Universal Interrupted Electronic Oil Primary R7184U Training Module What you will learn • R7184U Product Overview • Key Features and Benefits • Installation and Set Up • Troubleshooting • Product Cross Reference • R7184U Oil Primary Advantages HONEYWELL - CONFIDENTIAL 2 R7184U Interrupted Electronic Oil Primary • What is the R7184U? - It is a line voltage, safety rated, primary control for residential oil fired burners used in boilers, forced air furnaces and water heaters. Applicable for use with both hydronic and forced air systems. - Used with a cad cell flame sensor, operates an oil burner and optional oil valve. HONEYWELL - CONFIDENTIAL 3 Universal Oil Primary Part Numbers: R7184U1004 R7184U1012 R7184U1020 R7184U Key Features • Universal compatibility - This control replaces Carlin, White Rodgers and all prior Honeywell Oil Primary Controls • EnviraCOMTM communications enabled: - Includes EnviraCOM™ Connection for local networking & diagnostics - Compatible with the Honeywell EnviraLINK™ remote monitoring application, which enables dealers to monitor their customers systems remotely. HONEYWELL - CONFIDENTIAL 4 R7184U Key Features • Diagnostic LED - Indicator light monitors burner flame status and system lockout • The versatile R7184U includes these “Exclusive Features”: - Pump priming cycle - Cad cell flame strength indicator - Limited recycle • Extended Service Life (Control and Application) HONEYWELL - CONFIDENTIAL 5 Additional R7184U Features •Available in 15-, 30-, and 45-second lockout times R7184U1004 = 15 second lockout R7184U1012 = 30 second lockout R7184U1020 = 45 second lockout • Optional valve-on delay, blower-off delay models: - Models: 15 seconds, or selectable 0 or 15 second valve-on delay • Zero time or selectable 0-, 2-, 4-, 6-minute blower-off delay • Safe start check – check for flame presence prior to lighting the burner • Compatible with power venters without integral timers • Oil-resistant plastic cover for electronics HONEYWELL - CONFIDENTIAL 6 R7184U Feature Function Benefit FEATURE FUNCTION Pump Purge Temporary setting of safety timing to 4 minutes Allows installer to purge oil lines without remaining at oil primary CAD Cell Resistance Readout Flash CAD resistance range while burner is running Allows installer to check that flame strength is adequate prior to leaving job site Limited Recycle Limits recycle to 3 per any one call for heat Detects running saturation or poor combustion from partially clogged nozzle and locks out to prevent heat exchanger clogging or oil flooding Limited Reset Limits resets to 3 during any single call for heat Prevents homeowner from continually pressing reset button when service is needed Communications HVAC communications Allows local and remote diagnostics for better troubleshooting and new services HONEYWELL - CONFIDENTIAL 7 BENEFIT R7184U Feature Function Benefit FEATURE FUNCTION Communicating Accessories Additional devices to utilize communications capability Remote access, test tools Leadwire and Quick Connect Termination Support both quick connects and leadwire termination Replaces both OEM and installed base with one model Alarm Contacts Indication of control lockout Allows connection to security system or other indications to warn of control lockout Selectable Valve On Delays Field selectable valve on delay Allows user to inventory and carry one universal product for various valve on delay times Selectable Blower Off Delay Field selectable blower off delay Allows user to inventory and carry one universal product for various blower delay on times HONEYWELL - CONFIDENTIAL 8 BENEFIT Key Features: Oil Primary R7184U Diagnostic LED – enables monitoring of system status to speed troubleshooting EnviraCOM™ Communications Data Port Limited reset – prevents continued homeowner reset without proper service checkout EnviraCOM™ Terminals. T-T Terminals Timer Setting Dip Switches – Universal Alarm Contacts (dry contacts, Application normally open) – Provides switch action to remote alarm panels HONEYWELL - CONFIDENTIAL 9 Installation Installing the R7184U • Follow the installation instructions per the application: - Locate proper location - Mount - Wire per application type Oil fired boiler without EnviraCOMTM Oil fired boiler with EnviraCOMTM Oil fired forced air with EnviraCOMTM Etc. HONEYWELL - CONFIDENTIAL 11 Set-Up Set-Up of the R7184U: Setting Delay Times 15 Sec 0 Valve On Delay 1st Switch: Valve On Delay 2nd & 3rd Switches: Burner Motor OFF Delay ON Easy access to set up delay times. 1 2 ON ON 1 2 0 min. 13 3 ON 1 2 2 min. ON 1 2 4 min. HONEYWELL - CONFIDENTIAL 1 2 8 min. Setting Delay Times ON Oil Pump Delay 3 ON 2 ON 1 OR 3 Delay Off 3 Delay On HONEYWELL - CONFIDENTIAL 14 Setting Delay Times Delay Choices Model Valve ON Delay Blower OFF (Seconds) (Minutes) R7184A None None R7184B 15 None R7184P 15 0-2-4-8 R7184U 0 or 15 0-2-4-6 HONEYWELL - CONFIDENTIAL 15 Troubleshooting Troubleshooting of the R7184U • The indicator light on the control provides lockout, recycle and cad cell indications as follows: 1. Flashing at 1 Hz (1/2 second on, 1/2 second off): system is locked out or in restricted mode. 2. Flashing at 1/4 Hz (2 seconds on, 2 seconds off): control is in recycle mode. 3. On: cad cell is sensing flame. 4. Off: cad cell is not sensing flame. • Cad Cell Resistance Check - For proper operation it is important that the cad cell resistance is below 1600 ohms. During a normal call for heat, once the control has entered the Run mode, press and release the reset button. Indicator light will flash 1 to 4 flashes. See next slide for equivalent cad cell resistance. HONEYWELL - CONFIDENTIAL 17 Troubleshooting: Diagnostics • Push lockout button once to get cad cell resistance and system status Flashes Indication Steady Control is sensing flame Off Control is not sensing flame Flashing Control is in lockout or restricted mode ( ½ sec on / ½ sec off) Flashing ( 2 sec on / 2 Sec off) Control is in recycle mode 1 < 400 ohms 2 400 - 800 ohms 3 800 - 1600 ohms 4 1600 – 5000 ohms *CAD Cell Ohms decreases with increased flame brightness HONEYWELL - CONFIDENTIAL 18 Troubleshooting of the R7184U • For Honeywell EnviraCOM™ enabled equipment - Read EnviraCOM Error Codes - Line Voltage - Cad Cell Ohms •The QuickLookTM 72 is available through www.onwatchinc.com HONEYWELL - CONFIDENTIAL 19 Product Cross Reference Product Cross Reference • Where do I find Honeywell universal electronic oil primary cross reference information? - www.customer.honeywell.com - Honeywell Application Selection and Cross Reference Guide – Form 63-9575 - Honeywell Laminated Truck Visor – Form 63-9581 - Honeywell Oil Primary Countermat – Form 63-9661 - Honeywell Residential Technical Support: 1-800-468-1502 HONEYWELL - CONFIDENTIAL 21 Oil Primary Cross Reference Table This chart can be found in the Residential Combustion Application Guide: Form #63-9575 HONEYWELL - CONFIDENTIAL 22 www.customer.honeywell.com • See Cross Reference Search box in right column. HONEYWELL - CONFIDENTIAL 23 R7184U Oil Primary Advantages • When promoting the R7184U Universal Oil Primary keep these advantages in mind: • Universal Compatibility - This control replaces Carlin, White Rodgers and all prior Honeywell Oil Primary Controls • Honeywell R7184U “Exclusive Features” - Pump priming cycle - Cad cell flame strength indicator - Limited recycle • Diagnostic LED - Indicator light monitors burner flame status and system lockout • EnviraCOM communications enabled - It includes EnviraCOM™ Connection for local networking & diagnostics - Compatible with Honeywell EnviraLINK™ remote monitoring application HONEYWELL - CONFIDENTIAL 24 R7184U Interrupted Electronic Oil Primary Knowledge Test R7184U Oil Primary Knowledge Test • Now that you completed this training module, take the short quiz to test your knowledge. HONEYWELL - CONFIDENTIAL 26 Test 1. The R7184U can be used in both hydronic and forced air systems? T or F 2. The Honeywell R7184U can replace ALL prior Honeywell oil primary controls, as well as Carlin and White Rodgers controls? T or F 3. There is one way to determine cad cell ohms and that is through the diagnostic LED? T of F 4. The R7184U is available in 3 lockout times, 15, 30 and 45 seconds? T or F 5. The pump priming cycle requires that the installer be present at the oil primary to purge the line? T or F HONEYWELL - CONFIDENTIAL 27 Test 6. Limited reset prevents the homeowner from continually pressing the reset button instead of calling for service? T or F 7. The diagnostic LED can identify system lockout? T or F 8. The valve on and blower off delay times are factory set and cannot be set by the installer during installation? T or F 9. The limited recycle features can help prevent clogging the heat exchanger or flooding? T or F 10. EnviraLink is the remote monitoring service that can be used with R7184U EnviraCOM enabled oil primary? T or F HONEYWELL - CONFIDENTIAL 28 Answer Key 1. T 2. T 3. F 4. T 5. F 6. T 7. T 8. F 9. T 10. T HONEYWELL - CONFIDENTIAL 29