TRAINING BARRACKS PRESCRIPTIVE TECHNOLOGY SOLUTION SETS Alexander Zhivov, Ph.D., Dale Herron and Richard Liesen, Ph.D. USACE Engineer Research and Development Center Michael Deru, Ph.D. National Renewable Energy Lab List of Tables and Figure Tables 1 Training Barracks Climate Zone 1A Prescriptive Solution Table.................................................................... 2 2 Training Barracks Climate Zone 2A Prescriptive Solution Table.................................................................... 3 3 Training Barracks Climate Zone 2B Prescriptive Solution Table ................................................................... 4 4 Training Barracks Climate Zone 3A Prescriptive Solution Table.................................................................... 5 5 Training Barracks Climate Zone 3B and 3C Prescriptive Solution Table ...................................................... 6 6 Training Barracks Climate Zone 4A Prescriptive Solution Table.................................................................... 7 7 Training Barracks Climate Zone 4B and 4C Prescriptive Solution Table ...................................................... 8 8 Training Barracks Climate Zone 5A and 5B Prescriptive Solution Table ...................................................... 9 9 Training Barracks Climate Zone 6A and 6B Prescriptive Solution Table .................................................... 10 10 Training Barracks Climate Zone 7A Prescriptive Solution Table.................................................................. 11 11 Training Barracks Climate Zone 8A Prescriptive Solution Table.................................................................. 12 12 Characteristics of reflective roofing materials............................................................................................... 14 Figure 1 DOAS Schematic ................................................................................................................................................ 15 The use of a climate specific Prescriptive Technology Solution Set shown in Tables 1 to 11 for training barracks will result in an annual energy consumption less than or equal to the target energy budget figure shown in Attachment 2 for this facility type and climate zone, will meet life cycle cost effectiveness requirements, and will not require any calculations to demonstrate compliance with the EPACT 2005 30% better requirement utilizing the methodology described in ASHRAE 90.1 Appendix G. The actual energy consumption budget for each prescriptive solution/climate zone is shown in Attachment 2. Climate zone identification information for Army locations is also shown in Attachment 2. Energy and Water Conservation Design Requirements for SRM Projects Table 1. Training Barracks Climate Zone 1A Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-25ci U-0.0388 R-30 R-38 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-3.8ci R-4.2 c.i. R-6.3ci. 0.1067 Steel Joist R-13 Slab-on-Grade Unheated NR (4) Swinging U-0.70 U-0.70 U-1.45 U-1.45 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) NR (4) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Uninsulated 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-1.22 0.25 10% - 20% U-0.45 0.25 1.0 W/ft2 Whole Building 2 ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with air-to-air heat recovery exchanger with in series dual DX coils (3.52 COP) and HHW coil on central boiler SAT control 45ºF-62ºF with OAT 75ºF-54ºF None None Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Uninsulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Service Water Heating R-13 Wood Framed and Other 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) 80% Et Drain Water Heat Recovery (9) None 90% Et 1 in. / 1.5 in. (8) None 2 Energy and Water Conservation Design Requirements for SRM Projects Table 2. Training Barracks Climate Zone 2A Prescriptive Solution Table Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-25ci U-0.0388 R-30 R-38 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-3.8ci R-4.2 c.i. R-10.4ci. 0.0739 Steel Joist R-13 Slab-on-Grade Unheated NR (4) Swinging U-0.70 U-0.70 U-1.45 U-1.45 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) NR (4) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Uninsulated 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-1.22 0.25 10% - 20% U-0.45 0.25 1.0 W/ft2 Whole Building 2 ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with air-to-air heat recovery exchanger with in series dual DX coils (3.52 COP) and HHW coil on central boiler SAT control 45ºF-62ºF with OAT 75ºF-54ºF None None Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Uninsulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Service Water Heating R-13 Wood Framed and Other 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) 80% Et Drain Water Heat Recovery (9) None 90% Et 1 in. / 1.5 in. (8) None 3 Energy and Water Conservation Design Requirements for SRM Projects Table 3. Training Barracks Climate Zone 2B Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-25ci U-0.0388 R-30 R-38 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-3.8ci R-4.2 c.i. R-10.4ci. 0.0739 Steel Joist R-13 Slab-on-Grade Unheated NR (4) Swinging U-0.70 U-0.70 U-1.45 U-1.45 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) NR (4) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Uninsulated 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-1.22 0.25 10% - 20% U-0.45 0.25 1.0 W/ft2 Whole Building 2 ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Uninsulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Service Water Heating R-13 Wood Framed and Other 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) 80% Et Drain Water Heat Recovery (9) None 90% Et 1 in. / 1.5 in. (8) None 4 Energy and Water Conservation Design Requirements for SRM Projects Table 4. Training Barracks Climate Zone 3A Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-25ci U-0.0388 R-30 R-38 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-3.8ci R-4.2 c.i. R-10.4ci. 0.0739 Steel Joist R-13 Slab-on-Grade Unheated NR (4) Swinging U-0.70 U-0.70 U-1.45 U-1.45 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) NR (4) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery Uninsulated 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.37 10% - 20% U-0.45 0.31 1.0 W/ft2 Whole Building 2 ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with air-to-air heat recovery exchanger with in series dual DX coils (3.52 COP) and HHW coil on central boiler SAT control 45ºF-62ºF with OAT 75ºF-54ºF None None Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Uninsulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Service Water Heating R-13 Wood Framed and Other 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 5 Energy and Water Conservation Design Requirements for SRM Projects Table 5. Training Barracks Climate Zone 3B and 3C Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-25ci U-0.0388 R-30 R-38 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-3.8ci R-4.2 c.i. R-10.4ci. 0.0739 Steel Joist R-13 Slab-on-Grade Unheated NR (4) Swinging U-0.70 U-0.70 U-1.45 U-1.45 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) NR (4) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery Uninsulated 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.37 10% - 20% U-0.45 0.31 1.0 W/ft2 Whole Building 2 ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Uninsulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Service Water Heating R-13 Wood Framed and Other 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 6 Energy and Water Conservation Design Requirements for SRM Projects Table 6. Training Barracks Climate Zone 4A Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-30ci U-0.0325 R-30 R-49 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-13 U-0.0676 R-13 R-13 + R-7.5ci Wood Framed and Other R-13 + R-3.8ci Mass Floors Over Unconditioned Steel Joist Space Wood Framed and Other R-4.2 c.i. Slab-on-Grade Unheated NR (4) F-0.520 R-15.0 for 24 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) R-16.7ci. 0.0521 R-19 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.39 10% - 20% U-0.45 0.31 1.0 W/ft2 Whole Building 2 Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with air-to-air heat recovery exchanger with in series dual DX coils (3.52 COP) and HHW coil on central boiler SAT control 45ºF-62ºF with OAT 75ºF-54ºF None None Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Insulated 0.4 cfm/ft2 @ 75 Pa Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner R-19 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 7 Energy and Water Conservation Design Requirements for SRM Projects Table 7. Training Barracks Climate Zone 4B and 4C Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-30ci U-0.0325 R-30 R-49 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-19.5 U-0.0512 R-13 R-13 + R-12.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-7.5ci R-4.2 c.i. R-16.7ci. 0.0521 Steel Joist R-19 Wood Framed and Other R-19 Slab-on-Grade Unheated NR (4) F-0.520 R-15.0 for 24 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.39 10% - 20% U-0.42 0.39 1.0 W/ft2 Whole Building 2 Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Insulated 0.4 cfm/ft2 @ 75 Pa 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 8 Energy and Water Conservation Design Requirements for SRM Projects Table 8. Training Barracks Climate Zone 5A and 5B Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-30ci U-0.0325 R-30 R-49 Cool Roof for Low Slope & Light color all others Solar Reflectance (3) Mass Walls Steel Framed R-19.5 U-0.0512 R-13 R-13 + R-12.5ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-7.5ci R-4.2 c.i. R-16.7ci. 0.0521 Steel Joist R-19 Wood Framed and Other R-19 Slab-on-Grade Unheated NR (4) F-0.520 R-15.0 for 24 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.39 10% - 20% U-0.42 0.39 1.0 W/ft2 Whole Building 2 Electronic 4-Pipe Fan Coil with central chiller and boiler plus PTAC 12.0 SEER (3.05 COP) DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Insulated 0.4 cfm/ft2 @ 75 Pa 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 9 Energy and Water Conservation Design Requirements for SRM Projects Table 9. Training Barracks Climate Zone 6A and 6B Prescriptive Solution Table. Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-40ci U-0.0245 R-30 R-60 Solar Reflectance (3) NR (4) Mass Walls Steel Framed R-19 + R-3ci U-0.0373 R-13 R-13 + R-18.8ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-15.6ci R-4.2 c.i. R-25.1ci. 0.0377 Steel Joist R-30 Wood Framed and Other R-30 Slab-on-Grade Unheated NR (4) F-0.510 R-20.0 for 24 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.39 10% - 20% U-0.42 0.39 1.0 W/ft2 Whole Building 2 PTAC 12.0 SEER (3.05 COP) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery Electronic 4-Pipe Fan Coil with central chiller and boiler plus DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Insulated 0.4 cfm/ft2 @ 75 Pa 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 10 Energy and Water Conservation Design Requirements for SRM Projects Table 10. Training Barracks Climate Zone 7A Prescriptive Solution Table Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-40ci U-0.0245 R-30 R-60 Solar Reflectance (3) NR (4) Mass Walls Steel Framed R-19 + R-3ci U-0.0373 R-13 R-13 + R-18.8ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-15.6ci R-4.2 c.i. R-25.1ci. 0.0377 Steel Joist R-30 Wood Framed and Other R-30 Slab-on-Grade Unheated NR (4) F-0.510 R-20.0 for 24 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.57 0.49 10% - 20% U-0.33 NR 1.0 W/ft2 Whole Building 2 PTAC 12.0 SEER (3.05 COP) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery Electronic 4-Pipe Fan Coil with central chiller and boiler plus DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Insulated 0.4 cfm/ft2 @ 75 Pa 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 11 Energy and Water Conservation Design Requirements for SRM Projects Table 11. Training Barracks Climate Zone 8A Prescriptive Solution Table Item Component Baseline (1) Recommendation Min R-Value (2) Assembly Max (2) Roof Insulation Entirely Above Deck Attic and Other R-40ci U-0.0245 R-30 R-60 Solar Reflectance (3) NR (4) Mass Walls Steel Framed R-19 + R-3ci U-0.0373 R-13 R-13 + R-18.8ci Wood Framed and Other Floors Over Unconditioned Space Mass R-13 + R-15.6ci R-4.2 c.i. R-25.1ci. 0.0377 Steel Joist R-30 Wood Framed and Other R-30 Slab-on-Grade Unheated NR (4) F-0.434 R-20.0 for 48 in. Swinging U-0.70 U-0.50 Insulated U-1.45 U-0.50 Doors Non-Swinging Infiltration Vertical Glazing Interior Lighting Window to Wall Ratio (WWR) Thermal transmittance Solar heat gain coefficient (SHGC) Lighting Power Density (LPD) 0.25 cfm/ft @ 75 Pa (5) 10% - 20% U-0.46 NR 10% - 20% U-0.33 NR 1.0 W/ft2 Whole Building 2 PTAC 12.0 SEER (3.05 COP) Economizer Ventilation Outdoor Air Damper Demand Control Laundry Room Ducts Friction rate Sealing Location Insulation level Service Water Heating Gas hot water storage Pipe Insulation(d < 1.5in. / d ≥ 1.5 in.) Drain Water Heat Recovery Electronic 4-Pipe Fan Coil with central chiller and boiler plus DOAS (6) with a 14.0 SEER DX coil (3.52 COP) and HHW coil on central boiler SAT control 55ºF-62ºF with OAT 75ºF-54ºF None 70% - 75% sensible and 70% - 75% latent effectiveness Variable Speed pumps, fans, etc. None Motorized Control NR HVAC Gas Furnace ERV All equipment ≤ 0.9 W/ft2 Rooms 0.9 W/ft2 Corridors 0.5 W/ft2 Stairs 0.6 W/ft2 Rooms Manual On/Auto Off Compact Fluorescent (CFL) with electronic ballast Occupancy Controls Plug Load Lighting All Ballasts Air Conditioner Insulated 0.4 cfm/ft2 @ 75 Pa 80% Et None None Motorized Control NR Decoupled (7) 0.08 in. w.c./100 feet Seal class B Interior only R-6 (8) 80% Et 90% Et 1 in. / 1.5 in. (8) None Showers only; 30% efficiency (9) 12 Energy and Water Conservation Design Requirements for SRM Projects Notes: 1. Baseline requirements are from ANSI/ASHRAE/IESNA Standard 90.1-2004. 2. U-values and R-values for assemblies and their definitions, requirements, and determinations can be found in ANSI/ASHRAE/IESNA Standard 90.1-2007, Normative Appendix A. 3. Light colored and cool roofs: reflect and emit the sun's heat back to the sky instead of transferring it to the building below. "Coolness" is measured by two properties, solar reflectance and thermal emittance. Both properties are measured from 0 to 1 and the higher the value, the "cooler" the roof. A high reflectance keeps much of the sun’s energy from being absorbed, while a high thermal emittance radiates away any solar energy that is absorbed, allowing the roof to cool more rapidly. Cool roofs are typically white and have a smooth surface. Commercial roof products that qualify as cool roofs fall into three categories: single-ply, liquid-applied, and metal panels. The solar reflectance and thermal emittance property values represent initial conditions as determined by a laboratory accredited by the Cool Roof Rating Council. Cool roofs are cost effective over air-conditioned spaces for buildings located in climate zones 1 - 5. In these locations, a minimum of 75% of the entire roof surface not used for roof penetrations shall be covered with roofing products that comply with one or more of the following: Have a minimum initial SRI of 78 for a low-sloped roof (a slope less than or equal to 2:12) and a minimum initial SRI of 29 for a steep-sloped roof (a slope of more than 2:12). Comply with the criteria for the US EPA’s Energy Star Program Requirements for Roof Products – Eligibility Criteria. For industrial buildings with only heating and ventilation, cool roofs can improve the comfort conditions (and hence productivity) in the space. In order to be considered a cool roof, a solar reflectance of 0.67 when tested in accordance with ASTM C1549, ASTM E903, or ASTM E1918 and, in addition, a minimum thermal emittance of 0.75 when tested in accordance with ASTM C1371 or ASTM E408, or a minimum Solar Reflective Index of 78 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 where standard white is SRI = 100 and standard black has SRI = 0. An SRI can be determined by the following equations: SRI = 123.97 – 141.35(x) + 9.655(x2) 3 0 6 . 0 0 . 2 1 5 0 2 5 . 9 7 9 7 . 0 2 x Where: , Where: is the solar absorptance (= 1 – solar reflectance) is the thermal emissivity, which were derived from ASTM E1980 assuming a medium wind speed, and are listed in Table 12. 13 Energy and Water Conservation Design Requirements for SRM Projects Table 12. Characteristics of reflective roofing materials. Roofing Type Color New Solar Reflectance Aged Solar Reflectance New Thermal Emittance SRI (ASTM E1980 84 – 106 Roof Coatings White 0.70 – 0.85 0.50 –0.65 0.85 Roof Coatings Grey or Tan 0.70 0.50 0.85 84 Roof Coatings Terra Cotta or Brown 0.40 0.30 0.85 43 Roof Coatings Aluminized 0.50 0.40 0.50 42 Metal Paint Red 0.25 0.25 0.83 22 Metal Paint Terra Cotta 0.35 0.35 0.83 36 Metal Paint Bright Red 0.35 0.35 0.83 36 Metal Paint Beige/Off White 0.55 0.55 0.83 63 Metal Paint Tan 0.45 0.45 0.83 49 Metal Paint Dark Blue 0.25 0.25 0.83 22 Metal Paint Medium to Light Blue 0.32 0.32 0.83 32 Metal Paint Dark Brown 0.25 0.25 0.83 22 Metal Paint Medium to Light Brown 0.32 0.32 0.83 32 Metal Paint Dark Green 0.25 0.25 0.83 22 Metal Paint Medium to Light Green 0.32 0.32 0.83 32 Metal Paint White 0.65 0.65 0.83 77 Metal Paint Bright White 0.70 0.70 0.83 84 Metal Paint Black 0.25 0.25 0.83 22 Metal Paint Dark Grey 0.25 0.25 0.83 22 Metal Paint Medium to Light Grey 0.35 0.35 0.83 36 Metal Paint Pearlescent Colors 0.35 0.35 0.75 32 Galvalume Unpainted 0.65 0.55 0.05 45 Copper Metal Unpainted 0.85 0.18 0.03 89 Galvanized Steel Unpainted 0.40 0.20 0.50 26 EPDM Membrane Black 0.05 0.10 0.85 0 TPO Membrane White 0.80 0.60 0.85 99 TPO Membrane Grey 0.50 0.40 0.85 57 PVC Membrane White 0.80 0.60 0.85 99 PVC Membrane Grey 0.50 0.40 0.85 57 Asphalt Shingle Dark Color 0.10 0.10 0.85 4 Asphalt Shingle Light Color 0.25 0.25 0.85 23 Modified Bitumen Cap Sheet Dark Color 0.10 0.10 0.85 4 Modified Bitumen Cap Sheet Light Color 0.25 0.25 0.85 23 Modified Bitumen Cap Sheet White 0.50-0.60 0.40 – 0.45 0.85 14 57 - 71 Energy and Water Conservation Design Requirements for SRM Projects 1. NR means there is no requirement or recommendation for a component in this climate zone. 2. Increased Building Air tightness. Building air leakage (measured in cfm/ft2) is the average volume of air(measured in cubic feet per minute) that passes through a unit area of the building envelope (measured in square feet) when the building is maintained at a specified internal pressure (measured in Pascals). ASHRAE has proposed a building air tightness requirement of 0.4 cfm/ft2 @ 75 Pa as an addendum to Standard 90.1-2004. ASHRAE has also proposed an approach to complying with the new requirement with a pressurization test to show that the building leakage does not exceed 0.4 cfm/ft2 at 75 Pa. This air tightness requirement provides a number that can be used for the energy simulations and was assumed to be the baseline leakage rate. The air tightness requirement adopted by the U.S. Army for new construction is more stringent than the one proposed by ASHRAE and requires that the leakage rate must not exceed 0.25 cfm/ft2 at 75 Pa, and was assumed for the energy efficient building models. To convert the values used for building leakage tests at the pressure difference of 75Pa to the values which can be used to calculate required excessive outdoor air supply rates, the following equation can be used ΔQ = Q75 * (5/75)0.65 = 0.172 * Q75. The excessive airflow rate for the building complying with the new ASHRAE 90.1 Standard air leakage requirement is 0.069 cfm/ft2. Respective number for the building built to the Army model RFP requirement is 0.043cfm/ft2. 3. Dedicated Outdoor Air System. A central dedicated outdoor air system (DOAS, Figure 1), provides: a. outside air for building indoor air quality and humidity control, (the amount needed is typically less than the amount exhausted from the bathroom and kitchen), b. make-up air for bathroom and kitchen exhausts (when needed), and c. building pressurization to prevent infiltration which allows for reduction of heating/cooling and moisture loads on the system. Figure 1. DOAS Schematic. Central DOAS does not provide sensible heating or cooling. This is provided by a complementing heating and cooling system, which will be taking care of only sensible loads. Complementing system can be radiant ceiling system (suspended or embedded into the ceiling) or convective (four pipe or DX fan-coil units). There are 2 types specified: the first system is for humid climates with a high latent load specified with dual, in series DX coils and 45F supply air temperature on a reset schedule. The other system has a single high efficiency DX coil and a higher supply air temperature of 55F on a reset schedule. 4. Decoupling exhaust and supply systems for laundry rooms. To reduce unneeded energy use for heating and cooling of the make-up air and for air transportation of supply and exhausted air from the dryers, 15 Energy and Water Conservation Design Requirements for SRM Projects laundry exhaust and supply systems are separated in the efficient building model from the rest of the building exhaust and supply systems. Laundry exhaust system and corresponding make-up systems operate only when dryers are operating. 5. Duct and pipe insulation, values are from the ASHRAE Advanced Energy Design Guide for Highway Lodging. 6. Drain Water Heat Recovery System. Domestic hot water (DHW) is one of the major heating energy users in the Army barrack buildings. With an average usage rate of 30gal/day per occupant at 110oF, depending upon location and climate, DHW can consume more than 60% of the total annual heating energy supplied to barrack buildings and be the dominant hot water consumer during the non-heating season. Approximately 80-90% of hot water energy goes down the drain. Gravity-Film Heat Exchanger (GFX) is a vertical counterflow heat exchanger that extracts heat out of drain water and applies it to preheat the cold water be mixed with hot water to be used in the shower. The CFX consists of a 3-or 4-inch central cooper pipe (that carries the warm wastewater) with a ½-in.cooper coils wound around the central pipe. Heat is transferred from the wastewater passing through the large, central pipe to the cold water simultaneously moving upward through the coils on the outside of the pipe. The coils are flattened a little to increase the contact area and improve heat transfer. The system is beneficial for use with showers where the use of hot and cold water and the production of waste-water from the shower occur at the same time. The most efficient application is to combine several shower drains for each GFX. 16