Avtron K922A Resistive Medium Voltage Load Bank - 3000 to 7000 KW Testing Your Emergency Standby Generator with a Load Bank Means Reliability When it Matters Most. Key Features •High Capacity per Module •No Step-Down Transformer Required •Direct Connection to Medium Voltage Source •Reduced Installation Costs •Outdoor Construction •Vertical Air Discharge The Avtron Model K922A is a ultra high capacity resistive load bank used for testing medium voltage power sources. The Avtron K922A resistive load bank is ideal for testing medium voltage generators or turbines. Avtron is leading the industry by offering a true medium voltage load bank while others still supply a conventional step-down transformer and a low voltage load bank (typically 480 VAC). A medium voltage load bank eliminates the need for a costly step-down transformer, which reduces the overall package size and installation cost. The load bank is designed for permanent outdoor installation with vertical hot air discharge. Each load bank module is typically rated between 3 and 7 MW. Multiple modules are used when tens or hundreds of megawatts are required. Voltages from 5 KV to 15 KV class are available. The K922A load bank incorporates 4, 6, or 8 independent resistive stacks. Each resistive stack contains its own integral cooling fan. A medium voltage compartment houses the main input load bus connections as well as the medium voltage vacuum load step contactors. The operator controls are housed in a separate remote enclosure. The K922A is ideal for high power resistive loading of medium voltage generating systems in factory production lines or test cells. It is designed for permanent outdoor mounting. Superior Avtron quality combined with simple operation and maintenance will provide years of trouble free service. Avtron’s extensive line of Load Bank and Industrial Resis­tor Products are solid performers used throughout the world. For total technical support or additional information, please contact Avtron at (216) 573-7600 or LBsales@Emerson.com. Quality System Certified to ISO 9001 K922A 5000 KW Resistive Medium Voltage Avtron Load Bank. Avtron K922A Resistive Medium Voltage Permanent Load Bank - 3000 to 7000 KW Specifications subject to change without notice. Construction The load bank is fabricated from heavy gauge formed steel and welded structural steel, making a rigid, drip-proof structure suitable for permanent outdoor mounting. Cooling air for the resistive load elements is drawn in from the bottom and exhausted out the top. Weather-resistant exhaust hoods and welded intake screens provide maximum protection to the resistor cases and blower assemblies. Structural extension legs are provided for mounting the load bank at the proper field elevation. Protection Differential air pressure switches are provided for each blower. Overtemperature protection is provided via a thermal switch for each resistor stack. Should an air-loss or overtemperature condition occur, all load is automatically removed. Fuses and motor overload relays also protect the blowers. Load Capacity Ratings Total Load Voltage Load Step Resolution 3000-7000 KW per Module 5-15 KV class 250, 500, or 1000 KW typical. Bulk load also available. Load Bank Weight (approx.) 3000-5000 KW: 15,000 lbs. [6803.8 kg] 5500-7000 KW: 19,000 lbs. [8618.2 kg] Resistor Elements Options Avtron Helidyne™ load elements are helically wound from nickel chromium resistance alloy and are specially insulated for medium voltage. The elements are fully supported across their entire length with ceramic insulators on stainless steel support rods. •PLC Control •ADMS™ Digital Metering (V, A, KW, Hz) with Communicator EXT™ Data Logging Software •-40° F Arctic Design Control Power The K922A requires control power of 120 VAC, single phase, 60 Hz power (control transformer optional). EXHAUST HOODS The resistive load elements are air cooled by multiple integrally mounted blower motors. The blower motors are controlled by motor starter relays located within the load bank and feature a time delay starting sequence to reduce in-rush current. An external power source rated 460 VAC, 3 phase, 60 Hz is required to power the blowers. Motors rated 575 VAC, 60 Hz, 415 VAC, 50 Hz, or 380 VAC, 50 Hz are available as options. A rack-mounted control panel is provided for remote mounting. Controls include POWER ON-OFF switch, a POWER ON light, BLOWER ON-OFF push buttons with a BLOWER FAILURE light, OVERTEMPERATURE light, MASTER LOAD ON-OFF switch, and individual load step ON-OFF toggle switches which actuate the medium voltage vacuum contactors located within the load bank. PLC or computer based controls are also available as an option. 160.75 [4083.00] MAX. WITHOUT EXTENSION LEGS B14801 VTRON MANUFACTURING, INC. CLEVELAND, OHIO RESISTIVE LOAD BANK MODEL/ SYSTEM END ACCESS PANELS* *NOTE: ALL PANELS HAVE HINGED ACCESS WITH 1/4 TURN LATCHES & 3 HEAVY DUTY HINGES PER DOOR SN OPTIONS 190.75 [4845.00] MAX FAN CONDUIT AND P TUBING CARRIER LOW VOLTAGE CONTROL ENCLOSURE SCREENED INTAKE AIR (8 PLACES) 280.50 [7112.00] CENTER TO CENTER OF MOUNTING 294.00 [7468.00] REFERENCE CONCRETE PAD, PEDESTAL, OR STRUCTURE Emerson Network Power Avtron • 6255 Halle Drive, Cleveland, Ohio 44125, U.S.A. 216-573-7600 • FAX: 216-573-5953 • LBsales@Emerson.com EmersonNetworkPower.com/loadbank RESISTOR ASSEMBLY ACCESS PANELS* PANEL FOR VOLTAGE CONFIGURATION* Cooling Manual Controls STAINLESS STEEL EXHAUST SCREEN TYPICAL 8 PLACES LEG EXTENSIONS WITH STRUTS SHOWN (shipped loose) 88.50 [2248.00] CENTER TO CENTER OF MOUNTING 102.00 [2591.00] FANS NOT SHOWN ON THIS VIEW All dimensions are in inches [millimeters]. Emerson. Consider it Solved and Emerson Network Power are trademarks of Emerson Electric Co. or one of its affiliated companies. All the other marks are the property of their respective owners. Communicator EXT™ is a trademark of Electro Industries/GaugeTech. ADMS™ and Helidyne™ are trademarks of Avtron. SIGMA™ is a trademark of NJ Froment & Co. Ltd. Specifications subject to change without notice. ©2015 Emerson Network Power Bulletin 422• Rev. D