Edco TCS-T1 Series Power Switching & Controls Business-Critical Continuity

advertisement
Power Switching & Controls
For Business-Critical ContinuityTM
Edco TCS-T1 Series
T1 Line Protection Against Damaging Transients
Protection of your vital T1 lines should be part of the overall power protection plan for your facility.
The T1 Series provides you state-of-the-art protection in a small package.
T1 lines need protection from direct and indirect lightning, as well as power disturbances from
nearby AC lines. The Edco TCS-T1 Series prevents T1 line disturbances by providing a level of
protection typically not provided by the telephone company.
The Edco TCS-T1 Series devices combine highly reliable, nondegrading Silicon Avalanche Diode
(SAD) technology, along with high energy gas tube protection. This technology combination leverages
the best aspects of each protection method in a single, reliable design to ensure optimal performance.
The Edco TCS-T1 Series features two models with different clamping voltages. Both the Edco TCS-T1S and
the Edco TCS-T1DS support in-line connections via hardwire lugs or standard RJ-45 ports.
Features
■
Uses bipolar Silicon Avalanche Diode to provide
nondegrading protection
■
Provides unparalleled performance in a
compact, modular design
■
Offers RJ or hardwire connection capabilities to
provide installation flexibility
General Technical Specifications
Comes complete with ring terminals
and a male/male RJ-45 cable to make
installation easy
Performance Technical Specifications
Enclosure Dimensions†
Inches
3H x 2W x 1.5D
Centimeters
7.6H x 5W x 3.8D
0.313 lb; 140 k
Weight
Silicon Avalanche Diode
Primary Technology
■
Hardwire or RJ-45
Interface
3' (0.9m) Male to Male Supplied
TCS-T1S
TCS-T1DS
Operating Frequency
Up to 55 MHz
Up to 55 MHz
Signal Line Voltage
Up to 170 Vpk
Up to 8 Vpk
Clamping Voltage
211 Vpk
13 Vpk
5 ns or less
5 ns or less
Peak Pulse Current*
40,000 Amp
40,000 Amp
Leak Capacitance
55 Picofarad
55 Picofarad
L1-Gnd – L3-Gnd
L2-Gnd –L4-Gnd
L1-L2 – L3-L4
L1-Gnd – L3-Gnd
L2-Gnd –L4-Gnd
L1-L2 – L3-L4
Pin 1-Gnd – Pin 4-Gnd
Pin 2-Gnd – Pin 5-Gnd
Pin 1-Pin 2 – Pin 4-Pin 5
Pin 1-Gnd – Pin 4-Gnd
Pin 2-Gnd – Pin 5-Gnd
Pin 1-Pin2 – Pin 4-Pin 5
Response Time
Protection Modes:
Hardwire:
RJ-48C Standard (RJ-45)
†
Does not include mounting tabs.
*Based on component specifications for all T1 lines.
Emerson Network Power.
The global leader in enabling
Business-Critical ContinuityTM.
AC Power
Connectivity
DC Power
Emerson Network Power Contact information
Embedded Computing
Embedded Power
Industrial Power
Infrastructure Management & Monitoring
Outside Plant
Power Switching & Controls
Thermal Management
Racks and Integrated Cabinets
Service
www.EmersonNetworkPower.com/Surge
Surge Protection
100 Emerson Parkway
Binghamton, NY 13905
T: (607) 721-8840 (Outside U.S.)
T: (800) 288-6169 (Inside U.S. & Canada Only)
F: (607) 722-8713
E: SurgeTech@Emerson.com
SL-60102 1/14 Rev. 2 Printed in USA
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power
logo are trademarks and service marks of Emerson Electric Co. ©2014 Emerson Electric Co.
Download