Code No: R31023 R10 Set No: 1 III B.Tech. I Semester Regular and Supplementary Examinations, December-2013 POWER SYSYTEMS-II (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions All Questions carry equal marks ** 1. a) What is the effect of unsymmetrical spacing of conductors in a 3-phase transmission line. b) Derive the formula for the internal inductance in H/m of a hollow conductor having inside radius r1 and outside radius r2 and also determine the expression for the inductance in H/m of a single - phase line consisting of the hollow conductors described above with conductors spaced a distance D apart. c) A three phase, 50 Hz, 110 kV, transmission line has flat horizontal spacing with 3.5m between adjacent conductors. The conductor diameter is 1.05 cm. Find the capacitance to neutral and the charging current per km of line. Assume full transposition. 2. a) What is the justification in neglecting line capacitance in short transmission lines? b) What is the purpose of an overhead transmission line? How are these lines classified? c) Find the A, B, C, D parameters of a 3-phase, 50 Hz transmission line with series impedance (20+j40) Ω and a shunt admittance of 4 x10-6 mho based on nominal-T method. 3. a) What do you understand by long transmission lines? How capacitance effects are taken into account in such lines? b) A 50 Hz transmission line 300 km long has a total series impedance of 40+j125 ohms and a total shunt admittance of 10-3 mho. The receiving-end load is 50Mw at 220kV with 0.8 lagging power factor. Find the sending-end voltage, current, power and power factor using approximation. 4. a) When the transmission line is terminated by the inducting load. How do you find the reflected voltage and current wave? b) A voltage having a crest value of 3000 kV is traveling on a 750 kV line. The protective level is 1700 kV and the surge impedance of the line is 300Ω. Calculate (i) the current in the line before reaching the arrester, (ii) current through the arrester, (iii) the value of arrester resistance for this condition and (iv) reflect voltage. Verify the reflection and refraction coefficient. 5. a) What is corona? What are the factors which affect corona? b) A certain 3-phase equilaterally spaced transmission line has a total corona loss of 53kW at 106kV and a loss of 98kW at 110.9 kV. What is the disruptive critical voltage between lines? What is the corona loss at 113 kV? 1 of 2 |''|'||||''|''||'|'| Code No: R31023 R10 Set No: 1 6. a) How many types of suspension insulators are used in transmission systems? Explain them. b) Why String efficiency for a d.c. system is 100%? Discuss. c) In a 33kV overhead line, there are three units in the string of insulators. If the capacitance between each insulator pin and earth is 11% of self-capacitance of each insulator, find (i) the distribution of voltage over 3 insulators and (ii) string efficiency. 7. a) How do elasticity and temperature affect the sag and tension of the conductor? Find out the expression of tension when both of them are taken into account. b) A transmission line has a span of 150 m between level supports. The conductor has a cross-sectional area of 2cm2. The tension in the conductor is 2000kg. If the specific gravity of the conductor material is 9.9 g/cm 3 and wind pressure is 1.5 kg/m length, calculate the sag. What is the vertical sag? 8. a) Explain the causes of low power factor I the power systems. b) A 3-phase overhead line has resistance and reactance per phase of 50Ω and 20 Ω respectively. The load at the receiving end is 25mw and 33kV and a p.f of 0.8 lag. Find the capacity of the synchronous condenser required for this load connection if it is connected at the receiving end and the line voltage at both ends are maintained at 33kV. ** 2 of 2 |''|'||||''|''||'|'| Code No: R31023 R10 Set No: 2 III B.Tech. I Semester Regular and Supplementary Examinations, December-2013 POWER SYSYTEMS-II (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions All Questions carry equal marks ** 1. a) What is bundled conductor? Where and why is it used? What is the GMR of a tour strand bundle. b) Find the inductance of line consisting two ACSR conductors spaced between conductors is 1.3m as shown in below Figure. The outer diameter of the single layer of aluminum strand is 45.2mm and the radius of each strand is 7.3mm. Assuming neglect the effect of the central strand of steel on inductance. 2. a) Why do we analyze a 3-phase transmission line on single phase basis? b) What is the effect of load power factor on regulation and efficiency of a transmission line? c) A single phase overhead transmission line delivers 1100kW at 33 kV at 0.8 p.f. lagging. The total resistance and inductive reactance of the line are 10Ω and 15Ω respectively. Determine: (i) sending end voltage (ii) sending end power factor (iii) transmission efficiency. 3. a) Using rigorous method, derive expressions for sending end voltage and current for a long transmission line. b) A three-phase, 50 Hz transmission line is 400km long. The voltage at the sending-end is 220kV. The line parameters are r =0.125 ohm/km, x = 0.4 ohm/km and y= 2.8x10 -6 mho/km. Find (i) the sending -end current and receiving-end voltage when there is no-load on the line.(ii) The maximum permissible line length if the receiving end no-load voltage is not to exceed 235kV. 1 of 2 |''|'||||''|''||'|'| Code No: R31023 R10 Set No: 2 4. a) Develop the differential equation for the transient in the transmission systems. How voltage and current expressions are establish from the above differential equation? b) Two stations are connected together by an underground cable having a surge impedance of 30 ohms joined to an overhead line with a surge impedance of 300 ohms. If a surge having a maximum value of 115 kV travels along the cable towards the junction with the overhead line, determine the value of the reflected and the transmitted wave of voltage and current at the junction. 5. a) Explain skin effect and Ferranti effect of transmission lines? b) A 3-phase, 220kV, 50 Hz transmission line consists of 1.5 cm radius conductor spaced 2 meters apart in equilateral triangular formation. If the temperature is 400c and atmospheric pressure is 76 cm, calculate the corona loss per km of the line. Take m0=0.85. 6. a) Explain various methods of improving string efficiency. b) An insulator string consists of three units, each having a safe working voltage of 15kV. The ratio of self-capacitance to shunt capacitance of each unit is 8:1. Find the maximum safe working voltage of the string. Also find the string efficiency. 7. a) What do you mean by sag on transmission line? Find out the expression of the sag of the transmission line. b) A transmission line has a span of 200 m between level supports. The conductors has across-sectional area of 1.29 cm 2,weighs 1170 kg/km and has a breaking stress of 4218 kg/cm2 .Calculate the sag for a safety factor of 5,allowing a wind pressure of 122kg per square meter of projected area. What is the vertical sag? 8. a) Explain the importance of voltage control in the modern power systems. b) A 3-phase, 50Hz, 400V motor develops 75 kw, the p.f being 0.75lag and efficiency 92%. A bank of capacitors is connected in delta across the supply terminals and p.f raised to 0.95 lag. Each of the capacitance units is built of 4 similar 100V capacitors. Determine the capacitance of each capacitor. ** |''|'||||''|''||'|'| Code No: R31023 2R10 of 2 Set No: 3 III B.Tech. I Semester Regular and Supplementary Examinations, December-2013 POWER SYSYTEMS-II (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions All Questions carry equal marks ** 1. a) Calculate the capacitance of a two wire line. If the conductors are spaced equally, How do you calculate the capacitance of a three -phase line? b) A 220 kV, three-phase bundle conductor line with two sub conductor per phase has a horizontal configuration as shown in below Figure. Find the inductance per phase, if the radius of each sub conductor is 1.35cm 2. a) What are the drawbacks of localized capacitance methods? b) Deduce an expression for voltage regulation of a short transmission line, giving the vector diagram. c) The following data refers to a 50 Hz, three-phase transmission line: length 15 km; sending-end voltage =11 kV; load delivered at receiving end 75 kW at 0.85 p.f. lag; resistance of each conductor = 0.3 ohms/ km; reactance per phase = 0.5 ohms/km. Find (i) receiving-end voltage, (ii) line current and (iii) efficiency of transmission. 3. a) Prove that the magnitude of the current in a transmission line increases exponentially from receiving end when the receiving end impedance equal to the characteristic impedance. b) The per-unit-length parameters of a 220kV, 450km, 50Hz, three phase long 6 transmission line are y j 3 2 10 mhos per km per phase and z = (0.2 + j 0.5) ohm/km. The line supplies a 175 MW load at unity power factor. Determine (i) the voltage regulation, (ii) the sending-end power and (iii) the efficiency of transmission by using rigorous method. 4. a) Explain the causes for transients on power system. b) A unit -step voltage surge is travelling on a long line of surge impedance Z1. It reaches the junction with a cable of finite length whose far end is open. The cable has a surge impedance of Z2 and time of one-way wave travel on it is T. Draw the Bewley lattice diagram and find from it the value of voltage at the junction at time 4T after the surge reaches the line-cable junction. Given Z1/Z2=9. |''|'||||''|''||'|'| Code No: R31023 1R10 of 2 Set No: 3 5. a) Describe the various methods for reducing corona effect in an overhead transmission line. b) A 3-phase, 132kV line with 1.956 cm dia. conductor is built so that corona takes place, if the line voltage exceeds 210kV (r.m.s.) . If the value of potential gradient at which ionization occurs can be taken as 30kV per cm, find the spacing between the conductors. 6. a) What is strain insulator and where is it used? Give a sketch to show its location. b) A string of 5 insulators is connected across a100kV line. If the capacitance of each disc to earth is 0.1 of the capacitance of the insulator, calculate (i) the distribution of voltage on the insulator discs and (ii) the string efficiency. 7. a) Deduce an approximate expression for sag in overhead lines when (i) supports are at equal levels (ii) supports are at unequal levels. b) A transmission line has a span of 214 meters between level supports. The conductors have across-sectional area of 3.225 cm2. Calculate the factor of safety under the following conditions: Vertical sag= 2.35 m; wind pressure = 1.5 kg/m run 2 Breaking stress = 2540 kg/cm ; Weight of conductor = 1.125 kg/m run 8. a) Describe the synchronous condenser method of voltage control for the transmission line. Illustrates your answer with a vector diagram. b) A 3-phase motor connected to 400V, 50Hz supply takes 31.7A at a p.f of 0.7lag. Calculates the capacitance required in parallel with the motor to raise the p.f 0.9 lag. ** 2 of 2 |''|'||||''|''||'|'| Code No: R31023 R10 Set No: 4 III B.Tech. I Semester Regular and Supplementary Examinations, December-2013 POWER SYSYTEMS-II (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions All Questions carry equal marks ** 1. a) What do you understand by the constants of an overhead transmission line? b) An overhead line 50 km in length is to be constructed of conductors 2.56 cm in diameter, for single-phase transmission. The line reactance must not exceed 31.4 ohms. Find the maximum permissible spacing. c) Find the capacitance of phase to neutral per km of a three-phase line having conductors of 2 cm diameter placed at the corners of a triangle with sides 5 m, 6 m, and 7 m respectively. Assume that the line is fully transposed and carries balanced load. 2. a) Why is leakage conductance negligible in overhead lines? What about underground system? b) Discuss the terms voltage regulation and efficiency as applied to transmission line. c) A 3-phase, 50 Hz, overhead transmission line delivers 10MW at 0.8p.f lagging and at 66kV.The resistance and inductive reactance of the line per phase are 10Ω and 20Ω respectively while capacitance admittance is 4x10-4 siemen. Calculate : (i) the sending end current (ii) sending end voltage( line to line) (iii) sending end power factor (iv) transmission efficiency. Assume nominal T method. 3. Deduce expression for the magnitudes of incident and reflected voltages at any point on a transmission line in terms of voltage and current at receiving end characteristic impedance and propagation constant of the line. Show how these expressions are useful in determining voltage and current distribution along the line? 4. a) Explain about the surge impedance and give its significance. b) A voltage pulse of magnitude E0 and length D travels on a transmission line of characteristics impedance Z c at speed γ. In the middle of the line it meets a series lumped inductance L. Find the expression for the voltage wave as a function of time that will be injected into the line on the other side of the inductance. Also sketch the voltage wave form. 1 of 2 |''|'||||''|''||'|'| Code No: R31023 R10 Set No: 4 5. a) What is skin effect? Why is it absent in the D.C system? b) A three phase 220KV 50Hz transmission line consists of 1.2cm radius conductor spaced 2 meters apart in equilateral triangular formation. Find the disruptive critical voltage between the lines, if the temperature is 200C and atmospheric pressure is 72.2cm. Take mo=0.96. Dielectric strength of air=21.1KV (rms)/cm. 6. a) How many types of suspension insulators are used in transmission systems? Explain them. b) Each line of a three phase system is suspended by a string of 4 similar insulators. If the voltage across the second unit is 15 kV and across the third unit is 27.0 KV, calculate the voltage between conductors and string efficiency. 7. a) Explain effect of wind and ice on sag of the conductor. b) A transmission line conductor at a river crossing is supported from two towers at heights of 50 and 70 meters above water level. The horizontal distance between the towers is 270m. If the tension in the conductor is 2000kg, find (i) the maximum clearance between the conductor and water, (ii) the clearance between the conductor and water at a point mid way between the towers. Weight of conductor is 0.75 kg/m. Assume that the conductor takes the shape of a parabola. 8. a) Discuss the on load tap changing transformer method of voltage control. Lis out its merits. b) A load of 10,000kW at a p.f of 0.8 lag is supplied by a 3-phase line whose voltage has to be maintained at 33kV at each end. If the line resistance and reactance per phase are 5Ω and 10 Ω respectively. Calculate the capacities of the synchronous condenser to be installed for the purpose comment on the results. ** 2 of 2 |''|'||||''|''||'|'|