ECE 421/521 Electric Energy Systems Power Systems Analysis I 2 – Basic Principles Instructor: Kai Sun Fall 2013 1 Outline • Power in a 1-phase AC circuit • Complex power • Balanced 3-phase circuit 2 Single Phase AC System = i (t ) I m cos(ωt + θi ) + = v (t ) Vm cos(ωt + θ v ) - Z 3 Load Phasor Representation = v(t ) Vm cos(ωt += θv ) = + θi ) i (t ) I m cos(ωt = • V=|V|∠θv 2 | V | cos(ωt + θ v ) 2 | I | cos(ωt + θi ) I=|I|∠θi – RMS phasors of v(t) and i(t) Reference • A phasor is a complex number that carries the amplitude and phase angle information of a sinusoidal function • Phasors represent sinusoidal signals of a common frequency (ω) as vectors in the complex plane w.r.t. a chosen reference signal. • Phasor representation is a mapping from the time domain to complex number domain. 4 • Instantaneous power delivered to the load: p (t ) = v (t )i (t ) = Vm I m cos(ωt + θ v ) cos(ωt + θi ) 1 Vm I m [cos(θ v − θi ) + cos(2ωt + θ v + θi )] 1 cos A cos B = [ ] 2 2 1 = Vm I m {cos(θ v − θi ) + cos[2(ωt + θ v ) − (θ v − θi )]} 2 θ= θ v − θi 1 Impedance angle >0 for inductive load= and Vm I m {cos θ + cos[2(ωt + θ v ) − θ ]} <0 for capacitive load 2 1 = Vm I m [cos θ + cos 2(ωt + θ v ) cos θ + sin 2(ωt + θ v ) sin θ ] 2 Using trigonometric identity = cos( A - B ) + cos( A + B ) | V | V= 2, | I | I m / 2 m / p(t ) = V ⋅ I cos θ [1 + cos 2(ωt + θ v )] + V ⋅ I sin θ sin 2(ωt + θ v ) pR ( t ) Root-mean-square (RMS) values 5 pX ( t ) Example 2.1 v (t ) = 100 cos ωt Z= 1.25∠60° Ω 1 100∠0° Calculate the RMS current phasor:= I = 1.25 60° ∠ 2 = i (t ) 80 cos(ωt − 60o ) Assume 1 80∠ − 60° 2 v(t)=V cos ωt, i(t)=I cos(ωt -60) m m p(t)=v(t) i(t) 100 6000 50 4000 0 2000 -50 0 -100 0 90 180 ωt, degree 270 -2000 360 0 90 180 ωt, degree pX(t) Eq. 2.8 270 360 0 90 180 ωt, degree 270 360 pR(t) Eq. 2.6 4000 4000 3000 2000 2000 0 1000 0 -2000 0 90 180 ωt, degree 270 360 -4000 6 p (t ) = V ⋅ I cos θ [1 + cos 2(ωt + θ v )] + V ⋅ I sin θ sin 2(ωt + θ v ) pR ( t ) pX ( t ) • Observations on pR(t): – Oscillating at frequency 2*ω (twice of the source frequency) – Changing between 0 and 2|V|⋅|I|cosθ (always positive) – Average value is |V|⋅|I|cosθ – It is the energy flow into the circuit • Observations on pX(t): – Oscillating at frequency 2*ω (twice of the source frequency) – Changing between -|V|⋅|I|sinθ and |V|⋅|I|sinθ (either positive or negative) – Average value is zero – It is the energy borrowed & returned by the circuit. It does no useful work in the load but takes some line capacity 7 Real and Reactive Powers p(t ) = V ⋅ I cos θ [1 + cos 2(ωt + θ v )] + V ⋅ I sin θ sin 2(ωt + θ v ) pR ( t ) pX ( t ) |V | ⋅ | I | • Apparent power • Unit ~ volt ampere or VA (kVA or MVA) def Q P | V | ⋅ | I | cos θ = • Real power or active power (average power) • Unit ~ watt or W • Power factor (PF): cosθ= cos(θv-θi) – Lagging or leading when θ =θv-θi >0 or <0 def = Q | V | ⋅ | I | sin θ • Reactive power • Unit ~ var (volt-ampere reactive). Some people use Var, VAR or VAr • Q>0 or <0 when θ=θv-θi >0 or <0 8 P Characteristics of instantaneous power p(t) p (t ) = V ⋅ I cos θ [1 + cos 2(ωt + θ v )] + V ⋅ I sin θ sin 2(ωt + θ v ) pR ( t ) pX (t ) = P[1 + cos 2(ωt + θ v )] + Q sin 2(ωt + θ v ) For a pure resistor load (thermal load), • θ=θv-θi =0, PF=1 (unity PF) • P=|V||I|, so all electric energy becomes thermal energy For a pure inductive load, • θ=θv-θi =90, PF=0 • P=0, so electric energy = constant (no transformation to other forms) • p(t) oscillates between the source and the magnetic field associated with the inductive load For a pure capacitive load, • θ=θv-θi =-90, PF=0 • P=0, so electric energy = constant (no transformation to other forms) • p(t) oscillates between the source and the electric field associated with the capacitive load 9 Example 2.1 Z= 1.25∠60° Ω RMS phasors: v (t ) = 100 cos ωt = i (t ) 80 cos(ωt − 60o ) = V 100 ∠0°, = I 2 80 ∠ − 60° 2 o 4000 cos 60 [1 + cos 2ω sin 60o sin 2 p (t ) = V ⋅ I cos θ [1 + cos 2ωt ] + V ⋅ I sin θ sin 2ωt = t ] + 4000 ωt p (t ) pR ( t ) pX ( t ) P pR ( t ) Q v(t)=Vm cos ωt, i(t)=Im cos(ωt -60) X p(t)=v(t) i(t) 100 6000 50 4000 0 2000 -50 0 P -100 0 90 180 ωt, degree pR(t) 270 -2000 360 4000 3000 2000 2000 P 0 180 ωt, degree pX(t) Eq. 2.8 270 Borrowing Returning Q -2000 90 180 ωt, degree 270 360 -4000 10 360 Q 0 1000 90 Eq. 2.6 4000 0 0 0 90 180 ωt, degree 270 360 What does “absorbing” or “generating” reactive power mean? • “Reactive power” with a circuit element does not lead to real energy consumption • Starting from the time of v(t)=Vm, – An inductive element (lagging PF) first absorbs and then returns the same amount of electric energy. Such a pattern is considered “absorbing” reactive power, and it helps reduce oscillations of power – A capacitive element (leading PF) first generates and then absorbs the same amount of electric energy. Such a pattern is considered “generating” reactive power, and it helps maintain voltage • For a real-world power system with long-distance transmission, low voltage at receiving ends is usually a big reliability concern. Shunt/series capacitors can be added as “sources” of reactive power or var 11 Complex Power def S = P + jQ V I cos θ + j V I sin θ = V I ∠θ = * = V I ∠θ v − θ= VI i = | S | ∠θ = P 2 + Q 2 ∠θ Reference • |S| is the apparent power • θ=tan-1(Q/P) – When θ>0 (θi <θv, i.e. lagging PF), Q>0 i.e. absorbing Q (inductive load) – When θ<0 (θi >θv, i.e. leading PF), Q<0 i.e. generating Q (capacitive load) 12 PF=cosθ=P/|S| (lagging/leading is told by +/- sign of Q) P=|S|⋅ cosθ=|S|⋅ PF | S | ⋅ sin θ = | S | ⋅ 1 − PF 2 , if lagging Q= − | S | ⋅ 1 − PF 2 , if leading − | S | ⋅ sin θ = If the load impedance is Z, i.e .V=ZI, then |Z| X S = VI*= ZII*= Z|I|2= R|I|2+jX|I|2 = P + jQ P=R|I|2 R Q=X|I|2 • The load impedance angle θ is also called power angle (ϕ in some literature) • Apparent power |S|∝|I|2 indicates heating and is used as a rating unit of power equipment 13 • Some useful equations: * 2 2 V VV 2 * * = S VI = = = V Y * * Z Z V Z= * S V P= R • If Z is purely resistive 2 2 2 2 V V V Q = or • If Z is purely reactive= X −1/ ωC ωL 14 Y= S* V 2 Complex Power Balance S = VI * = V [ I1 + I 2 + I 3 ]∗ = VI1* + VI 2* + VI 3* = S1 + S2 + S3 P + jQ = P1 + jQ1 + P2 + jQ2 + P3 + jQ3 • Due to the conservation of energy, the total complex power delivered to the loads in parallel is the sum of complex powers delivered to each (by KCL). • In other words, a balance must be maintained all the time for both real power and reactive power 15 Example 2.2 V= 1200∠0° V, Z1= 60 + j 0Ω, Z 2 =6 + j12Ω, Z 3 =30 − j 30Ω Find the power absorbed by each load and the total complex power I= 1 V 1200∠0° 1200 = = = 20 + j 0 A Z1 60 + j 0 60 I= 2 V 1200∠0° 200 200(1 − j 2) = = = = 40 − j80 A Z2 6 + j12 1 + j 2 5 I= 3 V 1200∠0° 40 40(1 + j ) = = = = 20 + j 20 A Z 3 30 − j 30 1 − j 2 * S= VI= 1200∠0°(20 − j 0) = 24, 000 W+j 0 var 1 1 * S= VI= 1200∠0°(40 + j80) = 48, 000 W+j 96, 000 var 2 2 * S= VI= 1200∠0°(20 − j 20) = 24, 000 W − j 24, 000 var 3 3 S = S1 + S2 + S3 = 96, 000 W+j 72, 000 var 16 • Other approaches I =I1 + I 2 + I 3 =(20 + j 0) + (40 − j80) + (20 + j 20) = 80 − j 60= 100∠ − 36.87° A S =VI * =(1200∠0°)(100∠36.87°) =120, 000∠36.87° VA 96, 000 W + j 72, 000 var 2 V (1200)2 = = 24, 000 W + j 0 var S1 = Z1* 60 2 V (1200)2 = = 48, 000 W + j 96, 000 var S2 = Z 2* 6 − j12 2 V (1200)2 = S3 = = 24, 000 W − j 24, 000 var Z 3* 30 + j 30 17 Theorem of Conservation of Complex Power For a network supplied by independent sources all at the same frequency (all voltages and currents are assumed to be sinusoids), the sum of the complex power supplied by the independent sources equals the sum of the complex power received by all the other branches of the network • For a single source with elements in series or parallel, it is proved by Kirchhoff’s voltage or current law (KVL/KCL) • For a general case, it is proved by Tellegen’s theorem. • Application of the theorem: a part of the network can be replaced by an equivalent independent source 18 • Some examples on Bergen and Vittal’s book 19 20 21 Homework #2 • Read through Saadat’s Chapter 2.1~2.4 • ECE521: 2.1~2.6 • ECE421: 2.1, 2.3, 2.4, 2.5 • Due date: 9/11 (Wednesday) submitted in class or by email 22 Power Factor Correction P=|V||I|⋅ cosθ=|S|⋅ PF • When PF<1, current I needs to increase by 1/PF to deliver the same P as that with PF=1. • Thus, the major loads of the system are expected to have close to unity PFs. That is not a problem for residential and small commercial customers. • However, industrial loads are inductive with low lagging PFs, so capacitors may be installed to improve PFs 23 P+jQ Example 2.3 (a) Find P, Q, I and PF at the source (b) Find capacitance C of the shunt capacitor to improve the overall PF to 0.8 lagging C Solution: (a) (b) 200∠0° = 2∠0° A 100 200∠0° = 4 − j8 A I 2= 10 + j 20 I1 = * S= VI1= 200∠0°(2 − j 0)= 400 W+j 0 var 1 * S= VI = 200∠0°(4 + j8)= 800 W + j1600 var 2 2 New power angle = θ ′ cos −1 (0.8) = 36.87° Q ′ P tan θ ′ 1200 tan(36.87 = = = °) 900 var Qc = 1600 − 900 = 700 var S =P + jQ =1200 + j1600 =2000∠53.13° VA S * 2000∠ − 53.13° I= = = 10∠ − 53.13° A V* 200∠0° PF 2 V (200) 2 Zc = = = − j57.14 Ω Sc* j 700 cos(53.13 = ) 0.6 lagging 106 C = = 46.42 μF 2π (60)(57.14) 24 New apparent power and current S ′ = 1200 + j 900 = 1500∠36.87° 2000→1500 S ′* 1500∠ − 36.87° = = 7.5∠ − 36.87° 10→7.5 I=′ * V 200∠0° High-voltage capacitor bank (150kV - 75MVAR) Learn Example 2.4 (high-voltage) (Source: wikipedia.org) 25 P12+jQ12 Complex Power Flow V= V1 ∠δ1 1 I12 = = P21+jQ21 V= V2 ∠δ 2 2 V1 ∠δ1 − V2 ∠δ 2 Z ∠γ V1 V ∠δ1 − γ − 2 ∠δ 2 − γ Z Z S12 = V1 I12* = V1 ∠δ1 [ V1 V ∠γ − δ1 − 2 ∠γ − δ 2 ] Z Z 2 V V V = 1 ∠γ − 1 2 ∠γ + δ1 − δ 2 Z Z 2 V1 V V = P12 cos γ − 1 2 cos(γ + δ1 − δ 2 ) Z Z = P12 If R=0, i.e. |Z|=X and γ=90o 2 V1 V2 sin(δ1 − δ 2 ) X V Q12 =1 [ V1 − V2 cos(δ1 − δ 2 )] X V1 V V Q12 sin γ − 1 2 sin(γ + δ1 − δ 2 ) = Z Z 26 P12 V1 V2 sin(δ1 − δ 2 ) X V Q12 =1 [ V1 − V2 cos(δ1 − δ 2 )] X • Since R=0, there are no transmission line losses, and P12=-P21 • In a normal power systems, |Vi|≈100% and |δ1-δ2| is small (e.g. 5~30o). • P12∝sin(δ1-δ2)≈δ1-δ2 – Real power flow is governed mainly by the angle difference of the terminal voltages. – For example, if V1 leads V2, i.e. δ1-δ2>0, the real power flows from node 1 to node 2. – Theoretical maximum power transfer (i.e. static transmission capacity): V1 V2 V1 V2 = P12 max = sin 90 X X • Q12 ∝|V1|-|V2|cos(δ1-δ2) ≈|V1|-|V2| – Reactive power flow is determined by the magnitude difference of terminal voltages 27 S12=P12+jQ12 Example 2.5 S21=P21+jQ21 I21 Determine the real and reactive powers supplied or received by each source and the power loss in the line V= 120∠ − 5° V,V= 100∠0° V, Z = 1 + j7 Ω 1 2 120∠ − 5° − 100∠0° = 3.135∠ − 110.02° A 1 + j7 100∠0° − 120∠ − 5° = 3.135∠69.98° A I 21 = 1 + j7 = I12 1000 800 P 600 21 400 S12 = V1 I12* = 376.2∠105.02° = −97.5 W + j 363.3 var P, Watts 200 = S21 V1= I 21* 313.5∠ − 69.98 = ° 107.3 W − j 294.5 var PL 0 -200 S L = S12 + S21 = 9.8 W + j 68.8 var =PL + jQL -400 PL P R= I12 (1)(3.135) = 9.8 W 2 2 -800 = QL X= I12 (7)(3.135) = 68.8 var 2 12 -600 2 -1000 -40 28 -30 10 0 -10 -20 Source #1 Voltage Phase Angle, δ 20 1 30 Balanced Three-Phase Circuits • A balanced source: three sinusoidal voltages are generated having the same amplitude but displaced in phase by 120o – Instantaneous power delivered to the external loads is constant Positive phase sequence Negative phase sequence 29 Balanced Y-connected Loads E= E p ∠α A An EBn = E p ∠α A − 120° ECn = E p ∠α A − 240° V= E An − Z G I a An V= VAn − Z L I a an • Let Van be the reference: Phase voltages (line-to-neutral voltages): Van= V p ∠0° Vbn = V p ∠ − 120° Vcn = V p ∠ − 240° Line voltages (line-to-line voltages): Vab = Van − Vbn = V p (1∠0° − 1∠ − 120°= ) 3 V p ∠30° Vbc = Vbn − Vcn = V p (1∠ − 120° − 1∠ − 240°= ) Vca= Vcn − Van= V p (1∠ − 240° − 1∠0°= ) 3 V p ∠ − 90° 3 V p ∠150° 30 Vbc | VL |= 3 V p I= a Van | Van | ∠0 = = Z p | Z p | ∠θ I= b Vbn = Zp I p ∠ − 120° − θ I= c Vcn = Zp I p ∠ − 240° − θ Ip ∠ −θ IL = I p • On the neutral line (return line) In=Ia+Ib+Ic=0 • The neutral line may not actually exist (one line per phase) • The balanced 3-phase power system problems can be solved on a “per-phase” basis, e.g. for Phase A only. The other two phases carry identical currents except for phase shifts. 31 Balanced △-connected Loads VL = V p • Let Iab be the reference: I ab= I p ∠0° I bc= I p ∠ − 120° I ca= I p ∠ − 240° I= I ab − I ca= a I p (1∠0° − 1∠ − 240°= ) I= I bc − I ab= b I p (1∠ − 120° − 1∠0°= ) I= I ca − I bc= c 3 I p ∠ − 30° 3 I p ∠ − 150° I p (1∠ − 240° − 1∠ − 120°= ) 3 I p ∠90° | I L |= 3 I p 32 △-Y Transformation • Idea: compare Ia=f∆(Van, Z∆) and Ia=fY(Van, ZY) Z∆ Z∆ n Z∆ – Find Ia=f∆(Van, Z∆): Ia = Vab Vac Vab + Vac + = Z∆ Z∆ Z∆ Ia = Vca 3Van Z∆ – Find Ia=fY(Van, Z∆): Van Ia = ZY ZY = Vab= + Vac 3 Van ∠30° + 3 Van ∠ − 30° = 3 Van ( 3 / 2 + j / 2 + 3 / 2= − j / 2) 3Van 33 Z∆ 3 Balanced Three-Phase Power van 2 V p cos(ωt + θ v ) vbn 2 V p cos(ωt + θ v − 120°) vcn 2 V p cos(ωt + θ v − 240°) For balanced loads ian 2 I p cos(ωt + θi ) ibn 2 I p cos(ωt + θi − 120°) + V p I p [cos(θ v − θi ) + cos(2ωt + θ v + θi − 240°)] icn 2 I p cos(ωt + θi − 240°) + V p I p [cos(θ v − θi ) + cos(2ωt + θ v + θi − 480°)] = p3φ V p I p [cos(θ v − θi ) + cos(2ωt + θ v + θi )] Total instantaneous power: p3φ = vania + vbnib + vcnic Zero Total instantaneous power is constant: = 2 V p I p cos(ωt + θ v ) cos(ωt + θi ) p= P= 3 V p I p cos θ 3φ 3φ +2 V p I p cos(ωt + θ v − 120°) cos(ωt + θi − 120°) +2 V p I p cos(ωt + θ v − 240°) cos(ωt + θi − 240°) Where is reactive power? 34 • Extend the concept of complex power to 3-phase systems Q3φ = 3 V p I p sin θ S3φ =P3φ + jQ3φ =3V p I *p • Expressed in terms of line voltage VL and line current IL – Y-connection: V = V / 3 I p = I L I = I / 3 – ∆-connection: Vp = VL p L p L P3φ = 3 VL I L cos θ Q3φ = 3 VL I L cos θ θ is the angle between the phase voltage and the phase current for the same phase (e.g. Phase A) 35 Example 2.7 (a) The current, real power and reactive powers drawn from the supply (b) The line voltage at the combined loads (c) The current per phase in each load (d) The total real and reactive powers in each load and the line 36 V2=110-j20 37 Homework #3 • Read through Saadat’s Chapter 2.5~2.12 • ECE521: 2.7~2.10, 2.14~2.16 • ECE421: 2.7, 2.8, 2.10, 2.15, 2.16 • Due date: 9/20 (Friday) submitted in class or by email 38