THIS SHEET SHALL NOT FORM A PART OF THE BIDDING... REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.

advertisement
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
DEPARTMENT OF THE NAVY
NAVAL FACILITIES
ENGINEERING COMMAND
STANDARD SPECIFICATION
NAVFAC
NFSS-T40 (June 1989)
SPECIFICATION STANDARD
DAMAGE CONTROL TRAINER
NOTES ON THE USE OF THIS SPECIFICATION
1. The Standard Specification Sections listed below become part of the
project specification together with the addition of other required sections
prepared from NAVFAC Guide Specifications listed in NAVFAC P-34. The
Standard Specification Sections are included herein and shall not be edited,
changed or modified unless specific authorization is obtained from NAVFAC
Code 04.
STANDARD SPECIFICATION SECTIONS
FOR STANDARD DAMAGE CONTROL TRAINER
Section No.
ÄÄÄÄÄÄÄÄÄÄ
05150
07534
07950
13250
15450
15470
16450
16550
Title
ÄÄÄÄÄ
Steel Fabrications, Structural and Pressure
Reinforced CSPE Non-Vulcanized Polymeric Sheet
Roofing System
Calking, Sealants, and Fire Stopping
Damage Control Simulator Specialties
Water Supply and Drain Systems
Compressed Air System
Electrical and Signal Wiring Systems
Lighting, Control Trainer
Prepared by:
Stanley L. Peters and Associates, Inc.
Reviewed by:
__________________________Date:_____________
Approved:
EFD:
Date:
NAVFAC:
Date:
Branch Head:__________________
_______
________
________
Division Director:____________
_______
________
________
Approved for NAVFAC:___________________________________
________
1
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
2. The following NAVFAC Guide Specifications are applicable to Damage
Control Trainer construction and shall be included in the project
specification. The appropriate Guide Specifications listed in NAVFAC P-34
shall be edited to suit the project requirements and included in the project
specification as necessary. Information specified in the Technical Notes of
this Standard Specification shall be incorporated into the current edition
of the Guide Specifications indicated, and the sections prepared from these
Guide Specifications shall be included in the project specification.
GUIDE SPECIFICATION SECTIONS REQUIRED
Section No.
ÄÄÄÄÄÄÄÄÄÄÄ
01011
01012
01401
01560
02050
02221
02225
02250
02660
02722
03302
04230
05210
05311
06100
07110
07220
07600
08110
Title
ÄÄÄÄÄ
General Paragraphs
Additional General Paragraphs
Quality Control
Environmental Protection
Demolition and Removal
Earthwork for Structures and Pavements
Excavating, Backfilling, and Compacting for Utilities
Soil Treatment for Termite Control
Exterior Water Distribution System
Exterior Sanitary Sewer System
Cast-In-Place Concrete
Reinforced Masonry
Steel Joists
Steel Roof Decking
Rough Carpentry
Membrane Waterproofing
Roof Insulation
Flashing and Sheet Metal
Steel Doors and Frames
2
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
08710
09900
15011
15250
15850
15895
16011
16852
Finish Hardware
Painting
Mechanical General Requirements
Insulation of Mechanical Systems
Air Handling and Distribution Equipment
Ductwork and Accessories
Electrical General Requirements
Electric Space Heating Equipment
3. The below listed drawings forming a part of this specification are
STANDARD DRAWINGS and shall not be changed in any respect. This list shall
be edited to suit a specific project and incorporated in Section NFGS-01011,
"Additional General Paragraphs". All modifications necessary to suit a
specific project shall be shown on new drawings prepared for that purpose.
Use either the "Free Standing" or "Retrofit" listing as appropriate.
NAVAL FACILITIES ENGINEERING COMMAND DRAWINGS
FOR STANDARD DAMAGE CONTROL TRAINER
FREE STANDING
Drawing No.
ÄÄÄÄÄÄÄÄÄÄÄ
Title
ÄÄÄÄÄ
1404729
1404730
1404731
1404732
1404733
1404734
1404735
1404736
1404737
TITLE SHEET,INDEX,ABBREVIATIONS & SYMBOLS
FOUNDATION FLOOR PLAN
FLOOR PLAN
CEILING/FRAMING PLAN
ROOF PLAN & DETAILS
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
3
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
1404738
1404739
1404740
1404741
1404742
1404743
1404744
1404745
1404746
1404747
1404748
1404749
1404750
1404751
1404752
1404753
1404754
1404755
1404756
1404757
INTERIOR ELEVATIONS/BLDG. SECTIONS
SLAB DETAILS
FRAMING DETAILS
DOOR SCHEDULE & DETAILS
MISCELLANEOUS DETAILS
TYPICAL HATCH DETAILS
SEAM RUPTURE SIMULATOR
TORPEDO HIT SIMULATOR
PIPE BURST SIMULATOR
BULKHEAD COLLAPSE SIMULATOR
VOID SIMULATOR & FIRE STATION
COMPARTMENT SIGNAGE
PLUMBING PLAN & DETAILS
MECHANICAL PLAN & DETAILS
ELECTRICAL POWER PLAN
ELECTRICAL LIGHTING PLAN
ELECTRICAL DETAILS
ELECTRICAL SCHEDULES
WATER SUPPLY SYSTEM
SUMP PUMP SYSTEM
NAVAL FACILITIES ENGINEERING COMMAND DRAWINGS
FOR STANDARD DAMAGE CONTROL TRAINER
RETROFIT
Drawing No.
ÄÄÄÄÄÄÄÄÄÄÄ
Title
ÄÄÄÄÄ
1404758
1404759
TITLE SHEET, INDEX, ABBREVIATIONS & SYMBOLS
FOUNDATION FLOOR PLAN
4
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
1404760
1404761
1404762
1404763
1404764
1404765
1404766
1404767
1404768
1404769
1404770
1404771
1404772
1404773
1404774
1404775
1404776
1404777
1404778
1404779
1404780
1404781
1404782
1404783
1404784
1404785
FLOOR PLAN
CEILING/FRAMING PLAN
ROOF PLAN & DETAILS
INTERIOR ELEVATIONS/BLDG. SECTIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
INTERIOR ELEVATIONS/BLDG. SECTIONS
SLAB DETAILS
FRAMING DETAILS
DOOR SCHEDULE & DETAILS
MISCELLANEOUS DETAILS
TYPICAL HATCH DETAILS
SEAM RUPTURE SIMULATOR
TORPEDO HIT SIMULATOR
PIPE BURST SIMULATOR
BULKHEAD COLLAPSE SIMULATOR
VOID SIMULATOR & FIRE STATION
COMPARTMENT SIGNAGE
PLUMBING PLAN & DETAILS
MECHANICAL PLAN & DETAILS
ELECTRICAL POWER PLAN
ELECTRICAL LIGHTING PLAN
ELECTRICAL DETAILS
ELECTRICAL SCHEDULES
WATER SUPPLY SYSTEM
SUMP PUMP SYSTEM
4. The listed designations for publications referenced in this
standard specification are those that were in effect when this standard
specification was prepared, and the current edition shall be listed in the
project specification under the appropriate section. Designations that are
known to be out of date when project specifications are prepared shall be
changed to those current at that time, and the nomenclature, types, grades,
and classes referenced in this standard specification shall be checked for
conformance to the latest revision or amendment. The current issues of
NAVFAC P-34 "ENGINEERING AND DESIGN CRITERIA FOR NAVY FACILITIES", the
"DEPARTMENT OF DEFENSE INDEX OF SPECIFICATIONS AND STANDARDS", and other
applicable publication indices should be consulted before listing other
specifications and standards in the project specification.
5
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
TECHNICAL NOTES
A. The following items, materials, equipment, and requirements,
are unique for this construction and are not currently included in the
NAVFAC Guide Specifications. The information shall be added without
editing, except as specified herein, to the Guide Specifications indicated.
The Guide Specifications shall be edited to reflect the project requirements
and the sections prepared from these Guide Specifications shall be included
in the project specification. Use the Guide Specifications current at the
time the project specification is being prepared.
1.
Guide Specification NFGS 02050, "Demolition and Removal":
a.
2.
Include this section when Damage Control Trainer is retro-fit
in existing building. Edit and include the following:
1)
Walls at portlight and exhaust fans.
2)
Slabs at wall footings, void simulator, and buried
utilities; pavements if required for water and drain
system.
3)
Roofs if required for coaming, vent, and fan
penetrations.
Guide Specification NFGS-02221, "Earthwork For Structures And
Pavements":
a.
Edit and add the following as subparagraph to "MATERIALS"
1)
b.
"BURIED WARNING AND IDENTIFICATION TAPE FOR DAMAGE
CONTROL TRAINER: Polyethylene plastic warning tape
manufactured specifically for warning and identification
of buried utility lines, 3-inch-minimum width, color
coded as stated below for the intended utility with
warning and identification imprinted in bold black
letters continuously over the entire tape length.
Warning and identification to read, "CAUTION, BURIED
(intended service) LINE BELOW" or similar wording.
Color and printing is to be permanent, unaffected by
moisture or soil.
Add as subparagraphs to "SOIL MATERIALS":
6
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
c.
1)
"Backfill for Damage Control Trainer: Provide materials
classified as GW, GP, SW or SP, by ASTM D 2487. The
liquid limit of such material shall not exceed 35
percent when tested in accordance with ASTM D 4318. The
plasticity index shall not be greater than 12 percent
when tested in accordance with ASTM D 4318, and not more
than 35 percent by weight shall be finer than No. 200
sieve when tested in accordance with ASTM D 1140."
2)
"Pipe and Utility Bedding: Clean gravel or crushed stone
conforming to ASTM C 33 coarse aggregate grading Size
67."
Add as subparagraph to "FILLING AND BACKFILLING":
1)
d.
Add to table of "COMPACTION":
1)
3.
"Pipe and Utility Bedding: Place bedding in 4-inch
compacted lifts. Provide uniform and continuous support
for each section except at bell holes or depressions
necessary for making proper joints."
"Pipe and Conduit Bedding: Compact to 95 percent of ASTM
D 1557 maximum density."
Guide Specification NFGS-03302, "Cast-In-Place Concrete":
a.
Add the following to "APPLICABLE PUBLICATIONS":
1)
Under Subparagraph "American Society for Testing and
Materials (ASTM) Publications:"
"A 307-83A
Carbon Steel Externally Threaded
Standard Fasteners
A 354-84B
Quenched and Tempered Alloy Steel Bolts,
Studs, and Other Externally Threaded
Fasteners"
7
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
b.
Add the following as subparagraphs to "SUBMITTALS":
1)
c.
"Catalog Data:
Water Stops"
Edit and add following as subparagraph to "CONCRETE":
1)
"Concrete Mix Design for Damage Control Trainer: ACI
301, except as modified herein. Concrete shall have a
28-day compressive strength of 3,000 psi. Slump shall
be between 2 and 4 inches in accordance with ASTM C 143.
The slump may he increased to 5 inches for concrete
utilizing either fly ash, pozzolan, or ground slag for
10 percent (minimum) of the total cementitious material.
Provide ASTM C 33 aggregate Size No. 67 <and 4 to 6
percent air entrainment for concrete exposed to
freeze-thaw conditions. Accomplish air-entrainment
using an air-entraining admixture>."
<Use optional wording where exterior slab(s) are required.>
d.
Edit and add the following subparagraphs to "MATERIALS":
1)
"<Admixtures for Damage Control Trainer:
air-entrained concrete.>"
ASTM C260 for
<Use where exterior slab(s) are required.>
2)
"Reinforcing Bars:
ASTM A 615 Grade 60."
3)
"Welded Wire Fabric: ASTM A 185, 6 by 6, W2.9 by W2.9,
unless otherwise indicated."
4)
"Liquid Chemical Sealer - Hardener Compound: A suitable
sealer - hardener designed for coating and hardening in
addition to curing of the concrete."
5)
"Vapor Barrier for Damage Control Trainer Slab: ASTM C
171 polyethylene sheeting, minimum 6-mil thickness for
slab on grade <membrane waterproofing as specified in
Section 07110, "Membrane Waterproofing" for slabs placed
on existing concrete>."
<Use optional wording where new floor slab is placed on an
existing slab.>
8
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
e.
6)
"Polyvinyl Chloride Waterstops:
COE CRD-C-572."
7)
"Anchor Bolts for Damage Control Trainer:
A354."
ASTM A 307 or
Edit and add the following as subparagraphs to "PLACING
REINFORCEMENT AND MISCELLANEOUS MATERIALS":
1)
"Setting Miscellaneous Material: Place and secure
anchors and bolts, pipe sleeves, drains, valve box,
simulated void, and other such items in position before
concrete placement. Plumb anchor bolts and check
location and elevation. Temporarily fill voids in
sleeves with readily removable material to prevent the
entry of concrete."
2)
"Vapor Barrier: Provide beneath concrete floor slab.
<Use the greatest widths and lengths practicable to
eliminate joints wherever possible. Lap 12-inches
minimum. Remove torn, punctured, or damaged vapor
barrier material and provide new material prior to
placing concrete.> <Provide membrane waterproofing as
specified in Section 07110,"MEMBRANE WATER PROOFING".>
Place concrete to prevent damage to the vapor barrier
material."
<Use optional wording where new floor slab is placed on an
existing slab.>
3)
"Expansion Joints and Contraction Joints for Damage
Control Trainer: ACI 301. Provide as indicated. Make
expansion joints 0.5-inches wide, fill to within
0.5-inch of surface, and seal joints with joint sealant.
Do not extend reinforcement or other embedded metal
items bonded to the concrete through any expansion
joint, unless an expansion sleeve is used. Provide
formed contraction joints. Protect joints from
intrusion of foreign matter."
f.
Add the following as subparagraphs to "SURFACE FINISHES":
1)
"Damage Control Trainer Floor: Slope the floors
uniformly to drains. Slabs shall be sloped as indicated
and shall not vary more than 1/8-inch in 10 feet from
the required plane or slope. First, provide a floated
9
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989)
finish. When slab has attained a proper set, trowel to
a smooth, hard, dense finish. Hand-finish portions of
the slab not accessible to power finishing equipment to
match the remainder of slab. Power trowel three times
and finally hand trowel."
g.
2)
"Damage Control Trainer Curbs: Provide smooth rubbed
finish on newly hardened concrete within 24 hours
following form removal. Wet surfaces and rub with an
abrasive tool to provide uniform color and texture. Use
only the cement paste drawn from the concrete rubbing
process."
3)
"Damage Control Trainer Pads and Miscellaneous Slabs:
Provide a floated finish, then finish with a flexible
bristle broom. Permit surface to harden sufficiently to
retain the scoring or ridges. Broom at right angles to
the slope of the slab."
4)
Types of nonslip paints may be used:
a.
Premixed Paints: Paint shall have the abrasive
pigment already mixed in or pigment shall be
shipped separately and mixed just before use.
Application to be by brush or roller in a similar
manner to general floor paints. Ensure that the
abrasive pigment is thoroughly mixed and evenly
distributed.
b.
Broadcast Type: Abrasive is packaged separately
but is not added to the paint before use. The
paint is applied in the normal manner and then the
abrasive is broadcast over the wet paint film.
While painting, cover the floor area as to allow
the grit broadcaster to reach all areas as the work
progresses. The actual broadcasting should be done
only by experienced personnel. Be sure that the
abrasive is distributed evenly and at the proper
rate in accordance with manufacturer's printed
instructions.
Edit and add the following as subparagraph to "MISCELLANEOUS
CONSTRUCTION":
1)
"<Water Tank Hold Downs: Cast-in-place or precast
reinforced concrete as indicated, sized to resist uplift
10
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40
(JUNE 1989)
<Use optional wording where water supply tank is
required.> on empty tank as specified in Section 15450,
Water Supply and Drain Systems". Provide lifting eyes
and inserts in precast and embedded anchors in cast-inplace concrete for tie strap attachment.>"
h.
Add the following as subparagraph to "CURING AND PROTECTION":
1)
4.
"Liquid Chemical Sealer Hardener Curing for Damage
Control Trainer: Provide for slab, curb, and other
concrete surfaces. The coverage and number of
applications shall be in accordance with the
recommendations of the manufacturer of the compound."
Guide Specification NFGS-05230, "Reinforced Masonry":
a.
Add the following as subparagraph to "MORTAR MIXES":
1)
b.
"Mortar Proportions for Damage Control Trainer: Type S
in accordance with the proportion specifications of ASTM
C 270. The mortar shall have a flow, after suction., of
70 percent or more when tested for water retention in
accordance with ASTM C 91 except mortar shall be mixed
to an initial flow of 125 to 135 percent."
Edit and add as subparagraph to "GROUT MIXTURES":
1)
"Grout proportions for Damage Control Trainer: Mix in
laboratory established proportions to attain a
compressive strength at 28 days of not less than 1875
pounds per square inch when tested in accordance with
ASTM C 91 for fine aggregate and ASTM C 39 for grout
containing coarse aggregate. Grout shall be classified
as fine, low lift, and high lift types."
11
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
c.
Add as subparagraph to "KINDS AND SHAPES" of Masonry Units:
1)
d.
Add as subparagraph to "DEFORMED REINFORCING BARS":
1)
e.
"Reinforced Hollow Unit Masonry for Damage Control
Trainer: Hollow concrete masonry units reinforced
vertically with steel bars located within cells in the
units and with all cells filled solidly with grout."
"Bond Pattern for Damage Control Trainer:
units in running bond pattern."
Lay masonry
Add as subparagraph to "JOINTING":
1)
i.
"Steel Wire for Damage Control Trainer: ASTM A 82;
standard duty, 9 gage longitudinal and cross wires.
Fabricate joint reinforcement from wire zinc coated in
accordance with ASTM A 116, Class 3."
Add as subparagraph to "LAYING MASONRY UNITS":
1)
h.
ASTM A
Add as subparagraph to "DEFINITIONS":
1)
g.
"Reinforcing Bars for Damage Control Trainer:
615, Grade 60."
Add the following as subparagraph to "HORIZONTAL JOINT
REINFORCEMENT":
1)
f.
"Masonry units for Damage Control Trainer: Hollow
concrete masonry units, ASTM C 90, Grade N, Type I,
lightweight."
"Jointing for Damage Control Trainer: Flush cut joints
in concealed masonry surfaces and joints above
electrical outlet boxes. Tool joints in exposed masonry
surfaces slightly concave. Rake control joints and
joints between door frames and abutting masonry walls to
a depth of 3/4-inch ready for calking. Joint width
shall be 1/2-inch."
Add as subparagraph to "CONTROL JOINTS":
12
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
1)
"Joints for Damage Control Trainer: Provide in masonry
walls and partitions at 30-feet on centers. Construct
control joints using special control joint units, metal
sash jamb units and control joint keys, or open end
stretcher units. For dummy control joints in continuous
bond beams at control joint locations, rake control
joints as specified in paragraph entitled, "Jointing for
Damage Control Trainer". Calk control joints in exposed
exterior and interior masonry surfaces. Calking is
specified in Section 07950, "Calking, Sealants, and
Firestopping".
5. Guide Specification NFGS - 07110, "Membrane Waterproofing": (Use
where Damage Control Trainer floor slab installed over existing concrete
slab.)
a.
Add as subparagraphs to "MATERIALS".
1)
"Bitumen:
D41.
Asphalt, ASTM D449, Type II; primer, ASTM
2)
Bituminous Plastic Cement:
3)
"Felts:
The following requirements shall apply:
Felt
Material
ÄÄÄÄÄÄÄÄ
Glass (Felt) Mat
b.
ASTM D2822, Type I.
Saturant or
Impregnant
ÄÄÄÄÄÄÄÄÄÄ
Asphalt
Specification
ÄÄÄÄÄÄÄÄÄÄÄÄÄ
ASTM D 2178, Type III"
Add as subparagraphs to "APPLICATION":
1)
"Membrane Waterproofing for Damage Control Trainer:
Provide membrane waterproofing consisting of 2 plies of
felt and 3 moppings of bitumen on horizontal and
vertical surfaces applied over priming coat. Install
membrane using the shingle method so that the specified
number of plies are installed in a single operation by
providing the width of edge laps specified. Achieve
two-ply waterproofing by lapping each ply approximately
one-half over the preceding ply. Use appropriate width
starting strips of felt or fabric at the starting line
to provide the specified number of plies at the edge.
Lay each ply in separate sheets or unroll closely behind
the mopping of bitumen and brush into place so that
voids or air pockets do not develop. Extend membrane to
13
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
intersection with and secure to water stops. After all
plies and reinforcing membranes have been installed,
cover the entire surface uniformly with hot bitumen
applied at the rate specified.
1.1) "Flashing Flanges: Prime flashing flanges of the sleeves
of pipes penetrating the waterproofing membrane. Allow
primer to dry. Strip flanges in with 2 fabric membrane
collars cemented in place and to each other with
bituminous plastic cement. Extend collars 4 and 6
inches respectively beyond the edge of the flanges,
cover the flanges and fit tight against the sleeve. At
floor drains extend membrane into clamping device set in
heavy coating of bituminous plastic cement and clamp
securely."
6.
Guide Specification 07600, "Flashing and Sheet Metal": Use this
section where Damage Control Trainer is retro-fit in existing building and
roof is used as part of the training exercise.
a.
7.
Edit and include in section as required for base and
counterflashing at coaming penetration, pipe vent, and roof
ventilator. Strip flash deck flanges with flashing felt or
uncured neoprene or elastomeric sheet, as required for
compatibility with existing roofing membrane, set in asphalt
roof cement.
Guide Specification NFGS-08110, "Steel Doors and Frames".
a.
Add as subparagraph to "STANDARD STEEL DOORS".
1)
b.
"Doors for Damage Control Trainer: ANSI/SDI 100, Grade
III (extra heavy duty), Model 1, 3, or 5, of sizes and
designs indicated, with top edge closed flush. Doors
shall be 1-3/4-inches thick. Fill doors with mineral
fiber insulation. Doors and frames shall have 2-hour
fire rating conforming to NFPA 80 and so labeled".
Add as subparagraph to "SHELVES, LOUVERS, AND MOLDINGS":
1)
"Louvers for Damage Control Trainer Doors: Inverted Y
type. Weld or tenon louver blades to frame and fasten
the entire louver assembly to the door with moldings.
Moldings on the room/compartment or nonsecurity side of
the door shall be detachable; moldings on the security
side of the door shall be an integral part of the
14
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
louver. Form louvers of 16-gage steel with insect
screens rigidly secured to louvers to permit ready
removal. Provide aluminum wire cloth, 18 by 18 or 18 by
16 mesh. Louvers, before screening, shall have a
minimum of 30-percent net-free opening."
c.
Add as subparagraph to "STANDARD STEEL FRAMES":
1)
d.
Add as subparagraph to "STANDARD STEEL FRAMES":
1)
"Gaskets for Damage Control Trainer: Integral gasket,
extruded neoprene foam gasket made to fit into a
continuous groove formed in the frame. Insert gasket in
groove after frame is finish painted."
e.
Edit paragraph "FINISHES" to provide hot-dip zinc-coated and
factory primed finish for Damage Control Trainer doors and
frames.
f.
Add as subparagraph to "FABRICATION AND WORKMANSHIP":
1)
g.
"Frames for Damage Control Trainer: Fill with grout or
foam-in-place insulation conforming to Section 07950,
if "Calking, Sealants, and Firestopping".
Add as subparagraph to "INSTALLATION":
1)
8.
"Frames for Damage Control Trainer: ANSI/SDI 100. Form
frames to sizes and shapes indicated, with welded
corners. Provide 16-gage minimum metal thickness steel
frames with 10-gauge hinge plates, and suitable wall and
floor anchors".
"Doors and Frames for Damage Control Trainer: Install
doors and frames, including hardware, in accordance with
NFPA 80 and ANSI/SDI 100. Caulk both sides of frame as
specified in Section 07950, "Calking, Sealants, and
Firestopping"."
Guide Specification 08710, "Finish Hardware".
a.
Add the following as subparagraphs to "HARDWARE ITEMS":
1)
"Hinges: ANSI/BHMA A156.4 and ANSI/BHMA A156.7
(template), 4-1/2 by 4-1/2, nonremovable pin, ball
bearing hinges.
15
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
2)
"Locks and Latches: ANSI/BHMA 156.13, Series 1000,
operational Grade 1, Security Grade 1.
3)
"Door Closing Devices:
ANSI/BHMA A156.4, Series C02000,
Grade 1, with operational feature (o.f.) PT 4C.
b.
9.
4)
"Kick Plates:
ANSI/BHMA A156.6.
5)
"Door Stops:
ANSI/BHMA A156.16.
6)
"Thresholds: ANSI/BHMA A156.3, Type 26, with vinyl or
silicone rubber insert in face of stop."
Add as subparagraph to "HARDWARE SETS":
1
1
ea lockset, mortise
1/2 pairs, hinges
1
1
1
1
ea
ea
ea
ea
door closer
kick plate
threshold
stop
Series 1000, Grade 2
A5112 (Temp),
4 1/2" x 4 1/2", BHMA 630
C 02012 w/o.f. PT-4(C)
J102
26
L02161
Guide Specification NFGS-09900, "Painting":
a.
Edit and add the following as subparagraph to "LOCATION AND
SURFACE TYPE TO BE PAINTED":
1)
"Damage Control Trainer Painting: Includes new surfaces
of the Damage Control Trainer and appurtenances of the
types listed <; including items on or a part of the
roof>. Where a space or surface is indicated to be
painted, include the painting of exposed piping,
ductwork, conduit, supports, hangers, grilles,
registers, miscellaneous metalwork, insulation
coverings, and all other contiguous surfaces in the work
<and existing surfaces damaged during performance of the
work> unless indicated otherwise."
<Use optional wording in retrofit projects.>
b.
Edit and add as required to "APPLICATION" for painting of
Damage Control Trainer:
16
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
TABLE - I
EXTERIOR METAL SURFACES
SURFACE
PRIMER
DFT
INTERMEDIATE
DFT
TOPCOAT
DFT
AREA
COAT
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
****** FERROUS SURFACES ******
A.
New Steel
MIL-P-28577 2.5
MIL-P-28578
2.0
MIL-P-28578 2.0
That Has
Been Blastcleaned (up
to
SSPC-SP 7)
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
<B. Existing
Spot Prime
1.5
N.A.
TT-E-490 or 1.5>
Steel
MIL-P-28577
TT-P-19 or
That Has
on bare surMIL-P-28578
Been Spot- face previously
blasted
coated with
(Up to)
alkyd or
SSPC-SP 7) latex
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
17
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NFSS-T40 (June 1989)
TABLE - II
INTERIOR METAL SURFACES
SURFACE
PRIMER
DFT
INTERMEDIATE COAT
DFT
TOPCOAT DFT
AREA
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
A. Metal
MIL-P-24351,
2.0
TT-E-545
1.5
<TT-E-509>
1 coat on
shop-primed
surfaces and
2 coats on
non-shop-primed
surfaces
18
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
TABLE - III
BUILDING SYSTEMS SURFACES:
INTERIOR AND EXTERIOR
1. Mechanical, Electrical, and Miscellaneous Metal Items, Except Hot Metal
Surfaces and New Prefinished Equipment: Prefinishing of new mechanical and
electrical equipment is specified in the section covering the particular
item. <Paint copper pipe exposed in interior spaces.>
SURFACE
PRIMER
DFT
INTERMEDIATE
DFT
TOPCOAT
DFT
AREA
COAT
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
A. Surfaces Not MIL-P-24351 2.0
1.5
1.5
Adjacent to
Painted Surfaces
2 coats of same coating as used for
coating metal in same space
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
B. Surfaces
Coating systems as specified.
Adjacent to
Color of topcoat to match adjacent surfaces.
Painted
1.5 mils dry film thickness for each coat.
Surfaces
2. Insulation and Surfaces of insulation Coverings:
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
A. Cloth and Paper Glue size
N.A.
Coating to
Covering on
and primer
match
Insulation
recommended
adjacent
by material
surfaces
manufacturer,
1 coat each
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
19
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
TABLE - IV
INTERIOR/EXTERIOR CONCRETE AND CONCRETE MASONRY SURFACES
SURFACE
PRIMER
DFT
INTERMEDIATE
DFT
TOPCOAT
DFT
AREA
COAT
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
A. New
<CID-A-A-1500
TT-P-19
1.5
TT-P-19
1.5
<and Existing> on existing
Concrete,
concrete>
Excluding
Tops of Slabs
and Including
Soffits
** OR **
As recommended
by TT-C-555
Manufacturer
TT-C-555,
Type II
(See Note)
TT-C-555,
Type II,
(See Note)
Note: Sufficient coats to provide not less than 20 mils of finished
coating system. Texture: "Sand> <Coarse>
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
B. New <and Exist- <CID A-A-1500,
TT-P-19
1.5
TT-P-19
1.5
Ing> Concrete
on existing
Masonry
concrete masonry>
C. New <and Exist- <CID A-A-1500,
ing> Concrete
on existing
Masonry
concrete masonry>
20
10.0
DOD-C-24667
Coating
System
Nonskid, for
Roll or Spray
Application
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
TABLE - V
INTERIOR CONCRETE, CONCRETE MASONRY,
<AND> <WALLBOARD> SURFACES
SURFACE
PRIMER
DFT
INTERMEDIATE DFT
TOPCOAT
DFT
AREA
COAT
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
A. Concrete
TT-P-19
1.5
TT-E-545
1.5
TT-E-509 1.5>
Except Floors
B.
Concrete,
Masonry
CID A-A-1500
and TT-P-19
1.5
N.A.
<TT-E-509> 1.5
<TT-E-505>
C. Wallboard
TT-P-19
1.5
N.A.
<TT-E-509> 1.5
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
<Use optional wording in retrofit projects.>
10.
Guide Specification NFGS-15011, "Mechanical General Requirements";
a.
11.
Edit the section to include operation and maintenance manuals
and instruction to Government personnel as required by
Section 13250, "Damage Control Simulator Specialties".
Guide Specification 15250 "Insulation of Mechanical Systems":
a.
Edit and add the following as subparagraph to "DEFINITIONS":
1)
"Outside of Damage Control Trainer:
Open to view beyond
the exterior side of walls, above the roof, <and spaces
between overhead deck and existing ceiling or roof
construction when the deck is not used as part of
training exercise,> <and 8-feet minimum above overhead
deck when deck is used as part of training exercise>."
<Use optional wording as required for retrofit projects.>
b.
Edit "PRODUCTS AND REQUIREMENTS" to include: Insulation with
all-purpose jacket for Damage Control Trainer piping,
fittings, flanges, and valves. Buried piping shall not be
insulated. Materials and thickness as specified in Table 1.
21
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
c.
Edit "PIPE INSULATION" to include installation of piping
insulation for Damage Control Trainer, add the following as
subparagraph:
1)
d.
"Sleeves: Pack the space between jacket and sleeve to
1/2-inch or 1/2 the width of the joint, whichever is
less, and apply sealant to exposed joints as specified
in Section 07950, "Calking, Sealants, and
Firestopping"."
Edit and add the following to "TABLE I":
"INSULATION MATERIAL FOR PIPING"
SERVICE
MATERIAL
SPEC.
TYPE
CLASS
VAPOR BARRIER INSULATION
REQUIRED
THICKNESS
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
Water
Cellular
ASTM C 552 II
2
No
As indicated
Piping
Glass
NOTE: Insulation located outside Damage Control Trainer shall be one inch
thicker than that shown in the table above, <except where passing through
conditioned air spaces>."
<Use optional wording as required in retrofit projects.>
12.
Guide Specification NFGS 15895, "Ductwork and Accessories":
a.
Add to paragraph "American Society for Testing and Materials
(ASTM) Publications":
"A36-84A
b.
Structural Steel"
Add the following as subparagraphs to "PART 2 - PRODUCTS":
1)
"Low Pressure Ducts for Damage Control Trainer:
Construction, metal gage, and reinforcements shall
conform with SMACNA, LPDCS and NFPA 90A. Ductwork
shall be airtight and shall not vibrate or pulsate when
system is in operation. Except as modified herein, air
leakage shall be less than 5 percent of system capacity.
Construct and shall not vibrate or pulsate when system
is in operation. Except as modified herein, air leakage
shall be less than 5 percent of system capacity.
Construct ductwork of galvanized steel sheets conforming
to ASTM A 527."
22
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
2)
"Duct sleeves and prepared openings for Damage Control
Trainer: Fabricate from 20-gage galvanized steel in
masonry walls. Fabricate closure collars for ducts
penetrating steel plate ceilings and walls of 2-inch by
2-inch ASTM A-36 galvanized steel angles same thickness
as wall or ceiling plate thickness."
3)
"Louvers for Damage Control Trainer: SMACNA LPDCS,
Manual Type, with bird (insect) screen, frames and
screen shall be 16-gage galvanized steel."
4)
"Duct Heater: Packaged unit with frames for inserting in
and connecting air duct with electric type heating
elements directly in the air stream. UL 1096 and TJL
listed. Open coil or finned tubular type with
capacities indicated. Construct casings of steel.
Provide means where necessary to uniformly distribute
airflow across the heater face. Conform with electrical
characteristics as indicated. The interior surfaces and
heating elements shall be resistant to corrosion and
sagging. Wattage rating shall be within 5 percent of
the specified rating. Equip each unit with two
high-limit controls for protection against air stoppage:
(1) one or two automatic reset primary limit controllers
wired to power contact coils (2) secondary manual reset
thermal cut-off device wired to deenergize main power
supply, and (3) air flow switch to power contactor
control that will cut all power to the coil. Provide
settings, mounting equipment and accessories, including
but not limited to supports, vibration isolators,
stands, guides, anchors, clamps, and brackets.
Suspension for equipment shall conform to the
recommendations of the manufacturer, unless otherwise
indicated on drawings. Locate equipment as indicated on
the drawings. Provide electrical isolation between
dissimilar metals for the purpose of minimizing galvanic
corrosion. Clean the interior of cabinets or casings
before completion of installation. Prime all uncoated
ferrous-metal work and apply a finish coat of paint as
specified in Section 09900, "Painting of Buildings
(Field Painting)". Provide control system for on-off
operation. Thermostatic control for duct heater shall
be waterproof type, wall mounted."
23
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
c.
Edit paragraph "DIFFUSERS, REGISTERS, AND GRILLES" to include
aluminum diffusers, registers, and grilles, clear anodized
finish; sound pressure level 35-40 decibel noise criterion;
throw not to exceed 1.5 times the mounting height at 100-feet
-per-minute air velocity.
d.
Edit paragraph "INSTALLATION" to include installation of
Damage Control Trainer ductwork and accessories in accordance
with NFPA 90A and SMACNA LPDCS. Add the following as
subparagraphs:
1)
"Duct Sleeves and Prepared Openings for Damage Control
Trainer: Install for duct mains, duct branches, and
ducts passing through roofs and ceilings. Allow
one-inch clearance between duct and sleeve or prepared
openings except at grilles, registers, and diffusers.
Provide closure collars of not less than 2 inches wide
on each side of walls or ceilings where sleeves or
prepared openings are installed. Fit collars snugly
around ducts and pack to within 1/2-inch of top of
opening with Fed. Spec. HH-I-1030 mineral fiber in
spaces between sleeve or opening and duct and calk
smoke-tight as specified in 07950, "Calking, Sealants,
and Firestopping"."
2)
Edit paragraph "Duct Supports" to include minimum of two
one-inch by 1/16-inch galvanized strap-iron hangers,
spaced one on each side; and hangers and accessories
used for overhead ductwork within the damage control
training area shall have no sharp edges or projections.
13. Guide Specification NFGS 15850, "Air Handling and Distribution
Equipment":
a.
Edit "FANS" as required for Damage Control Trainer exhaust
fans and air handier with aluminum housings and fan wheels
and non-sparking construction. Add the following as
subparagraphs:
1)
"Centrifugal Fans: AMCA 210 with AMCA seal,
forward-curved single width type, v-belt drive for air
handler and v-belt or direct drive for roof/wall
ventilators, and inlet vanes. Inlet and outlet duct
connections shall be flanged."
24
THIS SHEET SHALL NOT FORM A PART OF THE BIDDING OR CONTRACT DOCUMENTS.
REMOVE THIS SHEET BEFORE ISSUING TO BIDDERS OR CONSTRUCTION CONTRACTORS.
NSFF-T40 (June 1989).
2)
"Power Roof and Wall Ventilators: UL 705 with UL label
and AMCA 210 with AMCA seal, centrifugal fans in
housings of corrosion-resistant metal or high-impact
plastic with glass fibre reinforcement. Equip motors
with unfused safety disconnect switches. <Provide
factory-fabricated roof curbs.>"
<Use optional wording in retrofit projects where roof mounted
ventilators are required.>
b.
15.
Edit "CENTRAL-STATION AIR HANDLERS" to provide single-zone
type air handler with supply blower and filter sections. Add
the following as subparagraphs:
1)
"Supply Blower (Fan) Section: Centrifugal fan of
forward-curved blade design with v-belt drive motor.
Bearings shall be grease-lubricated ball bearing type,
with a minimum average life of 200,000 hours at design
operating conditions."
2)
"Filter Box: Design filter box to hold replaceable
(throw-away) filters."
c.
Edit "MOTORS AND MOTOR STARTERS" to include totally enclosed
motors; manual type starters for up to 1/3 motor HP,
magnetic-across-the-line type elsewhere; with watertight
explosion-proof enclosure."
d.
Edit "PART 3 - EXECUTION" to include installation and testing
of fans and air handling unit for Damage Control Trainer in
accordance with Section 15840, "Ductwork and Accessories" and
13250, "Damage Control Simulator Specialties".
Guide Specification 16011, "Electrical General Requirements":
a.
Edit the section to include operation and maintenance manuals
and instruction to Government personnel as required by
Section 13250, "Damage Control Simulator Specialties".
25
SECTION 05150
STEEL FABRICATIONS, STRUCTURAL AND PRESSURE
PART I - GENERAL
1.1
APPLICABLE PUBLICATIONS: The publications listed below form a
part of this specification to the extent referenced. The publications are
referred to in the text by the basic designation only.
1.1.1
Federal Specifications (Fed. Spec.):
FF-W-84A(3)
Washers, Lock (Spring)
TT-C-49OC(1)
Cleaning Methods for Ferrous Surfaces and
Pretreatment of Organic Coatings
TT-P-645A
Primer, Paint, Zinc Chromate, Alkyd Type
1.1.2
Military Specifications (Mil. Spec.):
DOD-P-15328D
& Am 1
Primer (Wash), Pretreatment, (Formula
No.117 for Metals) (Metric)
DOD-P-21035A
Paint, High Zinc Dust Content, Galvanizing
Repair
1.1.3
American Institute of Steel Construction (AISC) Publications:
M011-80
1.1.4
Manual of Steel Construction, 8th Edition
Includes "Specification for the Design,
Fabrication and Erection of Structural
Steel for Buildings", "Code of Standard
Practice for Steel Buildings and Bridges",
and "Structural Joints Using ASTM A 325 or
ASTM A 490 Bolts"
American National Standards Institute (ANSI) Publications:
B18.22.1-65
(R 1981)
Plain Washers
NFSS-T40
05150-1
1.1.5
Publications:
American Society for Testing and Materials (ASTM)
A36/A36M-88
Structural Steel
A53-88
Pipe, Steel, Black and Hot-Dipped,
Zinc-Coated Welded and Seamless
A 120-84
Pipe, Steel, Black And Hot-Dipped
Zinc-Coated (Galvanized) Welded and
Seamless, for Ordinary Uses
A 123-84
Zinc (Hot-Dip Galvanized) Coatings on Iron
and Steel Products
A 153-82
Zinc Coating (Hot-Dip) on Iron and Steel
Hardware
A 283/A283M-88
Low and Intermediate Tensile Strength
Carbon Steel Plates, Shapes and Bars
A 307-88
Carbon Steel Bolts and Studs, 60,000 PSI
Tensile Strength
A 501-84
Hot-Formed Welded and Seamless
Carbon Steel Structural Tubing
A 525-87
Steel Sheet, Zinc-Coated (Galvanized) by
the Hot-Dip Process
A 563-88
Carbon and Alloy Steel Nuts
A 570/A57OM-88
Steel, Sheet and Strip, Carbon, Hot-Rolled,
Structural Quality
A 611-85
Steel, Sheet, Carbon, Cold-Rolled, Structural
Quality
A 780-80
Repair of Damaged Hot-Dip Galvanized Coating
C 827-87
Early Volume Change of Cementitious Mixtures
NFSS-T40
05150-2
1.1.6
American Welding Society (AWS) Publication:
B3.0-77
Welding Procedures and Performance
Qualifications
D1.1-88
Structural Welding Code, Steel
1.1.7 U.S. Army Corps of Engineers Waterways Experiment Station
Publication:
CRD-C621-83
1.1.8
Handbook for Concrete and Cement, Nonshrink
Grout, Volume II (1949 Ed.)
Steel Structures Painting Council (SSPC) Publications:
SSPC SP3-82
Surface Preparation Specification No. 3,
Power Tool Cleaning
SSPC SP6-85
Surface Preparation Specification No. 6,
Commercial Blast Cleaning
PS 9.01-82
Cold-Applied Asphalt Mastic Painting System
(Extra-Thick Film)
1.1.9 American Society of Mechanical Engineers (ASME) Publication:
Boiler and Pressure-Vessel code, Section VIII, Division 1
1.2 DESCRIPTION OF WORK: The work includes fabrication, shop
painting, erection and assembly of structural steel for wall (bulkhead)
and ceiling (overhead) construction; pressure vessel (seam rupture
simulator, torpedo hit simulator, void simulator) construction; and
miscellaneous metal fabrication as indicated and as specified in Section
13250, "Damage Control Simulator Specialties".
1.3
SUBMITTALS:
1.3.1 Shop Drawings: Submit shop drawings for approval by the
Contracting Officer prior to fabrication, erection and installation of
component parts, including the location type, and size of rivets, bolts,
welds, member sizes, and connection details. Use AWS standard welding
symbols.
a.
b.
Wall and ceiling construction
Special fabrications
1.3.2 Certificates of Compliance:
for the following:
Submit certificates of compliance
NFSS-T40
05150-3
a.
b.
c.
d.
e.
f.
Bolts, Nuts, and Washers
Welding Electrodes and Rods
Shop Painting Materials
Non-Shrink Grout
Steel Plates, Pipes and Shapes
Galvanizing
1.3.3 Welder, Welding Operation, and Tacker Qualification: Prior to
welding, submit certification for each stating the type of welding and
positions qualified for, the code and procedure qualified under, date
qualified, and the firm and individual certifying the qualification
tests.
1.3.4 Erection Plan: Submit for record purposes. indicate the
sequence of erection, temporary shoring and bracing, and a detailed
sequence of welding, including each welding procedure required.
1.4 DELIVERY AND STORAGE: Handle, ship, and store material in a
manner that will prevent distortion or other damage. Store material in a
clean, properly drained location out of contact with the ground. Replace
all damaged material with new material or repair the damaged material in
an approved manner.
PART 2 - PRODUCTS
2.1 STEEL: Materials shall conform to the respective specifications
specified herein. Materials not otherwise specified herein shall conform
to the ALSC "Manual of Steel Construction".
2.1.1
Carbon Grade Steel:
ASTM 4 36.
2.1.2
Structural Tubing:
ASTM A 501.
2.1.3
Mild Steel Plates and Shapes:
2.1.4
Steel Sheets:
ASTM A 283, structural quality.
ASTM A 570 or ASTM 4 611, structural quality.
2.1.5 Steel Pipe: ASTM A 53, Type E or S, Grade B; or ASTM A 120.
Fittings shall be standard malleable iron.
2.2
BOLTS, NUTS, AND WASHERS:
2.2.1 Common Bolts and Nuts: ASTM k 307, Grade A-bolts; ASTM A 563,
Grade A-hex style nuts.
2.2.2
Circular Washers for Common Bolts:
2.2.3
Lock Washers:
Fed. Spec.
ANSI B18.22.1, Type B.
FF-W-84, Class B.
NFSS-T40
05150-4
2.2.4 Beveled Washers for American Standard Beams and Channels:
ALSC "Specification for Structural Joints Using ASTM A 325 or ASTM A 490
Bolts".
2.3
ACCESSORIES:
2.3.1
Welding Electrodes and Rods: AWS Code D1.1.
2.3.2 Non-Shrink Grout: Corps of Engineers CRD-C-621. Grout shall
show no shrinkage when tested in the plastic state in accordance with ASTM C
827 and shall not break up under expansion due to moisture or gaseous
releases except that no grout containing ferrous or other staining metallic
aggregate shall be used.
PART 3 - EXECUTION
3.1 FABRICATION: Fabricate structural framing in accordance with the
applicable provisions of the Specification for the Design, Fabrication, and
Erection of Structural Steel for Buildings as set forth in Part 5 of the
AISC "Manual of Steel Construction". Fabricate Pressure Vessels (Seam
Rupture Simulator, Void Simulator, Torpedo Hit Simulator) in accordance with
the applicable provisions of NSME Boiler and Pressure Vessel Code, Section
8, Division I except that ASTM inspection and certification will not be
required. Fabrication and assembly shall be done in the shop to
the greatest extent possible.
3.1.1 Welding: AWS D1.1; ASME Boiler and Pressure Vessel Code,
Section 8, Division 1; by certified welders, AWS B3.0. Grind exposed Welds
smooth as indicated, weld in a manner to prevent permanent distortion to the
connected parts.
3.1.2 Shop Painting: Except as otherwise specified, shop paint all
steelwork, except zinc-coated surfaces and steelwork to be embedded in
concrete or mortar. Surfaces to be welded shall not be coated within
1/2-inch from the specified toe of the weld prior to welding. Insure that
surfaces are thoroughly dry and clean when the paint is applied. Do not
paint in freezing or wet weather except under cover. Do not apply paint
when the temperature is below 40 degrees F, or expected to drop to 32
degrees F or below within 5 hours of completing the application, before the
paint has completely dried. Do not apply paint to steel which is a
temperature that will cause blistering or porosity or will otherwise be
detrimental to the life of the paint. Apply paint in a workmanlike manner,
and coat all joints and crevices thoroughly. Prior to assembly, paint all
surfaces which will be concealed or inaccessible after assembly.
3.1.2.1 Cleaning: Except as modified herein, blast clean surfaces in
accordance with SSPC-SP6. Surfaces that will be exposed in spaces above
ceilings, attic spaces, crawl spaces, furred spaces, and chases may be
cleaned in accordance with SSPC-SP3 in lieu of being blast cleaned. Wash
cleaned surfaces which become contaminated with rust, dirt, oil, grease, or
NFSS-T40
05150-5
other contaminants with solvents until thoroughly clean. Insure that
steel to be embedded in concrete is free of dirt and grease. Do not paint
or galvanize bearing surfaces, including contact surfaces within frictiontype joints, but coat them with an approved rust preventative applied in the
shop. Remove such coating just prior to field erection using a remover
approved by the rust preventative manufacturer. Insure that the surfaces,
when assembled, are free from rust, grease, dirt, and other foreign matter.
3.1.2.2 Pretreatment: Immediately after cleaning, coat surfaces
with a pretreatment coating conforming to Mil. Spec. DOD-P-15328 applied to
a dry film thickness of 0.3 to 0.5 mil or with a crystalline phosphate base
coating conforming to Fed. Spec. TT-C-490, Method I, except apply Phosphate
base coating only to blast cleaned, bare metal surfaces.
3.1.2.3 Priming: Prime treated surfaces as soon as practicable
after the pretreatment coating has dried. Except as modified herein, prime
with zinc chromate primer conforming to Fed. Spec. TT-P-645, applied to a
minimum dry film thickness of 1.0 mil. repair damage to primed surfaces with
primer.
3.1.3 Galvanizing: Hot-dip galvanize items specified to be zinccoated, after fabrication where practicable. Galvanizing: ASTM A 123, ASTM
A 153 and NSTM A 525, as applicable.
3.1.3.1 Galvanize: Anchor bolts, specialties, washers, and parts
or devices necessary for proper installation, unless indicated
otherwise.
3.1.3.2 Repair of Zinc-Coated Surfaces: ASTM A 780. Repair surfaces
damaged by welding or other means with galvanizing repair paint conforming
to Mil. Spec. DOD-P-21035 or by the application of stick or thick paste
material specifically designed for repair of galvanizing, as approved.
Clean areas to be repaired and remove the slag from the welds. Surfaces to
which stick or paste material is applied, shall be heated with a torch to a
temperature sufficient to melt the metallics in stick or paste; spread the
molten material uniformly over surfaces to be coated and wipe the
excess material off.
3.2 ERECTION: Except as modified herein, erect steel in accordance
with the AISC "Manual of Steel Construction". Where parts cannot be
assembled or fitted properly as a result of errors in fabrication or of
deformation due to handling or transportation, report such condition
immediately to the Contracting Officer and obtain approval therefrom for the
methods of correction before proceeding with making any corrections. Do
not heat parts for straightening. Do not use impact torque wrenches to
tighten anchor bolts set in concrete.
3.3 ANCHORAGE: Provide anchorage for fastening work securely in
place. Set anchors in concrete as the work progresses and space not more
NFSS-T40
05150-6
than 2 feet on centers unless indicated otherwise. Sizes, kinds, and
spacings of anchors not indicated or specified shall be as necessary for the
purpose, as approved. Anchorage not otherwise specified or indicated
includes slotted inserts, expansion shields, and powder-driven fasteners,
when approved for concrete; toggle bolts and through bolts for masonry;
machine and carriage bolts for steel. Provide inserts of suitable and
approved types where required for support or anchorage of equipment and
finish construction inserts shall be gray or malleable iron castings or
galvanized steel. Slotted inserts shall be of types required to engage with
anchors. Anchors and anchor bolts shall be zinc-coated.
3.3.1 Threaded Connections: Make threaded connections up tight so
that threads are entirely concealed. Make bolted work up tight and nick the
threads or bush the stem to prevent loosening. Rivet, bolt, and screw heads
shall be flat and countersunk in exposed work and elsewhere as required.
Machine removable members and fit and secure by means of screws or bolts of
proper size and approved spacing.
3.3.2 Anchors and Connecting Members: Provide in concrete or masonry
as the work progresses, to avoid unnecessary cutting and drilling. Cut,
fit, and drill as necessary so all materials are properly set in place and
to permit engaging work to be properly installed.
3.3.3 Connections: Connections not detailed shall be designed in
accordance with AISC MO11 using common steel bolts. Use lockwashers under
nuts. Drill bolt holes.
3.3.4 Built-In Work: All metal work built-in with concrete or masonry
shall be formed for anchorage, or be provided with suitable anchoring
devices as shown or as required. Furnish metal work in ample time for
securing in place as the work progresses.
3.3.5 Base Plates and Bearing Plates: Provide column base plates for
columns. After final positioning of steel members, provide full bearing
under sill and base plates using non-shrink grout. Dry pack the area under
the plates solidly with a non-shrinking type of grout in accordance with the
grouting mortar manufacturer's instructions.
3.4 TOLERANCES: In accordance with the "Code of Standard Practice" of
the AISC "Manual of Steel Construction", or ASME Boiler and Pressure Vessel
Code, Section 8, Division 1, as-appropriate. Wall and ceiling panels,
exposed in the finished work, shall be free from buckle, warping, and oil
canning effects. Flatness of panels shall not deviate more than 1/8-inch
when measured with a 10-foot straightedge.
3.5 PROTECTION OF CONCEALED SURFACES: Steel surfaces buried in
concrete, including void simulator, shall receive one coat of asphalt mastic
applied to a minimum dry film thickness of 63 mils in accordance with SSPC
PS9.01. Steel surfaces abutting masonry or concrete walls shall receive one
NFSS-T40
05150-7
coat of Type D (firm) rust preventative compound applied to a minimum dry
film thickness of 30 mils. Apply protective coatings prior to concealment
of surfaces.
3.6
TESTS AND INSPECTIONS:
3.6.1 Visual Inspection of Welding: AWS D1.1, Section 6. Visually
inspect welding while the operators are making the welds and again after the
work is completed. After the welding is completed, hand or power wire brush
welds, and thoroughly clean them before the inspector makes the check
inspection. Inspect welds with magnifiers under strong, adequate light for
surface cracking, porosity, and slag inclusions; excessive roughness;
unfilled craters; gas pockets; undercuts; overlaps; size; and insufficient
throat and concavity. Inspect the preparation of groove welds for adequate
throat opening and for snug positioning of back-up bars.
3.6.2 Correction of Defective Welds: Weld areas containing defects
exceeding the standards of acceptance in AWS D1.1 or ASME Boiler and
Pressure Vessel Code Section 8, Division 1 shall be corrected in accordance
with appropriate standard.
*** END OF SECTION 05150 ***
NFSS-T40
05150-8
SECTION 07534
REINFORCED CSPE NON-VULCANIZED POLYMERIC SHEET
ROOFING SYSTEM
PART I - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publications listed below form a
part of this specification to the extent referenced. The publications
referred to in the text by the basic designation only.
1.1.1
American Society for Testing and Materials (ASTM) Publication:
D 413-82
Tests for Rubber Property - Adhesion to Flexible
Substrate
D 751-79
Testing Coated Fabrics
D 1149-86
Test for Rubber Deterioration - Surface Ozone
Cracking in a Chamber (Flat Specimens)
D 1204-84
Test for Linear Dimensional Changes of NonRigid
Thermoplastic Sheeting or Film at Elevated
Temperatures
D 2136-84
Testing Coated Fabrics - Low Temperature at Bend
Test
E 838-61
Practice for Performing Accelerated Outdoor
Weathering Using Concentrated Natural Sunlight
1.1.2
Federal Test Method Standards:
FTMS 101c
Method 2031
Federal Test Method Standard
Puncture Resistance
1.1.3 Factory Mutual Engineering and Research Corporation (FM)
Publications:
Approval Guide - Equipment, Materials, Services
for Conservation of Property
Loss Prevention Data Sheet 1-28, Insulated Steel
Desk
Loss Prevention Data Sheet 1-29, Adhered or
Mechanically Attached Single Ply Membrane Roof
Systems
NFSS-T40
07534-1
Loss Prevention Data 1-48, Nailable Decks (both
insulated and uninsulated)
Approval Sheet 4470, Roof Cover Standard
1.1.4
Underwriters' Laboratories, Inc. (UL) Publications:
Building Materials Directory
UL 790
Tests for Fire Resistance of Roof Covering
Materials
UL 1256
Roof Deck Constructions
1.2 SUBMITTALS: The preroofing conference will not be scheduled
until the Contracting Officer has received and approved all submittals
contained below:
1.2.1 Approval of Applicator: The CSPE sheet roofing system
manufacturer's written approval of the applicator for this specific roofing
job and the specified warranty.
1.2.2 Certificate of Conformance: The CSPE sheet manufacturer's
certifications that materials are physically and chemically compatible with
each other, that materials are in conformance with requirements of this
specification and that each material is suitable for the intended purpose.
1.2.3 Manufacturer's Data: Include materials descriptions, detailed
printed application instructions, and standard installation detail drawings
altered as required by these specifications.
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
Reinforced non-vulcanized polymeric sheet
Water-based latex adhesive
Contact adhesive
Lap cleaner and lap seam sealant (caulk)
Lap seam solvent welding solution
Lap seam adhesive
Flashing and flashing accessories
Water cutoff mastic
Mechanical fasteners and plates
Applicable Material Safety Data Sheets (MSDS)
Welding/primer reactivating agent
NFSS-T40
07534-2
1.2.4
Samples:
a.
b.
c.
d.
e.
f.
g.
h.
Reinforced non-vulcanized polymeric sheet - 4 square feet
Water-based latex adhesive - 1 quart
Contact adhesive - 1 quart
Lap cleaner and lap seam sealant (caulk) - 1 quart each
Lap seam solvent welding solution - 1 quart
Lap seam adhesive - 1 quart
Water cutoff mastic - 1 quart
Mechanical fasteners and plates - 10 of each type
1.2.5 Shop Drawings: Submit complete shop drawings showing roof
configuration, sheet layout, seam locations, fastener layout, details at
perimeter, and special conditions.
1.3 QUALIFICATION OF APPLICATOR: The roofing system applicator
shall be approved by the CSPE sheet roofing system manufacturer and shall
have a minimum of three years' experience as an approved applicator with
that manufacturer. The Contractor shall supply the names and location of
five CSPE projects that he has constructed within the previous three years.
1.4 QUALIFICATION OF MANUFACTURER: The CSPE sheet manufacturer
shall have manufactured the membrane specified herein for at least
three years.
1.5 PREROOFING CONFERENCE: Prior to starting the application of the
roofing system and insulation, there will be a preroofing conference with
the Contracting Officer to ensure that: (1) a clear understanding of
drawings and specifications; (2) onsite inspection and acceptance of the
roofing substrate and pertinent structural details relating to the roofing
system; and (3) coordination of the work of the various trades involved in
providing the roofing system and other components secured to the roofing.
The conference shall be attended by the Contractor personnel directly
responsible for the installation of roofing and insulation, flashing and
sheet metal work, and the roofing materials manufacturer. Conflicts shall
be resolved and confirmed in writing.
1.6
DELIVERY, STORAGE, AND HANDLING:
1.6.1 Delivery: Deliver materials in their original, unopened
containers or wrappings with labels intact and legible. The CSPE
membrane wrapping shall be intact, without tears. Any roll found with torn
wrapping or which shows evidence of having been opened when delivered on
site, will be rejected. Where materials are covered by a referenced
specification number, the labels shall bear the specification number. type,
class, compliance with UL requirements, and date of manufacture. In all
cases, where applicable, the shelf life expiration date shall be listed on
the label. Deliver materials in sufficient quantity to allow continuity of
work.
NFSS-T40
07534-3
1.6.2 Storage: Store and protect materials from damage and weather in
accordance with the manufacturer's instructions, except as specified herein.
Keep materials clean and dry. Use pallets to support and canvas tarpaulins
to completely cover stored material. Do not use polyethylene as a covering.
Locate materials temporarily stored on the roof in approved areas.
Distribute the load to stay within the live load limits of the roof
construction. Do not double-stack CSPE pallets. Only those materials to be
used during one day's work shall be placed on the roof, and unused material
shall be removed at the end of each day's work.
1.6.3 Handling: When hazardous materials are involved, adhere to
the special precautions of the manufacturer and the applicable Material
Safety Data Sheets (MSDS). Adhesives containing petroleum distillates are
extremely flammable; do not use near sparks or open flame. They are also
potentially hazardous when inhaled; personnel should be cautioned about
breathing vapors. Do not use materials contaminated by exposure to
moisture. Remove contaminated materials from the site.
1.7 ENVIRONMENTAL CONDITIONS: Do not install CSPE sheet roofing
during high winds, inclement weather (rain, snow, sleet, fog, etc.), when
such weather is threatening, or when there is ice, frost., moisture, or
visible dampness on the substrate surface. Unless recommended otherwise by
the CSPE sheet manufacturer in writing, do not install CSPE sheet when air
temperature is below 40 degrees F (4-5 degrees C) or within 5 degrees F (3
degrees C) of the dew point.
1.8 WARRANTY: Furnish the CSPE sheet manufacturer's premier warranty
to include the following for the roofing system. The warranty shall be
issued directly to the Government. In no event shall the warranty period be
less than ten years from the date of the Government's acceptance of the
work. The warranty shall provide that if within the warranty period the
CSPE sheet roofing system becomes non watertight, splits or tears,
alligators, separates at the seams, or shows any other symptoms of failure
because of defective materials and/or workmanship, the repair and/or
replacement of defective materials and correction of defective workmanship
shall be the responsibility of the CSPE sheet manufacturer. If the
manufacturer or his approved applicator fail to perform repairs within 72
hours of notification, emergency repairs performed by others will not void
the warranty, and shall be billed to the manufacturer issuing the warranty.
NFSS-T40
07534-4
PART 2 - PRODUCTS
2.1
MATERIALS:
2.1.1 Reinforced Non-Vulcanized Polymeric Sheet: Chlorosulfonated
polyethylene (CSPE) 45 mil nominal thickness with high strength, minimum 10
x 10, polyester scrim. The width and length of the sheet shall be as
recommended by the manufacturer. The CSPE polymer shall represent 90
percent by weight minimum of the total polymer portion of the rubber
compound. Physical properties shall be as follows:
SCRIM REINFORCED SHEET
PROPERTY
VALUE
TEST METHOD
Thickness, min., in.
0.041
ASTM D 751
Tensile Strength, min., lbf
200
ASTM D 751
Elongation, min., %
20
ASTM D 751
Tear Strength, min., lbf
(Tongue tear 8" x 8" sample)
75
ASTM D 751
Low Temperature Flexibility at
-40 degrees C
Pass
ASTM D 2136
Linear Dimensional Change, max. %
(1 Hr. at 100 degrees C)
1.0
ASTM D 1204
Ply Adhesion, min., lfb/in.
10.0
ASTM D 413
Type A Specimen
Hydrostatic Resistance, min., psi
200
ASTM D 751,
Method A
Puncture Resistance, min., lbs
225
FTMS 101c
Method 2031
Ozone Resistance,
7 x Magnification
28 days/40 degrees C/100 pphm
no cracks
ASTM D 1149
Method B
Weather Resistance, 3 Million
Langleys
no checking,
cracking or
crazing
ASTM E 838
NFSS-T40
07534-5
2.1.2 Adhesive: As recommended by the CSPE sheet man by the
elastomeric sheet manufacturer's printed instructions.
2.1.3 Water Cutoff Mastic, Lap Cleaner, Reactivating Agent, and
Sealant: As recommended by the CSPE sheet manufacturer's printed
instructions.
2.1.4 Flashing and Flashing Accessories: Flashing including perimeter
flashing and flashing around roof penetrations, shall be the same material
as the field sheet, either reinforced or nonreinforced, or as recommended by
the CSPE sheet manufacturer's printed instructions. Nonreinforced 45 mil,
noncured membrane shall be provided for field-fabricated vent stacks, pipes
and corners, per CSPE sheet manufacturer's printed application instructions.
2.1.5 Fasteners and Plates: Noncorrosive as recommended by the CSPE
sheet manufacturer's printed instructions and meeting the requirements of FM
Approval Sheet 4470.
2.1.6
Rubber Walkboards:
2.1.6.1
psf weight.
Rubber Walkboards:
One-half inch minimum thickness, 1-1/2
2.1.7 Roof Insulation Below CSPE Sheet: As specified in Section
07220. The insulation shall be compatible with the membrane as recommended
in the membrane manufacturer's printed instructions.
2.1.8 Fire Safety: The complete roof covering assembly being
installed shall have (G) UL 790 Class A classification, be listed as
fire-classified in the UL Building Materials Directory and bear the UL
label, or listed as Class I roof deck construction in the FM Approval Guide.
2.1.9 Windstorm Resistance: The complete roof covering assembly shall
be capable of withstanding an uplift pressure of 90 pounds per square foot
(psf) when tested in accordance with the Factory Mutual uplift pressure test
described in the FM Loss Prevention Data Sheets 1-28 and 1-29.
PART 3 - EXECUTION
3.1 PREPARATION: Coordinate work with that of other trades to ensure
that components which are to be incorporated into the roofing system are
available to prevent delays or interruptions as the work progresses.
Examine substrates to which the roofing materials are to be applied to
ensure that their condition is satisfactory for its application. Do not
permit voids greater than 1/8-inch (3 mm) wide in the substrate. Concrete
substrates shall be cured and free of laitance and curing compounds.
Install wood blocking at perimeters, curbs, and penetrations for use in
mechanically attaching the membrane. Substrates for roofing materials shall
be dry and free of oil, dirt, grease, sharp edges, and debris. Inspect
substrates, and correct defects before application of CSPE sheets.
NFSS-T40
07534-6
3.2
SPECIAL PRECAUTIONS:
a.
Do not dilute caulking materials or adhesives unless
specifically recommended by the CSPE sheet manufacturer's
printed application instructions. Do not thin liquid
materials with cleaners used for cleaning CSPE sheet.
b.
Keep all liquids in airtight containers, and keep containers
closed except when removing materials.
c.
Use liquid components, including adhesives, at least 60 days
before the end of their shelf life period. Store adhesives
at 60 degrees F to 80 degrees F (15 to 26 degrees C) for at
least 24 hours prior to use. Avoid excessive adhesive
application and adhesive spills. Follow adhesive
manufacturer's printed application instructions.
d.
Do not allow contact between various materials through mixing
of remains, dual use of mixing, transporting, or application
equipment. Do not use equipment containing the remains of
previous materials.
e.
Require workmen and others who walk on the membrane to wear
clean, soft-soled shoes to avoid damage to roofing materials.
f.
Do not use equipment with sharp edges which could puncture
the CSPE sheet.
g.
Install sheet material the same day the CSPE membrane roll is
removed from its protective wrapping. Any unused portions
shall be protected from direct exposure to sunlight until
installed.
3.3 WORK SEQUENCE: Arrange work to prevent use of newly constructed
roofing for storage, walking surface, or equipment movement. If access is
necessary, provide temporary walkways, platforms, or runways to protect new
roofing surfaces and flashings from mechanical damage.
3.4 APPLICATION: Apply CSPE sheet roofing in accordance with the CSPE
sheet manufacturer's printed application instructions and the following
requirements.
3.4.1 CSPE Sheet Roofing: The sheet shall be watertight and visually
free of pinholes, particles of foreign matter, undispersed raw material, or
other manufacturing defects that might affect serviceability. Edges of the
sheet shall be straight and flat so that they may be seamed to one another
without fishmouthing. All surfaces to be seamed shall be cleaned of all of
NFSS-T40
07534-7
all cured CSPE material (activated) prior to hot air seaming. Every seam
made per day shall be 100% probed by the Contractor by the end of the day's
work. Each defect shall be permanently marked and promptly repaired in
accordance with manufacturer's repair recommendations. Scrim exposed edges
shall be caulked using approved methods and materials provided by the
manufacturer.
3.4.1.1 Mechanically Fastened Reinforced CSPE Sheets (Scrim
Reinforced): CSPE sheets are attached using the manufacturers recommended
plates and screws meeting the requirements herein, and FM required fastening
pattern. Adjoining rolls of sheet membrane shall overlap fastened edge of
the installed membrane by a minimum of 4-1/2 inches.
3.4.1.2 Perimeter Fastening: Mechanically secure the CSPE sheet to
nailers at roof perimeter and penetrations with specified fasteners as
required by the CSPE sheet manufacturer's printed instructions. Space
fasteners a maximum of 8 inches (203 mm) o.c., except as recommended
otherwise by the CSPE sheet manufacturer's printed instructions. Strip
slash over the fasteners with a fully adhered layer of flashing material.
The type of flashing materials and procedures for strip flashing shall be
that recommended in the CSPE sheet manufacturer's printed instructions.
3.4.1.3 Temporary Work: Install temporary cutoffs around incomplete
edges of roofing assembly at the end of each day's work and when work must
be postponed due to inclement weather. Straighten the insulation line using
pieces of insulation loosely laid, and seal the CSPE sheet membrane to the
deck. Seal metal deck ribs as part of the cutoff. Remove the temporary
seals completely when work resumes. Provide temporary ballast on the
roofing as necessary to prevent wind damage to the CSPE sheet.
3.4.2 Flashing: Install flashing as roofing sheets are installed as
indicated. Extend base flashing not less than 8 inches (203 rmn) above
roofing surface. Completely adhere flashing sheets in place. Use
prefabricated pipe seals at pipe penetrations where possible, otherwise
field fabricate pipe seals as specified in paragraph entitled "Flashing and
Flashing Accessories".
NFSS-T40
07534-8
3.4.3 Insulation: Insulation or protection board must be approved by
the manufacturer for use on mechanically attached fully adhered
applications. Use the insulation manufacturer's approved fasteners and
plates. There shall be maximum 1/8-inch variation between adjacent boards
of insulation.
3.4.4 Roof Walkways: Install rubber walkways, where indicated, and
for access to mechanical equipment, in accordance with the CSPE sheet
manufacturer's printed instructions. Provide an additional CSPE sheet under
rubber walkways to protect the roofing.
3.5
FIELD TESTING
3.5.1 Test Cuts: Each day, in the presence of, and at a location
selected by the Contracting Officer, a minimum of one 6-inch square cut
sample across a field seam shall be taken by the Contractor and inspected
for proper lap, seaming, and cleanliness. Any deficiencies must be
corrected before work will be allowed to proceed. Cutting of the samples,
correction of deficiencies, and patching of the cut areas in accordance with
the CSPE manufacturer's printed instructions are the Contractor's
responsibility and will be performed at no additional cost to the
Government.
3.6 INFORMATION CARD: Provide a typewritten card, laminated in
plastic for interior display; and framed for exterior display a
photoengraved 0.032 inch (0.8-mm) thick aluminum card for each roof. The
card shall be a minimum size of 8-1/2- x 11-inches (216 mm x 279 mm) and
contain the information listed in the attached Form 1. Install the card
near the access to the roof or where directed. In addition to the framed
card, furnish a duplicate card to the Contracting Officer. Send a photocopy
of the card to __________________________________________________________.
3.7 INSTRUCTIONS TO GOVERNMENT PERSONNEL: Provide written and verbal
instructions on proper maintenance procedures to Government personnel
designated by the Contracting Officer. Instructions shall be provided by a
competent representative of the CSPE sheet manufacturer and shall include a
minimum of two hours on maintenance and repair of the membrane. Include a
demonstration of membrane repair, and give sources of required special
tools. Provide information on safety requirements during maintenance and
repair instructions and supply additional copies of Material Safety Data
Sheets on all maintenance/repair materials.
NFSS-T40
07534-9
FORM I
REINFORCED CSPE NON-VULCANIZED POLYMERIC SHEET ROOFING SYSTEM
1.
Contract Number
2.
Building Number & Location:
3.
NAVFAC Specification Number:
4.
Deck Type:
5.
Slope of Deck:
6.
Insulation Type & Thickness:
7.
Insulation Manufacturer:
8.
Vapor Retarder
9.
Vapor Retarder Type:
( ) Yes
( ) No
10. Sheet Polymeric Roofing Description:
Manufacturer (Name, address, & phone no.):
Type:
Method of attachment:
11. Statement of Compliance or Exception:______________________________
_______________________________________________________________________
_______________________________________________________________________
12.
Date Roof Completed:
13.
Warranty Period:
14.
Roofing Contractor (Name & Address):
15.
Prime Contractor (Name & Address):
Contractor's Signature____________________________ Date:
Inspector's Signature_____________________________ Date:
*** END OF SECTION ***
NFSS-T40
07534-10
SECTION 07950
CALKING, SEALANTS, AND FIRESTOPPING
PART I - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publications listed below form
a part of this specification to the extent referenced. The publications are
referred to in the text by the basic designation only.
1.1.1
Federal Specification (Fed. Spec.):
TT-S-001543A
1.1.2
1.2
Sealing Compound, Silicone Rubber Base,
for Calking, Sealing, and Glazing in
Buildings and Structures
American Society for Testing and Materials (ASTM) Publications:
C 920-87
Elastomeric Joint Sealants
E 84-88
Surface Burning Characteristics of Building
Materials, Standard Test Method for
E 136-82
Behavior of Materials in a Vertical Tube
Furnace at 750 Degrees C, Standard Test
Method for
E 814-83
Fire Tests of Through-Penetration Fire Stops,
Standard Method of
SUBMITTALS:
1.2.1 Certificates of Compliance: Submit certificates from the
manufacturers attesting that materials meet the specified requirements.
1.2.2 Manufacturers' Descriptive Data: Submit complete descriptive
data for each type of material indicated below. Data for sealant and
calking shall include application instructions, shelf life, mixing
instructions for multi-component sealants, and recommended cleaning
solvents.
a.
b.
c.
d.
e.
Calking and Sealing Compounds
Joint Primer
Backing Material
Bond Breaker
Firestopping; composition and performance characteristics
NFSS-T40
07950-1
1.3 DELIVERY AND STORAGE: Deliver materials to the job site in
the manufacturers' external shipping containers, unopened, with brand names,
date of manufacture, color, and materials designation clearly marked
thereon. Containers of elastomeric sealant shall be labeled as to type,
class, grade, and use. Carefully handle and store all materials to prevent
inclusion of foreign materials or subjection to sustained temperatures
exceeding 90 degrees F. or less than 40 degrees F. Calking compounds,
sealants and components more than six months old shall not be used.
PART 2 - PRODUCTS
2.1 ELASTOMERIC SEALANTS: For joints in vertical surfaces, provide
ASTM C 920, Type S or N, Grade NS, Class 25. For joints in horizontal
surfaces, provide ASTM C 920, Type S or M, Grade P, Class 25. Use as
appropriate for surfaces sealed.
2.2 SILICONE RUBBER BASE SEALANT: Silicone rubber base sealant shall
be class A single component cold-applied sealing compound conforming to Fed.
Spec.
TT-S-001543.
2.3 COLOR: Color of sealing compound shall match the color of
adjacent surfaces or be paintable to match adjacent surfaces.
2.4 PRIMER FOR SEALANT: Non-staining, quick-drying type as
recommended by the sealant manufacturer for the particular application, that
will seal the surfaces in joint grooves and prevent absorption of the
vehicle essential to the retention of elasticity by the sealing compound.
2.5 BACKING AND FIRESTOPPING MATERIAL: Glass mat, closed-cell
neoprene, butyl, polyurethane, expanded polyethylene, polyvinylchloride, or
a compatible rubber gasket or tape recommended by the manufacturer of the
compound. Materials shall be free from oil or other staining elements.
Oakum and other types of absorptive materials shall not be used.
Firestopping shall be asbestos free and capable of maintaining an effective
barrier against flame and gasses; flame spread 25 or less, smoke development
50 or less when tested according to ASTM F-84 and non-combustible according
to ASTM E 136.
2.6 BOND BREAKER: Bond breaking materials shall be pressure-sensitive
adhesive polyethylene tape, aluminum foil or wax paper. Bond breaking
materials are not required where backing material with bond breaking
characteristics is provided.
2.7 SOLVENTS AND CLEANERS: Solvents, cleaning agents and other
accessory materials used in connection with sealing compounds shall be of
type recommended by the compound manufacturer.
NFSS-T40
07950-2
PART 3 - EXECUTION
3.1 GENERAL REQUIREMENTS: All joints about the perimeter of portlite
and door frames, louvers, wall and ceiling plating, sleeves, masonry
expansion joints, other openings, and elsewhere indicated and specified,
shall be filled and calked with compound in a manner to provide watertight
and smoke-tight sealing. Except as specified otherwise herein, preparation
of surfaces, application and cleaning shall be in accordance with the
manufacturer's printed instructions and details.
3.2 SURFACE PREPARATION: Surfaces shall be clean, dry to the touch,
and free from frost, moisture, grease, oil, wax, lacquer, paint, and other
foreign matter that would tend to destroy or impair adhesion. Depth of
joints shall be approximately 1/2 their width, and shall never exceed the
joint width. Where adequate grooves have not been provided, clean out
grooves to a depth of 1/2 inch and grind to a minimum width of 1/4 inch
without damage to the adjoining work. No grinding shall be required on
metal surfaces.
3.3
APPLICATION:
3.3.1 Backing Material: Where joint cavities are constructed deeper
than 1/2 their width, tightly pack the back or bottom with backstop material
to provide a joint of the proper depth. Openings greater than 1/2 inch in
depth shall be first filled to within 1/2 inch of the surface with backing
material packed firmly in place. Install backstops dry and free of tears
and holes.
3.3.2 Firestopping: Provide firestopping in duct, conduit, and piping
penetrations through walls and ceilings. Firestopping at penetrations of
insulated piping shall be applied prior to insulation unless the insulation
meets the requirements for firestopping. Fill void spaces to within
1/2-inch of the surface with firestopping materials installed in accordance
with manufacturer's instructions.
3.3.3 Primer: Treat joints in concrete masonry units, wood, and
other porous surfaces with primer in accordance with the sealant
manufacturer's instructions. Apply primer to the joint surfaces to be
sealed. Surfaces adjacent to joints shall not receive primer.
3.3.4 Bond Breaking Materials: Bond breaking materials shall be
provided on the back or bottom of joint cavities to prevent the sealant from
adhering to these surfaces. The materials shall be carefully applied to
avoid contamination of adjoining surfaces or breaking bond with surfaces
other than those covered by bond breaking materials.
3.3.5 Sealing Compounds: Apply sealing compounds with an approved
type of calking gun, with nozzles of the sizes required to fit the several
widths of joints. The compound shall be forced into the joint grooves with
sufficient pressure to force out all air and to fill the grooves solidly.
NFSS-T40
07950-3
Calking around all openings shall include the entire perimeter of the
openings except at concrete sills and metal thresholds of doors. Upon
completion of the calking, all unfilled joints shall be roughened and filled
as specified and tooled smooth. All excess material shall be neatly
removed.
3.4
PROTECTION AND CLEANING:
3.4.1 Protection: Protect areas adjacent to joints from compound
smears. Masking tape may be used for this purpose if removed 5 to
10 minutes after the joint is filled.
3.4.2 Cleaning: Upon completion of compound application, remove all
remaining smears and stains resulting therefrom and leave the work in a
clean and neat condition. On non-porous building surfaces, excess uncured
sealant shall be removed with a solvent moistened cloth. On porous
surfaces, allow excess sealant to cure for 24 hours then remove by
wire-brushing or sanding.
*** END OF SECTION ***
NFSS-T40
07950-4
SECTION 13250
DAMAGE CONTROL SIMULATOR SPECIALTIES
PART 1 - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publications listed below form a
part of this specification to the extent referenced. The publications are
referred to in the text by the basic designation only.
1.1.1
Federal Specifications (Fed. Spec.):
L-P-387A
& Int Am 2
Plastic Sheet, Laminated, Thermosetting
(for Design Plates)
FF-S-92B
& Am 1
Screw, Machine, Slotted, Cross-Recessed, or
Hexagon Head
TT-C-490C(1)
Cleaning Method for Ferrous Surfaces and
Pretreatment for Organic Coatings
TT-P-645-k
Primer, Paint, Zinc-chromate, Alkyd Type
TT-V-51F
Varnish, Asphalt
ZZ-H-451G
Hose, Fire,Woven Jacketed Rubber-Or Latex or
Rubber Coated Fabric Lined, With Couplings
1.1.2
Military Specification (Mil Spec.):
DOD-P-15328D
Primer (Wash), Pretreatment, (Formula No. 117B
for Metal) (Metric)
DOD-P-21035A
Paint, High Zinc Dust Content, Galvanizing
Repair (Metric)
MIL-F-16377/11A
(SHIP)
Fixtures, Fluorescent, General Lighting, 40
Watts, 115 Volts, 60 Hertz, Watertight,
Symbols 77.4, 77.5, 344.2 and 344.3
MIL-F-16377/53
(SHIPS)
Fixtures, Incandescent, Detail Lighting,
Lantern Hand, Portable and Relay Watertight,
Symbols 100.2, 101.2, 102.2 and 08
NFSS-T40
13250-1
MIL-J-24649(i)
Jackbox, Jack and Plug for Telephone, Sound
Powered
MIL-T-24381/1
(SHIPS)
Terminal, Casualty Power, Bulkhead,
200-Ampere, 500 Volt, Three-Phase, Alternating
Current, Symbol Number 1025
MIL-T-24381/2
(SHIPS)
Terminal Casualty Power, Riser,
200-Ampere, 500 Volt, Three-Phase, Alternating
Current, Symbol Numbers 1032, 1033, and 1034
1.1.3 American Society for Testing and Materials (ASTM)
Publications:
A307-88
Carbon Steel, Externally and Internally
Threaded Standard Fasteners
B26-86
Aluminum Alloy Sand Castings
B108-87
Aluminum Alloy Permanent Hold Castings
B136-84
Measurement of Strain Resistance of Anodic
Coatings on Aluminum
B137-45
(R 1979)
Measurement of Weight of Coating on
Anodically Coated Aluminum
B209-88
Aluminum Alloy Sheet and Plate
B221-88/B221M-88
Aluminum and Aluminum Alloy Extruded Bars,
Rods Wire, Shapes and Tubes
B244-79
Measurement of Thickness of Anodic Coatings on
Aluminum and of Other Non conductive Coatings
on Nonmagnetic Base Metals with Eddy Current
Instruments
C1048-87
Heat-Treated Flat Glass - Kind HS, Kind FT
Coated and Uncoated Glass
1.1.4 National Association of Architectural Metal Manufacturers
(NAAMM) Publications:
Metal Finishes Manual (January 1976)
NFSS-T40
13250-2
1.1.5
American Welding Society (AWS) Publication:
B2.1-84
Welding Procedure and Performance
Qualification
D1.1-88
Structural Welding Code
1.1.6
American Institute of Steel Construction (AISC) Publication:
Manual of Steel Construction (8th edition)
Specification for the Design, Fabrication and Erection of
Structural Steel for Buildings, November 1, 1978
1.1.7
American Society of Mechanical Engineers (ASME) Publication:
Boiler and Pressure Vessel Code, Section VIII, Division 1
1.1.8
Steel Structures Painting Council (SSPC) Publications:
SP3-82
Surface Preparation Specification No. 3,
Power Tool Cleaning
SP6-85
Surface Preparation Specification No. 6, Commercial
Blast Cleaning
1.2 WORK INCLUDED: Provide fabricated or manufactured components
of Damage Control Simulator. Structural steel and fabrication of steel
items is specified in Section 05150, "Steel Fabrications, Structural and
Pressure". Mechanical and electrical requirements are specified in
Divisions 15 and 16, respectively.
1.3
SUBMITTALS:
1.3.1 Samples: Prior to fabrication or delivery to site of any
work or material, submit completely identified representative samples of
shop or factory fabricated stock items. Include fastening devices and
specified materials, finish, texture and, where required, furnish color
chips for approval.
1.3.2 Shop Drawings: Following approval of materials, but before
fabrication, submit shop drawings for all fabricated items. Show the
construction of the various members, kinds and gages of metal, notes as to
finishes and proposed methods of anchoring and securing all items.
1.3.3 Certificates of Compliance: Before delivery of equipment or
materials, except for material specified to bear markings or statements,
certificates from the manufacturer shall be submitted attesting that
materials meet the requirements specified herein.
NFSS-T40
13250-3
1.3.4 Manufacturer's Data: Manufacturer's data shall be submitted for
all factory fabricated items. Data which describe more than one type shall
be clearly marked to indicate which type the Contractor intends to provide.
Data shall be sufficient to show conformance to specified requirements.
1.3.5 Operation and Maintenance Manuals: As specified in section
15011, "Mechanical General Requirements" and Section 16011, "Electrical
General Paragraphs".
a.
b.
c.
d.
e.
f.
g.
Watertight doors
Hatch
Port lights
Clothes lockers
Fire stations
Duct heater
Shipboard light fixtures
h.
i.
j.
k.
l.
m.
Battle lanterns
Power terminals
Direct current power supply
Bulkhead collapse simulator
Torpedo hit simulator
Fans
1.4 QUALIFICATION OF WELDERS: Field and shop welding shall be
performed by certified welders qualified in accordance with AWS B3.0. Submit
certificates of qualification for welders.
1.5 INSTRUCTIONS TO GOVERNMENT PERSONNEL (TRAINING): Provide the
services of competent instructors) who will give full instruction to
designated personnel in the operation and maintenance of the Damage Control
Simulator. The Government personnel designated to attend training will have
a high school education or equivalent. A training day is defined as 8-hours
of instruction, including two 15-minute breaks and excluding lunch time,
Monday through Friday. Conduct training at the site for 2 consecutive days
at a time mutually agreeable between the Contractor and the Government.
Submit written notice to the Contracting Officer 2-weeks prior to scheduling
training.
1.6 DELIVERY, STORAGE, AND PROTECTION: Deliver materials to the site
in an undamaged condition. Carefully store materials off the ground to
provide proper ventilation, drainage, and protection against dampness.
Items shall be free from nicks, scratches and blemishes.
NFSS-T40
13250-4
PART 2 - PRODUCTS
2.1 MATERIALS: The provisions of this paragraph apply to special
equipment and items of miscellaneous metalwork. Gages shown on the drawings
or specified herein are U. S. Standard for ferrous metals, and Brown and
Sharp for non-ferrous metals. Gages and thicknesses of material shown or
specified are minimum. Materials shall conform to the requirements
specified for the particular item; and where these requirements are not
specified in detail, the materials shall be suitable for the intended usage
of the item.
2.1.1 Aluminum Alloy Products: Aluminum alloy products shall conform
to ASTM Standards B209 for sheet and plate, B221 for extrusions and B26 or
or B108 for castings, as applicable. Aluminum extrusions shall be at least
1/8-inch thick and aluminum plate or sheet shall be at least 16 gauge,
0.0508-inch thick. Aluminum alloys shall be 6063-T5 for extrusions,
1100-H14 for sheets and plates and 214 for castings.
2.1.1.1 Metal Surfaces: Exposed aluminum sheets, plates, and
extrusions shall, before finishes are applied, be free of roll marks,
scratches, rolled-in scratches, kinks, stains, pits, orange peel, die marks,
structural streaks, and any other defects which will affect the uniform
appearance of finished surfaces.
2.1.1.2 Anodizing: Hard oxide coating formed by electrolytic
treatment, and shall be applied to all aluminum work exposed to view.
Aluminum shall receive a minimum coating thickness of 0.7 mil and a minimum
coating weight of 27 milligrams per square inch. Test for anodizing shall
conform to ASTM B 137 for coating weight, ASTM B244 for coating thickness
and KSTM B136 for sealing.
2.1.1.3 Finishes: Except where indicated otherwise, finish shall
generally be caustic etch finish, medium matte, equal to National
Association of Architectural Metal Manufacturers Finish C22. Unexposed
sheet, plate and extrusions may be mill finish as fabricated. Castings
shall have sand blast finish, medium, equal to National Association of
Architectural Metal Manufacturers Finish M43.
2.1.2 Ferrous Metals: Ferrous metals shall conform to Section
05150, "Steel Fabrications, Structural and Pressure".
2.1.3
Fasteners:
2.1.3.1
Bolts and Nuts:
ASTM A307.
2.1.3.2
Machine Screws:
Fed. Spec. FF-S-92.
NFSS-T40
13250-5
2.1.4 Anchors: Expansion shields, plugs, bolts, and other anchorage
devices in masonry and concrete shall be approved type. Expansion shields
shall be hot-dipped galvanized.
2.1.5 Welding: Welding shall conform to the applicable requirements
of AWS D1.1 for arc and gas welding.
2.1.6 Fastening Devices: Provide screws, bolts and other fastening
devices for attachment and joints. All fastenings shall be concealed where
practicable. Where exposed in finished surfaces screw heads shall be
Phillips, oval type, unless otherwise shown, specified or approved. Oval
head screws shall be No. 6 with a No. 8 head. Standard bolts and screws
shall be used for attachment of work to structure. Where hollow concrete
masonry units make the use of expansion bolts unsuitable, provide toggle
bolts or other suitable fastening devices as approved. Wood plugs shall not
be used in any material. Use non-ferrous attachments for non-ferrous metal.
2.2 FABRICATION: All metalwork shall be fabricated in a first-class
manner by experienced mechanics skilled in the trade and in accordance with
the manufacturer's directions. Miscellaneous metalwork shall be well formed
to shape and size, with sharp lines and angles and true curves. All work
shall be fabricated to allow for expansion and contraction of materials.
Welding and bracing shall be of adequate strength and durability, with
tight, flush joints, dressed smooth and clean.
2.2.1 Built-In-Work: Metal work built-in with concrete or masonry
shall be formed for anchorage, or be provided with suitable anchors,
expansion shields, or other anchoring devices shown on drawings or as
required. Such metal work shall be furnished in ample time for setting and
securing in place in the concrete and masonry work as the work progresses.
2.3 MISCELLANEOUS METALWORK ITEMS: Miscellaneous steel brackets,
supports and shapes shall meet the requirements specified herein above,
shall be suitable for the intended use and shall be provided as indicated.
2.3.1 Steel Framing: The overhead and bulkheads of the Crew's
Berthing, Observation, Machinery and Engineering Stores Compartments shall
be fabricated as indicated. The overhead shall be tack welded to the
supporting beams with 2-inch beads every 2 feet along all joints and all
joints and other openings caulked with silicone sealant as per specification
Section 07950 "Calking, Sealants, and Firestopping". Special care shall be
taken to caulk gaps at the ends of the supporting beams and channels so that
the entire enclosure is rendered smoke-tight.
NFSS-T40
13250-6
2.4 DAMAGE CONTROL SIMULATOR SPECIALTIES: Possible sources of
commercially available specialty products are listed in Appendix A.
2.4.1 Watertight Doors: Provide watertight interior doors, sized as
indicated, high or low hinge, dogged as indicated, 15 psi (maximum
pressure), hasp as indicated. Provide with fabricated steel plate frame and
sub-frame for installation as indicated. Provide pressure test spigots in
each door as indicated. Shop primer shall be Fed. Spec. TT-P-645 zinc
chromate primer. Reference - Bureau of Ships (BUSHIPS) drawings
805-1626357, 805-1400072, 805-1400073, 805-1400074.
2.4.1.1 Hardware and Accessories: Provide 3/4-inch pipe dogging
levers and mounting clips. Install where indicated. Reference - BUSHIPS
drawing S 1602-917821.
2.4.2 Hatch With Scuttle: Watertight, 36-inch by 42-inch clear
opening, double braced, short side hinged, 30 psi, individually dogged
hatch. Scuttle in hatch cover shall be 18-inches in diameter, watertight,
quick acting wheel operated from either side. Height of coaming shall be as
indicated. Provide wrench for dog nuts and wrench storage slips. Mount at
top of hatch. Shop primer shall be TT-P-645 zinc chromate primer.
Reference - BUSHIPS Drawing 805-1624088D.
2.4.3 Port Lights: Provide three 16-inch diameter fixed aluminum
port lights fabricated in accordance with BUSHIPS drawing 805-1749038.
Glaze with 3/4-inch thick heat treated glass conforming to ASTM C1048, Kind
FT, condition A, Type I Class 1 (clear), quality q3. Provide hinged dead
light covers on Observation Compartment side of bulkhead plate. Position
with hinge pin at bottom and retainer toggle pin at top.
2.4.4
Crew's Berth and Clothes Lockers:
2.4.4.1 Crew's Berths: Provide two berth assemblies, each with three
berths and "without locker under" fabricated in accordance with NAVSHIPS
Drawing 80064-1409485, Sheets 1, 2, and 3 and as indicated. Stanchion pipes
of crew's berths shall be mounted with floor flanges and overhead brackets
and shall be removable. Berths shall be fastened to the stanchion with
removable 1/2-inch toggle pins and "C" section. Three 3/4-inch diameter
drain holes to be made in each berth as indicated.
2.4.4.2 Clothes Lockers: Provide two clothes lockers, steel Type B-1,
three compartments high, fabricated in accordance with Bureau of Ships
drawing 80064-804459767. Provide with right hand door. Modify standard
base to 8-inches high as indicated. Secure lockers to the bulkhead or frame
by means of brackets and removable 1/2-inch toggle pins, located at the
side.
NFSS-T40
13250-7
2.4.5 Fire Stations: Provide two false bulkhead plate mounted fire
stations. Stations shall include strainer, hose, nozzle, applicator,
spanner wrenches, hose camel, hinged hose rack, applicator, brackets, nozzle
bracket and wrench bracket. Items not commercially manufactured shall be
fabricated as indicated. Manufactured commercially available items shall be
as follows:
a.
Strainer: 1-1/2 inch marine strainer - Bureau of Ships
Drawing 810-1385901, 1-1/2 inch NPSH bronze body, perforated
nickel copper screen, barrel type self cleaning, NSN
4210-00-025-3364.
b.
Hose: Fifty feet, 1-1/2 inch fire hose, Federal
Specification ZZ-H-451, rubber lined, Type III, Class B, 600
psi test pressure, female to male threaded copper alloy
fittings, 1-1/2 inch NPSH.
c.
Hose Nozzle: 1-1/2 inch all purpose nozzle, Bureau of Ships
Drawing 810-1385834, NSN 4210-00-392-2943, three position
type, bronze threaded female hose connection 1-1/2 inch
NPSH.
d.
Applicator: 1-1/2 inch nozzle applicator, Bureau of Ships
Drawing 810-1385834, NSN 4210-00-372-0864, 4 feet long, head
end bent 60 degrees, used with 3 position nozzle.
e.
Wrenches: Provide 2 adjustable spanner wrenches, Federal
Specification GGG-W-665, Type 1, sized to fit 1-1/2 hose
couplings.
2.4.6
Space Heating:
Provide as indicated and specified herein.
2.4.6.1 Electric Duct Heater: An electric resistance duct-type
heater shall be installed in the ductwork in the mechanical equipment
compartment as indicated and specified in Section 15840, "Ductwork and
Accessories". The unit will be controlled by a waterproof thermostat
located in the Observation Compartment.
NFSS-T40
13250-8
2.4.7 Deck Drains: Type A: Provide deck drains, with trap, valve and
integral cast steel ring on bronze body as indicated. Reference - Bureau of
Ships Drawing 810-1385789. Provide deck drain control wrenches for bulkhead
mounting where indicated. Install drains as specified in Section 15450,
"Water Supply and Drain Systems".
2.4.8 Overflow Drains: Provide 4-inch overflow drains, with trap,
cast iron body and 4-inch nickel brass stand pipe with dome cover as
indicated and as specified in Section 15450, "Water Supply and Drain
Systems".
2.4.9 Shipboard Lighting Fixtures Type M: Provide 40 watt, 115 volt
60 hertz watertight, fluorescent fixtures conforming to Mil. Spec.
MIL-F-16377/11 (Ships), Symbol 77.4 or 344.2. Install in accordance with
Section 16550, "Lighting, Control Trainer".
2.4.10 Battle Lanterns: Provide lantern body assemblies, shipboard,
watertight, 5.6 inch x 6.5 inch, Mil. Spec. MIL-F-16377/53 (Ships), Symbols
101.2, 102.2 or 108. NSN 623-00-783-6510. Modify as follows: Batteries
shall not be provided, modify terminal to receive direct wiring from remote
6 volt D.C. source. Omit relay and test switch and provide suitable plug
for test switch hole. Provide as specified in Section 16450, "Electric and
Signal Wiring Systems" and 16550, "Lighting, Control Trainer".
2.4.11 Casualty Power Bulkhead Terminal: Provide Casualty Power
Bulkhead Terminal (Biscuit), 200 ampere 500 volt three phase, alternating
current, Mil. Spec. MIL-T-24381/1 (Ships), Symbol 1025 as indicated. Mount
biscuit 48 inches above floor. Provide two Casualty Power Terminal Wrenches
and double wall mounted holder for each biscuit. Mount tool holders as
indicated, adjacent to each biscuit at 60 inches above floor. Provide as
specified in Section 16550, "Lighting, Control Trainer".
2.4.12 Casualty Power Riser Terminal: Provide Casualty Power Riser
Terminals (Biscuits) 200 ampere 500 volt, three phase, alternating current,
Military Specification MIL-T-24381/2, Symbol 1032 where indicated. Mount
biscuit 48 inches above floor. Provide two Casualty Power Terminal wrenches
and double wall mounted holder for each biscuit. Mount tool holder as
indicated, adjacent to each biscuit at 60 inches above floor. Provide as
specified in Section 16550, "Lighting, Control Trainer".
NFSS-T40
13250-9
2.4.13 Junction Boxes: Shipboard type, waterproof with brass
coverplates conforming to NAVSHIPS drawing 900-S6202-F-74106, Symbol 2843,
alternate 6 Type 4 TD8-2 and as specified in Section 16450, "Electric and
Signal Wiring Systems".
2.4.14 Direct Current Power Supply: Provide unit converting 120
volt single phase AC input to 6 volt, 6.3 AMP, 250 WATT DC output, wired and
switched into system, as indicated and as specified in Section 16550,
"Lighting, Control Trainer".
2.4.15 Telephone Jack Boxes: Brass, submersible, sound powered
telephone jack boxes, with spaces for 4 jacks conforming to Mil. Spec.
MIL-J-24649, Type G-15C; and Section 16450, "Electric and Signal Wiring
Systems".
2.5
FABRICATIONS, ASSEMBLIES:
2.5.1 Water System: Piping and valves shall be in accordance with
Section 1545U "Water Supply and Drain System". The water shall be supplied
by a 2-inch line from the domestic water line through a gate valve and a
0-100 psi pressure gauge. The line shall pass through a back-flow preventer
to a pressure regulating Valve 0-100 psi set at 55 psi, the regulating valve
to be by-passed completely with a globe valve and two gate valves.
a.
The 2-inch line shall branch through gate valves to the fire lines
and to the Seam Rupture and Torpedo Hit Simulators. The lines
shall be fitted with water hammer arresters and circuit the Damage
Control Trainer as indicated, wrapped to 6-inches diameter to
simulate full size fore lines, and feed two Fire Stations, three
gate valves being provided to isolate each Fire Station. The
descending pipe to the Fire Station shall be wrapped to simulate
2-1/2-inch piping.
b.
The other main shall pass through a gate valve and another
pressure regulator set at 20 psi, past a 0-100 psi, 2-inch
diameter pressure gauge and through two isolating gate valves to
the Torpedo Hit and Seam Rupture simulators.
2.5.2
Bulkhead Collapse Simulator:
2.5.2.1 General: The Bulkhead Collapse Simulator shall be a
pneumatically operated moving bulkhead. Movement shall be limited to 3
inches and accomplished by four, double-acting, universal clevis mounted, 3
1/4-inch diameter air cylinders, one at each corner. The weight of the
bulkhead shall be supported by casters. Fabricate as indicated and
specified.
2.5.2.2 Framing and Fabrication: Opening shall be framed as
indicated. Weld channel cylinder mounting brackets to rear face at each
NFSS-T40
13250-10
corner of the channel frame. Movable front of bulkhead shall be 1/4-inch
steel plate with four vertical 4-inch framing members attached on Berthing
Room side and three horizontal 3-1/2 inch x 3-1/2 inch x 1/4 inch angles on
Observation Room side. Provide two 1/4 inch steel plate gusset brackets
welded to the bulkhead plate. Provide two rigid casters with 6-inch
diameter semi-steel wheels and sealed roller bearings. Weld top plate of
casters to gusset brackets.
2.5.2.3 Pneumatic System: Provide air compressor unit as specified in
Section 15470, "Compressed Air System". The pressure in the pneumatic
system shall be governed by an air pressure regulator control range 40-100
psi, located as shown. Unit shall incorporate an air pressure gauge
indicating pressure from 0 to 100 psi which shall be 2 inch dial indicator
type with rear connector fitting. Regulator shall also incorporate a filter
with automatic drain removing both airborne solids and water. Normal
operating pressure shall be 75 psig.
2.5.2.4 Bulkhead Control and Operation System: Provide the following
components for the movable bulkhead collapse control and operation system:
10
8
4
8
4
1
8
4
4
-
Push button valve operators - panel mounted
Flow control valves
Air operated valves
Blow down valves
Cylinders (3-1/4-inch bore)
Regulator with filter and gauge
Cast pivot mounting brackets
Cast clevises and pins
Steel rod clevises and pins
Assembly pins, retainers and jamb nuts, 1/8-inch and
3/8-inch copper and plastic tubing and fittings.
2.5.2.5 Identifying labels are to be mounted on the panels adjacent to
the push button controls, indicating the function of each button. The
labels to be of 1/4 inch high lettering on 1/2 inch wide, colored plastic
bands as specified in paragraph "Nameplates".
2.5.2.6 Hand Protectors: Install flexible neoprene sheet goods
hand protectors on the Crew's Berthing Compartment side of the movable
bulkhead as shown in the plans.
2.5.2.7 Bulkhead Shoring Stanchions: The steel columns supporting the
overhead in the Crew's Berthing Compartment are to be used in the Bulkhead
Collapse shoring exercise. Fabricate and connect as indicated and
specified.
2.5.3 Simulated Pipe Breaks: Provide six 5 foot long simulated pipe
break sections fabricated of 1-1/2 inch, 3-inches, 4-inches, and 6-inches
grooved end, galvanized schedule 40 pipe, standard bolted pressure
couplings, reducers and quick disconnect snap joint couplings.
NFSS-T40
13250-11
Reducers and couplings shall be galvanized. Provide compound, severed,
split, simple and ruptured flange simulated breaks as indicated. Several
breaks shall be connected together by 1/2-inch diameter rods, interior
welded to each pipe section. Where the severed break is too narrow to allow
welding of rod to pipe, the rods shall be extended and welded at the end.
2.5.3.1 Brackets: Fabricate brackets to hold pipe break sections
in line with the water line pipe connections, the brackets to be held
securely to the wall as indicated. Galvanize after fabrication.
2.5.3.2 Rack: Provide storage rack for pipe break sections where
indicated in the Damage Control Locker space. Galvanize after fabrication.
2.5.4 Torpedo Hit Simulator: Provide Torpedo Hit simulator and ten
torpedo hit plates with storage rack. Fabricate simulator as indicated.
Provide spray head and piping as indicated. Spray head shall be 120 degrees
conical wide angle flow pattern 8 gpm at 20 psi auto-spray nozzle, with
adjustable face, finished in rough nickel plate 1/2-inch pipe line with
globe valve to be provided to permit draining of simulator tank.
2.5.4.1 Plates: Provide ten 19-inch x 19-inch x 1/4-inch steel
Torpedo Hit plates with cuts (damage simulation) as indicated. Plates shall
be provided with 12 bolt holes for 1/2-inch diameter bolts for mounting to
bulkhead mounted studs. Provide 12 galvanized steel wing nuts (or dogs) and
a 1/4-inch thick neoprene gasket for mounting of plates to the bulkhead.
Galvanize plates after fabrication.
2.5.4.2 Rack: Provide storage rack for Torpedo Hit plates. Rack
shall be fabricated with a welded pipe frame with handles. Plate spacers
shall be 1/2-inch steel rod welded at 1-1/2 inch on center. Rack shall
accommodate 10 plates. Galvanize rack after fabrication.
2.5.4.3 Water Supply: Water supplied to the Torpedo Hit simulator to
be reduced in pressure by a regulating valve to 20 psi as specified in
Section 15450, "Water Supply and Drain Systems".
2.5.5 Seam Rupture Simulator: Provide Seam Rupture Simulator as
indicated. Water supplied to the Seam Rupture Simulator to be reduced in
pressure by a regulating valve to 20 psi as specified in Section 15450,
"Water Supply and Drain Systems".
2.5.6 Simulated Void: Provide steel tank, cover and angle coaming
(frame) as indicated. Fabricate tank of 1/8 inch steel with welded inlet
and outlet couplings. Depth shall be as indicated. Anchor tank to angle
coaming. Tank to be fitted with fill line, drain connection and sounding
tube with gate valve, threaded cap, and union below valve as indicated and
specified in Section 15450, "Water Supply and Drain Systems". Galvanize
after fabrication.
NFSS-T40
13250-12
2.5.7 Ships Ladder: Provide fabricated aluminum inclined ladder
assembly. Reference: Bureau of Ships Drawing 805-1749113 REV.C. Ladder
shall be Type 2, 24 inches wide with Type Y (pipe and chain) and Type X hand
rail. Stringers shall be 5 inches x 2-1/2 inches aluminum channels. Treads
shall be 6 inches wide, Type F, extruded aluminum. Reference: Bureau of
ships drawing 804-860041. Ladder and hand rail assemblies shall be
separately removable. Anchorage shall be with stainless steel toggle pins
with attached flexible keeper steel cable.
2.5.8 Fans: Provide exhaust and circulating fans as indicated
and specified in Section 15820, "Air Handling and Distribution Equipment".
2.5.8.1 Controls: In the Observation Gallery, provide system
control switches as indicated. Control system shall be as specified in
Section 16450, "Electrical and Signal Wiring Systems".
2.6 GRAPHICS: Where signs are indicated to identify the compartment
provide 2 inch high stencil letter, color black and provide a rectangular
painted background, color "sun yellow". Apply coatings as specified in
Section 09910, "Painting of Buildings".
2.6.1
Messages:
a.
The compartments shall be designated as follows:
CREW'S BERTHING COMPARTMENT
ENGINEERING STORES COMPARTMENT
MACHINERY COMPARTMENT
(Indicate Room Number if
Appropriate)
b.
Provide 2 inch high black stencil letters to designate the
frame members.
c.
Provide 1 inch high black stencil letter and black arrow on
the fire loop insulation.
2.6.2 Nameplates: Provide laminated plastic nameplates for equipment,
gages, valves, control panels and other labeling. Laminated plastic shall
be 0.125-inch thick melamine plastic conforming to Fed. Spec. L-P-387, black
with white center core. Surface shall be a matte finish. Corners shall be
square. Accurately align lettering and engrave into the white core.
Minimum size of nameplates shall be 1.0 inch by 2.5 inches. Lettering shall
be minimum of 0.25-inch high normal block lettering. Equipment nameplates
shall show the following information:
NFSS-T40
13250-13
a.
b.
c.
Manufacturer, type, and model number
Contract number and accepted date
Capacity or size
2.7 SHOP PAINTING: Except as otherwise specified, shop paint all
miscellaneous steelwork, except zinc-coated surfaces and steelwork to be
embedded in concrete or mortar. Surface to be welded shall not be coated
within three inches of the weld prior to welding. Insure that surfaces are
thoroughly dry and clean when the paint is applied. Do not paint in
freezing or wet weather except under cover. Do not apply paint when the
temperature is below 40 degrees Fahrenheit or expected to drop to 32 degrees
Fahrenheit or below before the paint has completely dried. Do not apply
paint to steel which is at a temperature that will cause blistering or
porosity, or will otherwise be detrimental to the life of the paint. Apply
paint in a workmanlike manner, and coat all joints and crevices thoroughly.
Prior to assembly, paint all surfaces which will be concealed or
inaccessible after assembly.
2.7.1 Cleaning: Except as modified herein, blast clean surfaces
in accordance with SSPC-SP6. Surfaces that will be exposed in spaces above
ceilings, attic spaces, crawl spaces, furred spaces, and chases may be
cleaned in accordance with SSPC-SP3 in lieu of being blast cleaned. Wash
cleaned surfaces which become contaminated with rust, dirt, oil, grease, or
other contaminants with solvents until thoroughly clean. Insure that steel
to be embedded in concrete is free of dirt and grease. Do not paint or
galvanize bearing surfaces, including contact surfaces within friction-type
joints, but coat them with an approved rust preventative, applied in the
shop. Remove such coating just prior to field erection using a remover
approved by the rust preventative manufacturer. Insure that the surfaces,
when assembled, are free from rust, grease, dirt and other foreign
matter.
2.7.2 Pretreatment: Except as modified herein, immediately after
cleaning and before any rust has formed, coat surfaces with a pretreatment
coating conforming to Mil. Spec. DOD-P-15328 applied to dry film thickness
of 0.3 to 0.5 mil or with a crystalline phosphate base coating conforming to
Fed. Spec. TT-C-490, Method I, except apply phosphate base coating only to
blast cleaned, bare metal surfaces.
2.7.3 Priming: Prime treated surfaces as soon as practicable,
after the pretreatment coating has dried. Except as modified herein, prime
with zinc chromate primer conforming to Fed. Spec. TT-P-645, applied to a
minimum dry film thickness of 1.0 mil. Surfaces that will be concealed
after construction and will require no overpainting for appearance may be
primed with a coat of asphalt varnish conforming to Fed. Spec. TT-V-51
applied to a minimum dry film thickness of 1.0 mil in lieu of zinc chromate
primer. Repair damage to primed surface with primer.
NFSS-T40
13250-14
2.8 REPAIR OF ZINC COATING: Repair zinc coating that has been damaged
in handling or transporting or in welding, riveting, or bolting by the
application of galvanizing repair paint conforming to Mil Spec. DOD-P-21035.
Clean all areas to be repaired and remove slag from the welds.
Do not heat surfaces to which the repair paint is applied.
PART 3 - EXECUTION
3.1 PREPARATION: Verify measurements and take necessary field
measurements before fabrication. Materials and parts necessary to complete
each item shall be included, even though such work is not definitely shown
or specified. Miscellaneous bolts and anchors, supports, braces, and
connections necessary for completion of the Damage Control Simulator shall
be provided.
3.2 INSTALLATION: All metal work shall be installed in a first class
manner by experienced mechanics skilled in the trade and in accordance with
the manufacturer's directions and shall be plumb and true to the exact lines
and levels, in the correct locations and in proper relation to adjoining
work. Build anchors and other connecting members which occur in concrete or
masonry into the concrete or masonry as the work progresses, so as to avoid
unnecessary cutting and drilling. Cut, fit and drill as may be necessary so
that all materials are properly set in place and so as to permit engaging
work to be properly installed.
3.2.1 Connections: Connections shall be at least equal to the Minimum
Standard Connections as shown in AISC "Manual of Steel Construction".
Joints shall be continuous along entire line of contact, except where spot
welding is indicated or permitted. Where exposed, welds shall be ground
smooth; where bolted or riveted connections are indicated, such connections
may be welded at the Contractor's option, but welds shall be ground
perfectly smooth. Threaded connections shall be made up tight so that
threads are concealed. Bolted work shall be made up tight and the threads
nicked or the stem bushed to prevent loosening. Rivet, bolt and screw heads
shall be flat and countersunk in exposed work. Removable members shall be
carefully machined.
3.2.2 Welding: AWS D1.1 by certified welders. Welding of Pressure
Vessels; ASME Boiler and Pressure vessel Code, Section 8, Division 1.
3.2.3 Buckle and Warping: Build-in reinforcement, wholly concealed
within the finished assembly, as shown or as required. All panels and
extrusions, exposed in the finished work shall be free from buckle, ,warping
and oil canning effects. The flatness of the panels shall not deviate more
than 1/8-inch plus or minus from the true plane when tested between any two
points or a panel casing. Long members built-up of extruded or drawn
members shall be held together at end Joints by concealed sleeves of similar
shape, welded or braced in place for a hairline joint.
NFSS-T40
13250-15
3.3 CORROSION PREVENTION: Insulate aluminum work in contact with
other metals, concrete, or masonry with building paper, zinc chromate or
bituminous paint.
3.4 FINISH PAINTING:
Section 09910, "Painting"
Surfaces shall be finished as specified in
3.5 FIELD TESTING: The Contracting Officer will conduct field
inspections and witness all field tests and trial operations specified. The
Contractor shall perform all trial operations and field tests and provide
all labor, equipment, and incidentals required for testing. All work shall
be constructed properly in accordance with the drawings and specifications.
Deficiencies found shall be corrected and affected work shall be retested.
3.5.1 Demonstration: Show that everything works as specified. Provide
2 man-days instruction to Government personnel on operation and maintenance
of Damage Control Trainer in accordance with Section 15011, "Mechanical
General Requirements, and Section 16011, "General Requirements, Electrical".
NFSS-T40
13250-16
APPENDIX A
Possible Sources for
Damage Control Trainer Specialties
Salient Characteristics
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
Commercially available products and fabrications meeting specified
requirements. Other products by other manufacturers will be acceptable
provided the products meet specified requirements.
(1)
(2)
WATERTIGHT DOORS AND HATCH WITH SCUTTLE SOURCES:
Railway Specialties Corp.
P.O. Box 29
Bristol, PA 19007
Overbeke - Kain
20905 Aurora Road
Cleveland, OH 44146
Tele: (216) 662-4242
Kerrfotl Division of Singer
550 South Fulton Avenue
Nt. Vernon, NY 10550
Tele: 914-664-6033
Lossett's Inc.
P.O. Box 173
Picayune, NS 39466
Tele: 601-798-6022
PORTLIGHT SOURCES:
The Rostand Manufacturing Co
33 Railroad Avenue
Milford, CT 06460
Tele: 203-874-2547
(3)
Cornell-Carr
620 Main Street R 125
Monroe, CT 06468
Tele: 203-261-2529
CREWS BERTHS AND CLOTHES LOCKER SOURCES:
Cole Division (Crews Berth Only)
Litton Systems, Inc.
640 Whiteford Road
York, PA 17405
Tele: 717-854-1545
NFSS-T40
13250-17
Jamestown Metal
104 Blackstone Avenue
Jamestown, NY 14701
Tele: 716-665-5410
(4)
(5)
(6)
FIRE STATION EQUIPMENT SOURCES:
Boston Coupling Company, Inc.
Extinguishers, Inc.
16 Bridge Street
P.O. Box 320
Watertown, MA 02172
Tele: 617-926-3233
Dixie Fire
P.O. box 686
Austen, GA 30001
Walter Kidde and Company, Inc.
P.O. Box 1147
Wake Forest, NC 27587
Tele: 919-556-6811
DESCO
DeSanno Foundry & Machinery Co.
1933 Peralta Street
Oakland, CA 94607
Tele: 415-832-0776
DRAIN SOURCES (DECK AND OVERFLOW):
DESCO
DeSanno Foundry & Machinery Co.
1933 Peralta Street
Oakland, CA 94607
Tele: 415-832-0776
Tate Temco
1941 Landsdowne Bldg.
Baltimore MD 21227
Tele: 301-247-8700
Liberty Equipment & supply
2744 16th Ave., S.W.
Seattle, WA 98134
Tele: 206-682-8700
J.M. Loeffler Company
U.S. Hwy.#1 & Robbins Ave.
Penndel, PA 19047
Tele: 215-757-2404
LIGHTING FIXTURES, JUNCTION AND TELEPHONE JACK BOX SOURCES
William & Watts, Inc.
Nova Division
319 Manley St.
West Bridgewater, MA 02379
Tele: 508-588-5434
Roflan Company
P.O. Box
Newburyport, MA 01950-5613
Tele: 508-462-1615
NFSS-T40
13250-18
L.C. Doane Co.
10 New City Street
Essex, CT 06426
Tele: 203-767-8295
(7)
BATTLE LANTERN SOURCES
Roflan Company
P.O. Box 913
Newburyport, MA 01950-5613
Tele: 508-462-1615
Dixie Fire Extinguishers,Inc.
P.O. Box 686
Austen, GA 30001
Young Engineering Company
P.O. Box 50327
New Orleans, LA 70150
Tele: 504-581-6292
(8)
CASUALTY POWER TERMINAL SOURCES:
Dorn Equipment Corporation
27 Upham Street
Melrose, MA 02176
Tele: 617-622-9300
General Marine Products
1 Gulf Drive
Auburn, N.Y. 13021
Tele: 315-252-4502
Young Engineering Company
P.O. Box 50327
New Orleans, LA 70150
Tele: 504-581-6292
(9)
PIPE BREAK REDUCER AND COUPLING SOURCES:
Aero Quip Corp.
Industrial Division
1225 W. Main St.
Van Wert, OH 45891
Tele: 419-238-1190
Victualic Co. of American
4901 Kesserville Rd.
P.O. box 31
Easton, PA 18042
*** END OF SECTION ***
NFSS-T40
13250-19
SECTION 15450
WATER SUPPLY AND DRAIN SYSTEMS
PART I - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publications listed below form a
part of this specification to the extent referenced. The publications are
referred to in the text by the basic designation only.
1.1.1
Federal Specifications (Fed.. Spec.):
RR-F-621D
Frames, Covers, Gratings, and Steps, Sump
and Catch Basin, Manhole
TT-P-645A
Primer, Paint, Zinc Chromate, Alkyd Type
WW-V-35C
Valve, Ball
1.1.2
Military Specifications (Mil. Spec.):
MIL-P-17552E
Pump Units Centrifugal, Water, Horizontal; General
Service
MIL-T-52777A
Tanks, Storage, Underground, Glass Fiber Reinforced
Plastic
1.1.3
American National Standards Institute (ANSI) Publications:
A112.21M-80
Floor Drains
A112.26.1M-84
Water Hammer Arresters
A112-36.2M-83
Metallic Cleanouts
B16.3-85
Malleable-Iron Threaded Fittings
B16.12-83
Cast-Iron Threaded Drainage Fittings
B16.18-84
Cast Copper Alloy Solder Joint Pressure Fittings
B16.22-80
Wrought Copper and Copper Alloy Solder Joint
Pressure Fittings
NFSS-T40
15450-1
B16-39-86
Malleable-Iron Threaded Pipe Unions
B40.1-85
Gages, Pressure, Indicating Dial Type, Elastic
Element
1.1.4
American Society for Testing and Materials (ASTM) Publications:
A 53-88
Pipe, Steel, Black and Hot-Dipped, Zinc-Coated
Welded and Seamless
A 74-87
Cast-Iron Soil Pipe and Fittings
A 120-84
Pipe, Steel, Black and Hot-dipped Zinc Coated
(Galvanized) Welded and Seamless for Ordinary Uses
B 32-87
Solder Metal
B 61-86
Steam or Valve Bronze Castings
B 62-86
Composition Bronze or Ounce Metal Castings
B 88-88
Seamless Copper Water Tube
C 270-86B
Mortar for Unit Masonry
C 478-88
Precast Reinforced Concrete Manhole Sections
C 564-88
Rubber Gaskets for Cast-Iron Soil Pipe and Fittings
F 441-88
Chlorinated Poly (Vinyl Chloride)(CFVC) Plastic
Pipe
1.1.5
American Society of Sanitary Engineers (ASSE) Publications:
1003-81
Water Pressure Reducing Valves for Domestic Water
Supply Systems
1010-82
Water Hamer Arresters
1.1.6
American Water Works Association (AWWA) Publications:
C105/A21.5-88
Polyethylene Encasement for Ductile-Iron Piping for
Water and Other Liquids
C506-78
Standard for Back-flow, Prevention Devices
C651-86
Disinfecting Water Mains
NFSS-T40
15450-2
1.1.7
Cast-Iron Soil Pipe Institute (CISPI) Publications:
301-78
Cast-Iron Soil Pipe and Fittings for Hubless
Cast-Iron Sanitary system
310-78
Patented Joint for use in Connection with Hubless
Cast-Iron Sanitary system
1.1.8
Manufacturers Standardization Society of the Valve and Fittings
Industry (MSS) Publications:
SP-58-83
Pipe Hangers and Supports - Materials, Design and
Manufacture
SP-69-83
Pipe Hangers and Supports - Selection and
Application
SP-80-87
Bronze Gate, Globe, Angle and Check Valves
1.1.9
Plumbing and Drainage Institute (PDI) Publications:
WH201-77
1.1.10
Water Hammer Arrestors
Southern Building Code Congress International (SBCC)
1988
w/Rev.90
Standard Plumbing Code
1.2 GENERAL REQUIREMENTS: Section 15011, "Mechanical General
Requirements", applies to this section, with the additions and modifications
specified herein.
1.3 DESCRIPTION OF WORK: The work includes providing plumbing related
work. The work also includes providing roughing-in and making final
plumbing connections to equipment furnished under other sections of this
specification. Provide each system complete and ready for operation.
Plumbing systems including equipment, materials, installation, and
workmanship shall be in accordance with the Standard Plumbing Code, as
required by local regulations, except as modified herein. The advisory
provisions shall be considered to be mandatory, as though the word "shall"
had been substituted-for the word "should" wherever it appears; referenced
to the "authority having jurisdiction", the Administrative Authority, the
Plumbing Official, and the Design Engineer shall be interpreted to mean the
Contracting Officer. Capacity of equipment shall be not less than that
indicated. Plumbing systems shall include all water supply and drain piping
buried and above ground.
NFSS-T40
15450-3
1.4 SUBMITTALS: <Use optional wording where water tank and/or
sump is required.>
1.4.1
Manufacturer's Data:
a.
b.
c.
d.
e.
f.
g.
h.
<i.
<j.
<k.
1.4.2
Certificates of Compliance:
a.
b.
c.
1.4.3
Pipe and fittings
Valves
Pipe Supports (hangers)
Gages
Strainers
Drains
Water hammer arresters
Backflow preventers
Tank>
Pump, Water>
Sump Pump>
Pipe and fittings
Valves
Backflow preventers
Certified Data:
a.
<b.
Backflow preventers
Pump test curves>
<1.4.4 Operation and Maintenance Manuals:>
<a. Pumps>
<1.4.5
Posted Operating Instructions:>
<a. Pumps>
1.5 INSULATION: Insulate equipment and piping under this section
as specified in Section 15250, "Insulation for Mechanical systems".
1.6 ELECTRICAL MOTORS, CONTROLLERS, CONTRACTORS, AND DISCONNECTS:
Furnish motors, controllers, contractors, and disconnects with their
respective pieces of equipment. Motors, controllers, contractors, and
disconnects shall conform to and shall have electrical connections provided
under Section 16450, Electrical and Signal Wiring Systems". Controllers and
contractors shall have a maximum of 120-volt control circuits, and auxiliary
contacts for use with the controls furnished. When motors and equipment
furnished are larger than sizes indicated, the cost of providing additional
electrical service and related work shall be included under this section.
NFSS-T40
15450-4
PART 2 - PRODUCTS
2.1 DV (DRAIN AND VENT) PIPING: Fittings shall be long radius
fittings, except fittings in vent piping may be short radius fittings.
2.1.1 Buried Piping: Buried piping includes piping up to but not
more than 6 inches above top of sleeve in floor slab. Completely encase
buried cast-iron piping with polyethylene tube or sheet in accordance with
AWWA C105.
2.1.1.1 Cast-Iron Huble as Pipe and Fittings:
310 coupling joints.
CISPI 301 with CISPI
2.1.1.2 Cast-Iron Hub and Spigot Pipe and Fittings: ASTM A 74 with
ASTM C 564 rubber compression gasket joints, or calked and leaded joints.
2.1.2
Above ground Piping:
2.1.2.1 Cast-iron Hubless Pipe and Fittings:
310 coupling joints.
CISPI 301 with CISPI
2.1.2.2 Cast-iron Hub and Spigot Pipe and Fittings: ASTM A 74
with ASTM C 564 rubber compression gasket joints, or calked and leaded
joints.
2.1.2.3 Copper Tubing: ASTM B 306, with ANSI B16.23, ANSI B16.29,
or ANSI B16.32 solder joint fittings using ASTM B 32, 50-50 tin-lead solder.
2.1.3 Cleanouts: ANSI A112.36.2; provide threaded bronze or
thermoplastic cleanout plug
2.1.3.1 Floor Cleanouts: Provide cast-iron floor cleanout with
anchor flange <suitable for waterproofing membrane>, polished bronze or
nickel bronze rim and scoriated floorplate with "00" cast in the plate.
Secure floor plate with countersunk screws for installation flush with
finished floor.
<Use optional wording where.membrane waterproofing is required.>
2.1.4 Drains: <Provide drains and clamping rings suitable for use
with waterproofing membrane>.
<Use optional wording where membrane waterproofing is required.>
2.1.4.1 Drains, Type A: Deck drain with trap, valve and integral cast
steel ring on bronze body as specified in Section 13250, "Damage Control
Simulator Specialties".
NFSS-T40
15450-5
2.1.4.2 Drains, Type D: ANSI A112.21.1M; Cast Iron Flush Strainer
Floor Drains. Provide with double flange, perforated or slotted cast
-bronze or nickel bronze strainer, adjustable collar and p-trap, and
backflow preventer. Drains of sizes 2, 3, and 4 inches shall have strainers
with minimum free drainage area of 5, 11, and 18 square inches,
respectively.
2.1.4.3 Overflow Drains: ANSI A112.21.1M and as specified in Section
13250, Damage Control Simulator Specialties", except without anti-backup
valve.
2.1.5 Valve Box: Cast-iron, ductile-iron or plastic box of a suitable
size. Provide cast-iron, ductile-iron, or plastic cover for the box with
DRAIN cast on the cover. Plastic boxes shall be constructed of ABS plastic
or inorganic fiber-reinforced black polyolefin plastic. Coat cast-iron and
ductile-iron surfaces not in contact with concrete with bituminous paint.
2.2
WATER PIPING:
2.2.1 Buried Piping and Above ground Piping: Completely encase buried
copper tubing and steel piping with polyethylene tube or sheet in accordance
with AWWA C105.
2.2.1.1 Copper Tubing: ASTM B 88, Type K, with ANSI B16.18 or ANSI
B16.22 solder joint fittings using ASTM B 32, 95-5 tin-antimony solder; ASTM
B 88, Type L, may be provided for above-ground piping.
2.2.1.2 Steel Pipe: ASTM A 53 or ASTM A 120, Schedule 40, hot-dip
galvanized, threaded end connections; with ANSI B16.12 hot-dip galvanized
threaded fittings.
2.2.2 Water Valves: Provide valves suitable for minimum of 125 psig.
Valves shall have threaded end connections with a union on all but one side
of the valve. Copper alloy and bronze valve body shall be ASTN B 61 or ASTM
B 62 copper alloy.
2.2.2.1
Gate Valves:
Fed. Spec. MSS-SP-80, Class 125.
2.2.2.2
Globe and Angle Valves:
2.2.2.3
Check Valves:
2.2.2.4
Water Pressure Reducing Valves:
Fed. Spec. MSS-SP-80, Class 125.
Fed. Spec. MSS-SP-80, Class 125, swing check.
ANSI A112.26.2
2.2.2.5 Ball Valves: Fed. Spec. WW-V-35 fullport design, copper
alloy. Valves shall have two-position lever handles.
NFSS-T40
15450-6
2.2.3 Gages: ANSI B40.1, single style pressure gage for water with
4.5-inch dial, brass or aluminum case, bronze tube, gage cock, pressure
snubber, and syphon. Provide scale range suitable for the intended service.
2.2.4 Dielectric Connections: Provide at connections between copper
and ferrous metal piping materials. ASTM F 441, Schedule 80, CPVC threaded
pipe nipples, 4-inch minimum length, may be provided for dielectric
connections in pipe sizes 2 inches and smaller.
2.2.5
1010.
Water Hammer Arresters:
PDI WH201, ANSI A112.26.1, or ASSE
2.2.6 Backflow Preventers: Backflow preventers shall be of the
reduced pressure principle type conforming to the applicable requirements of
AWWA C506. A Certificate of Full Approval or a current Certificate of
Approval shall be furnished for each design, size, and make of backflow
preventer being provided for the project. The certificate shall be from the
Foundation of Cross-Connection Control Research, University of Southern
California, and shall attest that this design, size, and make of backflow
preventer has satisfactorily passed the complete sequence of performance
testing and evaluation for the respective level of approval. A Certificate
of Provisional Approval will not be accepted in lieu of the above.
2.3
MISCELLANEOUS PIPING MATERIALS:
2.3.1
piping.
Unions:
ANSI B16.39 hot-dip galvanized steel for use in steel
2.3.2 Escutcheon Plates: Provide one piece galvanized steel flanges
for piping passing through walls and ceilings. Securely anchor flanges
in place with through-bolts.
2.3.3 Pipe Sleeves: Provide where piping passes through walls and
slabs. Secure sleeves in proper position and location during construction.
Provide sleeves of sufficient length to pass through entire thickness of
walls and partitions. Provide not less than 0.25-inch space between
exterior of piping, pipe insulation or jacket and interior of sleeve.
Firmly pack space with insulation and calk at both ends of the sleeve with
plastic waterproof cement as specified in Section 07950, "Calking, Sealants,
and Fire Stopping".
2.3.3.1 Sleeves in Concrete: Provide ASTM A 53 or ASTM A 120, Schedule
40 or Standard Weight, hot-dip galvanized steel pipe sleeves. Provide
sleeves 2-inches minimum above overflow drain inlet at floor sleeves in
spaces with overflow drains and 2-inches above slab elsewhere.
NFSS-T40
15450-7
2.3.4 Pipe Supports (Hangers): Provide MSS SP-58 and MSS SP-69, Type
1 or 6, of the adjustable type, except as indicated or specified herein.
Provide type 40 insulation protection shields for insulated piping. Provide
steel support rods. Provide nonmetallic, hair felt, or plastic piping
isolators between copper tubing and the hangers.
<2.3.5 Tank Vent Piping: Zinc-coated steel, ASTM A 53 or ASTM A 120
standard weight, with ANSI B16.3 zinc-coated malleable iron fittings.>
<Use optional wording where water supply tank is required.>
<2.4 WATER SUPPLY TANK: Provide prefabricated fiber reinforced plastic
(FRP) watertank conforming to MIL-T-52777, Type I (150 degree F), Class A
(vented). Size and configuration indicated, suitable for below grade
installation. Provide an 18-inch by 18-inch aluminum plate laminated on
inside bottom surface directly below manway, reinforced for 150 pounds per
square foot. Provide manway and cover. Provide galvanized corrugated steel
pipe collar conforming to Fed. Spec. WW-P-405, Class I or II, Shape 1,
coating A, Type C. Cast iron frame and cover conforming to Fed. Spec.
RR-F-621; <Traffic (Size 22A), frame-figure 1, cover-figure 8> <Non-traffic
(size 22), frame-figure 4, cover-figure 12>.
<2.4.1 Water Supply Controls: The water level in the tank shall be
controlled by a float valve to shut off the water supply at a high level
in the tank and a mercury switch at a low level in the tank to shut off
the pump drawing water from the tank.>
<2.5 PUMPS: Submit for approval the manufacturer's certified
characteristic performance curve for the impeller size to be finished.
Select the pump so that the operating point on the characteristic
performance curve for the impeller size to be furnished will be to the
left (shut-off side) of and not more than 5 percent below the point of
maximum efficiency for the impeller to be furnished. Provide lifting
attachments on pump.>
<2.5.1 Water Pump: Base mounted pump, Mil. Spec. MIL-P-17552, general
service, mechanical seals and drip-proof electric motor.>
<2.5.2: Submersible Pump: A submersible pump of 125 g.p.m. capacity
shall be supplied to pump the drainage water from the wet well to a suitable
drainage system. Provide factory assembled and tested submersible type pump
as indicated for operation under water. Pump shall be complete with
cast-iron casing, bronze impeller, stainless steel shaft, sealed heavy-duty
ball bearings, water-cooled hermetically sealed motor, built-in automatic
reset thermal protection, two float switches, and waterproof three-conductor
cables and grounding plugs. The float switches shall be mounted so that the
upper switch will start the pump and the lower switch shut-off the pump as
required to control the water level in the wet-well. Provide lifting
attachments and stainless steel chain.>
NFSS-T40
15450-8
<2.6 WET WELL: ASTM C 478 pre-cast concrete of approximately 500
gallons capacity. Set in full bed of ASTM C270 Type H mortar on cast-inpace or precast concrete base. Provide cast-iron <traffic> <non-traffic>
frame and cover as specified for water tank.>
<Use 2.4, 2.5 and 2.6 as required where water supply tank and/or sump
are used.>
PART 3 - EXECUTION
3.1 INSTALLATION: Installation of plumbing systems including
fixtures, equipment, materials, and workmanship shall be in accordance with
the applicable Plumbing code, except as modified herein.
3.1.1 Threaded Connections: Jointing compound for pipe threads shall
be polytetrafluoroethylene (PTFE) pipe thread tape, pipe cement and oil,
or PTFE powder and oil; apply only on male threads. Provide exposed ferrous
pipe threads with one coat of Fed. Spec. TT-P-645 primer applied to a
minimum dry film thickness of 1.0 mil.
3.1.2 Pipe Supports (Hangers): Provide additional supports at the
concentrated loads in piping between supports, such as for flanged
valves.
3.1.2.1 Piping to receive Insulation: Provide temporary wood spacers
between the insulation protection shield and the pipe in order to properly
slope the piping and to establish final elevations. Temporary wood spacers
shall be of the same thickness as the insulation to be provided under
Section 15250, "Insulation for Mechanical Systems".
3.1.2.2
Maximum Spacing Between Supports:
a.
Vertical Piping: Support metal piping at each floor, but at
not more than 10-foot intervals.
b.
Horizontal Piping:
follows:
Support steel piping and copper tubing as
MAXIMUM SPACING (FEET)
Nominal Pipe
Size (inches)
Steel Pipe
c.
One and
under
7
1.25
1.5
2
8
9
10
Support copper tubing as indicated
NFSS-T40
15450-9
3.1.3 Pipe Laying and Jointing: Before placing into position, clean
pipe, fittings, valves, and accessories and maintain in a clean condition.
Cut pipe accurately to measurements established at the site and work into
place without springing or forcing. Lay pipe so that the full length of
each section of pipe and each fitting will rest solidly on the pipe bedding.
Provide anchors and supports where necessary for fastening work into place.
Make provision for expansion and contraction of pipelines. Mon-pressure
pipe shall be laid with the bell ends pointing upgrade beginning at the
lower end of the pipeline.
<3.1.4 Underground Water Tank: Tank shall rest on a minimum of
12-inches of pea-gravel between reinforced concrete deadman anchors and
secured with overtank holddown straps attached to anchors. Tank shall
have an earth cover of not less than 3-feet. Pipe connections shall be
at top of tank. Backfill shall be pea-gravel placed evenly around tank
in 12-inch tamped layers to 12-inches above top of tank. Nominal pea
grave shall range in size of 100 percent passing a 3/8-inch sieve and
100 percent retained on No. 8 sieve. Before placing tank into excavation,
all foreign matter shall be cleaned from tank. Excavation shall be free
from all hard or sharp materials that may cause damage to the tank. Handle
tanks, during transportation and while lifting into ground, in such a manner
as to prevent damage to tank and accessories. After installation, ferrous
metal not in contact with concrete shall be cleaned and given a cost of
bituminous paint, prior to concealment.>
<3.1.5 Wet Well: Precast concrete manhole sections shall be laid in
full beds of portland cement mortar on precast or cast-in-place concrete
base. Base shall have smooth invert sloped to sump.>
<Use 3.1.4 and 3.1.5 as necessary where water tank and/or sump are
required.>
3.1.6 CONNECTIONS TO EXISTING WATER SUPPLY AND DRAIN SYSTEMS: Notify
the Contracting Officer in writing at least 15 days prior to the date the
connections are required; receive approval before any service is
interrupted. Furnish all materials required to make connections into the
existing water supply and drain systems and perform all labor as
required. Furnish the labor and the tapping or drilling machine for
making the actual connections to the existing system.
3.2 DISINFECTION: Disinfect the new water piping and existing water
piping affected by Contractor's operations in accordance with AWWA C601.
Fill the piping systems with solution containing minimum of 50 parts per
million of available chlorine and allow solution to stand for minimum of
24 hours. Flush the solution from the systems with clean water until
maximum residual chlorine content is not greater than 0.2 parts per
million.
NFSS-T40
15450-10
3.3 FIELD TESTING: Before final acceptance of the work, test each
system as in service to demonstrate compliance with the contract
requirements. Perform the following tests in addition to the tests
specified in the Standard Plumbing Code, except as modified herein. Correct
all defects in the work provided by the Contractor, and repeat the tests
until the work is in compliance with contract requirements. Furnish water,
electricity, instruments, connecting devices, and personnel for the tests.
3.3.1 Water Piping: Before insulation is applied, hydrostatically
test each piping system at not less than system working pressure with no
leakage or reduction in gage pressure for 2 hours.
3.3.2 DV Piping: Before the installation of fixtures, cap the ends of
each system, fill the piping with water to vent height, and allow to
stand until a thorough inspection has been made. After the piping and
simulated void have been set and filled with water, subject the entire
drain system to a final air pressure test of not more than 1.0 inch of
water column. Hold the pressure for 24 hours, repair leaks and retest.
<3.3.3 Water Tank: Test the tank and hold down straps in accordance
with Mil. Spec. MIL-T-52777.>
<Use where water tank is required.>
*** END OF SECTION ***
NFSS-T40
15450-11
SECTION 15470
COMPRESSED AIR SYSTEM
PART 1 - GENERAL
1.1 APPLICABLE PUBLICATIONS: The publications listed below form a
part of this specification to the extent referenced. The publications
are referred to in the text by the basic designation only.
1.1.1
Federal Specifications (Fed. Spec.):
L-P-39OC (2)
Plastic, Milking and Extrusion
Material, Polyethylene and Copolymers
W-B-654A (1)
Brazing, Alloys, Silver
WW-H-171 E(1)
Hangers and Supports, Pipe
WW-P-521G
Pipe Fittings, Flange Fittings, and Flanges; Steel
and Malleable Iron (Threaded and Butt-Welding)
Class 150
WW-T-696E
Traps, Steam and Air
1.1.2
Military Specifications (Mil. Spec.):
MIL-C-17596F
Compressors, Reciprocating or Rotary, Power Driven
(EMD), tir, Base Mounted, 10 HP to 300 HP
MIL-S-16293G
Strainers, Sediment, Pipeline, Water, Air, Gas,
Oil, or Steam
MIL-V-18634B
Valve, Safety, Relief, and Safety-Relief
MIL-T-27730A
Tape, Antiseize, Polytetrafluoroethylene, with
Dispenser
NFSS-T40
15470-1
1.1.3
American National Standards Institute (ANSI) Publications:
B2.1-68
Pipe Threads (Except Dryseal)
B16.18-84
Cast Bronze Solder-Joint Pressure Fittings
B16.22-80
Wrought Copper and Bronze Solder-Joint
Pressure Fittings
B31.1-83
Power Piping (Including Addenda 1981 to 1982)
B40.1-85
Gauges - Pressure Indicating Dial Type Elastic
Element
Z49.1-88
Safety in Welding and Cutting
1.1.4
American Society for Testing and Materials (ASTM) Publications:
A 120-84
Pipe, Steel, Black and Hot-Dipped Zinc-Coated
(Galvanized) Welded and Seamless, For Ordinary
Use
B88-88
Seamless Copper Water Tube
D1248-84
Polyethylene Plastics, Molding and Extrusion
Materials
1.1.5
American Society of Mechanical Engineers (ASME) Publications:
1986
1.1.6
Boiler and Pressure Vessel Code and
Interpretations (Including Addenda to date
of design)
Section II
Material Specifications
Section VIII
Division 1, Pressure
Vessels
Section IX
Welding and Brazing
Qualifications
American Welding Society (AWS) Publications:
A2.4-86
Symbols for Welding and Nondestructive
Testing, Including Brazing
A3.0-85
Welding Terms and Definitions
NFSS-T40
15470-2
1.1.7 Manufacturer's Standardization Society of the Valve and Fittings
Industry (MSS) Publications:
SP-58-88
Pipe Hangers and Supports - Materials, Design,
and Manufacture
SP-69-83
Pipe Hangers and Supports - Selection and
Application
SP-80-87
Bronze Gate, Globe, Angle and Check Valves
1.1.8
Occupational Safety and Health Act (OSHA) Standard:
29 CFR 1910.219
Mechanical Power-Transmission Apparatus
1.2 GENERAL REQUIREMENTS: Design, fabrication, and installation of
compressed air system shall conform to ANSI B31.1 and the ASME Boiler
and Pressure Vessel Code, except as specified otherwise. In ANSI B31.1
and the ASME Boiler and Pressure Vessel Code, the advisory provisions
shall be considered mandatory, as though the word "shall" had been
substituted for "should" wherever it appears; reference to the "authority
having jurisdiction" and "owner" shall be interpreted to mean the
Contracting Officer. Section 15011, "Mechanical General Requirements",
applies to this section except as specified otherwise.
1.2.1
Submittals:
1.2.1.1
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
1.2.1.2
a.
Manufacturer's Data:
Compressor
Receiver
Pipe and Tubing
Fittings
Valves
Adapters
Instrumentation and Controls
Condensate traps
Filters
Strainers
Flexible connections
Air cylinders.
Valves (blow down, flow control, push button)
Operation and Maintenance Manual:
Compressor
NFSS-T40
15470-3
1.2.1.3
a.
b.
Posted Operating Instructions:
Compressor
Compressed air system
1.2.1.4 Equipment Data: Submit the following data for all equipment
listed for "Operation and Maintenance Manuals".
a.
b.
c.
Name and address of authorized branch or service department.
Characteristic curves.
Following applicable data completely filled in:
Manufacturer and Model No.
Operating Speed
Capacity
(CFM)
Type of Bearings in Unit
Type of Lubrication
Type and Adjustment of Drive
Capacity of Tank
Electric Motor: Manufacturer, Frame and Type
-Motor Speed
RPM
Current Characteristics and HP of Motor
Thermal cut-Out Switch: Manufacturer, Type and Model
1.2.2
Safety Precautions:
1.2.2.1 Temperature Restriction: Compressor or other equipment shall
not discharge compressed air to the piping system above 100 degrees F.
NFSS-T40
15470-4
1.2.2.2 Rotating Equipment: Fully guard couplings, motor shafts, and
other exposed rotating or rapidly moving parts in accordance with OSHA
29 CFR 1910.219. Provide rigid and suitable secured guard parts readily
removable without disassembling guarded unit.
1.2.2.3 Welding:
to ANSI Z49.1.
1.3
Safety in welding and cutting of pipe shall conform
WELDING GENERAL REQUIREMENTS:
1.3.1 Performance: The Contractor shall be responsible for the
quality of all joint preparation, welding, and examination. 411
materials used in the welding operations shall be clearly identified and
recorded. The inspection and testing defined in this specification are
minimum requirements. Additional inspection and testing shall be the
responsibility of the Contractor when he deems.it necessary to achieve
the quality required. This shall be subject to the Contracting Officer's
inspections and surveillance.
1.3.2
Definitions:
Shall be in accordance with kWS k3.0.
1.3.3
Symbols: Shall be in accordance with AWS k2.4.
PART 2 - PRODUCTS
2.1 AIR COMPRESSOR, UP TO 125 psig SYSTEM: Conform to Mil. Spec.
MIL-C-17596, except as specified or indicated otherwise. Provide V-belt
driven, one or two stage, single-acting, air-cooled compressor completely
wired and piped with inlet filter, compressor, motor, starter, control,
mounted on a sturdy steel base. Capacity and motor horsepower not less than
3/4 HP. Automatic controls shall function to maintain not less than 60 psig
air pressure in receiver. See Section 13250,
2.1.1 Control: Regulate compressor by dual control. Dual system
shall consist of automatic start-and-stop control by automatic and
manual selector switch.
2.1.1.1 Start-and-Stop Control: When set for start-and-stop control,
motor shall stop automatically when discharge pressure reaches maximum
pressure setting 100 psig, and start automatically when discharge pressure
reaches minimum pressure setting 60 psig. Cylinders shall unload during
periods of motor shutdown.
2.1.1.2 Constant Speed Control: Compressor shall operate continuously
at constant speed. Provide means to automatically load and unload
compressor at preset minimum and maximum pressure settings respectively.
Provide means for automatic release of pressure within cylinders when the
unit is operating without load. Also provide means for manual or automatic
NFSS-T40
15470-5
unloading of cylinders during starting of unit. Equip compressor with a
timed control to stop compressor after a 10-minute unloaded period if air is
not used.
2.1.2 Safety Controls: In addition to controls specified elsewhere
in this specification, equip compressor with all of the safety controls
listed in Table I. Control shall provide an alarm of the appropriate
condition by sounding a horn and by flashing an amber light or shall cause a
shutdown of compressor as indicated in the table. Panel-mount gauges and
visual identification lights for control points or mount on a separate
working-height console.
TABLE I.
SAFETY CONTROLS
Shut
Alarm
Down
ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ
High discharge-air temperature
x
x
High discharge-air pressure
x
x
Excessively high motor temp.
x
Excessive vibration
x
2.1.3 Filters - Silencers: Provide filters-silencers on the air intake
to each compressor as recommended by compressor manufacturer. Provide dry
type unit suitable for use with each compressor unit herein described. Unit
shall include a filter section and silencer section. Construct filter
section of a pleated filter paper with protective stainless steel cloth on
both sides. Furnish one extra filter for compressor.
2.1.4
Receiver: Provide receiver to conform to Mil. Spec. MIL-C-17596.
Construct receiver in accordance with ASME Boiler and Pressure Vessel Code,
Section VIII, Pressure Vessels, for working pressures indicated and maximum
temperature of 450 degrees F. Air receiver shall have supporting legs, drain
valve, safety valve, pressure gage, and shut-off valve. Provide
certification of factory test.
NFSS-T40
15470-6
2.2
Low Pressure Compressed kir Piping and Accessories (125 psig):
2.2.1
Piping:
One of the following materials;
a.
Pipe: Black, seamless or welded, standard weight steel pipe
conforming to ASTM 120. Pipe fittings; screwed type for
pipes of 2 inches and smaller. Screwed joints: Threaded in
accordance with ANSI B2.1. Screwed type fittings: 150-pound
malleable iron conforming to Fed. Spec. WW-P-521.
b.
Pipe and Fittings: Type "L" copper tubing, hard drawn, Class
1, conforming to KSTM B 88, with wrought copper or cast
bronze fittings and silver brazed joints conforming to ANSI
B16.18 and B16.22. Silver solder shall conform to Fed.
Spec. QQ-B-654, Class III.
c.
Plastic Tubing: Low density polyethylene tubing conforming
to ASTM D1248, Type 1, Class A Category 3 and Fed. Spec.
L-P-390 Type 1, Class L, Grade 2, Category 3.
2.2.2 Air Cylinders: Shall be 3-1/4-inch bore x 3-inch stroke with
spherical bearing mounts, heavy duty air cylinders with 1/4-inch NPT ports.
2.2.3 Air Filter/Pressure Regulator: Port size 1/2-inch NPT, pressure
range 0/125 psi, polycarbonate bowl, 40 micron filter, automatic drain
removing both airborne solids and water, air pressure gauge with rear
connector to have 2-inch diameter dial type indicator and range of 0 to 125
psi.
2.2.4
ports.
2.2.5
Push Button Control Valves:
3 port, 2 position, 1/8-inch NPT
Air-operated Control Valves:
4 port, 3 position, 1/4-inch NPT.
2.2.6 Compressed kir Piping Valves: 150-pound class bronze gate
valves conforming to MSS SP-80 Type 11, class B, or globe valves conforming
to MSS SP-80 check valves: Lift or swing type conforming to MSS SP-80.
2.2.7 Pressure Gages, Low Pressure: Fed. Spec. GG-G-76, Class 1,
Style X, Type I, with steel or brass case, and nonshatterable safety glass,
and a pressure blowout back to prevent glass from flying out in case of an
explosion. Gages shall have a 3-1/2-inch minimum diameter dial and a dial
range of approximately twice working pressure.
2.2.8 Pressure Reducing Valves: Spring loaded type, with nominal
pressure rating of not less than inlet system pressure indicated. Provide
pressure reducing valves capable of being adjusted to specified flow and
pressure, and suitable for intended service.
NFSS-T40
15470-7
2.2.9 Pipe Hangers and Supports: Fed. Spec. WW-H-171. Furnish zinc
or cadmium plated pipe hangers and supports except for copper piping.
Provide tubing supports of U-shaped steel bolts and nuts firmly secured
to adequate support structure. Clips shall fit closely around piping but
shall have sufficient clearance to permit longitudinal movement of piping
during normal expansion and contraction. Provide supports at valves,
fittings, branch lines, outlets, changes in direction, equipment, and
accessories.
2.2.10 Relief Valves: Bronze conforming to Mil. Spec. MIL-V-18634,
Class 4, Style A. (threaded connections).
2.2.11 Quick Disconnect Couplings: All brass and suitable for a
working pressure of not less than indicated system pressure. Female side
of coupling (fixed end) shall have male thread connection with automatic
shutoff. Provide male side of coupling with hose stem and ball check to
bled pressure from hose and prevent hose whipping.
2.2.12 Single Cartridge Type Filters: Designed for 125 psig operating
pressure and filter housing of brass or bronze. Provide cellulose cartridge
filters of graded density construction capable of removing liquids and
solids of 5 microns and larger. Filter capacity shall be compatible with
rated flow of equipment or pressure reducing valves provided.
2.2.13 Strainers for Compressed Air Service: Bronze body, conforming
to Mil. Spec. MIL-S-16293, Class 125, Style Y, Type II, simplex type,
with 20-mesh Monel or stainless steel screen.
2.2.14 Traps: Fed. Spec. WW-T-696 and to drain water and other
liquids from system. Type of traps as indicated, and rated working pressure
not less than system operating pressure.
2.2.15 Flexible
reinforced corrugated
connections, suitable
manufacturer, but not
Connections: Vibration isolation, wire braid
metal hose type, line-sized, with bronze end
for pressure indicated. Length as recommended by
less than 18 inches.
2.2.16 Tetrafluoroethylene tape for screw-jointed pipe shall conform
to Mil. Spec. MIL-T-27730.
PART 3 - EXECUTION
3.1 INSTALLATION: Install materials and equipment as indicated and
in accordance with manufacturer's recommendations.
3.1.1 Piping: Piping shall follow the general arrangement shown. Cut
piping accurately to measurements established for the work. Work piping
into place without springing or forcing. Piping and equipment shall be
entirely out of the way of lighting fixtures and doors, windows, and
other openings. Locate overhead piping in the most inconspicuous
NFSS-T40
15470-8
positions. Do not bury or conceal piping until it has been inspected,
tested, and approved. Where pipe passes through structure, pipe joints
shall not be concealed, but shall be located where they may be readily
inspected and building structure shall not be weakened. Avoid interference
with other piping, conduit, or equipment. Except where specifically shown
otherwise, vertical piping shall run plumb and straight and parallel to
walls. Piping connected to equipment shall be installed to provide
flexibility for vibration. Adequately support and anchor piping so that
strain from weight of piping is not imposed on the equipment. Do not route
supply piping through simulator bulkheads.
3.1.1.1 Fittings: Use long radius ells where appropriate to reduce
pressure drops. Pipe bends in lieu of fittings may be used for low pressure
piping where space permits, however ASTM A 120 pipe shall not be used for
bending. Pipe bends shall have a uniform radius of at least five times the
pipe diameter and must be free from any appreciable flattening, wrinkling,
or thinning of the pipe. Mitering of pipe to form elbows, notching straight
runs to form full sized tees, or an similar construction shall not be used.
3.1.1.2 Cleaning: Before jointing and erection of piping or tubing,
thoroughly clean interiors of pipe sections, tube, and components. In
steel pipe, loosen scale and other foreign matter by rapping sharply and
expel by wire brush and swab. Blow out both steel pipe and copper tube
and components with compressed air at 100 psig or more. Maintain
cleanliness by closure of pipe/tube openings with caps or plugs. Before
making final terminal connections, blow out complete system with compressed
air at 100 psig or more.
3.1.1.3 Changes in Pipe Size: Use reducing fittings for changes in
pipe size. The use of bushings will not be permitted.
3.1.1.4 Drainage and Flexibility: Compressed air piping shall be
free of unnecessary pockets and pitched approximately 3 inches per 100 feet
in the direction of flow to low points. Provide flexibility by use of
fittings, loops, and offsets in piping. Install branches at top of a main
to prevent carryover of condensate and foreign matter.
3.1.2 Threaded Joints: Where possible use pipe with factory cut
threads, otherwise cut pipe ends square, remove all fins and burrs, and
cut taper pipe threads per ANSI B2.1. Threads shall be smooth, clean,
and full cut. apply thread tape to male threads only. Work piping into
place without springing or forcing. Backing off to permit alignment of
threaded joints will not be permitted. Engage threads so that not more
than three threads remain exposed.
3.1.3 Flare Fittings for Low Pressure Systems: Use flare fittings
only where necessary to connect copper tubing to equipment. Use short
sections of annealed tubing soldered or brazed to hard drawn tubing
using couplings on expanded ends on the annealed tubing made with
NFSS-T40
15470-9
special tools designed for that purpose. Make flares with the appropriate
flaring tools. Cut annealed tubing only with cutting wheel tool. Do not
ream out inside burr or lip left by the cutting wheel but fold back lip with
flare tool to form seal/gasket inside flare. When new, the flare should
cover not more than 75 percent of the flare seating surface of either the
male or female flare fittings. Put the flare nut on the tube before making
the flare.
3.1.4 Valves for Low pressure Systems: Install valves at the
locations indicated and elsewhere as required for the proper functioning
of the system.
3.1.4.1 Gate Valves: Gate valves shall be used unless otherwise
directed. Valves shall be installed in positions accessible for operation
and repair. Install valve with stem horizontal or above.
3.1.4.2 Globe Valves: Globe valves shall be installed so that the
pressure shall be below the disk. Globe valves shall be installed with the
stems vertical.
3.1.4.3 Pressure-Reducing Valves: The compressed air piping entering
each pressure-reducing valve shall be provided with a strainer. Each
pressure-reducing valve unit shall be provided with two block valves and
with a globe or angle bypass valve and bypass pipe. A bypass around a
reducing valve shall be of reduced size to restrict its capacity to
approximately that of the reducing valve. Each pressure-reducing valve
unit shall be provided with an indicating gage to show the reduced
pressure, and a safety valve on the low pressure side. These requirements
do not apply to small pressure regulating valves used to adjust pressure for
pneumatic equipment.
3.1.5 Hangers and Supports: Selection, fabrication and installation
of piping hangers and supports shall conform to MSS SP-58 and SP-69 except
that spacing of the hangers and supports shall be as per Table 1.
TABLE I. MAXIMUM SPAN FOR PIPE
-------------------------------------------------------------------DIAMETER
STD. WT.
INCHES
STEEL PIPE
SCHEDULE 40
-------------------------------------------------------------------1/2
5'-0"
-------------------------------------------------------------------3/4
5'-9"
-------------------------------------------------------------------1
6'-6"
--------------------------------------------------------------------
NFSS-T40
15470-10
3.1.6 Pressure Gages: Pressure gages shall have a shut-off valve or
petcock installed between the gage and the line.
3.1.7 Strainers: Strainers with meshes suitable for the services
shall be provided where indicated, or where dirt might interfere with the
proper operation of valve parts, orifices, or moving parts of equipment.
3.1.8 Equipment Installation: Equipment installation shall be
strictly in accordance with these specifications, and the installation
instructions of the manufacturers. All piping shall be installed in such
a manner as not to place a strain on any of the equipment. All piping
shall be graded, anchored, guided and supported, without low pockets.
3.1.9 Cleaning of System: As installations of the various system
components are completed, they shall be adequately cleaned before final
closing. All foreign matter shall be removed from equipment and surrounding
areas. Preliminary or final tests will not be permitted until the cleaning
is approved by the Contracting Officer.
3.1.10 Sleeves: Provide pipe sleeves where pipes and tubing pass
through masonry walls. Pack the space between pipe or tubing and the sleeve
with safing insulation and seal on both sides of sleeve as specified in
Section 07950, "Calking, Sealing and Firestopping".
3.2
TESTING:
3.2.1 General Requirements, Testing: Perform testing after cleaning
and acceptance of cleanness. Contractor shall furnish everything necessary
for tests. Tests shall be subject to the approval of the Contracting
Officer. Pressurize each piping system individually and check to assure
that there are no cross-connections between different systems prior to
operational tests.
3.2.2 Factory Tests: Test air compressors and compressed air dryers
at the factory to assure proper operation. Contractor shall certify
satisfactory accomplishment of tests.
3.2.3
Hydrostatic and Leak Tightness Tests:
a.
Remove or isolate from the system the compressor, air dryer,
filters, instruments, and equipment which would be damaged by
water during hydrostatic tests and reinstall after successful
completion of tests.
b.
Hydrostatically test piping systems for 30 minutes with water
at one and one-half times design working pressure.
NFSS-T40
15470-11
c.
After satisfactory completion of hydrostatic pressure test,
blow systems dry with clean, oil-free compressed air, and
test with clean, dry air at design working pressure. Brush
joints with soapy water solution to check for leaks. Install
a calibrated test pressure gage in piping system to observe
any loss in pressure. Calibrate the test pressure gage with
a dead weight tester within 15 days before use and certify by
initial and date on a sticker applied to dial face. Maintain
required test pressure for sufficient length of time to
enable an inspection of joints and connections.
3.2.4 Operational Tests: Test equipment as in service to determine
compliance with contract requirements and warranty. During the tests, test
equipment under every condition of operation. Test safety controls to
demonstrate performance of their required function. Completely test system
for compliance with specifications.
3.3 INSTRUCTION TO GOVERNMENT PERSONNEL: Provide 1 man-day of
instruction to I Government employee in accordance with Section 15011
"Mechanical General Requirements" for compressor.
*** END OF SECTION ***
NFSS-T40
15470-12
SECTION 16450
ELECTRIC AND SIGNAL WIRING SYSTEMS
PART 1 - GENERAL
1.1 APPLICABLE PUBLICATIONS: The documents listed below form a part
of this specification to the extent referenced. The documents are referred
to in the text by the basic designation only.
1.1.1
Federal Specifications (Fed. Spec.):
W-C-375B
Notice 1
Circuit Breaker, Molded Case, Branch
Circuit and Service
W-S-896E(2)
Switch, Toggle (Toggle and Lock), Flush
Mounted
1.1.2
Military Specifications (Mil. Spec.):
MIL-J-24649
1.1.3
Jack Box, Jack & Plug for Telephone, Sound
Powered
American National Standards Institute (ANSI):
C80.1-1983
Specification for Rigid Steel Conduit,
Zinc-Coated
C80.3-1983
Specification for Electrical Metallic Tubing,
Zinc-Coated
1.1.4
American Society for Testing and Materials (ASTM):
B 1-85
Hard Drawn Copper Wire
B 8-86
Concentric-Lay-Stranded Copper
Conductors, Hard Medium-Hard, or Soft
1.1.5
National Electrical Manufacturers Association (NEMA):
KS1-1983
(R 1985)
Enclosed Switches
WD1 -1983
General-Purpose Wiring Devices
ST20-1986
Dry-Type Transformers for General
Applications
NFSS-T40
16450-1
1.1.6
National Fire Protection Association (NFPA) Documents:
70-1990
National Electrical Code (NEC)
1.1.7 Underwriters' Laboratories, Inc. (UL) Documents: (All UL
documents shall be current editions published and available in print on
the date of advertisement of this contract.)
1
50
67
360
467
486A
486C
510
514A & B
854
869
943
1053
1242
Flexible Metal Conduit
Cabinets and Boxes
Panelboards
Liquid-Tight Flexible Steel Conduit
Grounding and Bonding
Wire Connectors and Soldering Lugs for
Use with Copper Conductors
Splicing Wire Connectors
Insulating Tape
Outlet Boxes and Fittings
Service-Entrance Cables
Service Equipment
Ground-Fault Circuit Interrupters
Ground-Fault Sensing and Relaying Equipment
Intermediate Metal Conduit
1.2 GENERAL REQUIREMENTS: Section 16011, "Electrical General
Requirements", applies to this section with additions and modifications
specified herein. In each of the standards referred to herein, consider the
advisory provisions to be mandated, as though the word "shall" had been
substituted for "should" wherever it appears. Interpret reference in these
standards to the "authority having jurisdiction", or words of similar
meaning, to mean the Contracting Officer.
NFSS-T40
16450-2
1.2.1 Service: Underground service conductors and associated conduit
shall be continuous from the service entrance equipment to the outdoor
power system connection. Overhead service conductors shall terminate at
the service entrance fittings outside the Damage Control Trainer.
1.3
SUBMITTALS:
1.3.1
Manufacturers' Data:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
1.3.2
Receptacles
Circuit breakers
Switches
Conduit and fittings (each type)
Device plates
Insulated conductors
Outlet and junction boxes
Catalog cuts of fixtures
Pilot lights
Disconnect switches
Control panels
Sound powered terminal boxes
Sound powered telephone jack boxes
Shop Drawings:
a.
Panelboard
PART 2 - PRODUCTS
2.1 MATERIALS AND EQUIPMENT, GENERAL: Materials, equipment, and
devices shall meet the requirements of UL where UL standards are established
for those items, and the requirements of NFPA 70.
2.2
CONDUIT AND FITTINGS:
2.2.1
fittings.
Rigid Steel Conduit (Zinc-Coated):
2.2.2 Intermediate Metal Conduit (IMC):
with threaded fittings.
NFSS-T40
16450-3
ANSI C80.1 with threaded
UL 1242, Zinc-coated steel
2.2.3 Electrical Metallic Tubing (EMT):
type fittings.
2.2.4
Flexible Metal Conduit:
2.2.4.1
ANSI C80.3 with compression
UL 1.
Liquid-Tight Flexible Metal Conduit (Steel): UL 360.
2.2.5 Fittings: UL 514B. All ferrous fittings shall be cadmium-or
zinc-coated in accordance with UL 514B. Split couplings are not acceptable.
2.3 OUTLET BOXES AND COVERS, ELECTRICAL:
coated ferrous metal.
UL 514A, cadmium-or zinc-
2.4 CABINETS, JUNCTION BOXES, AND PULL BOXES (WITH VOLUME GREATER
THAN 100 CUBIC INCHES): UL 50, hot-dip zinc-coated sheet steel.
2.5 WIRES AND CABLES: Wires and cables shall meet the applicable
requirements of NFPA 70 and UL for the type of insulation, jacket, and
conductor specified or indicated. Wires and cables manufactured more
than 12 months prior to date of delivery to the site shall not be used.
2.5.1 Conductors: Conductors No. 10 AWG and smaller shall be solid,
and those No. 8 AWG and larger shall be stranded. Unless indicated
otherwise, conductor sizes shown are based on copper.
2.5.1.1 Minimum Conductor Sizes: Minimum size for branch circuits
shall be No. 12 AWG, for Class 1 remote-control and signal circuits, No.
12 AWG.
2.5.1.2 Color Coding: Provide for all service, feeder, branch,
control, and signaling circuit conductors. Color shall be green for
grounding conductors, and white for neutrals, except where neutrals of
more than one system are installed in same raceway or box, the other
neutral shall be white with a colored (not green) stripe. The color of
the phase conductors shall be as follows:
a.
120/208 volt, 3-phase; Phase A - Black
Phase B - Red
Phase C - Blue
NFSS-T40
16450-4
2.5.2 Insulation: Unless specified or indicated otherwise, or
required to be otherwise by NFPA 70, all power and lighting wires shall
be 600-volt, Type THW, THWN, XHHW, or RHW, except that grounding wire
may be Type TW; remote-control and signal circuits shall be Type IEW or
TF.
2.5.3 Bonding Conductors: ASTM B 1, solid bare copper wire for sizes
No. 8 AWG and smaller: ASTM B 8, Class B, stranded bare copper wire for
sizes No. 6 AWG and larger.
2.5.4 Service-entrance (SE) and Underground Service-Entrance (USE)
Cables: UL 854.
2.6 SPLICES AND TERMINATION COMPONENTS: UL 486A as applicable for
wire connectors, and UL 510 for insulating tapes. Connectors for wires
No. 10 AWG and smaller shall be insulated pressure-type in accordance
with UL 486A or UL 486C (twist-on splicing connector). Provide
solderless terminal lugs on stranded conductors.
2.7 DEVICE PLATES: Provide UL listed, one-piece device plates for
outlets and fittings to suit the devices installed. Plates in Damage
Control Trainer and on fittings shall be of cast metal having round or
beveled edges. Plates shall be satin finish stainless steel minimum 0.03
inch thick. Screws shall be machine type with countersunk heads in a
color to match the finish of the plate. The use of sectional type device
plates will not be permitted. Plates shall be gasketed.
2.8
SWITCHES:
2.8.1 Toggle Switches: Fed. Spec. W-S-896, totally enclosed with
bodies of thermosetting plastic and a mounting strap. Handles shall be
brown. Wiring terminals shall be of the screw type, side wired. Switches
shall be rated quiet-type ac only, 120/277 volts, with the current rating
and number of poles indicated.
2.8.2 Pilot Lights: Provide yoke-mounted candelabra-base sockets
rated 125 volts and fitted with glass or plastic jewels. Provide a clear
6-watt lamp in each pilot switch. Jewels for use with switches controlling
motors shall be green and Jewels for other purposes shall be red.
2.8.3 Disconnect Switches: NEMA KS1. Switches serving as motordisconnect means shall be horsepower rated. Provide heavy duty, double
throw switches. Fused switches shall utilize Class R fuseholders and fuses,
unless indicated otherwise.
2.9 WEATHERPROOF RECEPTACLES: NEMA WD1, heavy-duty, grounding type.
Ratings: Heavy duty, NEMA 5-15R 120 volt 15 amp grounding receptacle.
Bodies shall be of brown thermosetting plastic supported on a metal
NFSS-T40
16450-5
mounting strap. Wiring terminals shall be of the screw type, side wired.
Connect grounding pole to the mounting strap. Provide in a cast metal
box with a gasketed, weatherproof, cast-metal cover plate and a gasketed
cap over each receptacle opening. The cap shall be provided with a
spring-hinged flap. Receptacle shall be UL approved for use in "wet
locations".
2.10 PANELBOARD: UL 67, UL 50 AND UL 869: Design shall be such that
any individual breaker can be removed without disturbing adjacent units
or without loosening or removing supplemental insulation supplied as a
means of obtaining clearances as required by installation of a breaker
sized as indicated. All panelboard locks shall be keyed alike.
Directories shall be typed to indicate load served by each circuit and
mounted in a holder behind transparent protective covering.
2.10.1 Panelboard Buses: Support bus bars on bases independent of
the circuit breakers. Main buses and back pans shall be designed so that
breakers may be changed without machining, drilling, or tapping. Provide
an isolated neutral bus in each panel for connection of circuit neutral
conductors. Provide a separate ground bus marked with a green stripe
along its front and bonded to the steel cabinet for connecting grounding
conductors.
2.10.2 Circuit Breakers: Fed. Spec. W-C-375 thermal magnetic type with
interrupting capacity of 10,000 amperes symmetrical minimum. Breaker
terminals shall be UL listed as suitable for the type of conductor provided.
Plug-in circuit breakers are not acceptable.
2.10.2.1 Multipole Breakers: Provide common-trip type with a single
operating handle. Breaker design shall be such that an overload in one
pole automatically causes all poles to open. Maintain phase sequence
throughout each panel so that any three adjacent breaker poles are
connected to Phases A, B, and C, respectively.
2.10.2.2 Circuit Breaker with Ground-Fault Circuit Interrupter: UL
1053 and NFPA 70. Provide with "push-to-test button, visible indication
of tripped condition, and ability to detect a current imbalance of
approximately 5 milliamperes.
2.10.3 Dummy Panels: As specified for panelboard, closed back, interior
rustproofed, provide empty conduit risers as indicated.
NFSS-T40
16450-6
2.11 SOUND POWERED TELEPHONE SYSTEM: Provide a system of conduits
with pull wires, terminal boxes, outlet and junction boxes, and other
accessories for complete system ready for installation of wire and
equipment.
2.11.1 Jackboxes, Junction Boxes and Cover Plates: Brass, shipboard,
as specified in Section 13250, "Damage Control Simulator Specialties".
2.12 GROUNDING AND BONDING EQUIPMENT: UL 467. Ground rods shall be
the sectional type, copper-encased steel, with minimum diameter of 3/4
inch and total length of 10 feet.
PART 3 - EXECUTION
3.1 INSTALLATION:
3.1.1 General Requirements: Electrical installations shall conform
to the requirements of NFPA 70, Section 16011, "General Requirements,
Electrical", and to the requirements specified herein.
3.1.2 Wiring Methods: Wiring method shall be insulated conductors
installed in conduit, except where specifically indicated or specified
otherwise, or required by NFPA 70 to be installed otherwise. An insulated
equipment grounding conductor shall be provided in all feeder and branch
circuits, including lighting circuits according to NEC Table 250-95.
3.1.2.1
Electrical Metallic Tubing:
Do Not:
1.
2.
3.
4.
5.
6.
7.
Use in Feeder Circuits
Install underground
Encase in concrete
Use in areas where subject to severe physical damage
Use in hazardous areas
Use in outdoor work
Use in sizes larger than 2 inches.
NFSS-T40
16450-7
3.1.2.2 Service Entrance Conduit, Overhead: Rigid steel or IMC from
the service equipment to the service entrance fitting or weatherhead outside
the building.
3.1.2.3 Service Entrance Conduit, Underground: Rigid steel or steel
IMC. The underground portion shall be encased in a minimum of 3 inches
of concrete, and shall be installed at least 18 inches below slab, or
grade.
3.1.2.4 Underground Conduit (Other Than Service Entrance): Plasticcoated rigid steel; plastic-coated steel IMC. Where nonmetallic conduit is
used, it shall be converted to plastic-coated rigid (or IMC) steel conduit
before rising through floor slab; plastic coating shall extend at least 6
inches above floor.
3.1.2.5
Conduit in Floor Slabs:
Rigid steel; steel IMC; Type EPC-40.
3.1.2.6 Conduit for Circuits Rated Above 600 Volts:
conduit or IMC only.
Use rigid metal
3.1.3 Conduit Installation: Install conduit parallel with or at right
angles to ceilings, walls, and structural members. Where conduits rise
through floor slabs, the curved portion of bends shall not be visible above
the finish slab.
3.1.3.1 Conduit Support: Support conduit by pipe straps, wall
brackets, hangers, or ceiling trapeze. Fasten by toggle bolts on hollow
masonry units; by concrete inserts or expansion bolts on concrete; by
machine screws, welded threaded studs, or spring-tension clamps on steel
work. Threaded C-clamps may be used on rigid steel conduit only. Do not
weld conduits or pipe straps to steel structures. The load applied to
fasteners shall not exceed one-fourth of the proof test load. Fill holes
that are not used. In partitions of light steel construction, use
sheet-metal screws.
3.1.3.2 Changes in Direction: Use symmetrical bends or cast-metal
fittings. Make field-made bends and offsets with a hickey or conduitbending machine. Do not install crushed or deformed conduits. Avoid
trapped conduits. Prevent plaster, dirt, or trash from lodging in conduits,
boxes, fittings, and equipment during construction. Free clogged conduits
of all obstructions.
3.1.3.3 Fastening: Fasten conduits to sheet metal boxes and cabinets
with two locknuts where required by MFPA 70, where insulated bushings
are used, and where bushings cannot be brought into firm contact with
the box; otherwise, use at least a single locknut and bushing. Locknuts
shall be the type with sharp edges for digging into the wall of metal
enclosures. Install bushings on the ends of conduits and provide
insulating type where required by NFPA 70.
NFSS-T40
16450-8
3.1.3.5 Flexible Connections: Maximum of 6 feet. Provide for
equipment subject to vibration, noise transmission, or movement; and for all
motors. Liquid-tight flexible conduit shall be used in wet locations. A
separate ground conductor shall be provided across flexible connections.
3.1.4 Boxes, Outlets, and Supports: Provide boxes in the wiring
or raceway systems wherever required for pulling of wires, making
connections, and mounting of devices or fixtures. Boxes for metallic
raceways shall be of the cast-metal hub type when located in normally wet
locations, when surface mounted on outside of exterior surfaces, when
installed exposed up to 7 feet above interior floors and walkways. Boxes in
other locations shall be sheet steel, except that aluminum boxes may be used
with aluminum conduit. Each box shall have the volume required by NFPA 70
for the number of conductors enclosed in the box. Boxes for mounting
lighting fixtures shall be not less than 4 inches square (or octagonal),
except that smaller boxes may be installed as required by fixture
configurations, as approved. Boxes for use in masonry walls shall be
square-cornered tile-type, or standard boxes having square-cornered
tile-type covers. Provide gaskets for cast-metal boxes. Fasten boxes and
supports with wood screws on wood, with bolts and expansion shields on
concrete, with toggle bolts on hollow masonry units, and with machine screws
or welded studs on steel work. Threaded studs driven in by powder charge
and provided with lockwashers and nuts may be used. In open overhead
spaces, cast boxes threaded to raceways need not be separately supported
except where used for fixture support; support sheet metal boxes directly
from the building structure or by bar hangers. Where bar hangers are used,
attach the bar to raceways on opposite sides of the box and support the
raceway with an approved type fastener not more than 24 inches from the box.
3.1.4.1 Boxes For Raceway Systems: Not less than 1-1/2 inches deep,
except where shallower boxes required by structural conditions are approved.
Boxes for other than lighting-fixture outlets shall be not less than 4
inches square, except that 4 inch by 2 inch boxes may be used where only one
raceway enters the outlet.
3.1.4.2 Pull Boxes: Construct of not less than the minimum size
required by NFPA 70 of code-gage aluminum or galvanized sheet steel, except
where cast-metal boxes are specified. Furnish boxes with screw-fastened
covers. Where several feeders pass through a common pull box, tag the
feeders to indicate clearly the electrical characteristics, circuit number,
and panel designation.
3.1.5 Mounting Heights: Mount panelboards, circuit breakers, and
disconnecting switches so the height of the operating handle at its highest
position will not exceed 78 inches from the floor.
Mount lighting switches
48 inches above finished floor, receptacles and other devices as indicated.
Measure mounting heights of wiring devices and outlets to the center of
device or outlet.
NFSS-T40
16450-9
3.1.6 Conductor Identification: Provide conductor identification
within each enclosure where a tap, splice, or termination is made. For
conductors No. 6 and smaller, color coding shall be by factory-applied
color-impregnated insulation. For conductors No. 4 and larger, color coding
shall be by plastic-coated self-sticking markers, colored nylon cable ties
and plates, or heat-shrink type sleeves. Identify control circuit
terminations.
3.1.7 Splices: Make splices in accessible locations. Make splices in
conductors No. 10 AWG and smaller with an insulated pressure type connector.
Make splices in conductors No. 8 AWG and larger with a solderless connector
and cover with an insulation material equivalent to the conductor
insulation.
3.1.8 Covers and Device Plates: Install with all four edges in
continuous contact with finished wall surfaces without the use of mats or
similar devices. Plates shall be installed with an alignment tolerance of
1/16 inch. The use of sectional type device plates will not be permitted.
Plates shall be gasketed.
3.1.9 Grounding and Bonding: NFPA 70. Ground non-current-carrying
metallic parts of electrical equipment, metallic raceway systems, grounding
conductor in nonmetallic raceways, and neutral conductor of wiring systems
with connection to driven ground rods on the exterior of the building.
Where ground fault protection is employed, take care that the connection of
ground and neutral does not interfere with the correct operation of the
fault protection.
3.1.9.1 Grounding Conductor: Provide an insulated, green-colored
equipment grounding conductor in all feeder and branch circuits in
accordance to NEC 70 Tables 250-94 and 250-95. This conductor shall be
separate from the electrical system neutral conductor.
3.2 FIELD TESTS: Submit written copies of test results. The
contracting Officer shall be given 5 working days notice prior to
testing.
3.2.1 Devices Subject to Manual Operation: Each device shall be
operated at least five times, demonstrating satisfactory operation each
time.
3.2.2 Test on 600-Volt Wiring: Verify that no short circuits or
accidental grounds exist. Perform insulation resistance tests on wiring No.
6 AWG and larger using an instrument which applies a voltage of
approximately 500 volts to provide a direct reading of resistance; minimum
resistance shall be 250,000 ohms.
NFSS-T40
16450-10
3.2.3 Grounding System Test: Test to assure continuity and that the
resistance to ground is not excessive. Make resistance measurements in
normally dry weather, not less than 48 hours after rainfall.
*** END OF SECTION ***
NFSS-T40
16450-11
SECTION 16550
LIGHTING, CONTROL TRAINER
PART 1 - GENERAL
1.1 APPLICABLE PUBLICATIONS: The documents listed below form a part
of this specification to the extent referenced. The documents are referred
to in the text by the basic designation only.
1.1.1
American National Standards Institute (ANSI):
C82.1-1985
Specifications for Fluorescent Lamp Ballasts
C82.2-1984
Methods of Measurement of Fluorescent Lamp
Ballast
1.1.2
National Fire Protection Association (NFPA):
70-1990
National Electrical Code (NEC)
101-1988
Life Safety Code
1.1.3
Underwriters' Laboratories, Inc., (UL):
1570-1988
Fluorescent Lighting Fixtures
35-1984
(R 1988)
Fluorescent Lamp Ballasts
1.2 GENERAL REQUIREMENTS: Section 16011, "Electrical General
Requirements", applies with the following additions and modifications. The
work includes the provision of shipboard type lighting fixtures, battle
lanterns, direct current power supply for Casualty Lighting and Emergency
Lighting Systems, bulkhead and riser biscuits, and systems for interior use,
including lighting fixtures. Materials not normally furnished by
manufacturers of these devices are specified in Section 16450, "Electrical
and Signal Wiring Systems".
1.3 SUBMITTALS: Data, shop drawings, and reports shall employ the
terminology, classifications, and methods prescribed by the IES Lighting
Handbook, as applicable, for the lighting system specified.
NFSS-T40
16550-1
1.3.1
Manufacturer's Data:
a.
b.
c.
d.
1.3.2
Lighting fixtures, including lamps and ballasts
Bulkhead biscuit terminals
Riser biscuit terminals
Direct current power supply
Shop Drawings:
a.
b.
Lighting fixture assemblies
Photometrics
PART 2 - PRODUCTS
2.1
FLUORESCENT LIGHTING FIXTURES:
UL 1570.
2.1.1 Fluorescent Lamps: Lamps shall be the energy efficient type
unless specifically indicated that standard lamps are required. The 48-inch
lamps shall be rated 35 watts (maximum) and 2900 initial lumens (minimum).
2.1.2 Fluorescent Ballasts: UL 935, ANSI C82.1, and shall be labeled
Certified Ballast Manufacturers (CBM) certified by Electrical Testing
Laboratories (ETL). Ballasts shall be high power factor type and shall be
designed to operate on the voltage system to which they are connected.
Ballasts shall be Class P and shall have sound rating "A" unless otherwise
noted. Fixtures and ballasts shall be designed and constructed to limit the
ballast case temperature to 90 degrees Celcius (C) when installed in an
ambient temperature of 40 degrees C. All ballasts shall be the energy
saving type.
2.1.2.1 Energy Saving Ballasts: Provide energy saving fluorescent
ballasts of the CBM certified full light output type. The ballasts shall
have an input wattage, when tested in accordance with ANSI C82.2, of:79 or
less when operating two 35 watt F40T12 lamps.
2.2
EMERGENCY LIGHTING EQUIPMENT:
NFPA 101.
2.2.1 Central Emergency System: Provide DC power supply as specified
in Section 13250, "Damage Control Simulator Specialties". Provide a Silicon
Current Rectifier (SCR) regulator to provide plus or minus 0.1 percent
regulation with a maximum efficiency of 75 percent. Provide series
inductance and a capacitor filter circuit for low noise operation over all
line and load conditions. Provide overload protection. System shall
contain solid state devices.
NFSS-T40
16550-2
2.2.1.1 Operation: When the single-pole double-throw switch is in the
normal position the fluorescent lights shall be fed. When the switch is in
the emergency position, the power supply shall be energized and shall feed
all the emergency DC loads.
2.3
EMERGENCY EQUIPMENT:
2.3.1 Casualty Power Terminals (Biscuits):
13250, "Damage Control Simulator Specialties".
As specified in Section
2.3.2 Riser Biscuit (SYM 1032): Shall be connected via a junction
box to the six volt source. "All terminal to be wired positive, "C"
terminal to be wired negative, and "B" terminal not to be wired.
2.3.2.1 RISER Biscuits in the Machinery Compartment and the
Engineering Stores Compartment: Connect to the junction boxes directly
above. From those junction boxes, wiring shall extend to the battle
lanterns.
2.3.2.2 BULKHEAD Biscuit (SYM 1025): Two terminals mounted on
opposite sides of a bulkhead, with the corresponding terminals
interconnected. There is no power source at a bulkhead biscuit.
2.3.3 BATTLE LANTERN: As specified in Section 13250, "Damage Control
Simulator Specialties". Lantern shall be modified to operate directly from
6-volt casualty power source as indicated.
2.3.4 SHIPBOARD LIGHTING FIXTURES, SHIPBOARD JUNCTION BOXES:
Fluorescent, watertight fixtures with lenses, and mounting bracket as
specified in Section 13250, "Damage Control Simulator Specialties".
PART 3 - EXECUTION
3.1 INSTALLATION; Set lighting fixtures plumb, square, and level
with ceiling and malls, in alignment with adjacent lighting fixtures, and
secure in accordance with manufacturers' directions and approved shop
drawings. The installation shall meet with the requirements of NFPA 70.
Mounting heights specified or indicated shall be to bottom of fixture.
Obtain approval of the exact mounting of lighting fixtures on the job before
installation is commenced and, where applicable, after coordinating with the
type, style, and pattern of the ceiling being installed.
NFSS-T40
16550-3
3.2 GROUNDING: Ground noncurrent-carrying parts of equipment as
specified in Section 16450, "Electric and Signal Wiring Systems". Where the
copper grounding conductor is connected to a metal other than copper,
provide specially treated or lined connectors suitable for this purpose.
3.3
FIELD TESTS:
Perform the following field tests.
3.3.1 Operating Test: After the installation has been completed,
conduct an operating test to show that the equipment operates in accordance
with the requirements of this section.
3.3.2 Insulation Resistance Test: Perform as specified in Section
16450, "Electrical and Signal Wiring Systems", both before connection of
fixtures and equipment and after fixtures and equipment are connected and
ready for use.
3.3.3 Ground Resistance Tests: Perform as specified in Section 16450,
"Electrical and Signal Wiring Systems".
*** END OF SECTION ***
NFSS-T40
16550-4
Download