TEMF PRESCRIPTIVE TECHNOLOGY SOLUTION SETS List of Tables

advertisement
TEMF PRESCRIPTIVE TECHNOLOGY SOLUTION SETS
Alexander Zhivov, Ph.D., Dale Herron and Richard Liesen, Ph.D.
USACE Engineer Research and Development Center
Michael Deru, Ph.D.
National Renewable Energy Lab
List of Tables
1
TEMF Climate Zone 1A Prescriptive Solution Table ........................................................................................ 2
2
TEMF Climate Zone 2A and 2B Prescriptive Solution Table ........................................................................... 3
3
TEMF Climate Zone 3A and 3B Prescriptive Solution Table ........................................................................... 4
4
TEMF Climate Zone 3C Prescriptive Solution Table ........................................................................................ 5
5
TEMF Climate Zone 4A, 4B, and 4C Prescriptive Solution Table ................................................................... 6
6
TEMF Climate Zone 5A and 5B Prescriptive Solution Table ........................................................................... 7
7
TEMF Climate Zone 6A and 6B Prescriptive Solution Table ........................................................................... 8
8
TEMF Climate Zone 7A Prescriptive Solution Table ........................................................................................ 9
9
TEMF Climate Zone 8A Prescriptive Solution Table ...................................................................................... 10
10
Characteristics of reflective roofing materials............................................................................................... 12
11
Light power density Levels ................................................................................................................................ 13
12
Fan efficiencies .................................................................................................................................................. 13
The use of a climate specific Prescriptive Technology Solution Set listed in Tables 1 to 10 for TEMF
facilities will result in an annual energy consumption less than or equal to the target energy budget
figure shown in Attachment 2 for this facility type and climate zone, will meet life cycle cost
effectiveness requirements, and will not require any calculations to demonstrate compliance with the
EPACT 2005 30% better requirement utilizing the methodology described in ASHRAE 90.1 Appendix
G. The actual energy consumption budget for each prescriptive solution/climate zone is shown in
Attachment 2. Climate zone identification information for Army locations is also shown in Attachment 2.
Energy and Water Conservation Design Requirements for SRM Projects
Table 1. TEMF Climate Zone 1A Prescriptive Solution Table
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-15ci
U-0.0750
Metal Building
R-13 + R-13
Attic and Other
R-19
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-11.4
U-0.1667
R-13
R-13
Metal Building
Floors Over
Unconditioned
Space
Mass
R-13
R-4.2 c.i.
R-13
NR (4)
Swinging
U-0.70
Non-Swinging
U-1.45
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
Ventilation
Ducts
Service Water
Heating
NR (4)
U-0.70
Uninsulated
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-1.22
0.25
< 10%
U-0.56
0.25
2%
U-1.36
0.36
See Lighting Power Table
2%
U-1.36
0.19
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
Make Up Air Unit Fans (8)
HVAC
R-13
Wood Framed and Other
Slab-on-Grade Unheated
Doors
R-6.3ci.
0.1067
Steel Joist
Gas Furnace
Hydronic radiant floor heat
ERV
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
2
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
80% Et
None
None
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
None
None
Variable Speed pumps, fans, etc.
NR
Motorized Control
NR
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
Nokne
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
2
Energy and Water Conservation Design Requirements for SRM Projects
Table 2. TEMF Climate Zone 2A and 2B Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-15ci
U-0.0750
Metal Building
R-13 + R-13
Attic and Other
R-19
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-11.4
U-0.1667
R-13
R-13
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13
R-4.2 c.i.
R-6.3ci.
0.1067
Steel Joist
R-13
Wood Framed and Other
R-13
Unheated
NR (4)
Heated
R-7.5 for 12 in
F-0.900
R-10 for 24 in
Swinging
U-0.70
U-0.70
Uninsulated
Non-Swinging
U-1.45
NR (4)
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-1.22
0.25
< 10%
U-0.45
0.25
2%
U-1.36
0.36
See Lighting Power Table
2%
U-1.36
0.19
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
Make Up Air Unit Fans
Gas Furnace
Hydronic radiant floor heat
ERV
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
2
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
80% Et
None
None
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
None
Variable Speed pumps, fans, etc.
NR
Motorized Control
NR
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
3
Energy and Water Conservation Design Requirements for SRM Projects
Table 3. TEMF Climate Zone 3A and 3B Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-15ci
U-0.0660
Metal Building
R-19 + R-19
Attic and Other
R-19
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-11.4
U-0.1667
R-13
R-13
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13
R-4.2 c.i.
R-6.3ci.
0.1067
Steel Joist
R-13
Wood Framed and Other
R-13
Unheated
NR (4)
Heated
R-7.5 for 12 in
F-0.860
R-15.0 for 24 in.
Swinging
U-0.70
U-0.70
Uninsulated
Non-Swinging
U-1.45
NR (4)
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.57
0.37
< 10%
U-0.45
0.37
2%
U-0.69
0.37
See Lighting Power Table
2%
U-0.69
0.19
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
NR
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
4
Energy and Water Conservation Design Requirements for SRM Projects
Table 4. TEMF Climate Zone 3C Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-15ci
U-0.0660
Metal Building
R-19 + R-19
Attic and Other
R-19
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-11.4
U-0.1667
R-13
R-13
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13
R-4.2 c.i.
R-6.3ci.
0.1067
Steel Joist
R-13
Wood Framed and Other
R-13
Unheated
NR (4)
Heated
R-7.5 for 12 in
F-0.860
R-15.0 for 24 in.
Swinging
U-0.70
U-0.70
Uninsulated
Non-Swinging
U-1.45
NR (4)
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-1.22
0.39
< 10%
U-0.45
0.39
2%
U-1.36
0.61
See Lighting Power Table
2%
U-1.36
0.19
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
NR
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
5
Energy and Water Conservation Design Requirements for SRM Projects
Table 5. TEMF Climate Zone 4A, 4B, and 4C Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-20ci
U-0.0490
Metal Building
R-19 + R-11 LS
Attic and Other
R-38
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-11.4
U-0.1667
R-13
R-13
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13
R-4.2 c.i.
R-10.4ci.
0.0739
Steel Joist
R-13
Wood Framed and Other
R-13
Unheated
NR (4)
F-0.520
Heated
R-7.5 for 12 in
F-0.843
R-15.0 for 24 in.
R-20.0 for 24 in.
Swinging
U-0.70
U-0.50
Insulated
Non-Swinging
U-1.45
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.57
0.39
< 10%
U-0.42
0.39
2%
U-0.69
0.49
See Lighting Power Table
2%
U-0.69
0.34
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
Yes
Yes
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
6
Energy and Water Conservation Design Requirements for SRM Projects
Table 6. TEMF Climate Zone 5A and 5B Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-20ci
U-0.0490
Metal Building
R-19 + R-11 LS
Attic and Other
R-38
Solar Reflectance (3)
Cool Roof for Low Slope & Light color all others
Mass
Walls
Steel Framed
R-15.0
U-0.0595
R-13 + 3.8ci
R-13 + 12.5ci
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13 + 13.0ci
R-4.2 c.i.
R-16.7ci.
0.0521
Steel Joist
R-19
Wood Framed and Other
R-19
Unheated
NR (4)
F-0.520
Heated
R-7.5 for 12 in
F-0.688
R-15.0 for 24 in.
R-20.0 for 48 in.
Swinging
U-0.70
U-0.50
Insulated
Non-Swinging
U-1.45
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.57
0.39
< 10%
U-0.42
0.39
2%
U-0.69
0.49
See Lighting Power Table
2%
U-0.69
0.39
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
Yes
Yes
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
7
Energy and Water Conservation Design Requirements for SRM Projects
Table 7. TEMF Climate Zone 6A and 6B Prescriptive Solution Table
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-20ci
U-0.0490
Metal Building
R-19 + R-11 LS
Attic and Other
R-38
Solar Reflectance (3)
NR (4)
Mass
Walls
Steel Framed
R-15.0
U-0.0595
R-13 + 3.8ci
R-13 + 12.5ci
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13 + 13.0ci
R-4.2 c.i.
R-25.1ci.
0.0377
Steel Joist
R-30
Wood Framed and Other
R-30
Unheated
NR (4)
F-0.510
Heated
R-7.5 for 12 in
F-0.688
R-20.0 for 24 in.
R-20.0 for 48 in.
Swinging
U-0.70
U-0.50
Insulated
Non-Swinging
U-1.45
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.57
0.39
< 10%
U-0.42
0.39
2%
U-0.69
0.49
See Lighting Power Table
2%
U-0.69
0.49
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
Yes
Yes
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
8
Energy and Water Conservation Design Requirements for SRM Projects
Table 8. TEMF Climate Zone 7A Prescriptive Solution Table.
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-25ci
U-0.0388
Metal Building
R-19 + R-11 LS
Attic and Other
R-49
Solar Reflectance (3)
NR (4)
Mass
Walls
Steel Framed
R-15.0
U-0.0595
R-13 + 3.8ci
R-13 + 12.5ci
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13 + 13.0ci
R-4.2 c.i.
R-25.1ci.
0.0377
Steel Joist
R-30
Wood Framed and Other
R-30
Unheated
NR (4)
F-0.510
Heated
R-7.5 for 12 in
F-0.671
R-20.0 for 24 in.
R-25.0 for 48 in.
Swinging
U-0.70
U-0.50
Insulated
Non-Swinging
U-1.45
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.57
0.49
< 10%
U-0.33
NR
2%
U-0.69
0.68
See Lighting Power Table
2%
U-0.69
0.64
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
Yes
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
9
Energy and Water Conservation Design Requirements for SRM Projects
Table 9. TEMF Climate Zone 8A Prescriptive Solution Table
Item
Component
Baseline (1)
Recommendation
Min R-Value (2)
Assembly Max (2)
Roof
Insulation Entirely Above Deck
R-15ci
R-30ci
U-0.0325
Metal Building
R-25 + R-11 LS
Attic and Other
R-49
Solar Reflectance (3)
NR (4)
Mass
Walls
Steel Framed
R-11.4 + R-3.0ci
U-0.0391
R-13 + 3.8ci
R-13 + 18.8ci
Metal Building
Floors Over
Unconditioned
Space
Slab-on-Grade
Doors
Infiltration
Vertical
Glazing
Skylights
Interior
Lighting
HVAC
Ventilation
Ducts
Service Water
Heating
Mass
R-13 + 19.5ci
R-4.2 c.i.
R-25.1ci.
0.0377
Steel Joist
R-30
Wood Framed and Other
R-30
Unheated
NR (4)
F-0.434
Heated
R-7.5 for 12 in
F-0.671
R-20.0 for 48 in.
R-25.0 for 48 in.
Swinging
U-0.70
U-0.50
Insulated
Non-Swinging
U-1.45
U-0.50
2
Insulated
Areas that are mechanically
cooled (i.e. office, restrooms,
etc.)
0.4 cfm/ft @ 75 Pa
0.25 cfm/ft @ 75 Pa (5)
Window to Wall Ratio (WWR)
Thermal transmittance
Solar heat gain coefficient
(SHGC)
Percent Roof Area
Thermal transmittance
SHGC
Lighting Power Density (LPD)
< 10%
U-0.46
NR
< 10%
U-0.33
NR
2%
U-0.58
NR
See Lighting Power Table
2%
U-0.58
NR
Daylight Controls
None
NR
Yes
Manual On/Auto Off (all periodically occupied spaces)
Occupancy Controls (7)
Plug Load Lighting
All Ballasts
Air Conditioner
2
Make Up Air Unit Fans (8)
PSZ-AC 12.0 SEER
See Fan Efficiency Tables
Gas Furnace
Hydronic radiant floor heat
ERV
80% Et
None
None
All equipment
Economizer
Outdoor Air Damper
Demand Control
Transpired Solar Collectors
Friction rate
Sealing
Location
Insulation level
Gas hot water storage
Pipe Insulation(d < 1.5in. / d ≥
1.5 in.)
Drain Water Heat Recovery
See Lighting Power Table (6)
Compact Fluorescent (CFL) with electronic ballast
Electronic
PSZ-AC 14.0 SEER
See Fan Efficiency Tables (8)
90% Et
Ground Floor
Yes (9)
Variable Speed pumps, fans, etc.
NR
Motorized Control
Yes
None
0.08 in. w.c./100 feet
Seal class B
Interior only
NR
Motorized Control
NR
None
R-6 (10)
80% Et
90% Et
1 in. / 1.5 in. (10)
None
None
10
Energy and Water Conservation Design Requirements for SRM Projects
Notes:
1. Baseline requirements are from ANSI/ASHRAE/IESNA Standard 90.1-2004.
1. U-values and R-values for assemblies and their definitions, requirements, and determinations can be found
in ANSI/ASHRAE/IESNA Standard 90.1-2007, Normative Appendix A.
2. Light colored and cool roofs: reflect and emit the sun's heat back to the sky instead of transferring it to
the building below. "Coolness" is measured by two properties, solar reflectance and thermal emittance.
Both properties are measured from 0 to 1 and the higher the value, the "cooler" the roof. A high
reflectance keeps much of the sun’s energy from being absorbed, while a high thermal emittance
radiates away any solar energy that is absorbed, allowing the roof to cool more rapidly. Cool roofs are
typically white and have a smooth surface. Commercial roof products that qualify as cool roofs fall into
three categories: single-ply, liquid-applied, and metal panels. The solar reflectance and thermal
emittance property values represent initial conditions as determined by a laboratory accredited by the
Cool Roof Rating Council.
Cool roofs are cost effective over air-conditioned spaces for buildings located in climate zones 1 - 5. In
these locations, a minimum of 75% of the entire roof surface not used for roof penetrations shall be
covered with roofing products that comply with one or more of the following:
 Have a minimum initial SRI of 78 for a low-sloped roof (a slope less than or equal to 2:12) and a
minimum initial SRI of 29 for a steep-sloped roof (a slope of more than 2:12).
 Comply with the criteria for the US EPA’s Energy Star Program Requirements for Roof Products –
Eligibility Criteria.
For industrial buildings with only heating and ventilation, cool roofs can improve the comfort conditions (and
hence productivity) in the space.
In order to be considered a cool roof, a solar reflectance of 0.67 when tested in accordance with ASTM
C1549, ASTM E903, or ASTM E1918 and, in addition, a minimum thermal emittance of 0.75 when
tested in accordance with ASTM C1371 or ASTM E408, or a minimum Solar Reflective Index of 78
when determined in accordance with the Solar Reflectance Index method in ASTM E1980 where
standard white is SRI = 100 and standard black has SRI = 0. An SRI can be determined by the
following equations:
SRI = 123.97 – 141.35(x) + 9.655(x2)
where
x
20.797    0.603  
,
9.5205    12.0
Where  is the solar absorptance (= 1 – solar reflectance) and  is the thermal emissivity, which were derived
from ASTM E1980 assuming a medium wind speed.
11
Energy and Water Conservation Design Requirements for SRM Projects
Table 10. Characteristics of reflective roofing materials.
Roofing Type
Color
New Solar
Reflectance
Aged Solar
Reflectance
New Thermal
Emittance
SRI
(ASTM
E1980
84 – 106
Roof Coatings
White
0.70 – 0.85
0.50 –0.65
0.85
Roof Coatings
Grey or Tan
0.70
0.50
0.85
84
Roof Coatings
Terra Cotta or Brown
0.40
0.30
0.85
43
Roof Coatings
Aluminized
0.50
0.40
0.50
42
Metal Paint
Red
0.25
0.25
0.83
22
Metal Paint
Terra Cotta
0.35
0.35
0.83
36
Metal Paint
Bright Red
0.35
0.35
0.83
36
Metal Paint
Beige/Off White
0.55
0.55
0.83
63
Metal Paint
Tan
0.45
0.45
0.83
49
Metal Paint
Dark Blue
0.25
0.25
0.83
22
Metal Paint
Medium to Light Blue
0.32
0.32
0.83
32
Metal Paint
Dark Brown
0.25
0.25
0.83
22
Metal Paint
Medium to Light Brown
0.32
0.32
0.83
32
Metal Paint
Dark Green
0.25
0.25
0.83
22
Metal Paint
Medium to Light Green
0.32
0.32
0.83
32
Metal Paint
White
0.65
0.65
0.83
77
Metal Paint
Bright White
0.70
0.70
0.83
84
Metal Paint
Black
0.25
0.25
0.83
22
Metal Paint
Dark Grey
0.25
0.25
0.83
22
Metal Paint
Medium to Light Grey
0.35
0.35
0.83
36
Metal Paint
Pearlescent Colors
0.35
0.35
0.75
32
Galvalume
Unpainted
0.65
0.55
0.05
45
Copper Metal
Unpainted
0.85
0.18
0.03
89
Galvanized Steel
Unpainted
0.40
0.20
0.50
26
EPDM Membrane
Black
0.05
0.10
0.85
0
TPO Membrane
White
0.80
0.60
0.85
99
TPO Membrane
Grey
0.50
0.40
0.85
57
PVC Membrane
White
0.80
0.60
0.85
99
PVC Membrane
Grey
0.50
0.40
0.85
57
Asphalt Shingle
Dark Color
0.10
0.10
0.85
4
Asphalt Shingle
Light Color
0.25
0.25
0.85
23
Modified Bitumen Cap Sheet
Dark Color
0.10
0.10
0.85
4
Modified Bitumen Cap Sheet
Light Color
0.25
0.25
0.85
23
Modified Bitumen Cap Sheet
White
0.50-0.60
0.40 – 0.45
0.85
57 - 71
3. NR means there is no requirement or recommendation for a component in this climate zone.
4. Increased Building Air tightness. Building air leakage (measured in cfm/ft2) is the average volume of
air(measured in cubic feet per minute) that passes through a unit area of the building envelope (measured in
square feet) when the building is maintained at a specified internal pressure (measured in Pascals).
ASHRAE has proposed a building air tightness requirement of 0.4 cfm/ft2 @ 75 Pa as an addendum to
Standard 90.1-2004. ASHRAE has also proposed an approach to complying with the new requirement with a
pressurization test to show that the building leakage does not exceed 0.4 cfm/ft2 at 75 Pa. This air tightness
requirement provides a number that can be used for the energy simulations and was assumed to be the
baseline leakage rate. The air tightness requirement adopted by the U.S. Army for new construction is more
stringent than the one proposed by ASHRAE and requires that the leakage rate must not exceed 0.25 cfm/ft2
at 75 Pa, and was assumed for the energy efficient building models. To convert the values used for building
leakage tests at the pressure difference of 75Pa to the values which can be used to calculate required
excessive outdoor air supply rates, the following equation can be used ΔQ = Q75 * (5/75)0.65 = 0.172 * Q75.
12
Energy and Water Conservation Design Requirements for SRM Projects
The excessive airflow rate for the building complying with the new ASHRAE 90.1 Standard air leakage
requirement is 0.069 cfm/ft2. Respective number for the building built to the Army model RFP requirement is
0.043cfm/ft2.
5. Light Power density Levels. in accordance with the values listed in Table 11.
Table 11. Light power density Levels
6. Daylighting. Daylighting should be included in the repair bays, vehicle corridor, and office.
7. Fan Efficiencies, use the values listed in Table 12.
Table 12. Fan efficiencies.
8. Energy Recovery Make Up Air Units. Energy recovery on the MAUs for the vehicle corridor and
consolidated bench shows a small energy savings and should be evaluated prior to inclusion for this climate
zone.
9. Duct and pipe insulation, values are from the ASHRAE Advanced Energy Design Guide for Highway
Lodging.
13