Comparison between PID and PSS effects on transient stability F. JURADO, A. CANO, M. ORTEGA Department of Electrical Engineering University of Jaén EUP Alfonso X, s/n. 23700. Linares (Jaén) SPAIN Abstract:- Transient stability is the ability of the power system to maintain synchronism when subjected to a severe transient disturbance. We examine the transient behavior of the generator by considering a torque perturbation about the operating point. The function of a PID controller is to add damping to the generator rotor oscillations. The power system stabilizer (PSS) uses auxiliary stabilizing signals to improve power system dynamic performance. Key-words:- AVR, exciter, damping. 1 Introduction For a simplified intuitive description of transient stability, a power system may be regarded as a set of synchronous machines and of loads interconnected through the transmission network. Under normal operating condition, all the system machines run at the synchronous speed. If a large disturbance occurs the machines start swinging with respect to each other, their motion being governed by differential equations. Transient stability of the generator is dependent on several factors. The generation excitation system maintains generator voltage and controls the reactive power flow. The sources of reactive power are generators, capacitors, and reactors. The primary means of generator reactive power control is the generator excitation control using automatic voltage regulator (AVR). The role of an AVR is to hold the terminal voltage magnitude of a synchronous generator at a specified level. In this paper, we examine the modeling issues arising from the use of the transient model for the generator in conjunction with a static network representation. The function of a PID controller is to add damping to the generator rotor oscillations and improve the dynamic response as well as to reduce or eliminate the steady-state error in AVR loop. The power system stabilizer (PSS) uses auxiliary stabilizing signals to control the excitation system so as to improve power system dynamic performance. Commonly used input signal to the PSS is shaft speed. 2 Transient stability Transient stability is the ability of the power system to maintain synchronism when subjected to a severe transient disturbance such as a fault on transmission facilities, loss of generation, a sudden increase in the mechanical power input, or loss of a large load [1,2]. The system response to such disturbances involves large excursions of generator rotor angles, power flows, bus voltages, and other system variables. Stability is influenced by the non-linear characteristic of the power systems. If the resulting angular separation between the machines in the system remains within certain bounds, the system maintains synchronism. Loss of synchronism because of transient stability, if it occurs, will usually be evident within 2 to 3 seconds of the initial disturbance. To study the stability of a generator connected to a very large or “infinite” system, the system may be modeled as an infinite bus, i.e., a constant voltage source with fixed frequency. This generator-line-infinite bus model is useful for initial stability studies of generation stations, and it is usually used to illustrate several of the stability issues described above when applied to power systems. Fig.2. Stable and unstable equilibrium points Fig.1. Generator-Infinite Bus Angle Stability The model depicted above is typically used to study this stability problem; all losses are neglected. The transmission system connecting the generator to the system is represented by an equivalent reactance XT . The generator is assumed to be a round rotor machine (saliency is usually neglected for this type of analysis), and is represented using the transient model, i.e., a constant voltage source E’ behind transient reactance X’d. The AVR is not considered, and the governor is assumed to deliver a fixed mechanical power to supply the demand of the system (infinite bus), i.e., Pm = P. Based on these models, the following set of equations may be used to study the stability of this system: dδ =ω dt dω 1 (P − Pe − Dω ) = dt M E 'V∞ Pe = sinδ X (1) where X = Xd’ +XT , and E’ is computed based on the initial reactive power demand Q of the system (power flow problem).The quantity Jω is called the inertia constant and is denoted by M. It is related to kinetic energy of the rotating masses, Wk. Wk = 1 2 1 Jω = Mω 2 2 (2) We now define the important quantity known as the H constant or per unit inertia constant. H= Wk SB (3) where SB is machine rating in MVA. The value of H ranges from 1 to 10 seconds, depending on the size and type of machine. We get, 2 H d 2δ = P( pu ) − Pe ( pu ) ω dt 2 (4) where P(pu) and Pe(pu) are the per unit mechanical power and electrical power, respectively. As long as there is a difference in angular velocity between the rotor and the resultant rotating air gap field, induction motor action will taken place between them, and a torque will be set up on the rotor tending to minimize the difference between the two angular velocities. This is called the damping torque. The damping power is approximately proportional to the speed deviation. Pd = D dδ dt (5) The damping coefficient D may be determined either from design data or by test. Additional damping torques are caused by the speed/torque characteristic of the prime mover and the load dynamic. The equilibrium points (δo,0) are given by Pe=P, i.e., the crossing points of the sinusoid Pe with P. This yields several equilibrium points, one s.e.p. (dP/dδ > 0) and two u.e.p.s (dP/dδ < 0). If a severe transient disturbance is applied to the system, the state variables (δ,ω) move away from the equilibrium point (δo,0). 3 Factors affecting transient stability From the above discussions we can conclude that transient stability of the generator is dependent on the following [3]: • How heavily the generator is loaded. • The generator output during the fault. This depends on the fault location and type. • The fault-clearing time. • The post-fault transmission system reactance. • The generator reactance. A lower reactance increases peak power and reduces initial rotor angle. • The generator inertia. The higher the inertia, the slower the rate of change in angle. This reduces the kinetic energy gained during fault; i.e., area Aa is reduced. • The generator internal voltage magnitude E’. This depends on the field excitation. • The infinite bus voltage magnitude V∞ . One of the most common controllers available commercially is the proportional-integralderivative controller (PID) [5,6,7]. The PID controller is used to improve the dynamic response as well as to reduce or eliminate the steady-state error. The derivative controller adds a finite zero to the open-loop plant transfer function and improves the transient response. The integral controller adds a pole at origin and increases the system type by one and reduces the steady-state error due to a step function to zero. The function of a PID controller is to add damping to the generator rotor oscillations and improve the dynamic response as well as to reduce or eliminate the steady-state error in AVR loop. As explained in [3], a PSS can be viewed as an additional block of a generator excitation control or AVR, added to improve the overall power system dynamic performance, especially to control power/frequency oscillations. Thus, the PSS uses auxiliary stabilizing signals such as shaft speed, terminal frequency and/or power to change the input signal to the AVR. This is a very effective method of enhancing small-signal stability performance on a power network. 4 Excitation systems The generation excitation system maintains generator voltage and controls the reactive power flow. The generator reactive powers are controlled by field excitation. The primary means of generator reactive power control is the generator excitation control using automatic voltage regulator (AVR). The role of an AVR is to hold the terminal voltage magnitude of a synchronous generator at a specified level. Fig.4. A typical block diagram of a PSS Fig.3. AVR system with PID controller Fig.3. AVR system with PID controller There are three basic blocks in a PSS, as illustrated in the typical block diagram of Fig. 4, namely, the Gain block, the Washout block and the Phase-compensation block [8,9,10]. The Phase-compensation block provides the appropriate phase-lead characteristic to compensate for the phase lag between the exciter input and the generator electrical (air-gap) torque; in practice, two or more first-order blocks may be used to achieve the desired phase compensation. The Washout block serves as a high-pass filter, where the time constant T3 is high enough to allow the signal associated with oscillations in rotor speed to pass unchanged; without the Washout block, the steady state changes would modify the terminal voltages. Finally, the stabilizer Gain block determines the amount of damping introduced by the PSS. In the current paper, a PSS with two Phase-Lead/Lags, a Washout block and a Gain block is used for controlling [4]. |Vt| 0.7 0.6 0 5 10 15 Time in sec 1500 delta 1000 500 0 8 9 10 11 12 Time in sec 13 14 15 Fig. 7. Plots for generator with PID, Si=1+0j, Tp =0.1 1.1 1 |Vt| In this paper, we examine using MATLABTM the transient behavior of the generator by considering a torque perturbation about the operating point. The generator-line-infinite bus model is used and the values of delivered complex power Si and torque perturbation about operating point Tp are subject to change in p.u. The characteristics of generator are: 18 kV 830MW. A PID and a PSS are added in the AVR system . 1 0.9 0.8 0.9 0.8 0.7 0.6 0 5 10 15 10 15 Time in sec 1.4 1.3 delta 5 Results 1.1 1.2 1.1 1 0 5 Time in sec Fig. 8. Plots Si=1+0j,Tp=0.1 1.1 |Vt| 1 for generator with PSS, 0.9 0.8 0.7 0.6 1.1 0 5 10 15 1 |Vt| Time in sec 1.5 0.9 0.8 delta 0.7 0.6 1 0 5 10 15 10 15 Time in sec 1.5 0.5 0 5 10 15 delta Time in sec Fig. 5. Plots for generator with PID, Si=0.8+0.6j, Tp =0.1 0.5 0 5 Time in sec Fig. 9. Plots for generator with PID, Si=0.8+0.6j, Tp =0.2 1.1 1 |Vt| 1 0.9 0.8 0.7 0.6 0 5 10 1.1 15 Tim e i n s e c |Vt| 1 0.8 0.9 0.8 0.75 0.7 delta 0.7 0.6 0 0.65 5 10 15 10 15 Time in sec 0.6 0.9 0.55 0 5 10 0.8 15 delta Tim e i n s e c 0.7 0.6 0.5 0 Fig. 6. Plots for Si=0.8+0.6j,Tp=0.1 generator with PSS, 5 Time in sec Fig. 10. Plots for generator Si=0.8+0.6j,Tp=0.2 with PSS, 6 Conclusion Methods of improving transient stability try to achieve reduction of the influence of the accelerating torque through control of excitation system. The results show a satisfactory transient response, however settling time is lower with PSS and damping is higher with PID. Power system is unstable with PID for delivered complex power Si with unity power factor. References [1] E. W. Kimbark, Power system stability, New York, IEEE Press, 1995. [2] M. Pavella, P.G. Murthy, Transient stability of power systems : theory and practice , 1st ed., John Wiley and Sons, 1995. [3] P.Kundur, Power System Stability and Control, McGraw-Hill, NY, 1994. [4] P. M. Anderson and A. A. Fouad, Power System Control and Stability, IEEE Press,1994. [5] K. J. Äström, T. Hägglund, Automatic Tuning of PID Controllers. Research Triangle Park: Instrument Society of America, 1988. [6] K. J. Äström, B. Wittenmark , Computercontrolled systems : theory and design, 2nd ed., Englewood Cliffs, Prentice Hall, 1990. [7] K. J. Äström, B. Wittenmark, Adaptive control, 2nd ed., Massachusetts, AddisonWesley,1995. [8] P. Kundur, M. Klein, G.J. Rogers, and M.S. Zywno, “Application of Power System Stabilizer for Enhancement of Overall System Stability,” IEEE Trans., vol. PWRS-4, pp. 614-626, May 1989. [9] IEEE Committee Report, “Dynamic Models for Steam and Hydro Turbines in Power System Studies,” IEEE Trans. vol. PAS-92, pp. 19041915, Nov/Dec. 1973. [10] EPRI Report EL-6627, “Long-Term Dynamic Simulation: Nuclear and Thermal Power Plant Models,” Final Report of Project 3144-01, prepared by Ontario Hydro and CRIEPI (Japan), Sep. 1992.