Case Studies 4 The case studies in this chapter illustrate techniques and methods that are discussed in this Guide. They are presented in order of climate zone, from warmest to coldest. Energy numbers are provided to benchmark these buildings against future buildings; however, all these case studies predate the publication of the Guide, and they were not developed using the recommendations in Chapter 3. These schools may or may not have achieved the 30% level if they had been constructed entirely according to the recommendations in this Guide. You are encouraged to view additional case studies and submit your own at www.ashrae.org/aedg. Case studies provide motivation and examples for others to follow. Zone 1—Waipahu Intermediate School Waipahu, Hawaii The Hawaii Department of Education piloted the Waipahu Intermediate School (WIS) cafeteria as a LEED project in educational facilities to support its commitment to conserve resources and provide better facilities. The 19,200 ft2 cafeteria, opened for the 2006–2007 school year, is designed to serve 750 people at a time. Daylighting features include shaded north- and south-facing clerestories and jalousies designed to bounce indirect daylight deep into the dining area. This reduces the electric lighting requirements by more than 55%. The roof was designed to create a thermal chimney for stack-effect ventilation, which, in addition to cross-ventilation, eliminates the need for ceiling fans and ductwork. The State of Hawaii Department of Business, Economic Development, and Tourism Report, Analyses of Economic, Environmental and Occupant Benefits of Sustainable Design, and LEED Certification for State of Hawaii and Public School Facilities, included the development of two energy-use scenarios for the cafeteria example: a base case (built to code) and a green case (incorporating high-performance features). The green case resulted in a 16% energy reduction. The kitchen area in the cafeteria example was primarily designed with conventional methods, so its energy use is assumed to be the same for both cases. 58 | Advanced Energy Design Guide for K-12 School Buildings Figure 4.1. Cafeteria building exterior views. © 2007 David Franzen Figure 4.2. Cafeteria interior view. Table 4.1. Waipahu Intermediate School Cafeteria Energy Saving Measures Description of Elements Tips Envelope Building Orientation Long east-west axis DL9 T-8s EL2 Lighting Lighting Systems Used Daylighting Window Design Clerestories with overhangs DL1–10 HVAC Natural cooling and ventilation EN22, HV32 SWH High-efficiency boiler WH1–6 Fully commissioned HV23, CX1–13 High-efficiency gas equipment AS2 System Controls Commissioning Additional Savings Kitchen Equipment Energy-Use Characteristics Baseline Electric Energy Use 14.0 kBtu/ft2⋅yr Simulated Electric Energy Use 11.7 kBtu/ft2⋅yr Photos and data are provided by the Hawaii Department of Business, Economic Development, and Tourism. Chapter 4—Case Studies | 59 Zone 2—Desert Edge High School Goodyear, Arizona Desert Edge High School, west of downtown Phoenix, was constructed in two phases for a total of 218,783 ft2 and a student capacity of 1600. Phase II was certified LEED Silver in 2006. The total build cost of the school was $21.3 million at an average of $97/ft2. Phase one was opened in time for the 2002–2003 school year, and phase two opened in time for the 2005–2006 school year. This climate zone 2 facility includes classrooms, administrative areas, a media center, a gymnasium, a 522-seat fine arts auditorium, a career technology area, and a student bookstore in the core. An in-school kiosk showcases many of the unique features of the high school through a virtual tour and the display of electricity, water, and carbon dioxide (CO2) savings. The kiosk also displays real-time animations of the heating and cooling systems, an interactive building directory, bus routes and schedules, real-time weather conditions, and more. Desert Edge is about 28% more energy efficient than other comparable high schools. The energy efficiency equates to roughly $58,000 in cost savings per year. The school showcases high-performance building strategies and features for a hot/dry climate zone, including an improved building envelope, daylighting, demand-controlled ventilation, and high-efficiency water-cooled chillers with a water-side economizer. The masonry walls include R-19 cavity insulation, and R-30 insulation is used on the built-up metal deck roof. The windows are high performance, low-e dual-paned glass windows with a U-factor of 0.33. The lighting system takes advantage of daylighting and uses a lowlighting power density to reduce the amount of artificial lighting. Lighting power density is 1.09 W/ft2 in classrooms and 1.04 W/ft2 in the gymnasium. Daylighting controls and occupancy sensors further reduce lighting loads. Multiple light switches are used to allow the teachers and students to light only the occupied space when daylighting is not sufficient. A high-efficiency central cooling and heating system uses two centrifugal chillers with a water-side economizer cycle and plate-and-frame heat exchanger. The water-based cooling towers include a chiller bypass to take advantage of indirect evaporative cooling possible in the dry climate. Classrooms have CO2 sensors that control outdoor air for the fan-coil units. Figure 4.3. Building exterior with window shading. 60 | Advanced Energy Design Guide for K-12 School Buildings Figure 4.4. Building exterior. (a) (b) Figure 4.5. (a) Centrifugal chiller and (b) cooling tower. Table 4.2. Desert Edge High School Energy Saving Measures Description of Elements Tips Envelope Building Orientation Long east-west axis DL9 Opaque Components Concrete block with R-19 insulation and R-30 built-up roof EN5 Vertical Glazing Low-e glass with a grey tint; assembled U-factor of 0.33 EN19–20 Lighting Lighting Systems Used T-8 lighting in most of the school with a lighting power density of 1.09 W/ft2 EL1–2, EL9–12 in classrooms, 1.04 W/ft2 in the gym, and 1.27 W/ft2 in the auditorium Controls Dual technology occupant sensors used in offices, administrative, and support areas; wall switch occupancy sensors are installed in small offices, storage, or other similar areas EL6, EL8 Window Design Low-e with double glazing and a third pane for integral microblinds DL1–4, DL9–12 Controls Daylight sensors used in conjunction with motion sensors DL13, DL17–18 HVAC central cooling and heating use high-efficiency centrifugal chillers with a hydronic economizer cycle with plate and frame heat exchanger and variable-speed pumps HV10 Daylighting HVAC Equipment System Controls Measurement and Verification DDC system with Web-based metering and feedback Temperature Control Individual room controls CO2 Sensors Installed in each zone of the building to for demand controlled ventilation Energy-Use Characteristics 28% better than ASHRAE Standard 90.1-1999 Photos and data are provided by Emc2 Group Architects Planners, Inc. Chapter 4—Case Studies | 61 Zone 3—Homewood Middle School Homewood, Alabama Homewood Middle School in climate zone 3 is a 190,000 ft2 facility with a capacity of 1000 students. The school consists of a classroom wing, an administration wing, and an activity wing. The cost to build the school was $23 million, or $121/ft2. Homewood opened in January 2005, replacing an old school on the same site that was originally built in 1955. When the time came to design the new building, the designers and school district worked together to create an energy-efficient, sustainable building. The result is a school that is 36% more energy efficient than ASHRAE Standard 90.1-1999. Daylighting is is used throughout the building as one of the primary strategies to achieve energy-efficiency goals. Ninety-five percent of the school utilizes daylighting, and all classrooms in the school have exterior windows. Shading devices, such as overhangs, are used on the south side of the school to reduce solar heat gain and glare in the school. Light shelves are used to project light deeper into the school. Windows on the north side of the school are large to increase the amount of indirect daylight in the school. Electrical lighting is controlled by photo sensors and occupancy sensors to make use of available daylighting and reduce electricity usage. Additional strategies include the following: • • • Mass walls are insulated with R-10 continuous insulation CO2 sensors in the gym control the local HVAC system A 9.8 EER central chiller VAV HVAC system utilizes air-side economizers Figure 4.6. Homewood Middle School. 62 | Advanced Energy Design Guide for K-12 School Buildings Figure 4.7. Building exterior with light shelves. (a) (b) Figure 4.8. (a) Large north-side windows and (b) school corridor. Table 4.3. Homewood Middle School Energy Saving Measures Description of Elements Tips Envelope Building Orientation Long east-west axis DL9 Opaque Components Mass walls R-10 c.i. EN5 Occupancy sensors and photocell dimmable control EL6, EL8 Daylighting in all classrooms, gym DL1–4 Equipment 9.8 EER chiller, VAV HV5 Cooling Tower Air cooled Lighting Controls Daylighting Window Design HVAC System Controls Measurement and Verification Yes Energy Use Characteristics 36% savings over ASHRAE Standard 90.1-1999 Measured Energy Cost 1.24 $/ft2⋅yr Measured Energy Use 64.4 kBtu/ft2⋅yr Years of Measured Data 2 years HV23 Chapter 4—Case Studies | 63 Zone 4—Knightdale High School Knightdale, North Carolina Knightdale High School in climate zone 4 is part of the Wake County School District. The 281,000 ft2 building was completed for the 2004–2005 school year at a project cost of $26.5 million, or about $95/ft2. The school was built for 1600 students and includes classrooms, offices, public assembly areas, a cafeteria, a gymnasium, athletic fields, and restrooms. The Triangle “J” High Performance Guidelines Version 1.0 guided the design and construction of this building. The building team committed to high-performance design from the beginning. The project was designed to use 58.7 kBtu/ft2, and after three years it is operating at 54.4 kBtu/ft2, annually. Clerestories provide daylighting in the main entry, the dining commons, and the media center. Additional daylighting is provided by skylights in the dining area and gym corridor. The classrooms in the three-story wing feature large windows to provide daylighting, exterior shading devices on the south-facing windows to control direct sunlight and reduce solar heat gain, dimmable and independently controlled lighting to control daylighting, and multiswitching modes for general classroom lighting. The building is heated and cooled with a four-pipe chilled- and hot-water system. Hot water is supplied by five high-efficiency condensing boilers, and the chilled water is supplied by standard-efficiency air-cooled chillers. Conditioned air is provided to the classrooms and administration areas with VAV AHUs through a VAV terminal box and hot-water reheat coil in each space. Relative humidity is monitored in the AHU return duct and controlled via AHU fan speed, cooling coils, and heating coils. The HVAC system is controlled through a DDC system. Figure 4.9. Knightdale High School. 64 | Advanced Energy Design Guide for K-12 School Buildings (b) (a) Figure 4.10. (a) Clerestory at main entrance and (b) classroom lighting system. Table 4.4. Knightdale High School Energy Saving Measures Description Tips Envelope Building Orientation North-south DL9 Opaque Components Roof/ceiling R-26; walls R-16 EN3, EN7 Vertical Glazing Door/window assemblies U = 0.81 EN13 Dimmable controls in classroom; separate general purpose lighting controls EL2, EL8 Large windows in three-story section DL1–DL4 Exterior light shading on south-facing windows DL12, DL20, DL22 Lighting Controls Daylighting Window Design Clerestories and skylights in common areas HVAC Equipment Standard chiller with variable-frequency drive pumps HV25 Boilers Condensing boilers HV26 Natural Ventilation VAV system with humidity-controlled cooling and reheat coils; air-handling units (AHUs) use variable-frequency drives and are outfitted with OA economizers for cooling with OA when possible HV5–6 SWH Natural gas-fired atmospheric water heater with storage tank, mixing valves and hot water recirculation pumps. SWH system is WH1–2 connected to a digital direct control system or scheduling of operation. System Controls Ventilation Direct digital control system; OA and CO2 intake is monitored for each AHU HV23 Additional Savings Exterior/Field/Parking Lot Lighting The sports field lighting fixtures are provided with internal louvers and hood visors to reduce glare and light trespass off of school property. EX1–2 Energy Use Characteristics Simulated Energy Use 58.7 kBtu/ft2⋅yr Measured Energy Use 54.4 kBtu/ft2⋅yr Years of Measured Data 3 years Photos and data are provided by the Boney Architects and Wake County Public Schools System. Chapter 4—Case Studies | 65 Zone 4—Third Creek Elementary School Statesville, North Carolina Third Creek Elementary School in Statesville is located in a suburban setting in climate zone 4. The 92,000 ft2 building was completed in July 2002 at a total project cost of $8.7 million, or $95/ft2 (land purchase excluded). This new construction project consolidated and replaced two aging schools. The finished school was the first K-12 school to earn a LEED v2.0 Gold Certification from the USGBC. Spaces include classrooms, offices, public assembly spaces, cafeteria, gymnasium, athletic field, and restrooms. The building team made a commitment to high-performance design from the beginning of the project. Examples are the gymnasium, stage, and dining room, which are located so they operate on separate systems for after-hours community use while the academic portion of the school is secured and not using energy. Energy demand was lowered though energy-efficient equipment and design, including extensive daylighting. Third Creek has an east-west axis orientation, with most classrooms facing either north or south. The southern façade has overhangs on the windows to shade from the summer sun. Each of the classrooms makes use of lightshelves to promote the dispersion of daylight. In addition to the lightshelves, reflective ceiling tiles were used to increase the effectiveness of daylighting. Also, in addition to the lighting systems employed within the school, Third Creek makes use of efficient exterior lighting. Energy modeling shows a reduction in annual energy costs of 25% over ASHRAE Standard 90.1-1999. After the first year of operation, energy reduction increased each year to a 33% reduction in 2005. Figure 4.11. Floorplan showing north- and south-facing classroom wings. 66 | Advanced Energy Design Guide for K-12 School Buildings © 2007 Sparks Productions. (a) (b) Figure 4.12. (a) Full exterior with view of main entrance and (b) classroom with internal light shelves. Table 4.5. Third Creek Elementary School Energy Saving Measures Description Tips Envelope Building Orientation Long east-west axis, classrooms facing north and south DL9 Opaque Components R-45 roof, R-22 walls EN3, EN7 Vertical Glazing Aluminum windows low-e; view glass 46% transmittance center of glass; light shelves glass; 70% transmittance center of glass EN24 Lighting Classroom T8 EL2 Controls Four levels of control per classroom EL8 Occupancy sensors EL6, DL13, L16–18 Overhangs on southern façade DL20 Interior light shelves in all classrooms DL22 Equipment High-efficiency water-source heat pumps w/ variable-frequency drives—14.5 EER; COP of 4.5 HV2 Boilers 97% thermal efficiency—condensing HV26 Cooling Tower 5 levels of control to match loads with minimal energy output Energy Recovery Ventilators Control humidity not to exceed 55% HV8–9 Measurement and Verification Direct digital control system HV23 Temperature Control Classroom by classroom basis Daylighting Window Design HVAC System Controls Additional Savings Computers ENERGY STAR AS2 Energy Use Characteristics Simulated Energy Use 59.6 kBtu/ft2⋅yr Measured Energy Use 59.8 kBtu/ft2⋅yr (purchased) Years of Measured Data 3 years Photos are provided by Spark Productions and data is provided by Moseley Architects. Chapter 4—Case Studies | 67 Zone 5—Bolingbrook High School Bolingbrook, Illinois Bolingbrook High School in Bolingbrook, Illinois, is located in a suburban setting in climate zone 5. The 569,000 ft2 building has a rated capacity of 3600. A master plan for the district included the new high school and renovations to two other high schools, one of which became a middle school. The total project cost for the new school was $96 million, or about $169/ft2. With a commitment to high-performance design, the building team registered the project with the USGBC. The educational planning concept of school-within-a-school was used in the design, with two academic houses in distinct wings and interior courtyards to maximize exterior views and daylight. In addition, the school incorporated a theatrical performance auditorium, a physical education gym, and a field house that is partially buried to reduce scale. Energy and environmental features include use or inclusion of the following: • • • • • • • A fully automated digital control system that allows for automatic control of HVAC systems turning on/off via a time schedule set according to the projected use of the different areas Fans that do not run unless scheduled and room thermostats that are digitally programmed between 68°F and 74°F so as to optimize energy savings Lights equipped with override switches that automatically turn on via a programmed schedule before school starts and automatically turn off after school Lights that are equipped with daylight harvesting sensors in the upper levels of the main concourse A condensate recovery system projected to save 360,000 gallons of water annually that collects and reuses water from the rooftop chillers Bio-swales to filter impurities from surface-water runoff A well-irrigation system for athletic fields and indigenous plantings Figure 4.13. Bolingbrook High School interior courtyard. 68 | Advanced Energy Design Guide for K-12 School Buildings (a) (b) (c) Figure 4.14. Daylighting and lighting views of (a) main corridor, (b) media center, and (c) cafeteria. Table 4.6. Bolingbrook High School Energy Saving Measures Description Tips Envelope Building Orientation Classrooms facing courtyards Opaque Components 2 in. rigid wall insulation in cavity with core insulation in CMU Vertical Glazing 1 in. insulated low-e glass EN19 Roofing System PVC membrane with white reflectance EN1 Lighting T-8 lamps in classrooms, metal halide in hallways EL2, EL5 Controls Automatic turnoff based on schedule with override capability in one-hour increments Hallways: light sensors to auto turn off when daylight is sufficient; Classrooms: two switches to allow for 33%, 67% and 100% lighting EL1–2, EL5, EL8, DL16–17 90% of occupied spaces have daylighting; controls on main corridor with clerestory DL1–4, DL16–17 Constant primary pumping and secondary VSD pumping HV5–6 Cx Full Cx included HV23 Temperature Control Individual classrooms Daylighting Window Design HVAC Pumps System Controls Additional Savings Exterior/Field/Parking Lot Lighting Metal halide cut-off with 0 ft candles at lot line EX1–2 Energy Use Characteristics Simulated Energy Use 86.6 kBtu/ft2⋅yr (from LEED submittal) Measured Energy Use 91.4 kBtu/ft2⋅yr Years of Measured Data 3 years (school operates 13 or more hours per day, 7 days per week) Photos and data are provided by Wight & Company. Chapter 4—Case Studies | 69 Zone 5—Whitman-Hanson Regional High School Whitman, Massachusetts Whitman-Hanson Regional High School in climate zone 5 is a 234,500 ft2 building designed for 1350 students. The total construction cost was $41 million, or $175/ft2. The school is a pilot project for the Massachusetts Green Schools Initiative, a partnership between the Massachusetts School Building Authority and the Massachusetts Technology Collaborative (MTC). Whitman-Hanson is 39% more efficient than ASHRAE Standard 90.1-1999. It makes use of daylighting, a well-insulated envelope, energy-efficient mechanical systems, a white roof, and energy-efficient appliances to reduce energy use. Natural light is used in the library, a two-story lecture hall, the classrooms, a performing arts center, and a double gymnasium to reduce the electrical lighting. The cafeteria is lit with natural light through skylights and daylight harvesting. Daylighting sensors are used in each classroom and the gymnasium to control electrical lighting, which comes from high-efficiency fluorescent fixtures, including pendant-mounted, direct/indirect lighting fixtures. The average lighting power density in the school is 1.15 W/ft2. The exterior walls are insulated with R-10 continuous insulation and 6 in. wall-cavity insulation. Under-slab insulation is used on the floors. The windows are highly insulated and low-e coated to reduce heat loss. They are designed to allow natural light to penetrate further into the building spaces. The HVAC system helps reduce energy use. Occupancy sensors are used throughout the building to provide adequate heating and cooling. Based on the occupancy, heating and air conditioning of each classroom is controlled by ventilation dampers and VAV boxes. A high-efficiency hybrid chiller is used. The primary base load chiller is a high-efficiency water-cooled chiller, and an air-cooled chiller provides additional capacity for peak periods. High-efficiency condensing boilers, demand-controlled ventilation with an energy recovery system, and variable-flow pumping are additional HVAC energy saving features. A 51-kW PV system on the roof supplies approximately 5% of the annual energy that is consumed and has become part of the students’ curriculum. The school uses the money it saves on energy to purchase high-tech (state of the art) educational aids, including interactive whiteboards and LCD projectors for all classrooms. Other teaching aids include a distance-learning center, cyber cafes, and instructional kiosks. Figure 4.15. Whitman-Hanson regional high school exterior. 70 | Advanced Energy Design Guide for K-12 School Buildings (b) (a) Figure 4.16. (a) Daylighted library and (b) classroom. Table 4.7. Whitman-Hanson Regional High School Energy Saving Measures Description of Elements Tips Envelope Building Orientation Long east-west axis DL9 Opaque Components—Exterior Walls R-10 c.i. plus 6 in. wall cavity insulation EN7 Opaque Components—Floors Under slab insulation EN10 Vertical Glazing Low-e EN19 Lighting Lighting System High-efficiency fluorescent fixtures including pendant-mounted direct-indirect lighting fixtures 2 EL1–2 LPD 1.15 W/ft average in the school EL9 Controls Photosensors in each classroom and the gymnasium DL17 Daylighting Window Design Highly insulated and low-e coated Natural Light Used in the library, two-story lecture hall, classrooms, performing arts center, and double DL36 gymnasium to reduce the use of electrical lighting Skylights Used in the cafeteria with daylight harvesting DL28 Equipment Water-cooled chiller for base load; air-based chiller used only for peaking HV25 Boilers High-efficiency condensing boiler HV26 Occupancy sensors control ventilation dampers and VAV boxes to adjust the heating and A/C in each classroom. HV5–6 51 kW PV system on the roof AS6 HVAC System Controls Temperature Control Additional Savings Renewable Energy Green Technology Cost Information Total Capital Cost 2.83% of the total cost Incremental Cost $4.85/ft2 Incentives Received $475,000 of the total $580,000 PV system from MTC Expected Payback (w/o Incentives) Nine years (excluding the solar electric generation) Expected Payback (w/Incentives) Almost immediate (incentives paid most of the initial cost for the green technology) Energy Use Characteristics 39% better than ASHRAE Standard 90.1-1999 Measured Energy Use 60.5 kBtu/ft2⋅yr (utility bills) MeasuredEnergy Cost 1.80 $/ft2⋅yr Years of Measured Data 3 years Chapter 4—Case Studies | 71 Zone 6—Westwood Elementary School Zimmerman, Minnesota Westwood Elementary School is located in a mixed suburban/rural setting in climate zone 6. The 75,000 ft2, two-story building has a current capacity of 500 students, and the core facilities have a capacity of 750 students. The school opened in the fall of 2004 and was built at a cost of $12 million, or $160/ft2. Spaces include classrooms, offices, public assembly areas, cafeteria, gymnasium, and athletic field. The school used LEED as the design guidance and was the first K-12 school in Minnesota and the fourth in the nation to earn LEED v2.1 certification. The building was oriented on the site to maximize solar and wind patterns. The highperformance design included increased insulation, daylighting, energy-efficient lighting with occupancy sensors, low-e glass to control heat gain and loss, displacement ventilation, energy-efficient gas kitchen equipment, and a condensing boiler for heating needs. Operable windows add to the energy-saving features and allow for passive ventilation. The building was designed to meet multiple community and school needs. The gymnasium, stage, and dining room are located strategically so they operate on separate systems after hours. In order to cut energy use and peak loads, Westwood uses energy recovery ventilators (ERVs). ERVs can recover as much as 80% of the energy from the exhaust airstream and transfer it to the supply airstream for heating and humidification in the winter months. The use of ERVs in the winter can cut humidification costs by up to 60%. The ERVs are used in the opposite manner for cooling in the summer months and transfer sensible and latent energy from the ventilation air to the exhaust airstream. The original design projected an energy use of 53.7 kBtu/ft 2 annually; however, the actual building operation has been modified from what was modeled due to year-round cooling. During the first three years of operation, the actual annual energy used to operate this building has been 75.9–84.0 kBtu/ft 2, with an average of 78.4 kBtu/ft 2. Figure 4.17. Westwood Elementary School aerial photo. 72 | Advanced Energy Design Guide for K-12 School Buildings Figure 4.18. Pulse condensing boiler. Table 4.8. Westwood Elementary School Energy Saving Measures Description Tips Envelope Building Orientation Long east-west orientation for classrooms DL9 Opaque Components Roof insulation: R-22 Wall insulation: R-18 EN3, EN7 Roofing 5-ply built up roof Vertical Glazing U-factor: 0.29 SHGC: 0.49 Visual transmittance: 0.69 EN19, Controls Occupancy and daylighting sensors EL6, DL17 Fixture Design 15% direct/85% indirect T5 pendent fixtures EL3 Equipment Fan-powered VAV w/displacement ventilation HV5–6 Boilers 94% efficiency HW condensing HV26 Cooling Air-cooled chiller (10.7 EER) HV25 Pumping Variable-frequency drives (VFDs) on hot-water and chilled-water loops. HV25–26 Window Design Operable for natural ventilation HV32 Energy Recovery Desiccant well HV9 SWH 94% efficient condensing (gas) WH1–2 Measurement and Verification Systems Cx HV23 Temperature Control Web-based building automation system (BAS) Demand-Controlled Ventilation Gymnasium and cafeteria AHUs Lighting HVAC System Controls Additional Savings Kitchen Equipment Energy-efficient equipment (gas) AS2 Energy Use Characteristics Simulated Code Base 113.7 kBtu/ft2⋅yr Simulated Design Model 53.7 kBtu/ft2⋅yr (original design—no summer operation) Measured Energy Use 78.4 kBtu/ft2⋅yr (actual operation) Years of Measured Data 3 years Photos and data are provided by Elk River Area School District ISD 728 and Johnson Controls. Chapter 4—Case Studies | 73 Zone 6—Alder Creek Middle School Truckee, California Alder Creek Middle School near Lake Tahoe is located in a rural setting in climate zone 6. The 87,000 ft2 building opened in 2004. The school was designed to serve 1000 students with an initial capacity of 700 students in sixth through eighth grades. The project was a CHPS demonstration school with a construction cost of $24 million ($30 million with contingency and soft costs), or $275/ft2. The school is a showcase of high-performance building strategies, including daylighting, energy efficiency, healthy IAQ, proper acoustics, building Cx, sustainable materials, waste reduction, preventive maintenance, site protection, and water conservation. The spaces in the school include classrooms, offices, public assembly spaces, cafeteria, gymnasium, athletic fields, and restrooms. Classroom light fixtures are 60% uplight and 40% downlight. The top row of windows is designed to provide daylight to the space. Ground-source heat pumps (GSHPs) operate with an energy savings of more than 51% compared to the typical four-pipe boiler chiller system previously installed. The school uses 288 wells that are drilled 300 ft deep beneath the soccer field. UPPER FLOOR LEGEND AD Administration AU Auditorium CC Covered Circulation CR Classroom E Electrical EC Enclosed Circulation G Gymnasium J Janitorial KT Kitchen L Lab/Learning Center M Mechanical MP Multipurpose Room P Portable Classroom PO Pull-Out Classroom S Storage T Toilets W Work Room Location of well field (288 wells approx. 315’ deep) ALDER CREEK MIDDLE SCHOOL Figure 4.19. Site plan showing geothermal well field location 74 | Advanced Energy Design Guide for K-12 School Buildings (b) (a) Figure 4.20. Alder Creek Middle School (a) classroom lighting system and (b) daylighted gym. Table 4.9. Alder Creek Middle School Energy Saving Measures Description Tips Envelope Building Orientation Long east-west axis DL9 Opaque Components Roof and walls R-19; cool roof EN1, EN3, EN7 Vertical Glazing Low-e EN19 Lighting Systems Used T5 direct/indirect in classrooms and offices; T5 HO in gym; T8 in all other areas EL2–3 Controls Sensor on row of lights near windows; Room occupancy sensors EL6 Window Design Low-e with dual glazing DL1–4 Controls Blinds inside windows act as light shelves DL12 Skylights Located in stairwells in classroom wing Lighting Daylighting HVAC Equipment GSHPs HV2 Boilers Backup and peak use only HV26 SWH Dedicated domestic boiler for hot water WH1–2 Measurement and Verification EMCS system used district wide HV23 Temperature Control Individual room controls with a 5° limit on user control CO2 Sensors Used in gym and cafeteria System Controls Additional Savings Computers Energy Star features enabled AS2 Exterior/Field/Parking Lot Lighting Metal halide lamps EX1–3 Energy Use Characteristics Simulated Energy Use 25% below Title 24 in California Measured Energy Use 54 kBtu/ft2⋅yr Years of Measured Data 2.75 years Photos and data are provided by the Tahoe Truckee Unified School District, CHPS case study, and Lionakis Beaumont Design Group, Inc. Chapter 4—Case Studies | 75 Zone 7—Silverthorne Elementary School Silverthorne, Colorado Silverthorne Elementary in Silverthorne, Colorado, is located in Summit County in climate zone 7. Silverthorne is a 62,500 ft2 building that houses 430 students ranging from K-5. The school opened in the fall of 2004. The build cost of the school was $9.3 million, or $148/ft2, which is in line with the typical cost of area schools. The building was designed by OZ Architecture of Denver in collaboration with BOORA of Portland Oregon. At an elevation of 9100 ft, the extreme climate was a factor in the design. By optimizing the building orientation, using daylighting to the fullest, increasing insulation levels, and using natural ventilation and economizers, the design team developed a design that will save the district $27,000 per year that would otherwise be spent on high utility bills. On warm days, outdoor air enters through the windows and rises to the top floor atria where it is vented by exhaust fans. When windows are closed, efficient mechanical ventilation is used. VAV air handlers deliver fresh air to the rooms and are regulated by CO2 sensors to ensure adequate ventilation. This design also keeps air-handler noise away from the classrooms, improving acoustics in learning areas. The design team’s goal was for daylighting to provide most of the light needed in classrooms, even on overcast days. In addition to ample windows, daylight is directed to illuminate the back wall of each classroom using light shafts. Daylighting controls in the classrooms and gyms control lights in response to the available daylighting. Figure 4.21. Interior view of skylights. 76 | Advanced Energy Design Guide for K-12 School Buildings (a) (b) Figure 4.22. (a) Silverthorne Elementary School exterior and (b) classroom lighting system. Table 4.10. Silverthorne Elementary School Energy Saving Measures Description Tips Envelope Building Orientation Long east-west axis DL9 Opaque Components 60 mil EPDM roof with R-30 polyiso insulation and R-19 wall insulation EN1, EN7 Vertical Glazing Clear double pane with spectrally selective low-e coating EN19 Lighting T-5 linear indirect classrooms and offices; high bay metal halide in gym EL3, EL5 Controls Occupancy sensors in all rooms and offices EL6 Daylighting Controls Automatic dimming and separate controls for each row of lights in classrooms EL8 Window Design Aluminum frame windows that are thermally broken DL1–4 Daylighting Design Light shelves on exterior southern exposure; clerestories for interior hallways; light shafts in back of every classroom; skylight spines along central circulation path, gym and admin offices (see photos) DL12 Equipment AHUs have VAV with reheat; cooling is by outdoor air economizer cycle HV6 Boilers Condensing boilers with 90+% efficiency HV26 Cooling Tower None Economizer Economizer cycle for all cooling HV13 Service Water Heating Solar preheat for domestic hot water WH1, WH3, WH5–6, AS7 System Controls HVAC controls include limiting outdoor air during unoccupied hours, optimum start/stop and outdoor air reset on heating hot water. HV21 Cx Partial commissioning HV23 OA Control Individual rooms with CO2 sensors Daylighting HVAC Additional Savings Computers Energy Star AS2 Renewable Energy Solar preheat for hot water AS7 Energy Use Characteristics Simulated Energy Use 76.7 kBtu/ft2⋅yr Measured Energy Use 88.0 kBtu/ft2⋅yr Years of Measured Data 2 years