Lead in Doors Lead on Floor Partitions (mm) & Control Slabs (mm) Windows (mm) Radiographic Fluoroscopic Room 1.5mm (3mm for 1.5 mm (3 mm None on 100 Special Procedures Diagnostic and Tele-Fluoroscopy Dark Room Side) Room Normal Weight Deep Therapy Room: Conventional Shielding as Determined by a Licensed Physicist (Ceiling Mounted X-Ray) on Partition on for Door to Dark Cobalt Height of Lead None 2100 mm (7") Slabs (mm) in Partitions mm (min.) Concrete (Ceiling Mounted X-Ray) 2 Lead on Ceiling CADD DETAIL NO. : SD134900-01.DWG 1 Lead in Betatrons Linear Accelerators None Dark Room Side) Room Weight Concrete 4 Animal X-Ray, Animal Research, Radiography and Fluoroscopy for Door to Dark 1.5mm (3mm for 1.5mm (3mm for Dark Room Side) Dark Room Side) 1 on Partition on on Partition on 5 Dental X-Ray Area Oral Surgery Room General Treatment Operatories 1 6 Dental X-Ray Room (Portable 50/65 KVP) None None 7 Fluoroscopic Rooms, Vertical or Tilt Type, 1.5 Gastroenterology (No Radiography) 1.5 mm (No Control Booth Required) Operating Room Including Animal Operating None None (Except 3 mm on Dark Room Side) (Except 3 mm on Dark Room Side) 8 (Portable X-Ray), Cardiac and Neurosurgical Operating Room (Portable X-Ray) 9 Cardiac Catheterization in cardiopulmonary Clinic (Fixed Equipment) Operating Room (Fixed Equipment) 10 Ultrasound & Thermography mm mm 100 mm 1.5 mm (3 mm for Door to Dark Room None None None on 100 mm None None Weight Concrete 2.* LEAD SHIELDING REQUIREMENTS IN PARTITIONS ADJACENT TO, FACING, OR PROXIMITY TO PHOTOGRAPHIC LABS SHOULD BE REVIEWED BY A REGISTERED PHYSICIST. on 100 mm None 2100 mm (7") None 2100 mm (7") Weight Concrete Room ALL RADIOLOGY FACILITY PROJECTS WILL BE REVIEWED BY THE VA HEALTH PHYSICS None (min.) Normal Dark Room Side) PROGRAM OFFICE FOR APPROPRIATE APPLICATION OF PROTECTIVE STANDARDS. 2100 mm (7") (min.) Normal None None None None None 1.5 mm (3 mm on Partition on None Weight Concrete 1.5mm (3mm for GENERAL NOTES: 1. mm on (min.) Normal for Door to Dark None on 100 mm None (min.) Normal None None None 2100 mm (7") None NONE 1.5 mm (3 mm on Partition on SCALE : 1.5mm (3mm for LINING IN X-RAY ROOMS Cystoscopic Room DETAIL TITLE / LEAD 3 DATE ISSUED :DECEMBER 2008 Room MILLI- DECIMALS FRACTIONS LBS. PER METERS OF AN INCH OF AN INCH SQ. FT LEAD GLASS EQUIVALENT 0.396 0.0156 1/64" 1 1 PLY APPROX. 1/4" 0.792 0.0312 1/32" 2 1 PLY APPROX. 1/4" 1.000 0.0391 5/128" 2 1/2 1 PLY APPROX. 1/4" 1.191 0.0469 3/64" 3 1 PLY APPROX. 1/4" 1.587 0.0625 1/16" 4 1 PLY APPROX. 1/4" 1.984 0.0781 5/64" 5 1 PLY APPROX. 1/4" 2.380 0.0937 3/32" 6 1 PLY APPROX. 1/4" 3.175 0.1250 1/8" 8 2 PLY APPROX. 1/2" 3.967 0.1562 5/32" 10 2 PLY APPROX. 1/2" 4.763 0.1875 3/16 12 3 PLY APPROX. 3/4" 5.555 0.2187 7/32" 14 3 PLY APPROX. 3/4" 6.350 0.2500 1/4" 16 4 PLY APPROX. 1" 7.142 0.2812 9/32" 18 4 PLY APPROX. 1" 8.465 0.3333 1/3" 20 5 PLY APPROX. 1 1/4" 9.525 0.3750 * 3/8" 22 1/2 6 PLY APPROX. 1 1/2" 10.160 0.4000 2/5" 24 6 PLY APPROX. 1 1/2" 10.317 0.4062 13/32" 25 6 PLY APPROX. 1 1/2" 11.112 0.4375 * 7/16" 28 7 PLY APPROX. 1 3/4" 12.700 0.5000 30 7 PLY APPROX. 1 3/4" 14.267 0.5625 34 8 PLY APPROX. 2" 15.876 0.6250 5/8" 38 9 PLY APPROX. 2 1/4" 16.934 0.6667 2/3" 40 9 PLY APPROX. 2 1/4" 19.050 0.7500 3/4" 44 10 PLY APPROX. 2 1/2" 20.637 0.8125 48 11 PLY APPROX. 2 3/4" 22.225 0.8750 7/8" 52 12 PLY APPROX. 3" 25.400 1.000 1" 60 14 PLY APPROX. 3 1/4" 1/2" * 9/16" * 13/16" GENERAL NOTES: 1. SHEET LEAD IN THIS TABLE GIVEN IN COMMERCIAL THICKNESSES EXCEPT AS NOTED. 2.* THESE SPECIAL THICKNESSES MAY BE ROLLED IF IN SUFFICIENT QUANTITIES DETAIL TITLE / LEAD SCALE : SHEET THICKNESS & WEIGHT NONE DATE ISSUED :DECEMBER 2008 CADD DETAIL NO. : SD134900-02.DWG [100mm] 10" 4'-0" 4" [100mm] [1670mm] [250mm] [1200mm] [100mm] METAL STUDS RACEWAY DOUBLE 4" [100mm] STUD WALL D FLOOR 1" [25mm] SPACE RACEWAY RACEWAY ABOVE CEILING SEE NOTE 2 THIS DWG. LINED PARTITION . SECTION E-E LEAD LINED PARTITION . 1.50 mm LEAD 4" [100mm] E METAL STUD . WALL 8'-6" E [2590mm] 10" 5/8" (16mm) GWB [250mm] 3 1/2" [90mm] VERTICAL RACEWAY 16'-0" CORRIDOR SIDE [4880mm] PLAN STUD WALL 5/8" (15mm) GYPSUM LEAD LINED FROM VERTICAL TRANSITIONAL SECTION PARTITION 1 1/2" GENERAL NOTES: 1. VERTICAL & HORIZONTAL RACEWAYS REQUIRE A 6" [152mm] DEPTH WHERE THERE IS A 3.5" [115mm] TOPPING & DEPRESS THE SLAB 2.5" [65mm]. WHERE THE SLAB DOES NOT HAVE A TOPPING, DEPRESS THE SLAB 6" [152mm]. 2. RACEWAY CORNERS ARE BEVELED AT 45 DEGREES TO FACILITATE CONDUIT INSTALLATION. 3. 6" [152mm] LEAD LINED PARTITION AT THE ENTIRE PERIMETER. FINISHED FLOOR [40mm] LEAD LINING CONCRETE IF REQ'D. FILL TOPPING 5" 5" [125mm] [125mm] SECTION F-F STRUCTURAL FLOOR SLAB DATE ISSUED :DECEMBER 2008 [760mm] 5/8" [15mm] GWB NONE X-RAY ROOM 2'-6" 4" [100mm] OR 6" [150mm] SCALE : PARTITION PLAN AND SECTIONS LEAD LINED [1525mm] SECTION D-D DETAIL TITLE / DOD / VA UNIVERSAL X-RAY (R-F) ROOM 4'-0" 5'-0" LINED PARTITION METAL STUDS ] [2950mm] 1" [25mm] SPACE 1.50 mm LEAD N. mm . RACEWAY 4" [100mm] OR 6" [150mm] [2130mm] D VERTICAL RACEWAY 12" [305mm] MI 9'-8" " 35 F [1930mm] 10" [250mm] RACEWAY 5/8" (16mm) GWB 7'-0" HIGH 6'-3" 1'-5" [430mm] ON VERTICAL 0 CONF. RM. 10" [250mm] MAIN BREAKER -6 [4 " 6 m] ' 3 6m COVER OFFICE OR F 135° 12" [305mm] PLATE RACEWAY [1625mm] [1 VERTICAL [1220mm] . . SUPPLY LOCATION . 10" [250mm] RACEWAY 5'-4" 1' 1'-5" [430mm] 4" [100mm] METAL STUDS METAL STUD POWER . 10" [250mm] PARTITION . 12" [305mm] LEAD LINED 5/8" [16mm] GWB CADD DETAIL NO. : SD134900-03.DWG [250mm] 5'-6" WALL [6100mm] 4" 4" MTL. STUD 20'-0" 10" SD134900-04.DWG 7'-0" HIGH PARTITION CADD DETAIL NO. : AT CONTROL BELOW 1/2" [12mm] DIA. HANGER RODS FOR CEILING PANELS PANELS CEILING SUPPORT GRID ATTACH CLNG. EDGE ANGLE TO CHANNELS A OR REFLECTED CEILING PLAN UNIVERSAL X-RAY ROOM PROVIDE SUSPENDED GRID OF STRUT CHANNELS TO SUPPORT X-RAY MACHINE RAILS. SHALL DESIGN SUPPORT SYSTEM TO SUIT BUILDING STRUCTURE. SUPPORT RAILS FROM A/E STRUCTURAL BEAMS OR JOISTS (PROVIDE INTERMEDIATE FRAMING AS NECESSARY). DO NOT SUPPORT FROM METAL DECK, CONCRETE SLABS, OR WALK-ON (INTERSTITIAL) DECKS. BRACE SUPPORT SYSTEM FOR LATERAL LOADS FROM MOVING EQUIPMENT AND SEISMIC. LIGHTING AND HVAC PER VA DESIGN MANUALS. WITH OPTIONAL CEILING CHANNELS TILE FLANGES A GENERAL NOTES: PROVIDE K-SERIES CHANNELS SERIES SUPPORT STRUT DETAILS LAY-IN CEILING DATE ISSUED :DECEMBER 2008 ACOUSTICAL ACOUSTICAL CEILING NONE TYP. SCALE : CEILING PANELS 2x2 MOUNTED X-RAY EQUIPMENT SYSTEM FOR CEILING LAY-IN ACOUSTICAL DETAIL TITLE / SUPPORT 26 TO 26-5/8" O.C. EQUALLY SPACED STRUTS FINAL LEVELING SD134900-05.DWG ABOVE CEILING ABOVE CEILNG CADD DETAIL NO. : RACEWAYS C RACEWAY IN FLOOR RACEWAY R/F ROOM SCHEME 1 USE WITH VA HOSPITAL BUILDING SYSTEM (VA HBS) 1 1/2" [40mm] [225mm] SECTION B RACEWAY [225mm] 10" [300mm] IF REQ'D [140mm] NOTE 2 NOTE 2 12" WIDE COVER PLATE FOR RACEWAY STEEL REMOVABLE COVER 1 1/2" [40mm] LEAD LINING 5 1/2" 10" [90mm] 3 1/2" [305mm] VCT OVER 1/4" [5mm] FIELD INSTALL WHERE REQ'D. 12" X-RAY TABLE BASE RWT-60 PARTITION RACEWAY SECTION C GENERAL NOTES: 1. REFER TO STANDARD DETAILS 13 49 00-1 & 13 49 00-2 FOR LEAD LINING REQUIREMENTS. 2. INSTALL DIVIDERS IN RACEWAYS IF REQUIRED. 3. LOCATE RACEWAY ON THE UNDERSIDE OF THE VA HBS WALK-ON DECK. 3 1/2" [90mm] 5" CONC. FILL TOPPING [125mm] 5" [125mm] STRUCTURAL FLOOR SLAB 6"x6"x1/4" STEEL PLATE [150mm x 150mm x 6mm] SECTION A 1" [25mm] DIA. I.D. STL. PIPE SLEEVE BONDED W/1mm LEAD & 5/8" [15mm] THRU BOLT. NONE R/F ROOM SCHEME 2 (CONVENTIONAL CONSTRUCTION) IN FLOOR SCALE : B SCHEME 1 & 2 B DETAIL TITLE / A A DOD / VA UNIVERSAL X-RAY (R-F0) ROOM RACEWAY LAYOUT C DATE ISSUED :DECEMBER 2008 RACEWAYS SEE P1000 A B C OR D P1000 4'-0" [1219mm] [1219mm] 10"[230mm] MAX. P2473 DIST. FROM WALL P2346 P1000 P2346 C P5500 [124mm] P1001 5-1/16" [127mm] 4-7/8" [127mm] P5500 P1001 P1000 WITH ANCHORS INSERTED IN CONCRETE SLAB. LAY-IN CEILING R/F ROOM SCHEME 1 P2346 TRACK(S) BY EQUIPMENT SUPPLIER P1000 P3184 F WHERE P1001 IS EXPOSED D CLEARANCE FOR RECESSED LIGHTS AND CEILING SECTION THROUGH SUPPORT SYSTEM NOTES: ALL SUPPORTS AND HANGERS SHALL BE ARRANGED L BENT P 1/4"X4"X4"X6" METAL PLATE [6mmX100mmX100mmX150mm] AS SHOWN ON ARCHITECTURAL DRAWINGS AND SHALL TERMINATE APPROX. 6" [150mm] FROM FACE OF WALLS OR PARTITIONS, EXCEPT FOR MEMBERS FLUSH WITH CEILING. THE NUMBER SHOWN ON DRAWING WITH A "P" PREFIX ARE UNISTRUT CATALOG NUMBERS USED AS A CONVENIENCE FOR IDENTIFYING DESIRED SHAPES AND THICKNESS OF MEMBERS. NOTE FOR ARCHITECT: DETAILS A, B, C & D SHOW ANCHORAGE SUPPORT ANCHOR BOLTS THROUGH INTO VARIOUS TYPES OF SLAB CONDITIONS. ACTUAL SUPPORT MUST BE DESIGNED TO SUIT THE CONCRETE SLAB PARTICULAR SITUATION. P2346 P1000 25" [625mm] APPROX. B NONE 4'-0" EXPANSION SHIELDS (MIN. FACTOR OF SAFETY OF 4). (PROVIDE ADEQUATE INSPECTION OR TESTING FOR PULL OUT). SCALE : ANCHOR BOLTS WITH A CADD DETAIL NO. :SD134900-06.DWG D DOD / VA UNIVERSAL X-RAY (R-F) ROOM SUPPORT OR SYSTEM FOR CEILING MOUNTED X-RAY EQUIPMENT C DETAIL TITLE / DIAGONAL BRACING MAY BE REQUIRED B P2473 5-1/16" PENDING THIS DIMENSION A SEE DATE ISSUED :DECEMBER 2008 P2346 P2346