 days of the incident. Complaints will be evaluated by the Compliance
Monitor.
Each Interchange Authority shall make the following available for inspection by the
Compliance Monitor upon request:
2.
1.4.5
For compliance audits and spot checks, relevant data and system log records for
the audit period which indicate an Interchange Authority’s verification that all
Arranged Interchange was balanced and valid as defined in R1. The Compliance
Monitor may request up to a three-month period of historical data ending with
the date the request is received by the Interchange Authority.
1.4.6
For specific complaints, only those data and system log records associated with
the specific Interchange event contained in the complaint which indicate an
Interchange Authority’s verification that an Arranged Interchange was balanced
and valid as defined in R1 for that specific Interchange
Levels of Non-Compliance
2.1. Level 1:
in R1.
One occurrence1 where Interchange-related data was not verified as defined
2.2. Level 2:
in R1.
Two occurrences where Interchange-related data was not verified as defined
2.3. Level 3:
Three occurrences where Interchange-related data was not verified as
defined in R1.
2.4. Level 4:
Four or more occurrences where Interchange-related data was not verified as
defined in R1.
E. Regional Differences
None
1
This does not include instances of not verifying due to extenuating circumstances approved by the Compliance
Monitor.
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 2 of 3
Standard INT-007-1 — Interchange Confirmation
Version History
Version
Date
Action
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Change Tracking
Page 3 of 3
Standard INT-007-1 — Interchange Confirmation
Appendix QC-INT-007-1
Provisions specific to the standard INT-007-1 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Interchange Confirmation
2.
Number:
INT-007-1
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope: Main Transmission System (MTS)
B.
Requirements
R1. No specific provision
R1.1. No specific provision
R1.2. All reliability entities involved in the Arranged Interchange are currently in the NERC
registry or the register of entities approved by the Régie de l'énergie
R1.3. No specific provision
R1.4. No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
Page QC-1 of 2
Standard INT-007-1 — Interchange Confirmation
Appendix QC-INT-007-1
Provisions specific to the standard INT-007-1 applicable in Québec
No specific provision
E.
Regional Differences
No specific provision
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
1
Date
Month xx, 201x
Action
Change Tracking
Effective Date
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
New
Page QC-2 of 2
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
A. Introduction
1.
Title:
Interchange Authority Distributes Status
2.
Number:
INT-008-3
3.
Purpose:
To ensure that the implementation of Interchange between Source and
Sink Balancing Authorities is coordinated by an Interchange Authority.
4.
Applicability:
4.1. Interchange Authority.
5.
Effective Date:
July 1, 2010
B. Requirements
R1.
Prior to the expiration of the time period defined in the Timing Table, Column C, the
Interchange Authority shall distribute to all Balancing Authorities (including Balancing
Authorities on both sides of a direct current tie), Transmission Service Providers and
Purchasing-Selling Entities involved in the Arranged Interchange whether or not the
Arranged Interchange has transitioned to a Confirmed Interchange.
For Confirmed Interchange, the Interchange Authority shall also communicate:
R1.1.
R1.1.1. Start and stop times, ramps, and megawatt profile to Balancing
Authorities.
R1.1.2. Necessary Interchange information to NERC-identified reliability
analysis services.
C. Measures
M1. For each Arranged Interchange, the Interchange Authority shall provide evidence that it
has distributed the final status and Confirmed Interchange information specified in
Requirement 1 to all Balancing Authorities, Transmission Service Providers and
Purchasing-Selling Entities involved in the Arranged Interchange within the time
period defined in the Timing Table, Column C. If denied, the Interchange Authority
shall tell all involved parties that approval has been denied.
For each Arranged Interchange that includes a direct current tie, the
Interchange Authority shall provide evidence that it has communicated the
final status to the Balancing Authorities on both sides of the direct current tie,
even if the Balancing Authorities are neither the Source nor Sink for the
Interchange.
M1.1
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last noncompliance to R1.
1.3. Data Retention
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 1 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
The Interchange Authority shall keep 90 days of historical data. The Compliance
Monitor shall keep audit records for a minimum of three calendar years.
1.4. Additional Compliance Information
Each Interchange Authority shall demonstrate compliance to the Compliance
Monitor within the first year that this standard becomes effective or the first year
the entity commences operation by self-certification to the Compliance Monitor.
Subsequent to the initial compliance review, compliance will be:
1.4.1
Verified by audit at least once every three years.
1.4.2
Verified by spot checks in years between audits.
1.4.3
Verified by annual audits of noncompliant Interchange Authorities, until
compliance is demonstrated.
1.4.4
Verified at any time as the result of a complaint. Complaints must be
lodged within 60 days of the incident. Complaints will be evaluated by
the Compliance Monitor.
Each Interchange Authority shall make the following available for inspection by
the Compliance Monitor upon request:
2.
1.4.5
For compliance audits and spot checks, relevant data and system log
records for the audit period which indicate the Interchange Authority’s
distribution of all Arranged Interchange final status and Confirmed
Interchange information to all entities involved in an Interchange per R1.
The Compliance Monitor may request up to a three-month period of
historical data ending with the date the request is received by the
Interchange Authority
1.4.6
For specific complaints, only those data and system log records associated
with the specific Interchange event contained in the complaint which
indicate that the Interchange Authority distributed the Arranged
Interchange final status and Confirmed Interchange information to all
entities involved in that specific Interchange.
Levels of Non-Compliance
One occurrence 1 of not distributing final status and information as
described in R1.
2.1. Level 1:
Two occurrences1 of not distributing final status and information as
described in R1.
2.2. Level 2:
Three occurrences1 of not distributing final status and information as
described in R1.
2.3. Level 3:
1
This does not include instances of not distributing information due to extenuating circumstances approved by the
Compliance Monitor.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 2 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
Four or more occurrences1 of not distributing final status and
information as described in R1 or no evidence provided.
2.4. Level 4:
E. Regional Differences
None.
Version History
Version
Date
Action
Change Tracking
1
May 2, 2006
Approved by BOT
New
2
May 2, 2007
Approved by BOT
Revised
3
April 8, 2010
Approved by FERC, Effective July 1,
2010
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Effe c tive Da te : J u ly 1, 2010
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 3 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
Timing Requirements for all Interconnections except WECC
Request for
Interchange
Submitted
Ramp
Start
Interchange Timeline with Minimum
Reliability-Related Response Times
A
B
C
D
If Arranged
2
Interchange (RFI)
is Submitted
IA Assigned
Time
Classification
IA Makes Initial
Distribution of
Arranged Interchange
BA and TSP Conduct
Reliability Assessments
IA Compiles and
Distributes Status
>1 hour after the RFI
start time
ATF
< 1 minute from RFI
submission
Entities have up to 2 hours
to respond.
< 1 minute from receipt of
all Reliability Assessments
NA
<15 minutes prior to
ramp start and <1
hour after the RFI
start time
Late
< 1 minute from RFI
submission
Entities have up to 10
minutes to respond.
< 1 minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
<1 hour and > 15
minutes prior to
ramp start
On-time
< 1 minute from RFI
submission
< 10 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 3 minutes prior to
ramp start
>1 hour to < 4
hours prior to ramp
start
On-time
< 1 minute from RFI
submission
< 20 minutes from
Arranged Interchange
receipt from IA
< 1 minute from receipt of
all Reliability Assessments
> 39 minutes prior to
ramp start
> 4 hours prior to
ramp start
On-time
< 1 minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from
IA
< 1 minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes
prior to ramp start
2
BA Prepares
Confirmed Interchange
for Implementation
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 4 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
Example of Timing Requirements for all Interconnections except WECC
Ramp
Start Time
RFI submit time
relative to start
time
5:55
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment
Interchange
Start Time
8:55
9:40
1 hour
before
ramp start
15
minutes
before
ramp start
20 minutes
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
9:55 10:00
10 minutes
11:00
2 hours
Page 5 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
Timing Requirements for WECC
A
B
IA Makes Initial
Distribution of
Arranged
Interchange
BA and TSP Conduct
Reliability Assessments
Entities have up to 2 hours to
respond.
If Arranged Interchange
(RFI) 3 is Submitted
IA Assigned
Time
Classification
>1 hour after the start time
ATF
< 1minute from RFI
submission
<10 minutes prior to ramp
start and <1 hour after the
start time
Late
< 1minute from RFI
submission
10 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
11 minutes prior to ramp
start
On-time
12 minutes prior to ramp
start
C
D
IA Compiles and
Distributes Status
BA Prepares Confirmed
Interchange for
Implementation
< 1minute from receipt of
all Reliability Assessments
NA
< 1minute from receipt of
all Reliability Assessments
< 3 minutes after receipt
of confirmed RFI
< 5 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
< 1minute from RFI
submission
< 6 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 7 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
13 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 8 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
14 minutes prior to ramp
start
On-time
< 1minute from RFI
submission
< 9 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
<1 hour and > 15 minutes
prior to ramp start
On-time
< 1minute from RFI
submission
< 10 minutes from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 3 minutes prior to ramp
start
> 1hour and < 4 hours prior
to ramp start
On-time
< 1minute from RFI
submission
< 20 minutes from Arranged
interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 39 minutes prior to ramp
start
> 4 hours prior to ramp
start
On-time
< 1minute from RFI
submission
< 2 hours from Arranged
Interchange receipt from IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
Submitted before 10:00 PPT
with start time > 00:00 PPT
of following day
On-time
< 1minute from RFI
submission
By 12:00 PPT of day the
Arranged Interchange was
received by the IA
< 1minute from receipt of
all Reliability Assessments
> 1 hour 58 minutes prior
to ramp start
3
Entities have up to 10 minutes
to respond.
Time Classifications and deadlines apply to both initial Arranged Interchange submittal and any subsequent modifications to the Arranged Interchange.
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 6 of 7
S ta n d a rd INT-008-3 — In te rc h a n g e Au th o rity Dis trib u te s S ta tu s
Example of Timing Requirements for WECC
Ramp
Start Time
9:35
RFI submit time
relative to start
time
5:50
9:40
8:50
9:50
10:00
11:00
1 hour
before
ramp start
4 hours
before
ramp start
2 hours
ATF
Late
On Time
Time
Classification
Assessment*
Interchange
Start Time
20 minutes
*If submitted before 10:00 PPT with
start time >= 00:00 PPT of the
following day then assessment is
>= 2 hours and by 12:00 PPT
10 minutes
10 minutes
2 hours
Submittal &
Assessment
Times
9:35 - 10
9:36 - 9
9:37 - 8
9:38 - 7
9:39 - 6
9:40 - 5
Ad o p te d b y NERC Bo a rd o f Tru s te e s : Oc to b e r 29, 2008
Adopted by the Régie de l'énergie (Décision D-201x-xxxx): Month xx, 201x
Page 7 of 7
Standard INT-008-3 — Interchange Authority Distributes Status
Appendix QC-INT-008-3
Provisions specific to the standard INT-008-3 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Interchange Authority Distributes Status
2.
Number:
INT-008-3
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope: Main Transmission System (MTS)
B.
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
No specific provision
E.
Regional Differences
No specific provision
Timing Requirements for all Interconnections except WECC
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-1 of 3
Standard INT-008-3 — Interchange Authority Distributes Status
Appendix QC-INT-008-3
Provisions specific to the standard INT-008-3 applicable in Québec
No specific provision
Example of Timing Requirements for all Interconnections except WECC
No specific provision
Timing Requirements for WECC
No specific provision
Example of Timing Requirements for WECC
No specific provision
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-2 of 3
Standard INT-008-3 — Interchange Authority Distributes Status
Appendix QC-INT-008-3
Provisions specific to the standard INT-008-3 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
0
Date
Action
Change Tracking
Month xx, 201x
Effective date
New
Adopted by the Régie de l’énergie (Décision D-201x-xxxx): Month xx, 201x
Page QC-3 of 3
Standard INT-009-1 — Implementation of Interchange
A. Introduction
1.
Title:
Implementation of Interchange
2.
Number:
INT-009-1
3.
Purpose:
To ensure that the implementation of Interchange between Source and Sink
Balancing Authorities is coordinated by an Interchange Authority such that the Balancing
Authorities implement the Interchange exactly as agreed upon in the Interchange confirmation
process.
4.
Applicability
4.1. Balancing Authority.
5.
Effective Date:
January 1, 2007
B. Requirements
R1.
The Balancing Authority shall implement Confirmed Interchange as received from the
Interchange Authority.
C. Measures
M1. The Balancing Authority shall provide evidence that Implemented Interchange matches
Confirmed Interchange as submitted by the Interchange Authority.
M2. Evidence shall demonstrate that the Interchange was implemented in the Balancing Authority’s
Area Control Error (ACE) equation, or the system that calculates the ACE equation. Evidence
may be on a net basis or an individual Interchange basis.
M3. Balancing Authorities that are interconnected with a direct current tie shall demonstrate that the
Interchange was implemented in the ACE equation or modeled as an equivalent generator/load
within its area.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last noncompliance to
Requirement 1.
1.3. Data Retention
The Balancing Authority and Interchange Authority shall each keep 90 days of historical
data. The Compliance Monitor shall keep audit records for a minimum of three calendar
years.
1.4. Additional Compliance Information
Each Balancing Authority shall demonstrate compliance to the Compliance Monitor
within the first year that this standard becomes effective or the first year the entity
commences operation by self-certification to the Compliance Monitor.
Subsequent to the initial compliance review, compliance may be:
1.4.1
Verified by audit at least once every three years.
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 1 of 2
Standard INT-009-1 — Implementation of Interchange
1.4.2
Verified by spot checks in years between audits.
1.4.3
Verified by annual audits of non-compliant Balancing Authorities, until
compliance is demonstrated.
1.4.4
Verified at any time as the result of a complaint. Complaints must be lodged
within 60 days of the incident. The Compliance Monitor will evaluate
complaints.
The Balancing Authorities shall make the following available for inspection by the
Compliance Monitor upon request:
2.
1.4.5
For compliance audits and spot checks, relevant data and system log records for
the audit period which indicate a Balancing Authority implemented all instances
of the Interchange Authority’s communication under R1 concerning the
implementation of a Confirmed Interchange. The Compliance Monitor may
request up to a three month period of historical data ending with the date the
request is received by the Balancing Authority
1.4.6
For specific complaints, only those data and system log records associated with
the specific Interchange event contained in the complaint which indicates a
Balancing Authority implemented the Interchange Authority’s communication
under R1 concerning the implementation of the Confirmed Interchange for that
specific Interchange.
Levels of Non-Compliance
2.1. Level 1:
in R1.
One occurrence1 of not implementing a Confirmed Interchange as described
2.2. Level 2:
Two occurrences1 of not implementing a Confirmed Interchange as
described in R1.
2.3. Level 3:
Three occurrences1 of not implementing a Confirmed Interchange as
described in R1.
2.4. Level 4:
Four or more occurrences1 of not implementing a Confirmed Interchange as
described in R1 or no evidence provided.
E. Regional Differences
None identified.
Version History
Version
Date
Action
Change Tracking
1
This does not include instances of not implementing due to extenuating circumstances approved by the
Compliance Monitor.
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 2 of 2
Standard INT-009-1 — Implementation of Interchange
Appendix QC-INT-009-1
Provisions specific to the standard INT-009-1 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Implementation of Interchange
2.
Number:
INT-009-1
3.
Purpose:
No specific provision
4.
Applicability: No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope:
B.
Main Transmission System (MTS)
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
No specific provision
E.
Regional Differences
No specific provision
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
Page QC-1 of 2
Standard INT-009-1 — Implementation of Interchange
Appendix QC-INT-009-1
Provisions specific to the standard INT-009-1 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
Date
1
Month xx, 201x
Action
Change Tracking
Effective Date
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
New
Page QC-2 of 2
Standard INT-010-1 — Interchange Coordination Exemptions
A. Introduction
1.
Title:
Interchange Coordination Exemptions
2.
Number:
INT-010-1
3.
Purpose:
Allow certain types of Interchange schedules to be initiated or modified by
reliability entities, and to be exempt from compliance with other Interchange Standards under
abnormal operating conditions.
4.
Applicability
4.1. Balancing Authority.
4.2. Reliability Coordinator.
5.
Effective Date:
January 1, 2007
B. Requirements
R1.
The Balancing Authority that experiences a loss of resources covered by an energy sharing
agreement shall ensure that a request for an Arranged Interchange is submitted with a start time
no more than 60 minutes beyond the resource loss. If the use of the energy sharing agreement
does not exceed 60 minutes from the time of the resource loss, no request for Arranged
Interchange is required.
R2.
For a modification to an existing Interchange schedule that is directed by a Reliability
Coordinator for current or imminent reliability-related reasons, the Reliability Coordinator
shall direct a Balancing Authority to submit the modified Arranged Interchange reflecting that
modification within 60 minutes of the initiation of the event.
R3.
For a new Interchange schedule that is directed by a Reliability Coordinator for current or
imminent reliability-related reasons, the Reliability Coordinator shall direct a Balancing
Authority to submit an Arranged Interchange reflecting that Interchange schedule within 60
minutes of the initiation of the event.
C. Measures
M1. The Balancing Authority that uses its energy sharing agreement where the duration exceeds 60
minutes shall have evidence it submitted Arranged Interchange per Requirement 1.
M2. The Reliability Coordinator that directs a modification to an existing Interchange shall have
evidence that a directive was issued to submit the Arranged Interchange in accordance with
Requirement 2.
M3. The Reliability Coordinator that directs the initiation of a new Interchange shall have evidence
that a directive was issued to submit the Arranged Interchange in accordance with Requirement
3.
D. Compliance
1.
Compliance Monitoring Process
1.1. Compliance Monitoring Responsibility
Regional Reliability Organization.
1.2. Compliance Monitoring Period and Reset Time Frame
The Performance-Reset Period shall be twelve months from the last noncompliance to
R1, R2, or R3.
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 1 of 3
Standard INT-010-1 — Interchange Coordination Exemptions
1.3. Data Retention
The Balancing Authority and Reliability Coordinator shall each keep 90 days of historical
data. The Compliance Monitor shall keep audit records for a minimum of three calendar
years.
1.4. Additional Compliance Information
Each Balancing Authority and Reliability Coordinator shall demonstrate compliance to
the Compliance Monitor within the first year that this standard becomes effective or the
first year the entity commences operation by self-certification to the Compliance
Monitor.
Subsequent to the initial compliance review, compliance may be:
1.4.1
Verified by audit at least once every three years.
1.4.2
Verified by spot checks in years between audits.
1.4.3
Verified by annual audits of non-compliant Balancing Authorities and Reliability
Coordinators, until compliance is demonstrated.
1.4.4
Verified at any time as the result of a complaint. Complaints must be lodged
within 60 days of the incident. The Compliance Monitor will evaluate
complaints.
The Balancing Authority and Reliability Coordinator shall make the following available
for inspection by the Compliance Monitor upon request:
2.
1.4.5
For compliance audits and spot checks, relevant data and system log records for
the audit period which indicate a Balancing Authority or Reliability Coordinator
acted in compliance with INT-010. The Compliance Monitor may request up to a
three month period of historical data ending with the date the request is received
by the Balancing Authority
1.4.6
For specific complaints, only those data and system log records associated with
the specific Interchange event contained in the complaint which indicates a
Balancing Authority or Reliability Coordinator failed to act in compliance with
INT-010.
Levels of Non-Compliance
2.1. Level 1:
There shall be a level one non-compliance if either of the following
conditions is present:
2.1.1
One occurrence of not submitting an Arranged Interchange as described in R1.
2.1.2
One occurrence of not directing the submittal of a new or modified Arranged
Interchange as described in R2 or R3.
2.2. Level 2:
There shall be a level two non-compliance if either of the following
conditions is present:
2.2.1
Two occurrences of not submitting an Arranged Interchange as described in R1.
2.2.2
Two occurrences of not directing the submittal of a new or modified Arranged
Interchange as described in R2 or R3.
2.3. Level 3:
There shall be a level three non-compliance if either of the following
conditions is present:
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Page 2 of 3
Standard INT-010-1 — Interchange Coordination Exemptions
2.3.1
Three occurrences of not submitting an Arranged Interchange as described in R1.
2.3.2
Three occurrences of not directing the submittal of a new or modified Arranged
Interchange as described in R2 or R3.
2.4. Level 4:
There shall be a level three non-compliance if any of the following
conditions is present:
2.4.1
Four or more occurrences of not submitting an Arranged Interchange as
described in R1.
2.4.2
Four or more occurrences of not directing the submittal of a new or modified
Arranged Interchange as described in Requirements 2 or 3.
2.4.3
No evidence provided.
E. Regional Differences
None identified.
Version History
Version
Date
Action
Adopted by Board of Trustees: May 2, 2006
Effective Date: January 1, 2007
Adopted by the Régie de l'énergie (Décision D-201x-xxxx) : Month xx, 201x
Change Tracking
Page 3 of 3
Standard INT-010-1 — Interchange Coordination Exemptions
Appendix QC-INT-010-1
Provisions specific to the standard INT-010-1 applicable in Québec
This appendix establishes specific provisions for the application of the standard in Québec. Provisions of
the standard and of its appendix must be read together for the purposes of understanding and
interpretation. Where the standard and appendix differ, the appendix shall prevail.
A.
Introduction
1.
Title:
Interchange Coordination Exemptions
2.
Number:
INT-010-1
3.
Purpose:
No specific provision
4.
Applicability:
No specific provision
5.
Effective Date:
5.1.
Adoption of the standard by the Régie de l’énergie: Month xx 201x
5.2.
Adoption of the appendix by the Régie de l’énergie: Month xx 201x
5.3.
Effective date of the standard and its appendix in Québec: Month xx 201x
6.Scope:
B.
Main Transmission System (MTS)
Requirements
No specific provision
C.
Measures
No specific provision
D.
Compliance
1.
Compliance Monitoring Process
1.1.
Compliance Monitoring Responsibility
The Régie de l’énergie is responsible, in Québec, for compliance monitoring with
respect to the reliability standard and its appendix that it adopts.
1.2.
Compliance Monitoring Period and Reset Time fFrame
No specific provision
1.3.
Data Retention
No specific provision
1.4.
Additional Compliance Information
No specific provision
2.
Levels of Non-Compliance
No specific provision
E.
Regional Differences
No specific provision
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
Page QC-1 of 2
Standard INT-010-1 — Interchange Coordination Exemptions
Appendix QC-INT-010-1
Provisions specific to the standard INT-010-1 applicable in Québec
F.Violation Risk Factor
No specific provision
Version History of the Appendix
Version
0
Date
Month xx, 201x
Action
Change Tracking
Effective Date
Adopted by the Régie de l’énergie (Decision D-201x-xxxx): Month xx, 201x
New
Page QC-2 of 2
Download