600 843 RATED POWER WEIGHT (kg) 30kVA 200 40, 60kVA 234 1400 NOTES: 268 120kVA 302 150, 160kVA 336 80 NOTES: 1. 350mm MINIMUM CLEARANCE AT THE BACK OF UNIT IS REQUIRED TO PERMIT ADEQUATE CIRCULATION OF AIR AND ADVISABLY MORE THAN 500mm TO FACILITATE MAINTENANCE. 2. THE UNIT USES TOP CABLE ENTRY AND BOTTOM CABLE ENTRY. 3. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. 586 FRONT VIEW 90, 100kVA SIDE VIEW 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE 1400 645 800 100 145 476 445 TOP VIEW BOTTOM VIEW TM DIMENSIONAL DWG (30 - 160kVA) 600 843 RATED POWER WEIGHT (kg) 200kVA 380 NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 1600 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 80 NOTES: 1. 350mm MINIMUM CLEARANCE AT THE BACK OF UNIT IS REQUIRED TO PERMIT ADEQUATE CIRCULATION OF AIR AND ADVISABLY MORE THAN 500mm TO FACILITATE MAINTENANCE. 2. THE UNIT USES TOP CABLE ENTRY AND BOTTOM CABLE ENTRY. 3. ALL WIRING IS TO BE IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. 586 FRONT VIEW 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE SIDE VIEW 1400 645 800 100 145 476 445 TM TOP VIEW BOTTOM VIEW DIMENSIONAL DWG - 200kVA 600 843 NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 1400 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE SIDE VIEW 1400 678 800 100 145 75 FRONT VIEW 475 TOP VIEW (door open) BOTTOM VIEW DIMENSIONAL DWG - WITH CASTER TM NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. MAINTENANCE SWITCH 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE TM POWER SWITCH (NX 30K-B) NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE MAINTENANCE SWITCH TM POWER SWITCH (30kVA - 160kVA) NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE MAINTENANCE SWITCH TM POWER SWITCH - 200kVA bA bB bC NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. mA mB mC 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. mN 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE oA oB oC PE oN BAT+ BAT N BAT- RIGHT SIDE VIEW TM FRONT VIEW TERMINAL DETAILS (NX 30K-B) NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. BAT+ BAT N BAT- mA mB mC mN 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE PE oA bA bB bC oB oC oN TM TERMINAL DETAILS (30kVA - 160kVA) NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. mN mA mB mC 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. oN oA PE oB bA bB bC 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE oC TM TERMINAL DETAILS - 200kVA BY CLIENT BY EMERSON / PARTNER BY CLIENT NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. INPUT CIRCUIT BREAKER STATIC SWITCH RECTIFIER 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. OUTPUT CIRCUIT BREAKER INVERTER TO CRITICAL LOADS DISTRIBUTION PANEL TO EMERGENCY POWER DISTRIBUTION BOARD (WITH 100% GENSET BACK-UP) MAINTENANCE BYPASS SWITCH 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE CHARGER BCB BATTERY BY CLIENT BY EMERSON / PARTNER SINGLE LINE DIAGRAM BY CLIENT TM TO CRITICAL LOADS DISTRIBUTION PANEL NOTES: 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER BY CLIENT BY EMERSON / PARTNER CHARGER BCB RECTIFIER INVERTER BY CLIENT INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH BCB BATTERY CHARGER INVERTER RECTIFIER STATIC SWITCH MAINTENANCE BYPASS SWITCH 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. BY CLIENT BY EMERSON / PARTNER BY CLIENT INPUT CIRCUIT BREAKER INPUT CIRCUIT BREAKER 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. TO EMERGENCY POWER DISTRIBUTION BOARD (WITH 100% GENSET BACK-UP) SINGLE LINE DIAGRAM TM TO CRITICAL LOADS DISTRIBUTION PANEL NOTES: 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. BY EMERSON / PARTNER CHARGER 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER BY CLIENT RECTIFIER INVERTER BY CLIENT INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH BCB BATTERY CHARGER RECTIFIER INVERTER INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH BCB BATTERY CHARGER INVERTER RECTIFIER STATIC SWITCH MAINTENANCE BYPASS SWITCH BY CLIENT BY EMERSON / PARTNER BY CLIENT INPUT CIRCUIT BREAKER INPUT CIRCUIT BREAKER 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. TO EMERGENCY POWER DISTRIBUTION BOARD (WITH 100% GENSET BACK-UP) TM SINGLE LINE DIAGRAM NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. TO CRITICAL LOADS DISTRIBUTION PANEL BY EMERSON / PARTNER CHARGER 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER OUTPUT CIRCUIT BREAKER BY CLIENT RECTIFIER INVERTER BY CLIENT INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH CHARGER RECTIFIER INVERTER INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH BATTERY CHARGER BCB RECTIFIER INVERTER INPUT CIRCUIT BREAKER STATIC SWITCH MAINTENANCE BYPASS SWITCH BCB BATTERY CHARGER INVERTER RECTIFIER STATIC SWITCH MAINTENANCE BYPASS SWITCH 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. BY CLIENT BY EMERSON / PARTNER BY CLIENT INPUT CIRCUIT BREAKER INPUT CIRCUIT BREAKER 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. TO EMERGENCY POWER DISTRIBUTION BOARD (WITH 100% GENSET BACK-UP) TM SINGLE LINE DIAGRAM NOTES: 1. PER NEC 2011 STANDARD CHAPTER 6.13.40.(A) ELECTRONIC SENSITIVE EQUIPMENT SHALL NOT HAVE A VOLTAGE DROP OF 1.5%. UPS Model NXR 30kVA NXR 40kVA NXR 60kVA NXR 90kVA UPS Rating 30kVA / 30kW 40kVA / 40kW 60kVA / 60kW 90kVA / 90kW NXR 100kVA 100kVA / 90kW Input Breaker 70 A 90 A 150 A 200 A 200 A NXR 120kVA 120kVA / 120kW 300 A NXR 150kVA 150kVA / 150kW 350 A NXR 160kVA 160kVA / 144kW 350 A NXR 200kV A 200kV A/ 180kW 400 A Input Conductor Input Neutral Conductor Input Grounding Conductor Input Conduit (Diameter) Output Breaker 1 x 3C 2 x 1C 1 x 1C 32mm 60 A THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 1 x 1C 1 x 1C 1 x 1C 1 x 1C 1 x 1C 1 x 1C 1 x 1C 1 x 1C 40mm 40mm 65mm 65mm 65mm 80mm 80mm 90mm 80 A 125 A 175 A 175 A 200 A 300 A 350 A 200 A Output Neutral Conductor Output Grounding Conductor Output Conduit (Diameter) Allowable Cable run 1 x 3C 2 x 1C 1 x 1C 32mm 61m THHN Cu THHN Cu 1 x 3C 2 x 1C 1 x 1C 40mm 72m THHN Cu THHN Cu 1 x 3C 2 x 1C 1 x 1C 40mm 78m THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 1 x 3C 2 x 1C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu 2 x 3C 2 x 2C THHN Cu THHN Cu Output Conductor 1 x 1C 65mm 115m 1 x 1C 65mm 104m 1 x 1C 65mm 30m 1 x 1C 80mm 47m 1 x 1C 80mm 52m 1 x 1C 90mm 52m 2. INDICATED AMOUNT OF INCREASE IN CABLE RUN LISTED IN THE TABLE BELOW IS EQUIVALENT TO 0.10% INCREMENT IN VOLTAGE DROP. 3. CONDUCTORS ARE RATED AND SIZE FOR THHN COPPER CONDUCTOR AND TO BE FITTED IN POLYVINYL CONDUIT. 4. VOLTAGE DROP COMPUTATION ARE BASED ON ALTERNATING CURRENT RESISTANCE FOR UNCOATED COPPER WIRES AND REACTANCE BASED ON POLYVINYL CONDUIT. 5. GROUNDING WIRES ARE SIZE BASED ON THE MINIMUM EQUIPMENT GROUNDING CONDUCTOR OF NATIONAL ELECTRICAL CODE TM SIZES OF CABLE FOR LIEBERT NXR (30-200KVA)