UL LLC 333 Pfingsten Road Northbrook, IL 60062 2015-02-03

advertisement
UL LLC
333 Pfingsten Road
Northbrook, IL 60062
2015-02-03
U.S. Environmental Protection Agency (EPA) Seal and Insulate with ENERGY STAR ®
Insulation Product Certification Report – Type EnergyGuard™ Polyiso Insulated Sheathing
Board Insulation Manufactured by GAF
GAF
1 Campus Dr.
Parsippany, NJ 07054
US
Report Number:
4786793274
Subject:
EPA Seal and Insulate with ENERGY STAR Insulation Product Certification
Report: GAF EnergyGuard™ Polyiso Insulated Sheathing Board Insulation
PURPOSE:
The purpose of this report is to certify the test results for EnergyGuard™ Polyiso Insulated Sheathing
Board Insulation manufactured by GAF Shown herein have been compared to the criteria provided by
the Seal and Insulate with ENERGY STAR Insulation Definitions and Testing Requirements for
Residential Insulation Version 1.0 and the IBC, IRC, and IRCC codes relative to Surface Burning
Characteristics. This Report is intended for use by the EPA. UL is an EPA recognized certification
body.
CODES and STANDARDS:
The following codes and standards were referenced in the development of this report.
•
•
•
•
•
•
•
International Building Code (IBC) – 2012
International Residential Code (IRC) – 2012
International Energy Conservation Code (IECC) – 2012
ANSI/UL723, “Test for Surface Burning Characteristics of Building Materials" 10th Edition,
dated September 10, 2008
ASTM E84-12, “Standard Test Method for Surface Burning Characteristics of Building
Materials”
ASTM C518-10, “Standard Test Method for Steady-State Thermal Transmission Properties
by Means of the Heat Flow Meter Apparatus”
Seal and Insulate with ENERGY STAR Insulation Definitions and Testing Requirements for
Residential Insulation Version 1.0
DEFINITIONS:
Board Insulation: Semi-rigid insulation preformed into rectangular units having a degree of
suppleness particularly related to their geometrical dimensions. Typical materials include, but are not
limited to fiberglass, expanded polystyrene (EPS), extruded polystyrene (XPS), polyisocyanurate, or
polyurethane. The product may or may not be faced.
Facing: A thin covering adhered to the surface of insulation prior to field installation. Facings may
include, but are not limited to kraft paper, metal foil, or polymer.
R-value: The inverse of the time rate of heat flow through a body from one of its bounding surfaces to
the other surface for a unit temperature difference between the two surfaces, under steady state
conditions, per unit area. For the purposes of this program, Imperial units will only be accepted [(h · ft2
·°F)/Btu].
Smoke-Development Index: The characteristic of a material to emit smoke when exposed to flame or
fire compared to red oak and inorganic cement.
Flame-Spread Index: The characteristic of a material to resist the spreading of flames when exposed
to flame or fire compared to red oak and inorganic cement.
TEST LABORATORIES:
The laboratories that have conducted this testing were ISO 17025 accredited at the time of testing.
PRODUCT:
The products covered by this report consisted of polyisocyanurate.
The products are 0-15% by weight 1-1, -dichloro-1-flueoroethane, 0-2% by weight
chlorodifluoromethane, 0-10% by weight cyclopentane, 0-8% by weight tris (monochloropropyl)
phosphate and less than 25% by weight fibrous glass. The remaining components of this product
are non-hazardous or are in small enough quantity as to not meet regulatory thresholds for
disclosure. These components contain no substances or impurities which would influence the
classification of this product.
USE / PREPARATION / INSTALLATION:
EnergyGuard™ rigid foam insulation is intended for use as re-siding, vaulted ceilings, interior
basement walls, exterior masonry walls, interior stud walls, and exterior stud walls.
Installation Instructions attached as Appendix A, show detailed methods of application and finishing.
Also included are detailed installation instructions and diagrams that meet the criteria set forth in the
Seal and Insulate with ENERGY STAR Partnership Commitments.
THERMAL RESISTANCE:
Tests were conducted in accordance with ASTM C518-10, Standard Test Method for Steady-State
Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus. Aging of the sample
was in accordance with ASTM C1289.
The R-Value test results were calculated by ATI, covered in Evaluation Report CCRR-0197. The
values for this product are listed below:
Thickness
(inches)
0.5
R-Value
(˚F ft² h/BTU)
0.75
1.0
1.25
1.5
1.75
2.0
3.6
4.9
6.1
7.6
8.9
10.3
11.7
The minimum R-Values exceed the minimum R > 3.0 required by Energy Star. Test results can be
found in Appendix B.
The samples utilized in this investigation were neither prepared nor selected by an Underwriters
Laboratories' representative such that no verification of composition can be provided. The results
relate only to items tested.
SURFACE BURNING CHARACTERISTICS:
The tests were conducted in accordance with the latest version of Standard ANSI/UL 723, “Test for
Surface Burning Characteristics of Building Materials” (ASTM E84-12) at the time of testing. There
have been no substantive, technical changes made between the version at time of test and the 2012
version pertaining to reflective insulation.
The test determines the Surface Burning Characteristics of the material, specifically the flame spread
and smoke developed indices when exposed to fire.
GAF’s polyisocyanurate, including EnergyGuard™ Polyiso Insulated Sheathing Board Insulation have
been tested for Surface Burning Characteristics by UL LLC. A copy of the UL Surface Burning
Characteristics results are provided below.
Sample Description
2 inch thick Foam Core from EnergyGuard™
Polyiso Insulated Sheathing
Flame
Spread
Smoke
Developed
45
130
All of the products have a Flame Spread and Smoke Developed index rating of less than 75 and 450
respectively and complies with applicable code requirements for Surface Burning Characteristics.
CONCLUSION:
These products are certified to meet the requirements of the Seal and Insulate with ENERGY STAR
Definitions and Testing Requirements for Residential Insulation Version 1.0.
The Classification Marking of Underwriters Laboratories Inc. on the product is the only method
provided by Underwriters Laboratories Inc. to identify products which have been produced under its
Classification and Follow-Up Service.
Evaluated by,
Reviewed by,
Scott Knighton (Ext. 41967)
Project Handler
Fire Protection Division
James F Smith (Ext. 42666)
Staff Engineering Assoc
Fire Protection Division
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
Personal Protective Equipment (PPE):



Always use appropriate Personal Protective Equipment (PPE) for safety when
handling and installing EnergyGuard™ Polyiso Wall Sheathing such as safety
hardhat, eye wear, gloves, dusk masks, appropriate clothes and boots.
Installation of a wall sheathing system is a construction process. As with any
construction process, safety is a key element. All applicable safety standards and
good roofing practices must be followed.
Always comply with all OSHA safety standards, fire codes and local code
requirements.
Site Preparation:
General: No manufacturer trained or certified installer is required for the
installation of GAF EnergyGuard™ Polyiso Wall Sheathing.





Work shall only begin when the substrates have been prepared as necessary,
and are ready and acceptable to have materials installed as specified. Providing
a smooth, even, sound, clean and dry substrate minimizes the likelihood that
underlying deficiencies will cause premature deterioration or even failure of the
wall sheathing.
Sheathing should be properly stored and weighted to avoid weather and wind
damage.
Do not install materials during inclement weather, except for temporary work
necessary to protect materials that are already installed. Remove all temporary
work before installing permanent materials.
Do not install materials when moisture, in any form, is present within the material
or on the substrate to which the materials are to be applied. Remove and replace
any wet or damaged materials prior to the installation of GAF EnergyGuard™
Polyiso Wall Sheathing.
There are no requirements for re-entry or re-occupancy times.
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing Diagrams
Re-Siding
Vaulted Ceiling
(Flush mounted)
Interior Basement Wall
Exterior Masonry Wall
Exterior Stud Wall #1
Exterior Stud Wall #2
Vaulted Ceiling
(Between joists)
Interior Stud Wall
Exterior Stud Walls #3
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
o Framed stud walls (exterior & interior)
o Re-siding
o Exterior masonry walls
o Vaulted/ cathedral ceilings
o Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com.
Exterior Framed Stud Walls… General Application Instructions:




Before applying any boards, make sure to use code-accepted
shear and corner bracing, such as metal strapping, let-in
diagonal wood bracing or structural sheathing, such as OSB or
plywood.
Install EnergyGuard™ Polyiso Wall Sheathing boards so that the
longer edge is positioned vertically with the edges resting on
the middle of the stud. Make sure that the board joints are in
contact with each other, with the printed side facing the
exterior. Contact your local building code official for
requirements on horizontal bracing.
Fasten all boards using galvanized ring shank nails with a
minimum 3/8” (9.5 mm) diameter heads or staples with
minimum 1” (25 mm) diameter plastic caps. Fasteners must be
long enough to penetrate the substrate at least 3/4” (19 mm).
Fasten EnergyGuard™ Polyiso Wall Sheathing boards 12” (305
mm) o.c. around the perimeter and 16” (406 mm) o.c. in the
field or as required by local codes. Do not overdrive the
fasteners.





Seal all exterior openings and penetrations with all-weather
sealant, such as silicone caulk, prior to taping. Make sure all
areas are clean prior to sealing and taping to ensure proper
adhesion.
Center and apply 3” (76 mm) wide foil flashing tape to all
board joints, penetrations, window flanges and door edges.
Apply tape and sealant in accordance with the
manufacturer’s application instructions.
Always cover EnergyGuard™ Polyiso Wall Sheathing with a
code-approved exterior cladding system, such as vinyl
siding, wood siding, aluminum siding, brick, stucco, cover board, etc.
Cladding should be installed in accordance with the cladding system manufacturer’s
application instructions.
In areas of high humidity or as required by local code, install a vapor retarder.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
o Framed stud walls (exterior & interior)
o Re-siding
o Exterior masonry walls
o Vaulted/ cathedral ceilings
o Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com.
Interior Framed Stud Walls …General Application Instructions:




If batt insulation is to be installed between studs, install it prior to the application of
the EnergyGuard™ Polyiso Wall Sheathing boards.
Install EnergyGuard™ Polyiso Wall Sheathing boards to the
framed stud interior wall so that the longer edge is positioned
vertically, with the edges resting on the middle of the interior
stud. Make sure the board joints are in contact with each other,
with the printed side facing the interior. Fasten all boards using
galvanized ring shank nails with a minimum 3/8” (9.5 mm)
diameter heads or staples with minimum 1” (25 mm) diameter
plastic caps. Fasteners must be long enough to penetrate the
substrate at least 3/4” (19 mm).
Fasten EnergyGuard™ Polyiso Wall Sheathing boards 12” (305
mm) o.c. around the perimeter and 16” (406 mm) o.c. in the field
or as required by local codes. Do not overdrive the fasteners.
Seal all interior openings and penetrations with all-weather sealant, such as silicone
caulk, prior to taping. Make sure that all areas are clean prior to sealing and taping
to ensure proper adhesion.



Center and apply 3” (76 mm) wide foil flashing tape to all board joints, penetrations,
window flanges and door edges. Apply tape and sealant in accordance with the
manufacturer’s application instructions.
Gypsum boards should be installed in accordance with the gypsum board
manufacturer’s application instructions.
In areas of high humidity or as required by local code, install a vapor retarder.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
o Framed stud walls (exterior & interior)
o Re-siding
o Exterior masonry walls
o Vaulted/ cathedral ceilings
o Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com.
Exterior Masonry Walls… General Application Instructions:







Install EnergyGuard™ Polyiso Wall Sheathing boards between the concrete wall
and the exterior masonry system so that the longer edge is positioned
horizontally against the inner concrete wall.
Make sure the board joints are in contact with each
other, with the printed side facing the exterior.
Fasten all boards using appropriate masonry
mechanical fasteners or construction-grade
adhesive following the adhesive manufacturer’s
instructions.
Fasteners must be long enough to penetrate the
concrete wall at least 3/4” (19 mm). Do not
overdrive the fasteners.
Fasten EnergyGuard™ Polyiso Wall Sheathing boards 12” (305 mm) o.c. around
the perimeter and 16” (406 mm) o.c. in the field or as required by local codes.
Install masonry wall ties between board joints.
Seal all exterior openings and penetrations with all-weather sealant, such as
silicone caulk prior to taping.



Make sure all areas are clean prior to sealing and taping to ensure proper
adhesion.
Center and apply 3” (76 mm) wide foil flashing tape to all board joints,
penetrations, window flanges and door edges.
Apply tape and sealant in accordance with the manufacturer’s application
instructions.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
2. EnergyGuard™ Polyiso Wall Sheathing boards can be applied to most oil-base
waterproofing coatings. Refer to coating manufacturer’s instructions.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
 Framed stud walls (exterior & interior)
 Re-siding
 Exterior masonry walls
 Vaulted/ cathedral ceilings
 Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com.
Re-Siding…General Application Instructions:





Before applying any EnergyGuard™ Polyiso Wall Sheathing
boards, make sure to consult the siding manufacturer for
specific recommendations and application instructions.
Existing siding should be moisture free and in relatively good
condition. Replace or repair any rotted trim, siding or wood.
Remove any obstructions, such as shutter or downspouts,
prior to installing the new insulation board.
Install EnergyGuard™ Polyiso Wall Sheathing boards over the
existing siding so that the longer edge is positioned vertically,
with the edges resting on the middle of the stud. Make sure the board joints are
in contact with each other, with the printed side facing the exterior.
Fasten all boards using galvanized ring shank nails with a minimum 3/8” (9.5
mm) diameter heads or staples with minimum 1” (25 mm) diameter plastic caps.
Fasteners must be long enough to penetrate the studs at least 3/4” (19mm).
Fasten EnergyGuard™ Polyiso Wall Sheathing boards 12” (305 mm) o.c. around
the perimeter and 16” (406 mm) o.c. in the field or as required by local codes. Do
not overdrive the fasteners.





Seal all exterior openings and penetrations with all-weather sealant, such as
silicone caulk, prior to taping. Make sure all areas are clean prior to sealing and
taping to ensure proper adhesion.
Center and apply 3” (76 mm) wide foil flashing tape to all board joints,
penetrations, window flanges and door edges. Apply tape and sealant in
accordance with the manufacturer’s application instructions.
Always cover EnergyGuard™ Polyiso Wall Sheathing with a code-approved
exterior cladding system such as vinyl siding, wood siding, aluminum siding,
brick, stucco, cover board, etc. The new cladding should be installed in
accordance with the cladding system manufacturer’s application instructions.
Fasteners for the exterior cladding should be long enough to penetrate through
all the material layers into the structural substrate as required by the cladding
manufacturer.
In areas of high humidity or as required by local code, install a vapor retarder.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
From: Technical Services
March 10, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
 Framed stud walls (exterior & interior)
 Re-siding
 Exterior masonry walls
 Vaulted/ cathedral ceilings
 Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com
Vaulted/Cathedral Ceilings… General Application Instructions:





Cut the EnergyGuard™ Polyiso Wall Sheathing boards to fit snugly between the
roof rafters.
Install the boards between the bottom sides of the roof rafters making sure the
boards stop flush.
Run the boards continuously without gaps the
entire length of the vaulted ceiling, starting from
the top or bottom.
The thickness of the EnergyGuard™ Polyiso Wall
Sheathing boards should be such so that when
they are installed flush with the bottom of the roof
rafters, there is a continuous air space between the top of the Polyiso boards
and the bottom of the roof deck. This gap is to provide enough net-free
continuous air space from the soffit vents up to the ridge vent so it does not
restrict air flow. For proper ventilation requirements, refer to local building code
or roofing manufacturer’s guidelines.
Polyiso board joints are to be in contact with each other, with the printed side
facing the interior.




Seal all interior openings and penetrations with all-weather sealant, such as
silicone caulk, prior to taping. Make sure all areas are clean prior to sealing and
taping to ensure proper adhesion.
Center and apply 3” (76 mm) wide foil flashing tape to
all board joints, penetrations and skylight flanges. Apply
tape and sealant in accordance with the manufacturer’s
application instructions.
Always cover EnergyGuard™ Polyiso Wall Sheathing
with a code-approved interior cladding system, such as
½” (13 mm) gypsum board. The gypsum boards or other interior cladding system
should be installed in accordance with the appropriate manufacturer’s
application instructions.
In areas of high humidity or as required by local code, install a vapor retarder.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
From: Technical Services
March 25, 2014
GAF EnergyGuard™ Polyiso Wall Sheathing
GAF’s EnergyGuard Polyiso Wall Sheathing is intended to be installed on residential
construction only. Application types include:
o Framed stud walls (exterior & interior)
o Re-siding
o Exterior masonry walls
o Vaulted/cathedral ceilings
o Interior basement walls
The following are general application instructions. Be sure to review complete
instructions at www.gaf.com.
Interior Basement Walls… General Application Instructions:




Install EnergyGuard™ Polyiso Wall Sheathing boards to the interior side of the
basement masonry wall so that the longer edge is positioned vertically against
the field of the wall. Make sure the board joints are in contact with each other,
with the printed side facing the interior.
Seal all interior openings and penetrations with allweather sealant, such as silicone caulk, prior to
taping. Make sure all areas are clean prior to sealing
and taping to ensure proper adhesion.
Center and apply 3” (76 mm) wide foil flashing tape
to all board joints. Make sure all areas are clean
prior to taping to ensure proper adhesion.
Apply tape in accordance with the manufacturer’s
application instructions.
Installation with Wood Furring
 Spot fasten all boards to wall using construction-grade adhesive following the
adhesive manufacturer’s instructions.





Center and apply 3” (76 mm) wide foil flashing tape to all board joints. Make
sure all areas are clean prior to taping to ensure proper adhesion.
Apply tape in accordance with the manufacturer’s application instructions.
Install wood furring strips a maximum 16” (406mm) o.c. vertically over the
EnergyGuard™ Polyiso Wall Sheathing boards with appropriate masonry
mechanical fasteners.
Be sure to install furring strips over the vertical joints of the insulation boards.
Fasteners must be long enough to penetrate through the furring strip into the
concrete wall at least 3/4” (19mm). Do not overdrive the fasteners.
Installation with Conventional Stud Wall
 Spot fasten all EnergyGuard™ Polyiso Wall Sheathing boards to the masonry
basement wall using construction-grade adhesive following the adhesive
manufacturer’s instructions.
 Center and apply 3” (76 mm) wide foil flashing tape to all board joints. Make
sure all areas are clean prior to taping to ensure proper adhesion.
 Apply tape in accordance with the manufacturer’s application instructions.
 Construct a conventional stud wall that firmly applies pressure to the installed
EnergyGuard™ Polyiso Wall Sheathing boards.
 Install batt insulation in between studs as required by local codes.
 Always cover EnergyGuard™ Polyiso Wall Sheathing boards with a codeapproved interior cladding system such as ½” (13mm) gypsum board. Install
gypsum boards in accordance with the gypsum board manufacturer’s application
instructions.
 In areas of high humidity or as required by local code, install a vapor retarder.
NOTE:
1. The insulation boards must be separated from the interior of the building by an
approved thermal barrier in accordance with IBC Section 2603.4 or IRC Section
R316.4 as applicable. Contact your local building code official for requirements
on fire barriers. Do not leave boards exposed to the weather or near high heat
sources. In addition, the insulation shall not come into contact with hot objects.
2. EnergyGuard™ Polyiso Wall Sheathing boards can be applied to most oil-base
waterproofing coatings. Refer to coating manufacturer’s instructions.
For other types of application or further information, contact our Technical Services at
800-ROOF-411 (800-766-3411) or www.gaf.com.
Download