15.9874 QPoint™ User Advice This shower is fitted with a QPoint Filter Capsule to retain bacteria that may be present in the water supply x ✓ Keep an appropriate distance below the Filter Capsule when using the shower. Do not touch. x! Do not clean.* x Do not remove. *Where professional cleaning protocols are in place, the external surfaces of the filter capsule may be cleansed using a new disposable wipe and commonly available chrome compatible cleaning solutions. At no point should the filter capsule be disconnected during cleaning. Note the water filter installation and exchange date. Troubleshooting The Filter Capsule is leaking where it joins the Docking Station The Filter Capsule has been dropped on the floor. Can it still be used? Ensure that the o’ring seal on the Docking Station is in position and intact. Ensure that Filter Capsule is fully engaged in the Docking Station. To confirm engagement, try to rotate the Filter Capsule to the left after connection. It should not rotate if fully engaged. No, you will need to replace the Filter Capsule. The Filter Capsule does not disconnect from the Docking Station Ensure the release button on the Docking Station has been fully lifted. If disconnecting from a QPoint Docking Station - Shower Assembly with Quick Connect Inlet, the Docking Station will need to be held to avoid rotation. Grasp the Filter Capsule and rotate left to disengage. Water flow through the Filter Capsule is slow If the Filter Capsule has been disconnected, air may have entered and caused air locking which can significantly reduce the flow of water through the device. If this is the case, the Filter Capsule should be replaced with a new one. If the Filter Capsule has not been disconnected then it is possible that the reduction in water flow may be as a result of heavy contamination of the water supply with particles, rust or micro-organisms. This particulate contamination may be intermittent and/or related to maintenance or building work associated with the water system. The Filter Capsule should be replaced with a new one when the flow rate becomes unacceptable. If appropriate contact your local Pall representative or distributor for suitable pre-filtration advice. Upstream, non-filtered water samples are needed for water quality testing If a water sample is required for testing between Filter Capsule exchanges, remove the existing Filter Capsule and dispose of according to local procedures. To achieve water flow from the water outlet, disconnect the Docking Station. Collect the water sample(s) as per local guidelines. Immediately reconnect the Docking Station and install a new Filter Capsule. If I have a problem who should I contact? If you have a problem which you are unable to resolve, please see www.pall.com/medical, and/ or contact your local Pall representative, distributor or retailer to discuss and if appropriate to return product(s) for further investigation. Products for return must be placed in a re-sealable bag and returned following instructions given by your local Pall representative, distributor or retailer. The Filter Capsule has been replaced, but the water flow is still reduced Ensure that the Filter Capsule is fully engaged with the Docking Station. Flow rates through the Filter Capsule are dependent on water pressure. If your water pressure is less than 1 bar, the pressure may not be enough to achieve sufficient flow through the device. Please contact a plumber or local estates department to advise if the water pressure can be increased. Pall Corporate Headquarters 25 Harbor Park Drive Port Washington NY 11050 Pall International Sàrl Avenue de Tivoli 3 1700 Fribourg Switzerland Pall Filtration Pte Ltd. 1 Science Park Road, #05-09/15 East Wing, The Capricorn Singapore Science Park II, Singapore 117528 (866) 347-3428 phone pouwater.us@pall.com email +41 (0)26 350 53 00 phone LifeSciences.EU@pall.com email +65 6389 6500 phone sgcustomerservice@pall.com email © 2016 Pall Corporation. Pall, and QPoint are trademarks of Pall Corporation. ® indicates a trademark registered in the USA. TM indicates a common law trademark. Part numbers quoted are covered by the Copyright of Pall Corporation. 8/13, GN15.9874