FTA550E XG Jockey Pump Controllers Model Number Selection Guide

advertisement
FTA550E XG Jockey Pump Controllers
Model Number Selection Guide
FTA550E XG JOCKEY PUMP CONTROLLERS
FTA550E-A A __ __ __ __ - __ (Example: FTA550E-AA015B-T-BY)
FTA NUMBER
FTA550E
OPTIONS & MODIFICATIONS
(See other side)
TIMER OPTION
-A
With Programmable
Running Period Timer
MOTOR CURRENT PROTECTION
-A
Circuit Breaker
*Suitable for Use as Service Equipment*
Short Circuit Current Rating
200-480V - 65kA
550-600V - 25kA
-F
Fusible Disconnect Switch w/ Fuses
*Suitable for Use as Service Equipment*
Short Circuit Current Rating
200-600V - 200kA (3-Phase)
110-240V - 5kA (1-Phase)
HORSEPOWER (KW)
014 - 1/4 HP (.18)
013 - 1/3 HP (.23)
012 - 1/2 HP (.37)
034 - 3/4 HP (.56)
001 - 1 HP (.75)
011 - 1 1/2 HP (1.1)
002 - 2 HP (1.5)
003 - 3 HP (2.2)
004 - 4 HP (3)
005 - 5 HP (3.7)
006 - 5 1/2 HP (4)
007 - 7 1/2 HP (5.5)
010 - 10 HP (7.5)
015 - 15 HP (11)
020 - 20 HP (15)
025 - 25 HP (19)
030 - 30 HP (22)
040 - 40 HP (29)
050 - 50 HP (37)
(See Voltage Selection for Maximum
HP/Voltage Combinations)
VOLTAGE 3-PHASE
(50/60 Hertz)
-H
-A
-F
-B
-C
200 - 208V
220 - 240V
380 - 415V WYE
440 - 480V WYE
550 - 600V WYE
VOLTAGE 1-PHASE *
(50/60 Hertz)
-D
-T
-E
110-120 Volts
200-208 Volts
220-240 Volts
MAX HP
25
30
40
50
50
MAX HP
5
15
15
* Single phase units supplied standard
with Fusible Disconnect Switch & Fuses
(Select Model FTA550E-AF....)
NOTE: For requirements not listed here please
contact a Firetrol representative or the
factory.
SPECIAL ENCLOSURES
-T
NEMA Type 3R (IEC IP22)
-E
NEMA Type 4 (IEC IP66)
-F
NEMA Type 4X (IEC IP66)
-FXP NEMA Type 4X (IEC IP66), #304 Stainless Steel,
Painted Finish
-FD
NEMA Type 4X (IEC IP66), #316 Stainless Steel,
Unfinished**
-FDB NEMA Type 4X (IEC IP66), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP NEMA Type 4X (IEC IP66), #316 Stainless Steel
Painted Finish
-G
NEMA Type 12 (IEC IP54)
** Unfinished (Not painted, polished or brushed)
-AC
HIGHER SHORT CIRCUIT CURRENT RATING
(See selection data sheet)
Fusible Disconnect Switch with Fuses (200kA)
-EF
ANTI-CONDENSATION SPACE HEATERS1
-H
120 Volt Space Heater
-J
120 Volt Space Heater With
Thermostat
-K
120 Volt Space Heater With
Humidistat
-L
240 Volt Space Heater
-M
240 Volt Space Heater With
Thermostat
-N
240 Volt Space Heater With
Humidistat
1
Power source supplied by others
PRESSURE TRANSDUCERS
-B
0-600 psi (0-42-25 bar) Pressure Transducer
for Fresh Water Service
-C
0-300 psi (0-21.1 bar) Pressure Transducer
for Corrosive Service
-D
0-600 psi (0-42.25 bar) Pressure Transducer
for Corrosive Service
MISCELLANEOUS
-AG
-AM
-AST
-AW
-BW
-BY
-CPL
-HV
-IEC
-IECI
-KH
-NZ
-OSP
-PE
-S
-SEI
-ZPA
-ZPJ
Contacts for Remote Indication,
Pump Run
Audible and Visible Low Reservoir alarm
Contacts for Remote Indication,
Failed to Start
Auto Start Contacts (for connection to
user supplied N.O. remote starting
device)
Contacts for Remote Indication,
Reservoir Low (Requires option -AG)
Contacts for Remote Indication,
Phase Failure/Reversal
Contacts for Remote Indication,
Pump Overload
Contacts for Remote Indication, System
Overpressure
Contacts for Remote Indication,
Switch Not in Auto
Audible Alarm
CE Marking with Externally Mounted Wet Parts
CE Marking (Internal Wet Parts)
Contacts for Remote Indication, Common
Output for Any Alarm
Interlock Input Contacts to Prevent Jockey
Pump from Starting During Main
Controller Operation
OSHPD Seismic Certification (State of California)
(Requires option -SEI)
Contacts for Remote Indication, Low Yystem
Pressure (Pump On Demand)
Tropicalization
Seismic Certification (in accordance
with IBC)
Customized, annual service display message
(when factory programmed or programmed by
Firetrol representative during start-up)
Communications, Serial Modbus over
RS485, 2 or 4 wire
*Export Packaging available for additional cost
NOTE: For requirements not listed here, please contact
your Firetrol representative or the factory.
Emerson Network Power - Global Headquarters
1050 Dearborn Drive
Columbus, OH 43085
Tel +1 614 888 0246
ASCO Power Technologies - Firetrol Brand Products
111 Corning Road, Suite 120
Cary, NC 27518
Tel +1 1 460 5200 … FaY +1 1 460 5250
EmersonNetworkPower.com
Firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, ASCO assumes no responsibility, and disclaims all liability, for damages resulting from use
of this information or for any errors or omissions. Information and specifications are subject to change without notice.
Emerson, Consider It Solved., Emerson Network Power, the Emerson Network Power Logo, ASCO, Firetrol and the Firetrol Logo are trademarks or registered trademarks of
Emerson Electric Co. All other names and logos referred to are trade names, trademarks, or registered trademarks of their respective owners. ©2013 Emerson Electric Co.
SD550E-01 (B)