Lateral Ignition and Flamespread Tests (LIFT) 1 When water enhancers, and to some extent foams were first introduced for firefighting in the wildland and interface environment, the primary objective was to prevent or slow ignition of vertical surfaces and to protect resources such as structures and seed or nesting trees. The time that it takes to ignite a piece of T1-11 siding using the LIFT apparatus and Forest Service protocols is one indication of the ability of a product (the combination of concentrate and water as prescribed by the manufacturer) to slow or prevent ignition, especially of a vertical surface. The LIFT test is used as a part of the evaluation for both foam and water enhancer products. Class A foams are typically used for wetting of fuels or to provide surface protection. The foams are tested using the LIFT test in two different ways. To evaluate effectiveness for surface protection, a 1.0-percent concentration of the product is applied to the T1-11 sample and immediately exposed to the heat source. To evaluate effectiveness for wetting and penetration, a 0.4-percent concentration of the product is applied to the T1-11 sample and allowed to soak and penetrate for 5 minutes prior and then exposed to the heat source. Water enhancers are typically used to provide surface protection and are evaluated using several mix ratios to span the approved range found on the Qualified Products List. All tests are performed by applying the product to the T1-11 sample and immediately exposed to the heat source. In all cases the time to ignition is measured and used to calculate the ignition reduction of the product at the specified mix ratio. The ignition reduction is a numeric value that compares the ignition time for water and the enhanced water mixture during the same test period. It is calculated as shown below: Ignition Reduction = Time to Ignition, mixed product Time to Ignition, water Products having different consistencies because of their basic make up, the concentration tested or the effect of water hardness and temperature. The water enhancer products currently in use are sensitive to the quality of the water used to prepare the mixed product. Hardness especially affects the consistency and ability of the product to remain on a vertical or uneven surface. In the field, the mix ratio and water quality, the condition of the wood surface, the weather, and fire intensity, and the characteristics of the product as well as the age and extent of the application of the enhanced water mixture or foam will impact the level of protection afforded by the product in an actual fire situation. Product Performance Data on next page 1 Standard Test Procedure 2.2 gives detailed instructions for the LIFT test. STP-2.2 is available at http://www.fs.fed.us/rm/fire/wfcs/tests/stp02_2.htm 4/27/12 Lateral Ignition and Flamespread Tests (LIFT) Water Enhancers Product Name (As Evaluated) Chemdal AquaShield 100 Barricade II Thermo-Gel 200L Thermo-Gel 500P Wildfire AFG Firewall II BioCentral Blazetamer 380 GelTech FireIce Phos-Chek Insul-8 Notes: Concentration Ignition Reduction 1 1.0% 0.4% 2.0% 1.0% 1.5% 1.0% 0.5% 1.2% 0.5% 3.0% 2.0% 1.0% 0.25% 0.65% 2.1% 1.4% 3.0% 1.5% 1.0% 0.37% 9.9 3.3 4.7 2.9 2.5 2.0 1.4 2.5 1.7 4.5 4.9 1.7 1.1 1.2 1.3 1.1 7.8 6.0 3.8 1.2 Time to Ignition, seconds Product Water Untreated 1179 ±74 368 ± 161 583 ± 235 327 ± 57 305 ± 39 224 ± 18 178 ± 26 311 ± 29 209 ± 72 495 ± 503 538 ± 707 190 ± 39 117 ± 18 128 ± 11 146 ± 46 125 ± 36 855 ± 209 663 ± 133 417 ± 121 132 ± 34 116 ± 23 112 ± 23 123 ± 24 112 ± 23 123 ± 24 112 ± 23 123 ± 24 123 ± 24 123 ± 24 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 110 ± 13 80 ± 22 80 ± 20 82 ± 26 80 ± 20 82 ± 26 80 ± 20 82 ± 26 82 ± 26 82 ± 26 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 75 ± 11 1 - Ignition Reduction = (Product, Ignition Time) / (Water, Ignition Time) 2 - Forest Service Protocol using T1-11 siding. All test mixtures were prepared with distilled water. 3 - Standard Test Procedure 2.2 gives instructions for the LIFT test. STP-2.2 is available at http://www.fs.fed.us/rm/fire/wfcs/tests/stp02_2.htm 4/2/12