S48-3000

Key Features n 3000 watt converter designed for -48V DC power applications n High conversion efficiency,

>98% n High MPP tracking efficiency, >99.5% n Proven DSP technology ensures ultra reliable system performance n Modular hot pluggable unit n Wide operating temperature window n Input & output protected against reverse polarity connection

The Solar Converter from Emerson Network Power brings reliability and high conversion efficiency to solar panel energy sources in telecommunications networks.

Description

The 3000 watt Solar Converter (S48-3000) from Emerson Network Power is designed to convert energy from solar panels into regulated -48VDC for telecom applications. The converter operates in MPPT (Maximum Power Point Tracking) mode, enabling maximum power extraction from the solar panels throughout the day.

The S48-3000 converter is used as an integral part of Emerson Network Power hybrid power systems for telecom applications.

Application

The Solar Converter provides energy from solar panels to telecom sites in the access and transmission network. Together with other energy sources (such as battery, diesel generator and wind turbine), the S48-3000 converter contributes to a reliable supply of energy. The high conversion efficiency and ability to accurately track the MPP (Maximum Power Point) will contribute to optimal utilization of the installed solar panel array.

2012.10

1

Solar Converter

Technical Specifications

DC Input

Input Voltage Range

Max Static Input Voltage

MPP Tracking Accuracy

58 to 150 VDC

165 VDC

99.5%

DC Output

Output Voltage Range

Output Power

Max Output Current

Temperature Derating

Efficiency

Psophometric Noise

Environmental

Temperature Range,

Operational

Relative Humidity

Audible Noise

Safety

Mechanics

Dimensions (H x W X D)

Weight

-48 to 58 VDC

3 kW

61 A

See diagram

> 98%

< 2 mV

-20 to +75 °C

≤ 95 %

≤ 50 dB

EN62109-1:2010 and EN50178:1997

3U x 1U x 292 mm

< 3 kg

Ordering Information

Catalog Number

S48-3000

Part Number

BMR 960 024/1

Description

3 kW MPPT solar converter

Diagrams

120

100

80

60

40

20

0

-40

Output Power vs. Temperature at Vin>Vout

55

65

70

-20 0 20 40 60 80

Ambient Temperature (C°)

100

Output voltage vs. Output current, max. output power 3000 W

50A 62A

30

20

10

0

70

60

50

40

0

10 15 20 25 30 35 40 45 50 55 60 65 70 75

Output Current (A)

EmersonNetworkPower.com/EnergySystems (North America)

EmersonNetworkPower.eu/EnergySystems (EMEA)

© Emerson Network Power Energy Systems North America 2012.

Business-Critical Continuity ™ , Emerson Network Power ™ , the Emerson Network Power logo, Emerson ® and Consider it Solved are service marks and trademarks of Emerson Electric Co.