ECE 422/522 Power System Operations & Planning/Power Systems Analysis II : 6 - Small Signal Stability Spring 2014 Instructor: Kai Sun 1 References • Kundur’s Chapter 12 • Saadat’s Chapter 11.4 • EPRI Tutorial’s Chapter 8 – Power Oscillations 2 Power Oscillations • The power system naturally enters periods of oscillation as it continually adjusts to new operating conditions or experiences other disturbances. • Typically the amplitude of the oscillations is small and their lifetime is short. • When the amplitude of the oscillations becomes large or the oscillations are sustained, a response may be required. • A system operator may have the opportunity to respond and eliminate harmful oscillations or, less desirably, protective relays may activate to trip system elements. 3 Small Signal Stability • Small signal stability (also referred to as small-disturbance stability or steady-state stability) is the ability of a power system to maintain synchronism when subjected to small disturbances – In this context, a disturbance is considered to be small if the equations that describe the resulting response of the system may be linearized for the purpose of analysis – It is convenient to assume that the disturbances causing the changes disappear (the details of the disturbance is not important) – The system is stable if it returns to its original state, i.e. a stable equilibrium point. – Such a behavior can be determined in the linearized model of the power system 4 Small Signal Stability of a Single-Machine-Infinite-Bus System • Because of the relative size of the large system to which the machine is supplying power, dynamics associated with the machine will cause virtually no change in the voltage and frequency of Thevenin’s EB • The large system is often referred to as an Infinite Bus (constant voltage and constant frequency) • The voltage phasor at the infinite bus can be the reference of the rotor angle, i.e. EB∠0 5 (Te) Consider the Classical Model P+jQ’ Pt+jQt PB+jQB (Tm) (Pe=Te) Linearize swing equations at δ=δ0 : Complex power behind X’d: =∆Tm-∆Te Define synchronizing torque coefficient With resistance (RT) neglected: KS Te= Pe= P= Pt= PB= Pmax= E’EB/XT 6 E EB cos 0 Pmax cos 0 XT 0Tm d 2 K D d K s 0 2 H dt 2H 2H dt 2 • Apply Laplace Transform: s 2 • K T KD s s 0 0 m 2H 2H 2H Characteristic equation: Note: KS =PS and KD=Dω0 in Saadat’s book 0Tm d 2 D0 d Ps 0 dt 2 2 H dt 2H 2H s2 D0 P s s 0 0 2H 2H 7 (K S E EB cos 0 Pmax cos 0) XT • Compared to the general form of a 2nd order system (0<ζ<<1 for a generator): s 2 2n s n 2 0 Undamped natural frequency: Note: resistance RT is ignored here, whose effect is to result in more damping Damping ratio: Two conjugate complex roots: s1 , s2 n jn 1 2 n jd Damped oscillation frequency: • When H ↑ or KS↓, oscillation frequency (ωn or ωd) ↓ (e.g. when XT ↑ or δ0 ↑) 8 High vs. Low Frequency Oscillations in Realistic Systems • When power flows, I2R losses occur. These energy losses help to reduce the amplitude of the oscillation. The higher the frequency of the oscillation, the faster it is damped. High frequency (>1.0 HZ) oscillations are damped more rapidly than low frequency (<1.0 HZ) oscillations. • Usually, in realistic systems: • Power system operators do not want any oscillations. However, it is better to have high frequency oscillations than low frequency. The power system can naturally dampen high frequency oscillations. Low frequency oscillations are more damaging to the power system, which may exist for a long time, become sustained (undamped) oscillations, and even trigger protective relays to trip elements 9 Blackout Event on August 10, 1996 970 MW loss 1. Initial event (15:42:03): Short circuit due to tree contact → Outages of 6 transformers and lines 2. Vulnerable conditions (minutes) Low-damped inter-area oscillations → Outages of generators and tie-lines 2,100 MW loss 11,600 MW loss 15,820MW loss 3. Blackouts (seconds) Unintentional separation → Loss of 24% load Malin-Round Mountain #1 MW 1500 15:42:03 15:47:36 15:48:51 1400 0.276 Hz oscillations Damping>7% 1300 1200 1100 200 300 0.264 Hz oscillations 3.46% Damping 400 500 0.252 Hz oscillations Damping ≈1% Time in Seconds 600 Oscillation frequency (ωn or ωd) ↓ when H ↑ or KS↓ (e.g. when XT ↑ or δ0 ↑) 10 700 System 800 islanding and blackouts System Response after a Small Disturbance Y( s ) = X( s) = ( sI − A ) −1 [ x(0)+B∆U ( s )] Zero-input Zero-state x1 x2 r / 0 x1 0 0 2 2 0 n x2 n Tm u 2H x1 0 Tm x2 1 2H x= (t ) Ax(t ) + B∆u (t ) 1 0 x1 y (t ) x(t ) 0 1 x2 sX ( s ) − x= (0) AX ( s ) + B∆U ( s ) U ( s ) u s s 2n 0 n 2 0 s x(0)+BU ( s ) X ( s ) 2 s 2n s n 2 s 2n 0 2 0 s ( s ) 2 n r ( s ) s 2n s n 2 (0) 0 ) ( r (0) u s Zero-input Zero-state Usually ∆ωr(0)≈0 following a disturbance 11 s 2n 0 2 ( s ) n 0 s r ( s ) s 2 2n s n 2 (0) 0 ) ( r (0) u s Note: u Zero-input response • • E.g. when there is a small increase in mechanical torque ∆Tm (= ∆Pm in pu) ω0 ∆u ∆δ ( s ) = s ( s 2 + 2ζωn s + ωn2 ) ( s 2n ) (0) ( s ) 2 s 2n s n 2 (0) / 0 s 2 2n s n 2 2 n (0) n t e Taking inverse Laplace transforms = ∆δ sin(d t ) 1 2 (0) nt e r n sin d t 2 0 1 θ = cos −1 ζ τ = 1 4H = ζωn K D Tm 2H Zero-state response E.g. when the rotor is suddenly perturbed by a small angle ∆δ(0)≠0 and assume ∆ωr (0)=0 r ( s ) r / 0 (r 0 ) / 0 ∆u ∆ωr ( s ) = s 2 + 2ζωn s + ωn2 ω0 ∆u 1 −ζω t 1 sin ω θ e t − + ( d ) 2 ωn2 1− ζ n ∆ωr = ∆u ωn 1 − ζ 2 (Response time constant) 12 e −ζωnt sin ωd t s 2n 1 2 ( s ) n s 2 2 ( s ) s 2n s n Note: Saadat’s book defines (0) 0 ) ( (0) u s 0 Zero-input response • • E.g. when there is a small increase in mechanical torque ∆Tm (= ∆Pm in pu) ∆u ∆δ ( s ) = s ( s 2 + 2ζωn s + ωn2 ) ( s 2n ) (0) ( s ) 2 s 2n s n 2 (0) s 2 2n s n 2 2 n (0) n t e θ = cos −1 ζ τ = ∆u 1 −ζωn t − + 1 e sin t ω θ ( d ) 2 ωn2 1− ζ ∆= δ sin(d t ) 1 4H = ζωn K D ∆u ∆ω ( s ) = s 2 + 2ζωn s + ωn2 Taking inverse Laplace transforms 1 (0) nt e n sin d t 2 1 2 0Tm 2H Zero-state response E.g. when the rotor is suddenly perturbed by a small angle ∆δ(0)≠0 and assume ∆ωr (0)=0 ( s ) u ∆ω = ∆u ωn 1 − ζ 2 (Response time constant) 13 e −ζωnt sin ωd t Saadat’s Example 11.2 and Example 11.3 • H=9.94 MJ/MVA, D=0.138, P=0.6 pu with 0.8 power factor. Obtain the zero-input and zero-state responses for the rotor angle and the generator frequency: (1) ∆δ(0)=10o=0.1745 rad (2) ∆P=0.2pu δ(0)=16.79+10o=26.79o 14 Zero-input response: ∆δ(0)=10o Zero-state response: ∆P=0.2pu δ(0)=16.79+10=26.79o δ(∞)=16.79+5.76=22.55o 15 Consider the Excitation System (see Kundur’s 12.4 for aij and b1) Te | fd K 2 K 3 [ K 4 (1 sTR ) K 5Gex ( s )] s 2T3TR s (T3 TR )1 K 3 K 6Gex ( s ) 16 • The effect of the AVR on damping and synchronizing torque components is primarily influenced by Gex(s) and K5 • With K5<0, the AVR may introduce a positive synchronizing torque Te | fd K 2 K 3 [ K 4 (1 sTR ) K 5Gex ( s )] 2 s T3TR s (T3 TR )1 K 3 K 6Gex ( s ) KR and KI are respectively the real and imaginary parts of the coefficient of ∆δ • For a given oscillation frequency s=jω: Te | fd K R K I j K R K I 0 r =K S ( fd ) K D ( fd )r j j / s / r 0 / Synchronizing and damping torque coefficients due to ∆ψfd 17 Example on effects of different AVR settings • Steady-state synchronizing torque coefficient: The effect of the AVR is to increase the synchronizing torque component at steady state • Damping and synchronizing torque components at rotor oscillation frequency 10 rad/s (s=jω=j10) 18 ∆Te= ∆TS+∆TD= KS ∆δ+KD∆ω • KS = KS(∆ψfd)+KS(gen & network) KD = KD(∆ψfd)+KD(gen & network) Usually, KS (gen & network)>0 KD(gen & network)>0 • Constant field voltage (KA=0): – KD>0 – Perhaps, KS=KS(gen & network) + KS(∆ψfd)<0 • With excitation control (large KA) – KS>0 – Perhaps, KD =KD(gen & network) + KD(∆ψfd)<0 19 Power System Stabilizer • The basic function of a power system stabilizer (PSS) is to add damping to the generator rotor oscillations by controlling its excitation using non-voltage auxiliary stabilizing signal(s) – If the transfer function from PSS’s output to ∆Te was pure gain, a direct feedback of ∆ωr would create a positive damping torque component. 20 • However, actual generators and exciters exhibit frequency dependent gain and phase-lag characteristics G( s) 1 1 s • Therefore, GPSS(s) should provide phase-lead compensation to create a torque in phase with ∆ωr G(s) 1/τ1 GPSS ( s ) 21 1/τ2 1 1s (1 2 ) 1 2 s PSS Model • Stabilizer gain KSTAB – determines the amount of damping introduced by PSS • Signal washout block: – High-pass filter with TW long enough (typically 1~20s) to allow signals associated with oscillations in ωr to pass unchanged. However, if it is too long, steady changes in speed would cause generator voltage excursions • Phase compensation block: – Provides phase-lead compensation over the frequency range of interest (typically, f=0.1~2.0 Hz, i.e. ω=0.6~12.6 rad/s) – Two or more first-order blocks, or even second-order blocks may be used. – Generally, some under-compensation is desirable so that the PSS results in a slight increase of the synchronizing torque as well 22 Kundur’s Example 12.4 23 PSS in NERC Interconnections • The WECC and the MRO Regions have operating requirements that mandate the use of PSS. All units with fast excitation systems must be equipped with well tuned PSS in these Regions. PSS are typically installed in the majority of generating units in the problem area. • Several units in the PJM system are equipped with PSS to address local oscillatory stability concerns 24 Characteristics of Small-Signal Stability Problems • Local or machine-system modes (0.7~2Hz): oscillations involve a small part of the system – Local plant modes: associated with rotor angle oscillations of a single generator or a single plant against the rest of the system; similar to the single-machine-infinite bus system – Inter-machine or interplant modes: associated with oscillations between the rotors of a few generators close to each other • Inter- or intra-area modes (0.1~0.7Hz): machines in one part of the system swing against machines in other parts – Inter-area model (0.1~0.3Hz): involving all the generators in the system; the system is essentially split into two parts, with generators in one part swinging against machines in the other parts. – Intra-area mode (0.4~0.7Hz): involving subgroups of generators swinging against each other. • Control or torsional modes: – Due to inadequate tuning of the control systems, e.g. generator excitation systems, HVDC converters and SVCs, or torsional interaction with power system control 25 Homework • Problems 11.10~11.13 in Saadat’s book (3rd ed), due by April 15 (Tuesday) in class or by email 26