2. SmartStruxure Lite Training

advertisement
SmartStruxure™ Lite Solution
Course SmartStruxure Lite Introduction
HOW ALL FITS TOGETHER
PPT ver. 1.1.0.0
IP/Ethernet network design
StruxureWare Building Expert (in
web browser)
Allows to configure and monitor
your deployment.
http
Monitor
Stand-alone deployment,
everything goes through
the monitor
(A monitor is needed if more then 1 MPM in the network
and if a network functionality is required)
LAN
Ethernet LAN
Passive nodes
BACnet points
collected by the
monitor
Cost effective solution for
small-to-medium buildings
Schneider Electric - SmartStruxure™ Lite solution Training
2
IP/Ethernet network design (cont’d)
Schneider Electric or third-party
BACnet Building Management
System (BMS)
Integration to BACnet system
No need for a monitor if all
nodes are connected through IP
LAN
BACnet IP /
BACnet Ethernet
Ethernet LAN
Passive nodes
Schneider Electric - SmartStruxure™ Lite solution Training
BACnet points
collected by
the BMS
directly
3
General network design
● Guidelines – network traffic only
● CANBus, Ethernet, ZigBee:
● Ratio of 24 passive nodes to 1 monitor node
BMS
Monitor
Monitor
Monitor
LAN
Ethernet LAN
or
CANbus
or
ZigBee
Up to 24 nodes
per group
Group A
Schneider Electric - SmartStruxure™ Lite solution Training
Group B
Group C
4
Network discovery
StruxureWare Building Expert
(in web browser)
Monitor
LAN
Monitor send a
heartbeat request
Ethernet
Schneider Electric - SmartStruxure™ Lite solution Training
By the network discover y
command and every 10
minutes
5
Network discovery (continued)
StruxureWare Building Expert
(in web browser)
The Monitor plays a significant role
both for monitoring and for
networking
Monitor
LAN
Remote
database
download
Ethernet
End-devices
Passive nodes
Schneider Electric - SmartStruxure™ Lite solution Training
6
Normal operation – COV based
StruxureWare Building Expert
(in web browser)
Monitor
LAN
Property Casts
sent on
change of
value (COV)
30 seconds by
default.
Ethernet
23.0 °C
22.8 °C
Passive nodes
Schneider Electric - SmartStruxure™ Lite solution Training
7
CANbus network design
● 120 Ohms resistors must be placed at both
termination points of the CANbus chain link.
● CANbus transfer rate is proportional to total
chain-link length.
BMS
● 125 Kbps: Up to 500 m
● 250 kbps: Up to 250 m (default setting)
● 500 kbps: Up to 100 m
● Must be the same speed configuration for all
MPMs
LAN
Monitor
Schneider Electric - SmartStruxure™ Lite solution Training
passive nodes
8
ZigBee concepts
● ZigBee coordinator is a device that sets up the network, is aware of all
the nodes within its network. Every ZigBee network must contain a
network coordinator.
● ZigBee router can act as an intermediate router, passing on data from
other devices.
End-devices
BMS
LAN
Monitor
Router nodes
Schneider Electric - SmartStruxure™ Lite solution Training
Coordinator
9
ZigBee network design – best practices
Building Expert
BMS
● Route redundancy
● Ideally no more than 5 wireless hops
● Example respecting guidelines
LAN
Router / Passive nodes
Site Monitor
Coordinator
Schneider Electric - SmartStruxure™ Lite solution Training
10
BAD wireless network design
Building Expert
BMS
● No Route redundancy
● Example not respecting guidelines
LAN
Coordinator
Monitor
Schneider Electric - SmartStruxure™ Lite solution Training
Passive nodes
Passive nodes
& Routers
& Routers
11
Using multiple network technology
● Possible if the Monitor is the originating
point of each technology segment.
Web browser
BMS
Passive nodes
Caution!
This is a theoretical
and principal schematic.
LAN
Ethernet
Passive nodes
CANBus
ZigBee
Passive nodes
Monitor
Coordinator
Schneider Electric - SmartStruxure™ Lite solution Training
12
Other
Get started
Application package
Schneider Electric - SmartStruxure™ Lite solution Training
14
Schneider Electric - SmartStruxure™ Lite solution Training
15
Uses cases
Schools
Hotels
School Needs
SmartStruxure™ Lite answers
Water based heating systems
Proven solution
● Perimeter heating with radiators
● Perimeter heating with fan coils
● Smart wireless actuator
● Wireless room and terminal controllers
School schedules
Wireless retrofit during school days
● Can’t disturb classes
● Can’t afford overtime pay
● Limit wiring to a minimum
● Limit invasiveness and disturbance
Out-buildings
Bring them in wirelessly with ZigBee
Hazards in the walls
Avoid renovation, repair & repaint work
● Dust or asbestos fears
● Keep parents and administrators happy
Tight budget
StruxureWare™ Building Expert
● Fixed costs of front-end, servers
and gateways limiting the ROI?
● No license fee! Low fixed costs!
● Scalable to StruxureWare™ Building
Operation, BACnet, EcoStruxure Web
Services, oBIX
Schneider Electric - SmartStruxure™ Lite solution Training
17
Perimeter heating school retrofit job
Problem
Boiler
● Single loop perimeter heating
● Comfort & energy cost issues
Objectives
● Add zone & remote control
● With a short payback
Solution
● Managers
●
●
●
●
Network throughout the building
Control actuators
Receive data from sensors
Host Building Expert over the LAN
LAN
● Smart wireless actuators
● EnOcean T° sensors
● Management via Building Expert
Schneider Electric - SmartStruxure™ Lite solution Training
18
Unit ventilator/fan coil school retrofit job
Building Expert
Network to other zones
LAN
Wireless manager
(one unit can manage many zones)
Light relay
with dimming
Swap old
stat with
SE7000
Light sensor
and light switch
Unit ventilator
or fan coil
If there are no old stats or
existing wiring isn’t usable,
inside
Schneiderplace
Electric -SEC-TE
SmartStruxure™
Lite unit
solution Training
19
Out-buildings & school trailers
Schools run out of space and use out-buildings to fill gap
● Integrating these buildings into an automation system is difficult & costly
● SmartStruxure™ Lite can integrate them easily and at a low cost
● Manage multiple buildings from StruxureWare Building Expert or use larger
systems
internet
StruxureWare™
Building Expert
EcoStruxure
WebService
internet
Up to 300 m line of sight
Schneider Electric - SmartStruxure™ Lite solution Training
20
Use case: simple & complete automation
Objectives: happy guests & bottom line
● Control heating and cooling costs
Room 205
SE7000
● Get your guests in the comfort zone
Room 204
● Remote management for more efficiency
FC, HP
Solution
● SE7000 to control HVAC in each room
Room 207
Room 206
Room 209
Room 208
● Embedded PIR motion sensor (optional) sets
temperature for occupied/unoccupied mode
● Guests can adjust setpoints for comfort
● Networking and integration performed by
MPM devices each handling several zones
● Management can set high and low limits
according to schedules
MPM-GW
Room 211
Room 210
● Management can put rooms into vacant mode
for maximum energy savings
Schneider Electric - SmartStruxure™ Lite solution Training
21
Use case: simple & complete automation
Solution (cont’d)
● Management via StruxureWare™
Building Expert
● Can import hotel floorplans and define
custom zones with color codes for
user-friendly visualizations
Scale over time with wireless
● Easily add points with EnOcean and
ZigBee
Room 205
● Lighting control
● Additional sensors
● Other applications
● Can integrate wireless keycard reader
to set occupied/unoccupied mode
Schneider Electric - SmartStruxure™ Lite solution Training
Light relay
Keycard reader
22
Use case: comfort, efficency & branding
Create loyalty with your brand
Customizable cover, color,
language and screensaver
my
Hotel
Or integration via
MPM devices
Direct integration to
BACnet
LAN
Swap old stat
with SE8000
StruxureWare Building
Expert for small hotels and
motels. Integrate to other
systems for larger buildings.
PIR motion
sensor included
Fan coil, heat pump
or other system
Use relay pack
for high voltage
fan coils
Schneider Electric - SmartStruxure™ Lite solution Training
23
Example scenario 1
● Small retail outlet
● 4 zones - HVAC
● Monitoring only
Example scenario 1
● A few SE7000
● One MPM connected to the LAN
● Management with StruxureWare
Building Expert
LAN
Example scenario 2
● Small retail outlet
● 5 zones - Lighting
● Monitoring and Override
Example scenario 2
● Two MPM-GW communicating via ZigBee
● Control of multiple EnOcean switches and relays
● Management with Building Expert
ZigBee Coordinator
Site Monitor
Connected to LAN
LAN
ZigBee Router
Passive
Example scenario 3
●
●
●
●
Small retail outlet
5 zones - Lighting
Monitoring and Override
Energy Metering
Example scenario 3
● Add MPM-UN with Modbus
to connect power meter
ZigBee Router
Passive
ZigBee Router
Passive
Modbus power meter
ZigBee Coordinator
Site Monitor
Connected to LAN
LAN
Room 101
Application:
Hotel room,
Dorm room,
Old age unit
or
Hospital room
Door
Sensor
Thermostat
Fancoil
Unit
Window
Sensor
Floor / Hotel
Controller
Automation
Server
SmartStruxure
Entreprise Server
Web-pages for
simple monitoring
& control
SmartStruxure
Building Operation
SmartStruxure Lite
Monitoring & Control Solution
Schneider Electric - SmartStruxure™ Lite solution Training
or
SmartStruxure Solution
Full Building Management System
30
VAV applications
Aggregation &
management
Use VAV managers
● Each unit has:
Building
Expert
● Pressure sensor
● Actuator (optional)
● Wireless networking
● Makes installation
faster and easier
Terminal controllers
(if direct control of
RTUs is needed)
MPM device
● Building Expert
● Has a PID loop
object to help
manage VAVs.
● Programming is
stored locally on
each VAV manager
for redundancy.
HVAC
RTU or other
HVAC equipment
Zoning
VAV managers
(MPM-VA)
VAV
boxes
Schneider Electric - SmartStruxure™ Lite solution Training
If required
Additional wired and
wireless sensors for
T°, H%, motion,
CO2, etc.
Each VAV manager has:
• Embedded pressure sensor
• 6 inputs and 6 outputs
• EnOcean wireless I/O
• Support for ZigBee peripherals
31
Metering and Sub-metering
Metering
For electrical, gas & water metering
● Multi-purpose managers can integrate
Modbus, EnOcean and ZigBee
metering and pulse-counting devices
● Building Expert has objects to facilitate
the integration of select Schneider
Electric and Veris products. Currently,
these products are:
● ION6200
● PM750
● Veris E5 series
● Veris H803 series
● iEM3250/5
● PM3250/5
● Data can be:
● Viewed in Building Expert
● Integrated into larger iBMS
● Exported over FTP
Schneider Electric - SmartStruxure™ Lite solution Training
Building
Expert
Pulse counting
and smart plugs
You can network
to reach metering
points separated
by long distances
MPM-UN can integrate
various devices using
Modbus, EnOcean and
ZigBee protocols
MPM-UN
Other
Modbus
meters.
Schneider Electric and
Veris meters with objects
in Building Expert to
facilitate their integration.
Terminal
controllers can
be used for fast
pulse counting
32
Basic and advanced lighting
Office single load, common
areas and outdoor lighting
Basic lighting
Daylight harvesting
Building
Expert
Wired and/or wireless
lighting control
● For wired and wireless
control, use the MPM-UN
● For wireless control only,
use the MPM-GW
Building Expert and
EnOcean
MPM-GW
MPM-UN
Connection to
Modbus lighting
panel or wired
contacts
● Objects to facilitate the
integration of light switches
and relays already exist.
● New objects are coming up
for the following sensors:
motion, light (lux), door
contact and window contact
Light
sensor
Relay
Occupancy
sensor
Switch
Schneider Electric - SmartStruxure™ Lite solution Training
Dimming
relay
Relays for
motorized
blinds & smart
windows
33
StruxureWare™ Building Expert
● StruxureWare Building Expert is a complete building automation IP
interface available from any internet connection.
● The Web server is active on every Manager (MPM).
● No license, no software to install
● Used to monitor and commission your network
● Supported browser: Firefox ESR
● From version 2.7 are the most
common browsers supported
● Local port : 80
Schneider Electric - SmartStruxure™ Lite solution Training
34
Resources for you
● Product Support Services (PPS) – After an approved certification test
● The Schneider Electric Exchange Download Center
● (https://buildingsdownloads.schneider-electric.com)
● Documentation.SmartStruxureLite.com
● Still valid but the above download center is the recommended solution
Schneider Electric - SmartStruxure™ Lite solution Training
35
End
Download