Spectra Plus - Introduction
Standard features
!
Conforming to IS13947-2/EN60947–2
!"
Compact dimensions
!
Available in 3P & 4P
!"
High performance microprocessor protection release
!"
Wide overload setting from 50% to 100%
!"
Current limiting
!"
Choice of rating plugs
!"
Variable short circuit and overload settings
!"
Suitable for isolation
!"
No line-load biasing
!"
Double forward facing insulation
!"
Trip free mechanism
!"
Positive ON/OFF indication flags
!"
Common field mountable internal accessories
General characteristics
Description
Spectra Plus moulded case circuit breakers with
microprocessor protection, are available in three and four
pole versions.
The Spectra Plus circuit breakers have individual rating
plugs and enable protected distribution of electricity within
a current range of 20A and 630A.
Spectra Plus - Introduction
02
Current limiting
The limiting capacity of a circuit breaker is the expression of the breaker’s capacity.
In the event of a short circuit, it reduces the let through current to a lower value than the
prospective fault current.
1
This characteristic is expressed by the following limiting curves:
1. Icc unlimited peak
2. Icc limited peak (actual)
The great limiting capacity of Spectra Plus circuit breaker is a result of the optimal
2
combination of:
!
A light moving part, reducing inertia.
!
A strong current loop, to generate maximum force of repulsion.
!
A slot motor with strong electro-magnetic field to accelerate the opening of the
contact.
!
!
Contact materials combining good conductivity and high durability.
An arc chamber combining a high energy absorption capacity, speed in breaking of
arc and cooling of gases.
This combination has enabled an exceptional breaking capacity/volume ratio. The
use of Spectra Plus circuit breaker enables a great reduction in stresses that normally
develop during a short-circuit:
!
Reduction in thermal constraints in conductors, increasing their life.
!
Reduction in mechanical constraints due to the reduction of the electrodynamic
forces of repulsion between conductors, which reduces the risk of deformation or
rupture of the wiring.
!
Reduction in electro-magnetic effects. The electro-magnetic field reduces and causes
less damage to neighboring devices and sensors.
Use
Spectra Plus circuit breakers provide a solution for standard and high performance levels
upto 50kA breaking capacity in 3 frames SE160, SF250 & SG400/630.
Suitability for visible isolation
Spectra Plus circuit breakers are ideal for fully visible isolation selection. With the handle
free, the indication “open” (green display) is only possible when the main contacts are
separated by a distance of >20mm. Spectra Plus circuit breaker conforms to standards:
IEC947-3, IS13947-3 recommended for isolation.
Double forward facing insulation
Spectra Plus circuit breakers are provided with forward facing spaces designed for
insertion of internal electrical auxiliaries. These spaces are completely insulated from the
power circuit.
Accreditation / Certification
IEC947-2, EN60 947.2, IS13947,
Lloyd’s Register of Shipping, RINA.
03
Spectra Plus - Introduction
High performance electronic protection
The current sensor output signal for each phase is sampled more than 30 times per
cycle in order to establish the true RMS value, independent of the network, the nature
of the load and the environment of the installation. Hence, Spectra Plus guarantees
“correct protection”.
Power source
The power source can be connected either from upline or downline of the Spectra Plus
circuit breaker, and up to the maximum voltage for use (690V).
Orientation
A fixed circuit breaker can be mounted as follows:
Spectra Plus - Introduction
Electrical auxiliaries
BA bell alarms, AS auxiliary ‘ON/OFF’ switches, ST voltmetric shunt releases and UV
undervoltage releases are common to all Spectra circuit breakers. e.g. an AS auxiliary
‘ON/OFF’ switch can be installed equally well on an SE 160 or SG 630 circuit breaker.
Thus it is not necessary to specify the type of circuit breaker. Only the release voltage
and the type of contact (standard or low level) has to be indicated with the order.
Assembly
As this is intended for installation in compartments that are accesssible from the
front, it is not necessary to take off the cover of the circuit breaker.
Left-hand compartment
Option of connecting UV or ST releases plus 3 pole BA. 1 or 2 additional AS contacts
can be connected to 4 pole SG400 to SG630 circuit breaker (an extra socket is
provided for this).
On each circuit breaker, ducts for the wiring are provided enabling the passage of the
cables to the right, left, or to the rear side of the device, without increasing its original
dimensions.
Right-hand compartment
Option of connecting 1 or 2 AS auxiliary switches.
On each circuit breaker, ducts for the wiring are provided enabling the passage of the
cables to the right, left, or to the rear side of the device, without increasing its original
dimensions.
Maximum possibilities for auxilliaries
Circuit Breaker
3P
4P
AS
2
2
BA
1
1
ST or UV
1
1
04
05
Spectra Plus - Accessories
Electrical auxiliaries
AS auxiliary ‘ON/OFF’ switches.
Description
Indicates the "open" or "closed" position of the circuit breaker to other auxiliaries such
as logic circuits, relays, displays, etc.. for control, locking, or remote indicator functions.
Characteristics
open close
Changeover contacts get activated at the same time as main poles. 2 versions:
1 changeover C/O or 2 changeover C/O (in the same volume).
(V)
Load
AC 50-60 Hz
22
12
14
21
11
common
11
common
DC
120 to 240
48 to 125
-
resistive
inductive
Wiring colour code
12: BNWH (brown & white)
14: RD (red)
11: WH (white)
22: OGWH (orange-white)
24: OG (orange)
21: GY (grey)
Uninterrupted current
(A)
5
0.5
0.25
Breaking capacity
(A)
5
0.5
0.25
Closing capacity
(A)
5
0.5
0.25
BA bell alarm contacts
Description
Changeover contacts signalling the "tripped" status of the circuit breaker caused by a
fault or opening by voltmetric ST or UV trip devices, or by an earth leakage device.
The contact returns to the "normal" position on resetting of the circuit breaker.
The BA contact is not activated with a normal closing or opening of the circuit breaker.
normal default
96
98
Characteristics
95
common
Standard contacts
Operating voltage
(V)
Load
AC 50-60 Hz
DC
120 to 240
48 to 125
-
resistive
inductive
Wiring colour code
96: GN (green)
98: BN (brown)
95: YE (yellow)
Uninterrupted current
(A)
5
0.5
0.25
Breaking capacity
(A)
5
0.5
0.25
Closing capacity
(A)
5
0.5
0.25
Earth fault module
Description
EFM250* Earth fault module is a compact and microprocessor based solution used
with the Spectra Plus range for providing effective Earth fault protection.
- Range 5% to 80% of In (In settable)
- Delay 50msec to 5 sec.
- Suitable for 3Phase 3Wire and 3Phase 4Wire system up to 630A
* For 400/630A please contact our nearest office.
24
14
12
Standard contacts
Operating voltage
open close
Spectra Plus - Accessories
Shunt release ST
Description
Shunt release ST causes the remote opening of the circuit breaker as soon as it
receives power (power can be permanent). Operation is guaranteed from 55% of
Un with alternating current and from 70% of Un with direct current.
Characteristics
Standard contacts
Operating voltage
(V)
AC 50-60 Hz
AC
DC
50-60 Hz
380/415
Wiring colour code:
Max. ringing current
(mA)
300
300
500
400
400
C1 - C2: Black(BK)
Average current
(mA)
10
10
6
5
6
Release breaking time
(ms)
min.
(100% Un)
max.*
15
45
12
30
10
35
15
50
15
50
24
48
110/127 220/250
* 55% of Un for AC - 70% of Un for DC
Undervoltage release UV
Description
Undervoltage release UV causes opening of the circuit breaker in the event of a drop
in voltage (35% to 70% of Un) guaranteed closure of the circuit breaker if Un > 85%.
Operating range:
0.85 < Uc < 1.1 Un.
When the release does not receive power, or voltage is too low, the circuit breaker
cannot be reclosed; the contacts do not touch.
Characteristics
Standard contacts
Operating voltage
Max. calling current
Average current
Release breaking time
(V)
(mA)
(mA)
AC 50-60 Hz/DC
24
48
110/127
220/250(2)
100
100
200
200
80
45
45
45
(ms)
mini
(100% Un)
maxi
(1)
3
45
75
75
85
120
250
250
(1) 55% of Un for AC - 70% of Un for DC.
(2) Time release MVR retarder (250, 500, 800, 1000 ms.) at 220V AC 50Hz.
Avoids untimely tripping with sudden loss of voltage.
Wiring colour code
D1 - D2: Blue (BL)
06
07
Spectra Plus - Data sheet
Extended rotary handle
Extended rotary handle ensuring a smooth operation of MCCB. The new extended
handle has three distinct positions - ON, OFF & TRIP with padlock facility.
Seperators / Spreaders
Spectra Plus range has been designed for ease of proper termination with help of
spreaders. Seperators are an integral part of MCCB and they help to enhance the
insulation level between live terminals.
Technical specifications
Circuit Breakers
SG 160
SG 250
SG 400
SG 630
S
N
S
N
S
N
S
N
Rated current lth (A) at 400C
160
160
250
250
400
400
630
630
Rated operating voltage Ue AC 50/60Hz (V)
690
690
690
690
690
690
690
690
Rated insulation voltage Ui (V)
690
690
690
690
690
690
690
690
Ultimate short-circuit breaking capacity lcu
50/60Hz 380/415V (kA)
36
50
36
50
36
50
36
50
Service short-circuit breaking capacity lcs AC
50*60 Hz 380/415V (kA)
36
50
36
50
36
50
36
50
Rated short-circuit making capacity lcm Ac
50/60 Hz 380/415V (kA)
76
110
76
110
76
110
76
110
Rated impulse voltage Uimp (kV)
8
8
8
8
8
8
8
8
Operational category
A
A
A
A
A
A
A
A
Number of poles
3-4
3-4
3-4
3-4
3-4
3-4
3-4
3-4
Endurance
Mechanical operations
Electrical operations
15000
4000
15000
4000
15000
4000
15000
4000
10000
3000
10000
3000
10000
3000
10000
3000
Total fault elimination time (ms)
<8
<8
<8
<8
<8
<8
<10
<10
Degree of pollution
3
3
3
3
3
3
3
3
Rating Plugs
3Pole / 4Pole
(Setting: 50-100%)
Current Rating
32A
32A
125A
125A
250A
250A
400A
400A
63A
63A
250A
250A
400A
400A
630A
630A
100A
100A
160A
160A
Spectra Plus - Dimensions
Spectra Plus SE 160 Frame
3P
4P
Spectra Plus SF 250 Frame
3P
4P
Spectra Plus SG 400/630 Frame
3P
4P
08
09
Spectra Plus - Dimensions
Door Drive Details - E Frame
Door Drive Details - F Frame
Spectra Plus - Dimensions
Door Drive Details - G Frame
Door Drilling Details for Mounting Handle on Panel Door
10
GE introduces Spectra TME125, a thermal magnetic MCCB in 3 / 4 pole for overload and short
circuit protection. Spectra TME125 has been tested for breaking capacities upto 25kA at 415VAC.
This MCCB provides protection for transformers, distribution circuits, cables and other equipment.
Spectra TME125
Features
Magnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuit
?
Current limiting, quick make, quick break mechanism that operates independent of manual force
?
?
Positive trip indication knob comes to a distinct position when the breaker trips due to overcurrent or
short circuit faults
?
Effective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage and increasing
the contact’s life
?
Red colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanism
?
Contacts are made of silver alloy with an anti-welding property
?
Internal and external accessories that can be fitted on site
?
Variable thermal setting from 80 -100%
?
Trip free mechanism
?
Thermal memory
Technical Particulars
Rated Currents (In)
16A, 20A, 32A, 40A,50A, 63A, 80A, 100A, 125A 16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125A
Rated Operational Voltage
415VAC
415VAC
Rated Insulation Voltage
690VAC
690VAC
Rated Frequency
50Hz
50Hz
No. of Poles
3 / 4 Pole
3 / 4 Pole
Utilization Category
A
A
Rated Ultimate Short Circuit Breaking
Capacity
18kA
25kA
Rated Service Short Circuit Breaking
Capacity
50%
40%
Overload Adjustability
80 - 100%
80 - 100%
Reference Standard
IS13947-2 & IEC947-2
IS13947-2 & IEC947-2
Termination
35sqmm Cu cable, or 16 X 6mm links
35sqmm Cu cable, or 16 X 6mm links
112.6
145±0.2
110±0.2
83.8
35±0.2
35±0.2
35±0.2
35±0.2
5.5
78.8
9
11.5
17.5 17.5
35±0.2
17.5 17.5
152±0.2
170±0.2
147
PUSH TO TRIP
0910/GR/SP
PUSH TO TRIP
170±0.2
NEUTRAL
GE India Industrial Pvt. Ltd.
The Millenia, Level 6, Tower B, #1 & 2, Murphy Road, Ulsoor, Bangalore 560 008
Ph: (080) 41434000, Fax: (080) 41434199
Email: query@ge.com
GE introduces Spectra TM200, a thermal magnetic MCCB in 3 / 4 pole for overload and short
circuit protection. Spectra TM200 has been tested for breaking capacities upto 36kA at 415VAC.
This MCCB provides protection for transformers, distribution circuits, cables and other equipment.
Spectra TM200
Features
Variable thermal setting from 80 -100%
?
?
Current limiting, quick make, quick break mechanism that operates independent of manual force
?
Positive trip indication knob comes to a distinct position when the breaker trips due to over-current or
short circuit faults
?
Effective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage and
increasing the contact’s life
?
Contacts are made of silver alloy with an anti-welding property
?
Magnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuit
?
Red colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanism
?
Internal and external accessories that can be fitted on site
?
Trip free mechanism
?
Thermal memory
Technical Particulars
Rated Currents (In)
160A, 200A
160A, 200A
Rated Operational Voltage
415VAC
415VAC
Rated Insulation Voltage
690VAC
690VAC
Rated Frequency
50Hz
50Hz
No. of Poles
3 / 4 Pole
3 / 4 Pole
Utilization Category
A
A
Rated Ultimate Short Circuit Breaking
Capacity
25kA
36kA
Rated Service Short Circuit Breaking
Capacity
100%
75%
Overload Adjustability
80 - 100%
80 - 100%
Reference Standard
IS13947-2 & IEC947-2
IS13947-2 & IEC947-2
Termination
50sqmm Cu cable, or 20 X 6mm links
50sqmm Cu cable, or 20 X 6mm links
95
30±0.2
15±0.115±0.1
15±0.1
83±0.1
30±0.2 30±0.2
30±0.2
15±0.1
8.6
30±0.2
150±0.2
150±0.2
132.8±0.2
2-INSERT M4
25
25
6 - Ø9.0
4 - Ø8.5
114.5
124.5
DIMENSIONAL DETAILS 160A - 200A
4 POLE
0910/GR/SP
DIMENSIONAL DETAILS 160A - 200A
3 POLE
62.0
67.3
72.0
84
GE India Industrial Pvt. Ltd.
The Millenia, Level 6, Tower B, #1 & 2, Murphy Road, Ulsoor, Bangalore 560 008
Ph: (080) 41434000, Fax: (080) 41434199
Email: query@ge.com
GE introduces Spectra TM125, a thermal magnetic MCCB in 3 / 4 pole for overload and short
circuit protection. Spectra TM125 has been tested for breaking capacities upto 36kA at 415VAC.
This MCCB provides protection for transformers, distribution circuits, cables and other equipment.
Spectra TM125
Features
Variable thermal setting from 80 -100%
?
?
Current limiting, quick make, quick break mechanism that operates independent of manual force
?
Positive trip indication knob comes to a distinct position when the breaker trips due to over current or
short circuit faults
?
Effective arc runner pushes the arc in the arc chute thereby reducing the contact tip damage and
increasing the contact’s life
?
Contacts are made of silver alloy with an anti-welding property
?
Magnetic instantaneous trip actuates the trip mechanism without any delay in the event of short circuit
?
Red colour ‘PUSH TO TRIP’ button is provided to check the tripping mechanism
?
Internal and external accessories that can be fitted on site
?
Thermal memory
?
Trip free mechanism
Technical Particulars
Rated Currents (In)
16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125A 16A, 20A, 32A, 40A, 50A, 63A, 80A, 100A, 125A
Rated Operational Voltage
415VAC
415VAC
Rated Insulation Voltage
690VAC
690VAC
Rated Frequency
50Hz
50Hz
No. of Poles
3 / 4 Pole
3 / 4 Pole
Utilization Category
A
A
Rated Ultimate Short Circuit Breaking
Capacity
25kA
36kA
Rated Service Short Circuit Breaking
Capacity
100%
75%
Overload Adjustability
80 - 100%
80 - 100%
Reference Standard
IS13947-2 & IEC947-2
IS13947-2 & IEC947-2
Termination
50sqmm Cu cable, or 20 X 6mm links
50sqmm Cu cable, or 20 X 6mm links
95
30±0.2
15±0.115±0.1
15±0.1
83±0.1
30±0.2 30±0.2
30±0.2
15±0.1
8.6
30±0.2
150±0.2
150±0.2
132.8±0.2
2-INSERT M4
25
25
6 - Ø9.0
4 - Ø8.5
114.5
124.5
DIMENSIONAL DETAILS 16A - 125A
4 POLE
0910/GR/SP
DIMENSIONAL DETAILS 160A - 200A
3 POLE
62.0
67.3
72.0
84